You are on page 1of 12

Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917

Project Name: Date: 30 Sep 2011


Contract Number: Page 1 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

This specification has been revised as indicated below and described in the revision record on the
following page. Please destroy all previous revisions.

Revision Date Originator's Reviewed/Checked By Pages


No. Name & Initials Name & Initials
0 1-13-2011 Jared Trueman Sohail Saleem 17
1 2-25-2011 Domingo Rodriguez Sohail Saleem 27
2 9-30-2011 Domingo Rodriguez Sohail Saleem 12

APPROVALS SIGNATURES DATE

Lead Engineer
Project Manager: Russell Shulz
Client Approval:

ISSUED FOR : Construction X Other FOR APPROVAL


Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 2 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

RECORD OF REVISIONS
Revision Date Description
No.

0 1-13-2011 ISSUED FOR APPROVAL

1 2-25-2011 ISSUED APPROVED FINAL

2 9-30-2011 ISSUED FOR APPROVAL


Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 3 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

TABLE OF CONTENTS
1.0 GENERAL .................................................................................................................................... 4
2.0 REFERENCE ............................................................................................................................... 4
2.1 MARAFIQ ............................................................................................................................. 4
2.2 SASO - Saudi Arabian Standards Organization.................................................................... 4
2.3 SAF Directives ...................................................................................................................... 4
2.4 Factory Mutual (FM) ............................................................................................................. 5
2.5 NFPA - National Fire Protection Association......................................................................... 5
2.6 OSHA - Occupational Safety & Health Administration .......................................................... 5
2.7 UL - Underwriters' Laboratories, Inc...................................................................................... 5
3.0 DEFINITIONS............................................................................................................................... 5
4.0 HEALTH AND SAFETY CONSIDERATIONS ............................................................................... 5
5.0 SUBMITTALS ............................................................................................................................... 5
6.0 QUALITY CONTROL.................................................................................................................... 6
6.1 Engineering Responsibility.................................................................................................... 6
6.2 Single-Source Responsibility ................................................................................................ 6
6.3 Product Quality ..................................................................................................................... 6
6.4 Electrical Components, Devices and Accessories ................................................................ 7
7.0 WET CHEMICAL EXTINGUISHING SYSTEM USES AND LIMITATIONS ................................... 7
8.0 DESIGN CRITERIA ...................................................................................................................... 7
8.1 Calculations .......................................................................................................................... 8
9.0 PRODUCTS ................................................................................................................................. 8
9.1 Discharge nozzles ................................................................................................................ 8
9.2 Wet Chemical Containers ..................................................................................................... 8
9.3 Control Panel ........................................................................................................................ 8
9.4 Discharge Indicator............................................................................................................... 8
9.5 Warning Sounder / Strobe .................................................................................................... 9
9.6 Pipes, joints and fittings ........................................................................................................ 9
9.7 Pipe Hangers and Supports.................................................................................................. 9
10.0 EXECUTION ................................................................................................................................ 9
10.1 Protection of Piping and Equipment Against Damage........................................................... 9
11.0 INSTALLATION ............................................................................................................................ 9
11.1 Power source........................................................................................................................ 9
11.2 Control Panel ...................................................................................................................... 10
11.3 Gas Storage Cylinders........................................................................................................ 10
11.4 Discharge Indicator............................................................................................................. 10
11.5 Local Release Switch / Abort Switch................................................................................... 10
11.6 Warning Sounder / Strobe .................................................................................................. 10
11.7 Piping.................................................................................................................................. 10
11.8 Hanging, Bracing and Restraint of System Piping............................................................... 10
11.9 Pipe Sleeves....................................................................................................................... 10
11.10 Escutcheon Plates .............................................................................................................. 11
11.11 Installation/Caution Signs ................................................................................................... 11
12.0 COORDINATION........................................................................................................................ 11
13.0 TESTING.................................................................................................................................... 11
14.0 CERTIFICATION ........................................................................................................................ 11
15.0 TRAINING .................................................................................................................................. 12
16.0 DELIVERY, HANDLING AND STORAGE................................................................................... 12
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 4 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

1.0 GENERAL

This specification contains the minimum design, installation, testing and commissioning
requirements for an Automatic Wet Chemical Extinguishing System. The Automatic Wet
Chemical Extinguishing System is to assure the safety of personnel and property during a fire.
The design of the Automatic Wet Chemical Extinguishing System shall conform to this
specification and the complete Automatic Wet Chemical Extinguishing System shall be fully
compatible to all components supplied.

