You are on page 1of 13

Q/J# Date: 27.09.

2018
Job Name Rev: 0
Title Design: MST
Bldg Name Check: KNR

NOTE: Only yellow color cells are inputs.


S.no Description
1 Width of Building (O/O) (Shorter dim) 24.70 mts
2 Length of Building (O/O) (Longer dim) 27.00 mts
3 Bay Spacing (C/C) 5.00 mts
4 Eave Height 5.25 mts
5 Wind speed Basic (Vb) 47.00 m/sec
6 Vz Reduction factor(For Eave height < 10 mts) 0.80
7 K1 - Risk Coefficient 1
8 K2 - Terrain, Height factor Category-2 1.0
9 K3 - Tropography factor 1
10 K4 - Importance factor in cyclonic region 1.15
11 Offshore Wind velocity 1.00
12 Kd - Wind Directionality factor 1.00
13 Ka - Area Averaging factor for Rafter 123.5 0.800
Ka - Area Averaging factor for Column 26.25 0.898
Ka - Area Averaging factor for Purlin 7.5 1.000
14 Kc - Combination factor 1.0
15 Purlin or Girt spacing (C/C) (i.e,Whichever is small) 1.500
Kd * Ka * Kc = 0.8 0.800
Vz - Design wind speed = (Vb*K1*K2*K3*K4) 54.05 m/sec
Pz -Wind Pressure at Height 5.25 m =0.6Vz^2 1.402 Kn/m^2

For Rafter Pd -Design Wind Pressure for Rafter (P z*Kd*Ka*Kc) 1.122 Kn/m^2

For Column Pd -Design Wind Pressure for Column (Pz*Kd*Ka*Kc) 1.260 Kn/m^2

For Secondary Pd -Design Wind Pressure for Purlin (Pz*Kd*Ka*Kc) 1.753 Kn/m^2

Notes for Ref:-


1
2
3
Wall 00 coefficients Cpi Wall 900 coefficients Cpi Roof coefficients Cpi
C1 0.70 0.20 C1 -0.50 0.2 C3 -0.94 0.2
C2 -0.20 0.2 C2 -0.50 0.2 C4 -0.40 0.2
C5 -0.50 0.2 C5 0.70 0.2 C7 -0.80 0.2
C6 -0.50 0.2 C6 -0.10 0.2 C8 -0.80 0.2

Column Rafter
Internal members End Members Internal members End Members
Memb Along - A 12 ** W - 00 Along - EF 10 11 **
Memb Along - B 34 ** W - 00 Along - GH 12 13 **
Memb Along - C ** ** W - 900
Memb Along - D ** ** W - 900 Interpolation
5 0.9
Internal Column Spacing/? 5.71 X
Bay Spacing 5.000 S wall & Roof End wall 10 1.2
Wind col spacing 6.000 2 2 X = 0.943
***************************
Copy from below
*H/W=5.25/ 24.7 = 0.213
*L/W=27/ 24.7 = 1.094
*Wind Speed = 47 m/sec
*K1 = 1
*K2 = 1.0
*K3 = 1
*K4 = 1.15
*Kd = 1
*Ka = 0.8
*Kc = 1
*Vz = 47*1*1.0*1*1.15 = 54.05 m/sec
*Pz -Wind Pressure at Height 5.25 m =0.6Vz^2=1.4022732
*0.8 Pz factor will be multiplied to Pz if the height of building is less than 10.0 mts
*Pd -Design Wind Pressure for Rafter (Pz*Kd*Ka*Kc)=1.12181856
*Pd -Design Wind Pressure for Column (Pz*Kd*Ka*Kc)=1.259708758
*C1 = 0.7
*C2 = -0.2
*C3 = -0.94
*C4 = -0.4
*Cpi = 0.2
***PRESURE***
****COLUMN***
*(0.7 -0.2)*5*1.26 = 3.149
*(-0.2 -0.2)*5*1.26 = -2.519
*(-0.5 -0.2)*6*1.26 = -5.291
****RAFTER*****
*(-0.94 -0.2)*5*1.26 = -7.180
*(-0.4 -0.2)*5*1.26 = -3.779
***************************
LOAD 3 WLL-P
MEMBER LOAD
*COLUMN
1 2 UNI GX 3.149
** UNI GX 1.575
3 4 UNI GX 2.519
** UNI GX 1.260
** UNI GZ -5.291
** UNI GZ -2.645
** UNI GZ 5.291
** UNI GZ 2.645
*RAFTER
10 11 UNI Y 7.180
** UNI Y 3.590
12 13 UNI Y 3.779
** UNI Y 1.890
***************************
LOAD 4 WLR-P
MEMBER LOAD
*COLUMN
1 2 UNI GX -2.519
** UNI GX -1.260
3 4 UNI GX -3.149
** UNI GX -1.575
** UNI GZ -5.291
** UNI GZ -2.645
** UNI GZ 5.291
** UNI GZ 2.645
*RAFTER
10 11 UNI Y 3.779
** UNI Y 1.890
12 13 UNI Y 7.180
** UNI Y 3.590
**********************************************************************
***SUCTION***
****COLUMN***
*(0.7 +0.2)*5*1.26 = 5.669
*(-0.2 +0.2)*5*1.26 = 0.000
*(-0.5 +0.2)*6*1.26 = -2.267476
****RAFTER*****
*(-0.94 + 0.2)*5*1.26 = -4.661
*(-0.4 + 0.2)*5*1.26 = -1.260

