e S TRANE
Purge Systems Operation
e@ Technical Training
Student Handbook
ST-MNLSPurge Systems Operation
CONTENTS,
INTRODUCTION 4
WHY PURGE SYSTEMS ARE NEEDED 4
HOW THE PURGE ELIMINATES AIR.
WHEN TO PURGE A UNIT ..... oo
HOW PURGE DESIGNS HAVE CHANGED .
Bolt Drive Purge.......
Cil-Less Purge
Oit-Less Purge
Purifier Purge
HOW PURGE SYSTEMS WORK "
Belt-Drive Purge
Oi-Less Purge :
Oil-Less Purge with UCP... -
Purifier Purge” ......00000ce220005
SUMMARY pooaad 2
Ucr
‘This manual is a companion piece to the Trane seminar of the same name.
‘To order additional copies, contact:
Service Literature Department
The Trane Company
3600 Pammel Creek Road
La Crosse, WI 54601
608-787-3684
Please specify the order number, ST-MNL-3.
‘The following support materials are also available through Trane
Service Literature:
PRG-OM-3A Operation and Maintenance Manual for Purifier Purge
PRG-IN-1A Retrofit Installation of Purifier Purge
The Trane Company, La Crosse, Wisconsin 54601-7599INTRODUCTION
easy
Figure 1
(Figure 1) In this section, we will introduce the
operational aspects of the various purge systems
utilized over the years by The Trane Company.
WHY PURGE SYSTEMS
ARE NEEDED
er
Cee
Figure 2
(Figure 2) Why do we need purge systems?
Because many centrifugal chillers operate in a
vacuum, there is an opportunity for contaminates
to get into the system from any leaks or minor
servicing errors. These contaminates are classified
‘as noncondensables requiring a method for
disposal. This is known as purging.
ers as
Figure 3
(Figure 3) The primary noncondensables requiring
urge systems are air and moisture. While both air
and moisture are collected by the purge systems,
‘only air can be removed automatically from the
system by means of some form of bleed or relief
valve. Moisture or water must be removed
manually through a blow-down valve system or
methods using water absorbing materials.
Most Cen
rere
Figure 4
(Figure 4) All low pressure centrifugals operate
completely or partially below atmospheric
pressures. These machines use low pressure
refrigerants such as R-113, R-11 or the new
replacement refrigerant, R-123.
Because the system operates below atmospheric
pressure, there is the possibility for refrigerant
contamination by way of leaks in the system.
While some people may consider purge systems
to be a nuisance, they actually play an important
part in maintaining centrifugal chiller system
integrityFigure 5
(Figure 5) This figure illustrates the difference
between a low pressure and a high pressure
system. It also may help you to understand why a
purge system is used only on low pressure
systems.
In the example on the left, an operating high
pressure system is represented using Refrigerant-
12. The high and low operating range for this
refrigerant is indicated as positive pressures (PSI
above atmospheric pressure). The example on the
right with Refrigerant-11 is operating in a negative
or partial vacuum measured in inches of mercury.
Ifa leak were to occur with either of these
systems, what would be the result? The high
pressure refrigerant machine would probably lose
all of its charge if the leak were not discovered in
time. A leak of this type is hazardous to personnel
and may result in injury. The low pressure
machine would simply leak air into the machine.
By simply monitoring the frequency of the purge
relieving noncondensable geses, the operator
‘could spot the increasing leak rate in the low
Pressure machine. The actual loss of refrigerant,
then, depends only on the efficiency of the purge
in separating air from refrigerant in the purge
process,
Since there is increased interest in reducing
‘atmospheric emissions of all refrigerants to an
absolute minimum, the importance of an efficient
leak prevention program will become paramount
for all chiller systems, regardless of the type of
refrigerant being used
Pern emcees
oer
moe
Figure 6
(Figure 6) Generally, we can isolate air and
‘moisture contamination to three areas: equipment
leaks, poor service evacuation practices and
contaminated refrigerants. All of these conditions
can be improved by increased attention to the
fundamentals of machine operation and
maintenance, and a strong educational program,
Improper or limited evacuation by service
personnel is usually the result of haste in
completing the job of restarting a machine after
servicing. The service technician may opt for
inadequate evacuation in the interest of time and
the mistaken belief that the purge can handle all
the air and moisture remaining in the chiller
following major work.Pees
ong
Valea
Figure 7
(Figure 7) Leaks can adversely affect the operating
capacities and efficiencies of any air conditioning
or refrigeration equipment. In large centrifugal
chillers such as the Trane CenTraVac* chiller, the
low pressure areas are most suspect when purge
‘operation rates increase, indicating an increase of
noncondensable gas being relieved.
