Professional Documents
Culture Documents
Kato Generator Manual PDF
Kato Generator Manual PDF
Serial Number
BEARING LUBRICATION
012-68369-07 012-68369-06
SUMP CAPACITY
Safety instructions 4
Ratings/description 4
Rotor 7
Bearings 8
Connection boxes 8
Excitation system 9
PMG system 11
Installation 12
Receiving inspection 12
Location 12
Base design 12
Note: Because of rapid changes in designs
and processes and the variability of Kato Assemble to prime mover, alignment 13
Engineering’s products, information in this
manual must not be regarded as binding Two-bearing alignment 13
and is subject to change without notice.
Foot deflection 15
The image on the front cover is representa-
tive only. Several variations are available Doweling 15
within the range of generators covered
within this manual. Electrical connections 15
Space heaters 15
Continuous operation 22
Idling 23
Parallel operation 23
Maintenance 26
Schedules 26
Maintenance procedures 28
Cleaning 29
Please read this manual in its entirety before unpacking, installing, and
operating your generator.
Safety instructions
In order to prevent injury or equipment damage, everyone involved in
installation, operating and maintenance of the generator described in this
manual must be qualified and trained in the current safety standards that
govern his or her work.
Ratings/description
Nameplates, which are located on the side of the generator, include
serial and model number as well as rating information and bearing and
lubrication information.
• Air filtered
• Air-to-air heat exchanger cooled (TEAC/CACA)
• Air-to-water heat exchanger cooled (TEWAC/CACA)
• Weather protected II
• IP 22, 23,25,44,54
• Sealed windings
See your drawings included in the drawing section for details on your
unit.
Stator
The stator consists of the supporting frame, core, and armature windings.
The stator core is made from laminations, thin sheets of electrical steel,
which are stacked and held in place by steel end rings and support
bars. The rings and bars are welded to or are part of the steel frame.
Base mounting plates are welded to the bottom of the frame. The base
mounting plates allow the assembly to be mounted on the genset base.
Some stators are made of rolled steel with foot gussets. See Figure 2.
Rotor
The main rotor assembly is the revolving field. It consists of windings
in a core, which is in turn mounted on a steel shaft. The exciter armature
assembly and permanent magnet generator (PMG) rotor are also mounted
on the shaft as are the fan(s) and other optional accessories. The core
consists of laminations, thin sheets of electrical steel, which are stacked
together. The core makes the salient poles. See Figure 3.
The end plates are brazed to adjacent poles to form a continuous damper
winding. The ends of the windings are supported with bars or aluminum
pole shoes. Some designs have neither end shoes or plates. The rotor is
vacuum-pressure impregnated with resin.
The shaft is made from high-strength rolled or forged steel and machined
to accommodate all the rotating generator components. Keyways in the
shaft ensure precise positioning of the rotor, fans, exciter armature, and
PMG rotor as well as drive couplings. On the exciter side, the shaft has
a slot or hole in its centerline for running the revolving field leads to the
rectifier.
Connection boxes
The main lead connection box houses the load lead terminals, and may
be located either side or on top. In addition, the generator may have
auxiliary connection boxes for connecting temperature detector outputs,
space heater connectors, and sensing outputs. See your drawings for
details. See Figure 5.
Output leads
Main stator
(armature)
PMG stator Exciter stator
(armature) (field)
Page 10
PMG rotor
(field)
Rectifier
The PMG stator is a stationary armature and is located within the stator
assembly that also contains the exciter stator or is a separate stator
mounted next to the exciter stator. The PMG stator consists of steel
laminations. The laminations are held in place by steel compression rings
and are welded to the frame bars of the exciter-PMG frame. The PMG
windings are placed in slots in the laminations. Insulating wedges are
inserted at the top of each slot to hold the coils in position.
The PMG rotor consists of rectangular permanent magnets and cast pole
tips secured to a steel hub with nonmagnetic stainless steel bolts. The
PMG rotor is keyed to the shaft and secured with a nut and lock washer.