***************************
LOAD 5 WLL-S
MEMBER LOAD
*COLUMN
1 2 UNI GX 5.669
** UNI GX 2.834
3 4 UNI GX 0.000
** UNI GX 0.000
** UNI GZ -2.267
** UNI GZ -1.134
** UNI GZ 2.267
** UNI GZ 1.134
*RAFTER
10 11 UNI Y 4.661
** UNI Y 2.330
12 13 UNI Y 1.260
** UNI Y 0.630
***************************
LOAD 6 WLR-S
MEMBER LOAD
*COLUMN
1 2 UNI GX 0.000
** UNI GX 0.000
3 4 UNI GX -5.669
** UNI GX -2.834
** UNI GZ -2.267
** UNI GZ -1.134
** UNI GZ 2.267
** UNI GZ 1.134
*RAFTER
10 11 UNI Y 1.260
** UNI Y 0.630
12 13 UNI Y 4.661
** UNI Y 2.330
***LONG - 90*******************************************************
***PRESURE***
****COLUMN***
*(0.7 -0.2)*6*1.26 = 3.779126274
*(-0.1 -0.2)*6*1.26 = -2.267475764

*(-0.5 -0.2)*5*1.26 = -4.409


****RAFTER*****
*(-0.8 -0.2)*5*1.26 = -6.299
***************************
LOAD 7 WLL-P (W-90)
MEMBER LOAD
*COLUMN
** UNI GZ 3.779126
** UNI GZ 1.889563
** UNI GZ 2.267476
** UNI GZ 1.133738
1 2 UNI GX -4.409
** UNI GX -2.204
3 4 UNI GX 4.409
** UNI GX 2.204
*RAFTER
10 11 UNI Y 6.299
** UNI Y 3.149
12 13 UNI Y 6.299
** UNI Y 3.149
***************************
LOAD 8 WLR-P (W-90)
MEMBER LOAD
*COLUMN
** UNI GZ -2.267
** UNI GZ -1.134
** UNI GZ -3.779
** UNI GZ -1.890
1 2 UNI GX -4.409
** UNI GX -2.204
3 4 UNI GX 4.409
** UNI GX 2.204
*RAFTER
10 11 UNI Y 6.299
** UNI Y 3.149
12 13 UNI Y 6.299
** UNI Y 3.149
***************************
***SUCTION***
****COLUMN***
*(0.7 + 0.2)*6*1.26 = 6.802
*(-0.1 + 0.2)*6*1.26 = 0.756
*(-0.5 + 0.2)*5*1.26 = -1.890
****RAFTER*****
*(-0.8 + 0.2)*5*1.26 = -3.779
***************************
LOAD 9 WLL-S (W-90)
MEMBER LOAD
*COLUMN
** UNI GZ 6.802
** UNI GZ 3.401
** UNI GZ 0.756
** UNI GZ 0.378
1 2 UNI GX -1.890
** UNI GX -0.945
3 4 UNI GX 1.890
** UNI GX 0.945
*RAFTER
10 11 UNI Y 3.779
** UNI Y 1.890
12 13 UNI Y 3.779
** UNI Y 1.890
***************************
LOAD 10 WLR-S (W-90)
MEMBER LOAD
*COLUMN
** UNI GZ -0.756
** UNI GZ -0.378
** UNI GZ -6.802
** UNI GZ -3.401
1 2 UNI GX -1.890
** UNI GX -0.945
3 4 UNI GX 1.890
** UNI GX 0.945
*RAFTER
10 11 UNI Y 3.779
** UNI Y 1.890
12 13 UNI Y 3.779
** UNI Y 1.890
WIND APPLICATION IS-875 (PART-III) :2015