2.0 REFERENCE

The referenced codes and standards are intended to provide an acceptable level of quality for
materials, products and workmanship. In case of conflict between these standards and the
text of this Specification, the Specification text shall govern.
The latest revision of the referenced codes and standards shall be used as a minimum guide.
In case of conflict, the Contractor shall propose equipment, materials and processes
conforming to one group of codes and standards.
2.1 MARAFIQ
 MQ-SP-P-4922– PROTECTED PREMISES AND PROPRIETARY STATION
FIRE ALARM SYSTEM
 MQ-SP-P-5001 – PROCESS AND UTILITY PIPING DESIGN, LAYOUT AND
DRAWING
 MQ-SP-P-5002 – PIPING – MATERIAL SPECIFICATION LINE CLASS –
PROCESS AND UTILITY PIPING
 MQ-SP-P-5003 – SHOP FABRICATION AND HANDLING – PROCESS AND
UTILITY PIPING
 MQ-SP-P-5004 – FIELD FABRICATION AND INSTALLATION – PROCESS
AND UTILITY PIPING
 MQ-SP-P-5005 – INTERNAL CLEANING OF PIPING SYSTEMS
 MQ-SP-P-5007 – BOLT TORQUE AND TENSIONING REQUIREMENTS
 MQ-SP-P-5008 – PIPE MARKERS AND VALVE TAGS FOR COMMODITY AND
SAFETY ID
 MQ-SP-P-5009 – GENERAL PIPING SPECIFICATION – PIPING STANDARD
DETAILS
 MQ-SP-P-5015 – PURCHASE SPECIFICATION FOR PIPE, FITTINGS, AND
FLANGES
 MQ-SP-P-5016 – PURCHASE SPECIFICATION FOR BOLTS, NUTS, AND
GASKETS
 MQ-SP-P-5024 – PIPING SUPPORT ELEMENTS
 MQ-SP-P-5029 – WELDING / NDE SPECIFICATION FOR SHOP/FIELD
FABRICATED PIPE
2.2 SASO - Saudi Arabian Standards Organization
2.3 SAF Directives
 Safety & Fire Protection Directives for the industrial facilities under High
Commission for Industrial Security
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 5 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

2.4 Factory Mutual (FM)


2.5 NFPA - National Fire Protection Association
 NFPA 17A – Standard for Wet Chemical Extinguishing Systems
 NFPA 70 - National Electrical Code
 NFPA 72 - National Fire Alarm and Signaling Code
 NFPA 101 - Life Safety Code
2.6 OSHA - Occupational Safety & Health Administration
 Subpart-L Fire Protection
2.7 UL - Underwriters' Laboratories, Inc
 UL - Fire Protection Equipment Directory
 UL 300 - Wet Chemical Extinguishing System Units

3.0 DEFINITIONS

Refer to NFPA 17A.

4.0 HEALTH AND SAFETY CONSIDERATIONS

All works undertaken in relation to this Specification are to be completed in full compliance
with the respective health and safety requirements established by the following:
 MARAFIQ Standards
 Kingdom of Saudi Arabia
Legislation, Regulation, Standards and Codes.
 Contractor
Health and Safety Standards and Systems as accepted by MARAFIQ
 Health and Safety Conditions
Refer to NFPA 17A.
In the absence of any of the above, best accepted industry practice shall be employed
throughout.

5.0 SUBMITTALS

The Contractor shall submit the following items for review and approval before commencing
the work:
 Product Data
Product data shall include principal dimensions, general construction and material for
each item intended to be furnished and installed.
Manufacturer's catalog data sheets shall be submitted for all nozzles, valves, controls and
all other accessories and system components.
 Installation Instructions
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 6 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

Submit copies of the manufacturer's installation and maintenance instructions for all
equipment. Include valve data and servicing instructions.
 Shop Drawings
Working plans, prepared according to NFPA 17A.
 Calculations
The calculations for the entire Automatic Wet Chemical Extinguishing System shall be
by a computer generated calculation program. The calculations shall meet the
requirements of NFPA 17A

 As-Built Drawings
Clearly indicate nozzles, cylinders, and piping on the Shop Drawings and As-built
plans.
Clearly indicate valves, alarms and control locations.

