Professional Documents
Culture Documents
MLFB-Ordering data
6SL3210-1PE31-1AL0
Figure similar
Output
Ambient conditions
Number of phases 3 AC
Cooling Internal air cooling
Rated voltage 400 V
Rated current (LO) 110.00 A Cooling air requirement 0.083 m³/s (2.931 ft³/s)
Overload capability
1.1 x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s 1.5 × rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s
1.5 × output current rating (i.e., 150 % overload) for 57 s with a cycle time of 300 s 2 × output current rating (i.e., 200 % overload) for 3 s with a cycle time of 300 s
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated Wed Nov 27 18:51:39 CET 2019
Page 1 of 2
Data sheet for SINAMICS Power Module PM240-2
MLFB-Ordering data
6SL3210-1PE31-1AL0
Figure similar
Net weight 28.00 kg (61.73 lb) Conductor cross-section 25.00 ... 70.00 mm² (AWG 4 ... AWG -1)
Depth 237 mm (9.33 in) Conductor cross-section 25.00 ... 70.00 mm² (AWG 4 ... AWG -1)
Comparison with the reference converter (90% / -52.95 % Conductor cross-section 10.00 ... 35.00 mm² (AWG 8 ... AWG 2)
100%)
Cable length 10 m (32.81 ft)
I
1197.0 W (1.57 %) 1387.0 W (1.82 %) 1699.0 W (2.23 %)
PE connection Screw-type terminals
100%
Max. motor cable length
663.0 W (0.87 %) 732.0 W (0.96 %) 838.0 W (1.10 %) Unshielded 300 m (984.25 ft)
50%
Standards
480.0 W (0.63 %) 511 W (0.67 %)
25%
Compliance with standards UL, cUL, CE, C-Tick (RCM), SEMI F47
50% 90% f
CE marking Low-voltage directive 2006/95/EC
The percentage values show the losses in relation to the rated apparent power of the converter.
The diagram shows the losses for the points (as per standard EN 50598) of the relative torque
generating current (I) over the relative motor stator frequency(f). The values are valid for the basic
version of the converter without options/components.
*converted values
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated Wed Nov 27 18:51:39 CET 2019
Page 2 of 2