AFP1010
Intelligent Fire Detection
and Alarm System
Section: Intelligent Fire Alarm Control Panels
GENERAL
The AFP1010 is an intelligent, addressable, fire alarm con-
* * MEA
trol panel with the capacity for 792 individually identifiable 289-91-E
and controllable detection/control points. The modular
hardware design and easy-to-define system operation soft-
Approved
CS118 *(also approved for
ware allows the user to easily configure the AFP1010 in CS733 automatic release and
the field. S635
pre-action deluge)
S5511
The AFP1010 is UL Listed under the following Standards: 93/60140 (E1)
UL 864 Control Units for Fire Protective Signaling Systems;
UL 1076 Proprietary Burglar Alarm Units; and UL 1610 U.S. California *
State Fire
Central Station Burglar Alarm Units. The AFP1010 also Coast Marshal
meets the requirements of NFPA Local, Auxiliary, Remote Guard 7165-0028:141
Station, Proprietary, and Emergency Voice/Alarm Fire Sys- 161.002/27/1 7170-0028:153
tems.
Addressable/intelligent detectors help fire-fighting person-
nel quickly locate a fire during its early stages.
FEATURES
Completely field-programmable and configurable, no
computer programming skills required. System contin-
ues to provide fire protection while program is being ed-
ited.
System capacity: 396 intelligent detectors plus 396 moni-
tor/control modules (792 total points) and 240 software
zones, plus 2,048 annunciator/control points.
Intelligent (Analog) Detectors: Ionization, Photoelectric,
3341ph1.tif, NFSrev00.wmf
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
5952cov.wmf
pander). Provides up to 6.0 am-
between LIBs functions in the event of a CPU failure. This
peres of regulated power for
bus allows all programmed local mode points to operate
compatible notification appliance
as a common alarm when programmed.
circuits. Includes battery input
All wiring from the Loop Interface Board is power limited and transfer relay, and overcur-
per UL requirements, and connected with plug-in terminal rent protection. Mounts on one
blocks. All connections may be made to these terminal of four positions on a CHS-4L or
blocks, allowing for the identification and corrections of any CHS-4 chassis.
field wiring faults prior to the final connection of the termi-
MBT-1: Municipal Box Trip for
nal blocks to the Loop Interface Board.
NFPA 72 auxiliary applications. Use in conjunction with
SIB-2048A: Serial Interface Board provides the follow- one CMX module and
ing interfaces: 0713sib8.wmf one A77-716B power
Dual EIA-232 terminal supervision relay.
ports (2400 baud, ASCII) CHS-4: (at right)
5262chs4.wmf
for CRT, and other EDP- Chassis, four position.
listed devices. Use for APS-6R
Dual EIA-232 printer port modules.
for PRN Printer, VGAS, DP-1: Blank dress panel. Use to cover unused rows in
and other EDP-listed de- cabinet, or CHS-4/CHS-4L chassis.
vices.
CAP-1: The CAP-1 capacitor is used to filter-out high-
EIA-485 annunciation
frequency AC interference between Earth Ground and Sys-
ports (20 K baud, ASCII)
tem Common within the same cabinet (one per power sup-
for ACS annunciators,
ply).
AMG, and Network Interface Board.
The SIB-2048A has full optical isolation on the EIA-232 CAB-3 Series Cabinets: (see data sheet DN-3549 for
interfaces to avoid ground-fault problems with EDP-listed cabinet options).
devices. All terminal blocks plug-in to simplify installation
and service.
SECURITY EQUIPMENT
RKS-1 Remote Keyswitch
SIB-NET: Network interface board for NOTIFIRENET
(see separate data sheet). STS-1 Security Tamper Switch
MPS-24A: The Main Power Supply mounts in the lower
CONSTRUCTION
left of the cabinet, and provides the following capabilities:
The basic equipment for the AFP1010 is the BE-1010N,
Electrically regulated system power supply (24 VDC and which includes one DIA-1010; one CPU-2, and one ICA-
5 VDC). 4L. SIB and LIB boards are then plugged into ICA-4L chas-
Resettable electrically regulated power for four-wire de- sis and an MPS Series power supply is installed in the cabi-
tectors. net. The maximum AFP includes 2 LIBs and 1 SIB, and
Non-resettable electrically regulated power for indicat- will fit in the CAB-A3 enclosure. Larger enclosures may be
ing appliances and/or ACS annunciators (3.0 amps). ordered if desired for additional power supplies, XP tran-
Dual-rate battery charger for gell-cell batteries (up to 55 sponders, etc. Each cabinet includes space at bottom for
AH) and NiCad cells up to 32 amp hours (NiCads mount power supply and up to 25 amp hours of batteries. The
external). BB-55 and cabinet may be used for 55 AH batteries.
Ground (earth) fault detection, with LED display.
AC fail/brownout detect and battery switchover, with LED ELECTRICAL SPECIFICATIONS
indicator. Primary input power: 120 VAC, 50/60 Hz.
120 VAC and 240 VAC Primary input power: 240 VAC, 50/60 Hz. Add an E to
(MPS-24AE) options end of the model number (example: MPS-24AE).
with circuit breaker and Primary AC power supervision with automatic switcho-
transient protection. ver to supervised standby batteries.
PTC power limiting
and overload protec-
tion on all outputs.
Switched regulation
0713mps2.wmf