 Maintenance and Operating Instructions


Submit data conforming to NFPA 17A for maintenance of the system.
Equipment manufacturer recommended spare parts and tools list.

 Operation and Maintenance Manuals.


 Test Reports
Accurately record and report the methods of testing, times and dates of the test,
witnesses to the test, and the results of the test.

6.0 QUALITY CONTROL

The Contractor shall be responsible for the quality of work and shall develop and propose
programs and methods of construction and testing to achieve the specified quality for
approval.
The Contractor shall prepare and submit a set of As-Built Drawings and hydraulic calculations
of the system, maintenance and instruction bulletins and the applicable parts of the
Contractor’s material and test certificates covering material and tests certifying that the work
has been completed and tested in accordance with plans and specifications.
6.1 Engineering Responsibility
Preparation of working plans, calculations and field test reports by professional
specialized fire protection engineer.

6.2 Single-Source Responsibility


System components and accessories shall be obtained from one source and a single
manufacturer, as far as possible.

6.3 Product Quality


Products shall be free of defects in materials, fabrication, finish and installation.
All materials and performance shall meet the appropriate NFPA standard.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 7 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

All equipment shall be constructed using new materials designs and built in
accordance with the best practices of the industry.
Each item of equipment shall be listed by Underwriters Laboratories (UL) and/or
approved by Factory Mutual (FM).
Each major item of equipment shall bear the manufacturer’s name, trademark, serial
number and a UL or FM label.
Any nozzle that is damaged, painted, or sprayed with any obstructive material shall
not be accepted.

6.4 Electrical Components, Devices and Accessories


Electrical components, devices and accessories shall be UL Listed and/or FM
Approved and shall meet the requirements of NFPA 70 and NFPA 72.

7.0 WET CHEMICAL EXTINGUISHING SYSTEM USES AND LIMITATIONS

A Wet Chemical Extinguishing System shall be used on the following hazards;


 Restaurant, commercial, and institutional hoods
 Plenums, ducts, and filters with their associated cooking appliances
 Special grease remocal devices
 Odor control devices
 Energy recovery devices installed in the exhaust system

8.0 DESIGN CRITERIA

Automatic Wet Chemical Extinguishing System shall be designed to discharge a wet


extinguishing agent to extinguish a fire in the area being protected. The minimum volume and
rate of application shall meet the requirements of NFPA 17A
The Automatic Wet Chemical Extinguishing System shall utilizing a fixed pipe and nozzle
distribution network, designed in accordance with NFPA 17A standard, to provide fire
protection.
Automatic Wet Chemical Extinguishing System shall be capable of full operation even in the
event of an electric power supply failure and shall comply with requirements of NFPA 70
standard.
The Automatic Wet Chemical Extinguishing System shall be designed to avoid undue danger
to the lives and safety of its occupants from a fire.
The nozzles, controlling devices, protective devices, alarm systems, supervisory devices and
related equipment shall be made compatible so that all equipment shall function together as
specified.
System design and installation shall reflect high quality professional work that properly
accounts for practical maintenance concerns and aesthetic concerns, as well as meets the
design requirements.
The piping system shall be sized in accordance with a calculation technique to ensure
availability of flows and pressures required for correct performance of the system.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 8 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

Duration of the agent shall meet the requirements of NFPA 17A and Project Specifications.
8.1 Calculations
The pipe diameters of the Automatic Wet Chemical Extinguishing System shall be
based on calculations to determine the required pressures and required flows to the
nozzles.

9.0 PRODUCTS

All goods and products covered by these Specifications shall be procured, when available,
from an in-Kingdom manufacturer. Procurement of all goods and products manufactured out-
of-Kingdom must be approved. All products, system components and hardware shall be in
compliance with NFPA 17A. Only listed materials and devices shall be used in the installation
of the Automatic Wet Chemical Extinguishing System.
All products, system components and hardware shall be in compliance with the applicable
NFPA standards and the Project Specifications.
All valves, nozzles, alarms and any additional fire fighting equipment shall be UL listed and/or
FM approved.
9.1 Discharge nozzles
Discharge nozzles shall be listed for rate of discharge, effective range, and pattern or
area of coverage.
Discharge nozzles shall be provided with blow-out caps to ensure unobstructed
opening upon system operation.
Discharge nozzles shall be permanently marked for identification, as per the NFPA
17A.