Figure 8: PMG
Base design
The type of base to be used will depend upon the nature of the
installation site. However, the generator base must be rigid, level, and
free from vibration. Mounting holes must be larger than the fasteners to
allow for alignment.
Follow the tolerances specified by the coupling manufacturer when they Use dial indicators that are rigid so indicator
are less than described in this manual. sag won’t be a factor. Using the shortest
offset distance of the indicator bracket will
reduce the effects of indicator droop or sag.
Use shims, if necessary, between the mounting pad and the base to
properly level and align the generator to the prime mover. During alignment, you may also need to
compensate for engine expansion due to
Install the coupling(s) on the generator and engine drive shafts in heating. Generator expansion is generally
accordance with coupling manufacturer installation procedures. Use a not considered a factor.
straight edge and a thickness gauge for rough alignment as shown in
Figure 9. Check for angular and parallel alignment as follows: If the genset is moved to a different
location, check alignment before startup.
Straight edge
Caution: Do not pry on the generator fan.
Thickness gauge
Figure 9: Rough alignment
Dial indicator
Doweling
In case the mounting bolts loosen during operation, doweling will
prevent movement of the generator. Dowel as follows:
Check the alignment after the generator has been in operation for at least
48 hours. If alignment is not satisfactory, realign.
Drill holes through the footpads and into the base in two mounting pads
opposite each other. Drill the holes slightly smaller than the dowel pin.
Ream the holes to the proper diameter for the pin. Clean out chips, and
install the pins.
Electrical connections
If the generator was subjected to a rapid change in temperature, freezing
or wet conditions during shipment or storage, measure the insulation
resistance of each winding and dry the generator, if necessary, as
described in the maintenance section.
Space heaters
To prevent water condensation during long periods of downtime, connect Warning: The space heaters are designed
the space heaters so they start when the generator is turned off and stop to be energized when the generator is
when the generator is switched on. Refer to the electrical diagrams for shut down. They are hot enough to cause
skin burns. Terminals for power at the
the space heater characteristics.
space heaters are live during operation.
Disconnect power to the space heaters
Inspection before startup before removing the generator covers.
After electrical connections have been made, perform the following
checks:
c. Turn the rotor slowly with the appropriate starting mechanism (bar
the engine or flywheel) through one revolution to see if the rotor
turns freely.
e. Determine the direction of the engine rotation, and make sure that it
matches the rotation of the generator.
f. Make sure the power requirements comply with the data on the
generator nameplate.
i. Remove tools and other items from the vicinity of the generator.
Make sure the storage area temperature is between 10º F (-12o C.) and
120º F (49o C.) and the relative humidity is less than 60%.
(Store the generators in an ambient temperature of approximately normal
room temperature if possible).
1. Remove oil drain port plug and drain oil from the bearing (refer
to the specific generator outline drawing for drain location).
2. Identify the sleeve bearing casing oil inlet port on one side of the
bearing (refer to the specific generator outline drawing oil inlet
Caution: Before using this product, the location).
operator must read carefully the MSDS
sheet to ensure that the process is
carried out safely for the operator and the
3. Attach a manual pump filled with Daubert Nox-Rust VCI-10
preservative. Flush 2 gallons of the preservative through
environment.
the oil inlet port for 1 minute at 2 GPM flow.
Drain the bearing casing after flushing and reinstall the
drain and oil plugs. Repeat this procedure for each bearing.
When the unit is taken out of storage, check the insulation resistance on
all windings. See pages 30 and 31.
Note: It should not be necessary to open
Clean the shaft of anti-corrosion agent. the bearing for cleaning the remaining
preservative before starting the generator,
however it is recommended to verify the
compatibility of the VCI-10 oil with the
specific oil used to lubricate the bearings.
6. Actuate the auto voltage rheostat. Then start the genset, and bring it
to rated speed. Adjust the voltage to the desired value.