Interpolation
distance depth

*************************** 0 0.8
DEFINE MATERIAL START
ISOTROPIC STEEL 2.86 X
E 2.05e+008
POISSON 0.3 5 0.9
DENSITY 76.8195
ALPHA 1.2e-005 X = 0.857
DAMP 0.02
END DEFINE MATERIAL Bay Spacing 7.9 m
*************************** Collateral Load 0
CONSTANTS Pipe & tray Load 0
MATERIAL STEEL ALL
***************************
UNIT MMS KN DL : 0.20 2 TO 3 II 0.1
MEMBER PROPERTY INDIAN LL : 0.57 III 0.16
**COLUMN Seismic Zo IV IV 0.24
1 2 TAPERED V 0.36
***************************
UNIT METER KN 1 Support nodes Column Rafter
SUPPORTS 26 1 TO 7 15 TO 17
1 PINNED Eave height 8.5 m 28 30 29 8 TO 14 18 TO 20
*************************** Shorter Di 54.0 m
* BAY SPA 7.9 M Longer Di 150.0 m
*************************** Kd 0.90 Kd- Wind directionality factor.
DEFINE 1893 LOAD Wind speed (Vb) : 55.00 m/sec Ka 0.80 Ka- Area averaging factor
ZONE 0.24 RF 4 I 1 SS 3 ST 2 k1 : 1 Kc 1.00 Kc- Combination factor.
SELFWEIGHT k2 : 1.05 0.72 Note that this value should not be less
*DL= 0.2 * 7.9 = 1.58 Kn/m k3 : 1 than 0.70
k4* : 1 *Refer k4 info
MEMBER WEIGHT Vz : 57.75 m/sec
pz 2.00
2 TO 3 UNI 1.58 Wind pressure : 1.44 Kn/m^2
***************************
LOAD 8 EQ+VE
1893 LOAD X 1
***************************
LOAD 9 EQ-VE
1893 LOAD X -1
***************************
LOAD 1 DL
SELFWEIGHT Y -1
*DL= 0.2 * 7.9 = 1.58 Kn/m
MEMBER LOAD
2 TO 3 UNI GY -1.58
***************************
LOAD 2 LL
*LL= 0.57 * 7.9 = 4.503 Kn/m
MEMBER LOAD
2 TO 3 UNI GY -4.503
***************************
*H/W=8.5/ 54 = 0.158
*L/W = 150/54 = 2.778
*Wind Speed = 55 m/sec
*K1 = 1
*K2 = 1.05
*K3 = 1
*Vz = 55*1*1.05*1 = 57.75 m/sec
*Pz = 0.6*Vz^2 = 2002/1000=1.441 Kn/m2
*C1 = 0.7
*C2 = -0.25
*C3 = -0.857
*C4 = -0.4
*Cpi = 0.2
***PRESURE***
****COLUMN***
*(0.7 -0.2)*7.9*1.441 = 5.691 Cpi Cpi Cpi