9.2 Wet Chemical Containers


The wet chemical agent containers and expellant gas shall be floor mounted and
suitably supported on steel rack for each bank of cylinders, and shall have facilities
for convenient individual servicing.

9.3 Control Panel


The control panel shall provide centralized monitoring and control of the fire
detectors, local release devices, abort switches, alarm appliances, and solenoid
valves. On receiving a fire signal from fire detectors or a local release device, the
control panel shall activate the solenoid valves and alarms.
The control panel shall be UL listed and/or FM approved, and complies with the
requirements of NFPA 17A and NFPA 72.

9.4 Discharge Indicator


The discharge indicator shall be designed to display a message to personnel. It shall
be operated by an alarm signal from the control panel and its operation shall continue
even after the agent discharge. The message on the indicator shall flash in red to
keep out of the protected room. The device shall operate on 24 VDC and shall be
powered from control panel.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 9 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

9.5 Warning Sounder / Strobe


Sounders and strobes shall operate on 24 VDC and shall be powered by the control
panel.

9.6 Pipes, joints and fittings


Piping and fittings shall meet the requirements of NFPA 17A.
Pipe and fittings shall be suitable for the agent used.
Galvanized pipe and fittings shall be used unless specifically listed with the system.
Copper pipe and fittings shall not be used.

9.7 Pipe Hangers and Supports


Pipe hangers and supports shall meet the requirements of NFPA 13 and NFPA 17A.

10.0 EXECUTION

All products and equipment shall be installed in accordance with MARAFIQ regulations,
applicable local codes and standards, the manufacturer's written installation instructions and
Project Specifications.
The Automatic Wet Chemical Extinguishing System shall be installed in accordance the
applicable NFPA standards.
Provisions shall be made to facilitate frequent inspection, testing and maintenance as
described in NFPA 17A.
Protect all equipment and materials at all times.
Cover and protect equipment and materials from dirt, water, chemical or mechanical damage.
10.1 Protection of Piping and Equipment Against Damage
Protect all equipment materials at all times.
Close pipe openings with caps or plugs during installation. Cover and protect
equipment materials from dirt, water, chemical or mechanical damage.

11.0 INSTALLATION

All materials and equipment used in the installation of the Automatic Wet Chemical
Extinguishing System shall be new and the latest design by the manufacturer.
All materials, valves and devices essential to successful system operation shall be UL Listed
and/or FM approved.
All openings in the room walls and slab made either for present or future equipment, cables
and HVAC ducts shall be properly sealed using approved fire stops.
11.1 Power source
The primary source of energy for the operation and control of the system shall have
the capacity for intended service and shall be reliable.
In the event of a primary power failure, the control panel shall have battery backup to
support the entire system for 24 hours and then perform an alarm sequence for the
maximum discharge time for the longest system discharge plus at least 10 minutes
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 10 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

extra. A charger shall be provided to recover the batteries in 48 hours from a fully
discharge condition. Standby batteries shall be of the sealed, lead acid type.

11.2 Control Panel


The Control Panel shall be installed at a location near to the entrance to facilitate
easy access. Enclosure shall permit front access only.

11.3 Gas Storage Cylinders


The wet chemical agent shall be stored in a dry location at ambient temperature.
Cylinders shall be floor mounted and suitably supported on steel rack for each bank
of cylinders, and shall have facilities for convenient individual servicing.
The cylinder bank shall be located as near as possible to the area to be protected.

11.4 Discharge Indicator


The discharge indicator shall be installed above the entrance of the protected
facilities.

11.5 Local Release Switch / Abort Switch


The local release switch shall be located outside, near the main door or near the area
being protected. The abort switch shall be installed at the same location where the
local release switch installed.

11.6 Warning Sounder / Strobe


Sounders and strobe lights alarm shall be located inside and outside the protected
room or area.