Leaks are most likely to occur around the low
pressure flanged or gasketed areas, tube and pipe
fitting areas, and wherever contro! linkages must
connect to the compressor inlet guide vanes.
High pressure leaks are also possible past the
‘compressor’s first stage in the flange areas and at
pressure taps. These leaks will occur when the
chiller is running and will not be detected with the
increased purging rate. It is useful, therefore, to
monitor the machine room air for traces of
refrigerant gas and periodically leak check these
areas simply to minimize these types of refrigerant
losses,
HOW THE PURGE ELIMINATES AIR
Pope ey
Crees Uren
Figure 8
(Figure 8) How the purge eliminates air from the
chiller is the subject of the next area of discussion.
Basie Separations
Figure 9
(Figure 9) The first step to understand a purge
system is to know how the noncondensables and
refrigerant separate in a closed container. The
container in Figure 9 shows the separation or
stratification process of liquids and gases based
on their different weights.
Since air is the lightest of the components shown
here, it will always rise to the top. Next in
sequence is refrigerant vapor, water and finally
refrigerant liquid, Because air is lightest, and is at
the top of the container, it is a simple process to
slowly release that air by means of a relief valve
(provided that the container gases are not stirred
or mixed in any way).Preece
Tank Operate?
Figure 10
(Figure 10) Using the basic separation process just
covered, let's look at a typical purge condenser
tank that is found on many chillers manufactured
from the 1950's through the 1980's. First we will
assume that noncondensables are not present.
Refrigerant vapor comes from the chiller's
condenser via a purge compressor and is directed
to the purge condenser tank. The higher pressure
{gas comes into contact with a coil which acts as a
condenser. Using cool water flowing in the coil,
the purge condenser transforms the refrigerant
{2s to a liquid and it drops to the bottom of the
tank.
AA Tiquid level is maintained by a float-valve which
meters the liquid back to the chiller’s evaporator.
Since noncondensables did not enter the purge
condenser tank with the refrigerant vapor, the
pressure of the refrigerant in the purge tank will
stay fairly close to the saturation temperature
imposed by the cooling water in the coil.
eee
nae
Figure 11
(Figure 11) This figure shows a system
contaminated with air. The contaminated
refrigerant and air mix is drawn from the unit
condenser via the purge compressor and again is
directed to the purge condenser tank. The gas
mixture comes into contact with the purge
condenser coil. With the mixture of gases, only
the refrigerant portion will condense to a liquid.
The remaining air becomes trapped within the
purge condenser tank and will accumulate.
Because pressures of dissimilar gases have an
additive effect, the combined gas pressures reach
the release pressure of the relief valve located on
top of the purge drum, and the valve vents the
air mixture.
Because refrigerant vapor is present in the purge
condenser tank when the relief valve is activated,
some refrigerant can be lost with the air being
vented. The efficiency of this method of purge
depends, in part, on the condensing temperature
in the purge drum. The temperature should be as
low as possible to lower the distillation
temperature of the refrigerant-air mixture. This will
minimize the percentage of refrigerant vapor
volume relative to the air volume in the drum
while gases are being vented.WHEN TO PURGE A UNIT
Figure 12
(Figure 12) Is it best to purge when the unit is
operating or when the unit is shut down? It
depends on where the purge pickup is located on
the machine. Referring to Figure 12, note that the
pickup is about halfway down the condenser tube
bundle. With this form of pickup, an operating
machine is more effectively purged than a
machine that is standing idle.
With the compressor forcing high velocity
discharge gas into the top of the condenser shell
air will be mixed with the refrigerant. A quiet zone
is provided at the side of the condenser shell to
help trap and hold air to be picked up by the
purge compressor. With the unit off, there is @
Stratification of air to the top of the condenser.
‘The pickup becomes less effective because less
air is actually exposed to the pickup point.