*(-0.25 -0.2)*7.9*1.441 = -5.122 C1 0.70 0.2 C1 0.70 0.2 C5 -0.60 0.2
****RAFTER***** C2 -0.25 0.2 C2 -0.25 0.2 C6 -0.60 0.2
*(-0.857 -0.2)*7.9*1.441 = -12.031
0.9426/
*(-0.4 -0.2)*7.9*1.441 = -6.829 C3 -0.86 0.2 0.9283 C3 -0.86 0.2 C7 -0.80 0.2
*************************** C4 -0.40 0.2 C4 -0.40 0.2 C8 -0.80 0.2
LOAD 3 WLL-P
MEMBER LOAD
*COLUMN
26 UNI GX 5.691
28 30 29 UNI GX 5.122
*RAFTER
1 TO 7 15 TO 17 UNI Y 12.031
8 TO 14 18 TO 20 UNI Y 6.829
***************************
LOAD 4 WLR-P
MEMBER LOAD
*COLUMN
26 UNI GX -5.122
28 30 29 UNI GX -5.691
*RAFTER
1 TO 7 15 TO 17 UNI Y 6.829
8 TO 14 18 TO 20 UNI Y 12.031
***************************
***SUCTION***
****COLUMN***
*(0.7 + 0.2)*7.9*1.441 10.244
*(-0.25 + 0.2)*7.9*1.4 -0.569
****RAFTER*****
*(-0.857 + 0.2)*7.9*1. -7.478
*(-0.4 + 0.2)*7.9*1.44 -2.276
***************************
LOAD 5 WLL-S
MEMBER LOAD
*COLUMN
26 UNI GX 10.244
28 30 29 UNI GX 0.569
*RAFTER
1 TO 7 15 TO 17 UNI Y 7.478
8 TO 14 18 TO 20 UNI Y 2.276
***************************
LOAD 6 WLR-S
MEMBER LOAD
*COLUMN
26 UNI GX -0.569
28 30 29 UNI GX -10.244
*RAFTER
1 TO 7 15 TO 17 UNI Y 2.276
8 TO 14 18 TO 20 UNI Y 7.478
***************************
***LONG - 90***
****COLUMN***
*(-0.6 - 0.2)*7.9*1.441 = -9.106
*(-0.6 - 0.2)*7.9*1.441 = -9.106
****RAFTER*****
*(-0.8 - 0.2)*7.9*1.441 = -11.382
*(-0.8 - 0.2)*7.9*1.441 = -11.382
***************************
LOAD 7 WL LONG 90
MEMBER LOAD
*COLUMN
26 UNI GX -9.106
28 30 29 UNI GX 9.106
*RAFTER
1 TO 7 15 TO 17 UNI Y 11.382
8 TO 14 18 TO 20 UNI Y 11.382
***************************
Wall 00 coefficients Cpi Wall 900 coefficients Cpi Roof coefficients Cpi
C1 0.70 0.20 C1 -0.50 0.2 C3 -0.94 0.2
C2 -0.20 0.2 C2 -0.50 0.2 C4 -0.40 0.2
C5 -0.50 0.2 C5 0.70 0.2 C7 -0.80 0.2
C6 -0.50 0.2 C6 -0.20 0.2 C8 -0.80 0.2