11.7 Piping
Installed pipe and fittings shall meet the requirements of NFPA 17A.
All pipe and fittings shall be installed aboveground.
Close pipe openings with caps or plugs during installation.
Copper pipe and fittings shall not be used.

11.8 Hanging, Bracing and Restraint of System Piping


Installation of hangers, hanger rods, supports and fasteners shall be in accordance
with the requirements of NFPA 17A.
All piping, cylinder banks, valves and other appurtenances shall be properly
supported and/or anchored to prevent any movement in the system.

11.9 Pipe Sleeves


Sleeves shall be provided where piping passes through walls, floors, roofs, beams
and partitions. Sleeves shall be of sufficient length to pass through entire thickness of
walls, floors, roofs and partitions.
Sleeves shall be secured in proper position and location.
Size and install so that system piping is not stressed.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 11 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

Sleeves shall be installed prior to construction of walls or pouring of concrete.

11.10 Escutcheon Plates


One piece or split hinge type metal plates shall be provided for piping passing
through floors, walls and ceilings in exposed areas.
Plates shall be securely anchored in place with setscrews or other approved positive
means.

11.11 Installation/Caution Signs


The system shall be installed in accordance with all applicable NFPA 17A
requirements and manufacturer’s design, installation, recharge and maintenance
instructions by a factory trained and authorized personnel.
Visual and audible warning signs/devices shall be provided in conspicuous locations
in every protected space.
Appropriate warning signs/indications shall be affixed outside of those spaces where
concentrations of gas can accumulate, not only in protected areas but in adjacent
areas also where fire suppression agent could migrate or leak. Warning
signs/indications shall include emergency lighting, illuminated escape arrows,
emergency exit signs and the like. Safety caution and indication signs shall be
installed at clear locations stating “Gas Protected Area”.

12.0 COORDINATION

Coordinate location of all nozzles, pipe, gas cylinders, control panels and all necessary
accessories for proper operation of the system.

13.0 TESTING

The completed installation shall be inspected, tested and commissioned by an approved fire
suppression system specialist Engineer of the Fire Suppression System designer/supplier, in
the presence of Company’s representatives.
All mechanical and electrical components including detection and actuation devices shall be
tested as per NFPA 17A, 72 and according to the manufacturer’s recommended procedure.
Standard tests shall be carried out for checking the various instruments, instrument loops,
insulation and continuity for cables.
Concealed pipe joints such as those in walls, ceilings and the like shall be tested before the
piping is concealed.
On completion of the testing and commissioning, the fire suppression system, and the fire and
gas detection system shall be left in a “live” condition.

14.0 CERTIFICATION

The Contractor shall prepare and submit a set of As-built Drawings and calculations of the
system, maintenance and instruction bulletins, and the applicable parts of the Contractor’s
material and test certificates covering material and tests certifying that the work has been
completed and tested in accordance with plans and specifications.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4917
Project Name: Date: Sept. 30, 2011
Contract Number: Page 12 of 12
Revision 2

SPECIFICATION – AUTOMATIC WET CHEMICAL EXTINGUISHING SYSTEMS

15.0 TRAINING

Prior to acceptance of the installed system, Contractor shall provide on site training by an
approved fire suppression system specialist Engineer of the Fire suppression system
designer/supplier, for operation, maintenance and trouble shooting of the system. Training
shall consist of:
 System Operation
 Control system operation
 Trouble shooting procedures
 Emergency procedures
 Safety requirements
 Demonstration of the system excluding gas release
 Periodical Inspection

16.0 DELIVERY, HANDLING AND STORAGE

The Contractor shall deliver, handle and store equipment and material units in accordance
with Project Specifications.
All products shall be inspected at time of delivery for damage and for compliance with
specifications.
All products shall be handled and stored as recommended by the manufacturer.
Nozzles must be handled with care.
Nozzles shall be delivered in their original packages, containers or bundles bearing the brand
name and the name of the material.
All equipment shall be stored in a cool, dry place.
Pipe, fittings, valves, and nozzles shall be stored with open ends sealed until removed for
installation.
Materials shall be protected from weather, soil; and damage during delivery, storage and
construction.
Any products that are damaged or found not to be in accordance with the specifications shall
be immediately replaced.

You might also like