Why is the pickup always located in the condenser
and not in the evaporator? Air will always tend to
be trapped in the condenser. With the unit
running, the condenser has a liquid seal at the
condenser discharge; air cannot travel past this
point. With the chiller off, air in the machine will
rise to the top of the condenser. Either way, the
evaporator is not an effective source for the point
of purge pickup.
HOW PURGE DESIGNS
HAVE CHANGED
Why Did Trane Ch
Figure 13
(Figure 13) Trane and other manufacturers of low
pressure centrifugal chillers have all changed their
design of purge units over time, In the centrifugal
chillers of the 1930's, purging was often done by
releasing the air-mixed refrigerant directly from
the top of the condenser barrel.
concerns about refrigerant losses; and owner
‘These were the priorities before the current
concern af reducing refrigerant emissions to the
lowest possible levels due to environmental
concerns. The design requirements for purge
effectiveness have changed!BELT DRIVE PURGE
eon
Figure 14
(Figure 14) The belt drive purge was the earliest
purge design Trane used. One of the main reasons
for using this purge system for so many years was
‘that its endurance record was well proven. It had
an open drive type compressor supplied to Trane
from several vendors. Other components were
the oil separator, purge condenser tank and a
fractional horsepower motor which drove the
‘compressor with a belt drive system.
‘The operation of this type of purge system can be
controlled by the operator through the use of a
three-position rocker switch. In the MANUAL
position, the purge unit will run continuously with
no respect to the operating mode of the chiller.
Occasionally running the purge in the manual
position was the preferred method of purging the
chiller by many operators because it allowed them
‘to monitor the relief of noncondensables.
In the OFF position, the purge unit is totally
disabled. In the AUTO position, the purge unit
would operate continuously when the chiller was
on line and running. When the chiller shut down,
‘the purge system would be stopped.
This purge design required careful operation and
maintenance to keep the system running
effectively. The oil separator, purge drum, float
mechanisms, relief valve and purge tank al
required cleaning and periodic service. The
external components such as the motor and belt
drive also had to be maintained. As with all open
drive compressors, the seals often were subject to
leaks and had to be inspected and serviced.
OIL-LESS PURGE
ee
Conventional Cont
Figure 15
{Figure 19) Shortly after the introduction of the
Tiane three- stage CeriraVac chiller, the oil-less
purge system was introduced. The main feature of
this system was that the purge compressor did
not utilize an oiMfilled crankcase, and because of
this, it did not require a oil separator to recover oil
‘An advantage to this approach was lower
maintenance.
However this design did have a number of
drawbacks. For example, continuous purging
operations of long duration caused premature
wearing of the purge compressor. The oil-less
purge system again used a three-position rocker
switch to control the purging of the chiller.
In the MANUAL position, the purge system would
run continuously with no respect to the chiller’s
operation. In the manual position, it was
imperative that chilled water be flowing through
the purge condenser. This again was the preferred
method of purging by many operators.
In the OFF position, the purge system was totally
disabled.
In the AUTO position, the purge unit would
operate for five minutes of each hour that the
chiller is operating. This five minutes of purging
was sufficient to remove noncondensables;
however, the actual amount of noncondensables
removed could not be determined in this mode of
operation.
This oil-ess purge unit, as well as preceding purge
units, had no way of maintaining a record of the
duration of operations or the number of purges.
Without this information, it was difficult to
determine both the condition of the system as
well as the purge compressor overhaul needs.OIL-LESS PURGE WITH UCP
Oit-Less Purge System
reaver
PURIFIER PURGE
Figure 16
(Figure 16) The next step was to interface the oi
less purge system with the new Trane three-stage
CeniraVac unit control panel (UCP). This allowed
for better control of the system.
‘The unit contro! panel (UCP) cil-less purge system
again used a three-position rocker switch to
control its operation. In the MANUAL position, the
purge system operated continuously, regardless of
the operating mode of the chiller.
In the OFF position, the purge system was totally
disabled,
In the AUTO position, the purge operated five
minutes out of each two hours of chiller operation
(assuming that no significant purge gases were
present).
Although the basic oil-less purge system was the
same, the method of control and recording
capabilities were enhanced. This enhancement
included the addition of a start counter to count
the number of actual purge relief operations and
an hour meter that would record the run hours,
accumulated on the purge compressor.