7. Close the output circuit breaker. Then check the generator voltage
Caution: Operating the unit beyond name- and voltage regulation. Apply load in steps until the rated load is
plate values may cause equipment damage reached.
or failure.
8. Check for vibration levels at no load and rated load. A slight increase
is normal. As the load is maintained for 2-3 hours, the vibration
levels will gradually increase and reach a final level.
3. Close the output circuit breaker, and apply load in gradual steps
until the rated load is reached. Note the voltage regulation with the
changes in load steps.
4. Check for vibration levels at no load and rated load. A slight increase
is normal. As the load is maintained for 2-3 hours, the vibration
levels will gradually increase and reach a final level.
EF2 EF1
2. Disconnect the exciter field coil wires EF1 at the terminal EF1 and
EF2 at the terminal EF2, and connect the battery positive lead to the
field coil lead EF1.
3. Flash the field by touching the battery lead to the field coil circuit
terminal EF2.
5. Reconnect the field coil lead EF1 to terminal EF1, and reconnect the
field coil lead EF2 to terminal EF2.
6. Start the generator, and check for voltage build up. Reflash if
the generator output voltage does not build up, or flash with the
generator running, the field coil wires connected to the regulator, and
a 3-amp or larger diode off the positive terminal of the battery per
Figure 12.
The guide is used in the following manner: Find the point where the
vertical line (determined by the maximum current in any of the phases
and expressed in percent of rated current) crosses the horizontal line
(determined by the minimum current in any of the phases and expressed
in percent of rated current). Ensure the point where these two lines
intersect is within the permissible allowable unbalance region for safe
operation of the generator.
100
Min. current in any phase (% of rated)
80
Allowable
unbalance
60
Excessive
40 unbalance
20
0 20 40 60 80 100
Where the generator set is provided with field circuit breakers, set the
circuit breaker to the off position while the generator is running at idle
speed.
Where the generator set does not have any of the above options, remove
the wires from the voltage regulator input power terminals when the
engine is running at less than rated speed.
Parallel operation
For the generator to operate in parallel with a system in operation, the
phase sequence of the generator must be the same as that of the system.
Use transformers to reduce the voltage to an acceptable level, and then
use a phase rotation meter or incandescent lamp method, described in
electrical machinery handbooks, for a phase sequence check.
The output voltage at the paralleling point must be the same each instant,
which requires that the two voltages be of the same frequency, same
magnitude, same rotation, and in coincidence with each other.
Load Synchronizing
switch lamps
Each prime mover in the system must have the same speed regulating
characteristics, and the governors must be adjusted to give the same
speed regulation as determined by applying load that is proportional to
the full load rating of the generator.
If the set is provided with a unit/parallel switch, set the switch to the
parallel position on the unit being synchronized.
Every day
Visually check generator bearing housings for any sign of oil seepage.
Check the control panel voltmeter for proper stability and voltage output.
With generators that have sleeve oil bearings, check the operating
temperatures and sight glass levels (if applicable).
Every week
Visually inspect the bearing exterior for dirt, and clean if necessary.
Inspect any generator air filters for build up of contaminants, and clean or
replace as required
Clean the inside of the outlet box, air screens, bearing housings, and air
baffles with compressed air and electrical solvent if needed.
With generators that have sleeve oil bearings, replace the bearing oil.
Remove the endbrackets, and visually inspect the generator end windings
for oil or dirt contamination. Excessive contamination may necessitate
surface cleaning with compressed air and electrical solvent.
Clean the generator windings using either (depending upon the severity
of contamination) 1) compressed air and electrical solvent or 2) de-
greaser and high pressure hot water wash. Dry the windings to acceptable
resistance levels (see the dry out procedure).
With generators that have ball or roller bearings, replace the bearings.
With generators that have sleeve bearings, replace the bearing liners and
oil seals.