Column Rafter Interpolation


Memb Along - A 1235 1242 W - 00 Along - EF1328 1332 TO 1337 1399 1402 0 0.8
Memb Along - B 1325 1327 W - 00 Along - GH1329 1340 TO 1345 1403 1404 2.86 X
Memb Along - C - W - 900 5 0.9
Memb Along - D - W - 900 X = 0.857

Wind col spacing 7.381


***************************
Copy from below
*H/W=5.25/ 24.7 = 0.213
*L/W=27/ 24.7 = 1.094
*Wind Speed = 47 m/sec
*K1 = 1
*K2 = 1.0
*K3 = 1
*K4 = 1.15
*Kd = 1
*Ka = 0.8
*Kc = 1
*Vz = 47*1*1.0*1*1.15 = 54.05 m/sec
*Pz -Wind Pressure at Height 5.25 m =0.6Vz^2=1.4022732
*0.8 Pz factor will be multiplied to Pz if the height of building is less than 10.0 mts
*Pd -Design Wind Pressure for Rafter (Pz*Kd*Ka*Kc)=1.12181856
*Pd -Design Wind Pressure for Column (Pz*Kd*Ka*Kc)=1.259708758
*C1 = 0.7
*C2 = -0.2
*C3 = -0.94
*C4 = -0.4
*Cpi = 0.2
***PRESURE***
****COLUMN***
*(0.7 -0.2)*5*1.26 = 3.149
*(-0.2 -0.2)*5*1.26 = -2.519
****RAFTER*****
*(-0.94 -0.2)*5*1.26 = -7.180
*(-0.4 -0.2)*5*1.26 = -3.779
***************************
LOAD 3 WLL-P
MEMBER LOAD
*COLUMN
1235 1242 UNI GX 3.149
1325 1327 UNI GX 2.519
*RAFTER
1328 1332 TO 1337 1399 1402 UNI Y 7.180
1329 1340 TO 1345 1403 1404 UNI Y 3.779
***************************
LOAD 4 WLR-P
MEMBER LOAD
*COLUMN
1235 1242 UNI GX -2.519
1325 1327 UNI GX -3.149
*RAFTER
1328 1332 TO 1337 1399 1402 UNI Y 3.779
1329 1340 TO 1345 1403 1404 UNI Y 7.180
**********************************************************************
***SUCTION***
****COLUMN***
*(0.7 +0.2)*5*1.26 = 5.669
*(-0.2 +0.2)*5*1.26 = 0.000
****RAFTER*****
*(-0.94 + 0.2)*5*1.26 = -4.661
*(-0.4 + 0.2)*5*1.26 = -1.260

***************************
LOAD 5 WLL-S
MEMBER LOAD
*COLUMN
1235 1242 UNI GX 5.669
1325 1327 UNI GX 0.000
*RAFTER
1328 1332 TO 1337 1399 1402 UNI Y 4.661
1329 1340 TO 1345 1403 1404 UNI Y 1.260
***************************
LOAD 6 WLR-S
MEMBER LOAD
*COLUMN
1235 1242 UNI GX 0.000
1325 1327 UNI GX -5.669
*RAFTER
1328 1332 TO 1337 1399 1402 UNI Y 1.260
1329 1340 TO 1345 1403 1404 UNI Y 4.661
***LONG - 90*******************************************************
***PRESURE***
****COLUMN***
*(-0.5 -0.2)*5*1.26 = -4.409
****RAFTER*****
*(-0.8 -0.2)*5*1.26 = -6.299
***************************
LOAD 7 WLL-P (W-90)
MEMBER LOAD
*COLUMN
1235 1242 UNI GX -4.409
1325 1327 UNI GX 4.409
*RAFTER
1328 1332 TO 1337 1399 1402 UNI Y 6.299
1329 1340 TO 1345 1403 1404 UNI Y 6.299
***************************
DQ/PCT/J# 0 Date 27.09.2018
Job Name 0 Rev 0
Title 0 Design: MST
Bldg Name 0 Check: KNR

Input
Slope 1 20 0.6175
Number of braced bays 5 nos

Design Wind Pressure 2.625


Pz 1.260 kN/m2 5.25

Rectangular area Force 40.84 kN

Triangular area Force 4.80 kN

Total Force 45.64 kN 24.7

Force on Each Braced Bay 9.13 kN 12.35

DESIGN OF BRACING ROD


9.13
Height of the Bracing 8.35 m
Bay Spacing 5.00 m

Diagonal length of the Bracing Rod 9.73 m

Force in the Bracing Rod 17.77 kN

Dia of the Rod 40.00 m

Capacit of the rod 150.80 kN 5 m


Hence Safe

DESIGN OF TUBE AT EAVE LEVEL

Force in the Tube P 9.13 kN


Length of the Tube L 5.00 m
Modules of Elastcitiy E 200000 N/mm2
Yield strength fy 250 N/mm2
Select Tube NB-100

Section Properties
Area a 1550.00 mm2
Radius of Gyration r 38.90 mm

Check for Slenderness ratio


L/r 128.53 <250 Hence Safe

Permissible Compressive Stress (As per IS:800-1984 )


σac 75.00 N/mm2
Allowable compression in the tube 116.25 KN >P Safe