Another feature was the extended purge cycle, a
slightly more flexible approach to purge. This
feature increased purging time by an additional
four minutes each time a call for relief was
required. This increased the ability of the purge
system to completely free its system of air and
minimize the number of run hours accumulating
on the purge compressor and extend the time
between purge compressor overhauls.
This unit also had a small purge tank and a
solenoid valve controlled by the control panel
instead of a relief valve.
Figure 17
(Figure 17) In 1990, the Purifier Purge” system
‘was introduced. This style of purge also uses
intelligent controls. In addition, it exhibits a whole
new concept in purging methods. The net results
‘re more accurate and informative purging.
‘The features are numerous, the first being that the
new system purges by monitoring a refrigerant
‘temperature instead of pressure. It does not need
water connections for condensing purposes;
therefore the purge system can be operated easily
without the chiller running, and there is little
chance of water contamination or accidental
discharge of the refrigerant.
This system dramatically reduces the amount of
refrigerant emissions by about 90 percent. The
purifier release of air to refrigerant ratio has been
measured at .5 to 1 pound of refrigerant for each
pound of air purged from the system. This
‘compares to a ratio of three to seven pounds of
refrigerant to each pound of air in the old system.
‘There are similarities and differences in the
‘operation of this system. For example, when the
three-position rocker switch is in the OFF position,
the purge system is totally disabled, as with
previous systems.
‘When the switch is in the AUTO position, the
purge system will operate continuously with the
chiller in a run mode. When the chiller shuts
down, so does the purge system,
When the switch is in the ON position, constant
sampling is the result, regardless of the chiller’s,
‘operating mode and discharge noncondensables
when needed. It also records minutes of relief
operations.HOW PURGE SYSTEMS WORK
ee eee
Figure 18
(Figure 18) Now let's take a look at how these four
purge systems work.
BELT DRIVE PURGE
Figure 19
(Figure 19) The belt drive purge system took
refrigerant samples from the unit condenser via @
solenoid valve that had been energized to allow
that sample to be compressed by the purge
compressor and sent to the oil separator.
Notice that the purge gas mix must be elevated to
a higher pressure in order to develop sufficient
pressure for this design of purge system to work.
The oil separator is needed because the purge
compressor has a crankcase filled with oil. The oil
coming off the crankshaft lubricates the cylinder
wall, As the piston comes down on an intake
stroke of the compressor, some of the oil
lubricating the cylinder wall slips past the piston
rings.
u
The oil will leave the compressor by way of the
discharge line on the compression stroke. This oil
must be recovered and returned to the crankcase
of the purge compressor by an oil separator. The
oil separator must be kept warm through the use
of heaters to insure the flashing of any refrigerant
entrained with the oil
‘The higher temperature and pressure refrigerant
vapor is then sent to the purge tank, where it's
condensed to a liquid. The liquid refrigerant is
then returned to the evaporator to do useful work
OIL-LESS PURGE
Figure 20
(Figure 20) The oil-less purge operation is very
similar to the belt drive purge with one evident
‘exception and that is no requirement for an oil
separator. All other purge functions are the same.
It’s interesting to note that this compressor was
originally designed to operate as an air
compressor, but was redesigned to operate in a
refrigerant atmosphere. Even though air
compressor and refrigerant parts are
interchangeable, parts designed for use in
refrigerant atmosphere only should be used
because of the difference in the life expectancy of
the parts.OIL-LESS PURGE WITH UCP Pe rr aE
ees
forveerny
Figure 23
(Figure 23) The initial big change we see is that
a the purge pickup and purge liquid return are both
‘gure located in the unit condenser. This system has
some advantages in that flow is established
through migration of the refrigerant sample from.
the unit condenser and returns by gravity flow.
(Figure 21) The unit control panel controlled oil-
less purge is the same as the earlier oll-less purge,
xcept thatthe newer purge system operates on i
ommand signals froma figher source and os So, the Purifier Purge system must be installed
command signals from a ngher source ore onthe top of the condenser. The return flow an
ered Gat te alle ry Wa cae = moisture content of the refrigerant is monitored by
valve instead of the standard relief valve. melee ne
This sample process is an improvement because it
PURIFIER PURGE™ does not rely on elevated pressure for condensing
or refrigerant return. It also reduces the possibility
of leaks because fewer components and
‘connections are used, and the refrigerant sample @
is being taken from and returned to the same
vossel.