Cleaning
Exterior: Wipe loose dirt from the exterior with a clean, lint-free cloth. Warning: When using cleaning solvents,
Remove stubborn accumulations of dirt with a detergent or solvent ensure adequate ventilation and user
that won’t damage the paint or metal surfaces. Use a vacuum to clean protection.
ventilating ports.
After the initial cleaning with a vacuum, compressed air may be used to
remove the remaining dust and dirt. Compressed air used for cleaning
must be clean and free of moisture or oil. Air pressure or velocity must
be adequately controlled to prevent mechanical damage to the insulation.
4. Ground the exciter field leads to the exciter field frame for several
minutes after the megger has been disconnected. This will allow the
voltage build up to be properly discharged.
Note: New generators should measure
about 100 megohms minimum of insulation 5. Repeat steps 1-4 for the PMG armature (stator).
resistance when meggered. Generators that
read 50 megohms or less should be dried
out according to the dry out procedures Exciter armature
here. Generators with insulation resistance
readings of 10 megohms or less should be 1. Disconnect the exciter armature leads from the rotating rectifiers.
investigated.
4. Ground the field leads to the shaft after disconnecting the megger for
a minimum of 1 minute. This will allow the voltage build up to be
properly discharged.
Main stator
4. Ground the leads to the frame after the 1-minute megger test. This
will allow the voltage build up to be properly discharged.
Drying with external heat: Place heat lamps, space heaters (in addition
to the ones already supplied) or a steam pipe near the windings. Monitor
winding temperatures. Raise winding temperature gradually at a rate
of 10-20° F (-12° to -6° C) per hour up to 200° F (93° C). Measure
insulation resistance at 1-hour intervals. Typically the insulation
resistance will slowly drop while the temperature is coming up, and then
gradually increase and level out.
Bearing lubrication
Sleeve bearings: Lubricate the bearings in accordance with the
lubricating instructions attached to the generator and the bearing
lubrication instructions, which are provided in the manual package as
supplementary material.
Rectifier tests
If a failure of a rectifier is suspected, remove the exciter cover. Remove
the nut and washer holding the rectifier in the heat sink, and remove the
diode lead wire. Lift the rectifier from the heat sink (see figure 20 for
an overview). Test the entire rectifier with an ohmmeter or test lamp as
follows:
Negative
Positive
Positive
Cathode
Ohmmeter
Anode
Loosen or remove the bolts (as needed) from the coupling to separate the
coupling halves.
1. Remove the clips securing the exciter field leads to the exciter
frame, the generator frame and generator endbell.
Caution: Do not pull on the edges of the
rectifier or on the exciter armature windings. 2. Disconnect the generator field (rotor) leads from the positive
(+) and negative (-) exciter armature lead terminals located on
the rotating rectifier assembly.
3. Using a hoist and strap, slide out and remove the exciter
armature and rectifier tube assembly, which is keyed onto the
shaft.
4. Loosen the bolts that connect the carriers to the housing, and Note: If necessary, tap the bearing housing
remove them. lightly with a rubber or fiber mallet to loosen
it.
5. Loosen and remove the split line bolts.
7. Remove the garter springs and the gap seal and labyrinth seal.
3. On the DE side lift the housing out and over the top of the
generator.
5. Lift the shaft up slightly (about 0.015 to 0.25 inch) on both ends
of the rotor to the point where the shaft and bottom half of the
bearing liner do not touch each other.
Warning: Before transport or lifting bearing 7. On the opposite-drive-end side, remove the bottom halves of the
components, check if the eye bolts are tight. bearing liners.
Insecure eyebolts could result in the part
coming loose and falling Make sure the
eyebolts are not exposed to bending stress, 8. Rotate the bottom half of the liner 180º so it is facing upward
otherwise they could break. Make sure the
(where the top half of the liner was). Move the shaft
lifting equipment does not contact the seal
and running surfaces of the shaft. as necessary. Slide the liner forward so it rests on the bottom
bearing housing’s top surface.
