Professional Documents
Culture Documents
Headline
Adjustable-Trip Circuit Breakers
Subheadline
240.6(C) - Restricted Access Adjustable-Trip Circuit Breakers
Discussion
Section 240.6(C) has been revised for clarity and a new
parenthesis (4) has been added to address new technology.
Access to the adjusting means associated with adjustable-trip
circuit breakers shall be achieved by one of the methods listed.
The new parenthesis (4) adds a password protected option
when the password is accessible only to qualified persons.
Modern electronic trip units provide the ability to set a password
in order to keep unauthorized and/or non-qualified people from
changing the settings.
1
2020 NEC: Significant Changes | Application Guide
Headline
Arc Energy Reduction
Subheadline
240.67 - Arc Energy Reduction
Code Change Details injection testing or another approved method when first
installed on site. This testing shall be conducted by a
2020 NEC qualified person(s) in accordance with the manufacturer’s
Arc Energy Reduction. Where fuses rated 1200A or higher are instructions.
installed, 240.67(A) and (B) shall apply. This requirement shall A written record of this testing shall be made and shall be
become effective January 1, 2020. available to the authority having jurisdiction.
(A) Documentation. Documentation shall be available to those Informational Note: Some energy reduction protection
authorized to design, install, operate, or inspect the systems cannot be tested using a test process of primary
installation as to the location of the fuses. current injection due to either the protection method
Documentation shall also be provided to demonstrate that being damaged such as with the use of fuse technology or
the method chosen to reduce clearing time is set to operate because current is not the primary method of arc
at a value below the available arcing current. detection.