Seay
eee
Figure 22
(Figure 22) The Purifier Purge is a new and
exciting concept. Its basic purpose is the same as
that of all purge systems, but it performs in an
entirely different manner.
Figure 24
(Figure 24) The refrigerant vapor sample is
brought into the bottom of the purge condenser.
In the purge condenser there is @ vapor inlet and a
liquid refrigerant return tube. There also are two
filter drier cores installed end to end, the purpose
of which is to remove any moisture that may be
entrained with the refrigerant sample.
2‘The reftigerant vapor sample, having passed
through the filter drier cores, will next encounter a
serpentine coil, which acts as a heat exchanger.
‘The serpentine coil cools the refrigerant vapor and
causes it to condense to a liquid and allows it to
collect in the bottom of the purge tank.
The liquid level rises in the bottom of the tank
until it exceeds the height of the liquid refrigerant
return tube and then returns the liquid to the unit
condenser.
‘Any water present in the tank is prevented from
returning to the unit condenser by a water
separation tube that extends below the liquid level
isolating the lighter water above the refrigerant,
where it will be visible through the sight glass in
the purge tank. This visible water line will serve as
a cue that service is required and the filter drier
cores should be replaced.
re, Peon erst
Figure 25
(Figure 25) in order for the purge condenser
serpentine coil to act as a heat exchanger, a small
refrigeration circuit is used. This refrigeration
circuit is much like the one in a home refrigerator.
Its purpose is to supply low temperature
refrigerant, approximately 0 F, to the coil by way
of an automatic expansion valve, The serpentine
coil heat exchanger removes the heat from the
refrigerant sample. The low temperature
refrigerant supplied by the refrigeration unit now
completes its circuit and returns at a higher
temperature, sometimes as high as the chiller
condensing temperature.
2
arene
Figure 26
(Figure 26) What happens when air collects in the
purge condenser tank? The diagram on the left
shows a normal operating purge condenser. We
know it’s operating because the temperature
control is monitoring a return refrigerant
‘temperature of 22 F or greater.
But the diagram on the right is a different story.
As more air collects at the top of the tank, the air
will begin to insulate the serpentine coil,
preventing it from doing its job.
AAs the volume of air increases in the tank, more
and more of the serpentine coil surfaces become
inefficient in absorbing heat. The temperature
control monitors this condition and senses air is
trapped in the purge tank because of the lower
return refrigerant temperature.eect
Figure 27
{Figure 27) Once the temperature control has
sensed 18 F or below, indicating the presence of
air in the purge tank, it will initiate and energize
the purge solencids and the pump out compressor
to remove the air. The temperature control will
continue monitoring the returning refrigerant
temperature from the serpentine coil and when it
sees the temperature rise above 22 F, it will
discontinue the purge relief cycle.
It should be noted that there is a restricter located
between the solenoid valves and the pump out
‘compressor. This restricter’s purpose is to slow
down the discharge rate of the pump out
‘compressor to prevent excessive release of
refrigerant vapor with the trapped ait. The slower
release of air reduces turbulence inside the tank
from the entering vapor.
Also notice that there are two opposing solenoids
installed in the pump out line. These solenoids
provide a positive seal when they are de-
energized to mir leak potential
“
fo}
Figure 28
(Figure 28). As discussed, three circuits are
involved in the purge system. The refrigeration
circuit supplies the low temperature refrigerant for
condensing purposes to the purge serpentine coil
‘The purge pickup and return circuit to the unit
condenser supplies the refrigerant sample for
testing purposes. The solenoid valves and the
pump out compressor reject air from the system.Figure 29
(Figure 29) There are several control schemes
involved in the Purifier Purge control system. One
of the control schemes relates only to a version
which operates only by its own controls for use
with older chillers.
Another scheme involves the interfacing of the
chiller’s microprocessor panel with the purge
control system, allowing for a centralized control
point. To get an explanation of the full sequence of
‘operation, refer to the applicable operators
manual. Be sure to use the correct manual.
This figure shows indicator lights and operational
switches. The open solenoid and run pump out
switch acts as a momentary service switch. This
switch is meant to be used by service personnel
10 test for operation of the purge solenoid valves
and the pump out compressor.
‘The ON, OFF/RESET, AUTO switch is used only
with field retrofit of the newest version of the
purifier purge system. The purpose of this switch
is to reinitialize the internal purifier purge 24-hour
smart timer.
There are three i
purge control panel:
itor lights mounted on the
Run: This light indicates that the purge system is
‘operating. It should be noted that the purifier
purge runs continuously as long as the chiller is
operating,
Fault: This light will illuminate any time that the
actual purge relief has exceeded the time value
set in the 24-hour smart timer (factory set at
12 minutes).
Bypass: This light is illuminated when the purge
relief 24-hour fault timer has been bypassed
intentionally. One reason for this intentional
bypass may be because of a service requirement.
The final switch, 24-hour bypass or normal, is a
momentary switch and is used to reinitialize the
24-hour bypass fault timer for an additional
24 hours.
Figure 30
(Figure 30) To get the maximum performance out
of any purge system, certain maintenance
requirements must be met. In the remainder of
this manual, we will cover these necessary steps.Figure 31 Figure 32
(Figure 31) Performing regular, scheduled (Figure 32) The oil-less purge system maintenance
maintenance will help assure proper operation of checks are basically the same, except those items
the purge belt drive system. Here are suggested referring to the oil separator. The current
service schedules: recommendation is to overhaul the oil-less purge
compressor at 750 hours of accumulated run time.
Daily: Check and log operating purge pressures. If Use only replacement parts which are suitable for
the purge compressor has a sightglass, check for ‘operations in a refrigerant atmosphere.
oil levels. Check the purge drum for proper level
and any indication of moisture. Check the oll
separator for proper operating temperature.
Weekly: Operate the purge as required. Check the
oil separator heaters for proper setpoints and.
operating temperature.
Monthly: Loak check all purge components, tines,
connections and fittings. Check the purge drum
water temperature. (It should be less than 80 F),
Check the purge compressor oi! level.
Quarterly: Lubricate purge motor bearings.
‘Semiannually: Check the purge belt drive for wear
and proper tension. Clean all water strainers. Flush
the oil separator with fresh oil.
Annually: Check the purge relief for the correct
‘elief setting. Inspect, clean and recalibrate (if
necessary) all safety and operating controls
associated with the operation of the purge system,
Figure 33
(Figure 33) The service requirements are basically
the same for an oil-less purge system which uses
unit control panel inputs. In addition, itis
necessary to monitor the start counter and the run
hour meter daily logs. Doing this will reveal any
adverse operating conditions.
Overhaul the purge condenser tank, disassemble,
clean the tank, check the float and purge tank
baffle. Change the purge compressor crankcase oil
Check the purge compressor valves. Check purge
compressor shaft seals. Clean the oil separator and
recharge with fresh oil. Leak check all purge
‘system components, lines, connections and
fittings,
6Figure 34
(Figure 34) The Purifier Purge” has similar
checkout requirements for maintenance, although
there are some differences we should discuss.
Daily: Check and log the status lights of the purge
control panel. Record the minute meter and note
any changes in the accumulated time recorded.
If the accumulated minutes setting has changed,
be sure to take into consideration the operating
schedule of the chiller. Make a visual inspection of
the purge tank and liquid line sight glass and note
any changes.
Weekly: While the purge is operating, check the
purge tank condensing activity at the sight glass.
‘A continuous flow of refrigerant droplets should
be visible,
Check the moisture indicator on the liquid return
Tine. If the indicator shows the presence of
moisture, itis time to replace the filter drier cores.
Check the purge tank sight glass for the presence
‘of water. If water is present, there will be a visible
line of separation between the water and the
refrigerant.
The presence of water in the purge tank indicates
that service is required. See the appropriate
operators manual for a description of the above
mentioned conditions.
Monthly/Semiannually: inspect the air-cooled
condenser coil and clean as needed. A fouled coil
will reduce purge efficiency and capacity.
Annually: Perform a purge system control check
as outlined in the operators manual. Perform
purge tank service as described in the operators
manual
SUMMARY
Figure 35
(Figure 35) To summarize, there are different types
of purge systems. The new Purifier Purge” system,
represents an opportunity for increased control
over refrigeration emissions.