Note: On the DE side, you can remove
the bearing liners after the rotor has been 9. Use lifting eyes and hoist to remove the liner.
removed.
10. Remove the bottom half of the bearing housings from the frame.
Caution: Make sure the RTD is removed
before rotating the bearing liner. 11. Remove the opposite-drive end bearing bracket and air baffle.
Caution: Make sure the pipe is strong Float out the rotor.
enough to support the weight of the rotor
and that it does not have rough edges on 1. Fit a pipe over the shaft. Depending upon the space available,
the inside, which could damage the shaft. you may have to use a pipe that can be assembled, adding an
To prevent tension on the shaft, put slings additional piece during each stage of movement outward.
around the largest shaft step possible. Make
sure the rotor does not hit the stator. 2. Attach slings around the pipe on one end and around the shaft
on the opposite end.
Note: If the generator is mounted on
the engine base, the drive end bearing 3. Lift up the rotor, and move it out, gently resting the rotor on
bracket and air baffle may not be able to be the stator as the slings are moved down the pipe for the next
removed until the rotor passes through the lifting stage. (See figure 23).
generator.
4. Remove the drive-end side bearing liners from the shaft.
1. Make sure the surfaces are clean. Apply STP Oil Treatment
over the running surface on the shaft where the liner will sit.
2. Make sure the engraved numbers on the top and bottom halves
correspond and are on the same side. Mate the top liner over the
bottom liner on the shaft.
3. Put Loctite 242 on the split line screws, insert the screws, and
tighten.
Caution: Make sure the pipe is strong
enough to support the weight of the rotor
Float in the rotor. and that it does not have rough edges on
the inside, which could damage the shaft.
1. Move the rotor up and in line with the stator. Fit a pipe over To prevent tension on the shaft, put slings
the drive end of the rotor. Depending upon the space around the largest shaft step possible. Make
available, you may have to use a pipe that can be disassembled, sure the rotor does not hit the stator.
taking off an additional piece during each stage of movement
inward.
2. Attach slings around the pipe on one end and around the shaft
on the opposite end.
3. Lift up the rotor, and move it in, gently resting the rotor on the
stator as the slings are moved down the pipe
Install the bottom bearing housings. Before installing, brush Nox rust on
frame mating surfaces that will fit into bearing housing.
1. Lift the shaft up slightly (about 0.005 inch) on both ends of the
rotor to the point where shaft and bottom half of the liner do not
touch each other.
2. Make sure the surfaces are clean. Apply STP Oil Treatment
over the running surface on shaft where the liner will sit.
4. Remove the lifting eyes from the liner. Move the rotor gently
from side to side and up and down as necessary, and slide the
liner down into the housing. If the liner doesn’t turn easily, check
the position of the shaft and the alignment of the housing.
3. Put Loctite 242 on the split line screws, insert the screws, and
tighten.
3. Put the top housing in place, making sure the dowel pin in
the inside diameter of the top housing lines up with the pin hole
in the bearing liner. Put Loctite 242 on the split lines screws,
and fasten the housings together, leaving the screws snug but not
tight.
1. Cut the gasket, if necessary to fit it over the shaft. Coat it with
Loctite Hi-Tack gasket sealant or equivalent, and fit it over the
shaft.
2. Attach the gap seal and labyrinth seal with the labyrinth
seal nearest the bearings. Put the two halves of the seals
together, and slip the garter springs around the seals to fasten
them. (The outside seal carrier on the drive end side only
gets a labyrinth seal.)
3. Align the PMG rotor with the key on the shaft and holding by
the inside magnets, slide the PMG into position.
Check the air gap between the PMG rotor and PMG stator.
2. Keep the gage at the tightest point, and turn the generator over
to measure the air gap as the rotor turns. Minimum air gap is
0.035 inch.
Check the air gap between the exciter armature and exciter stator.
2. Keep the gage at the tightest point, and turn the generator over Caution: Do not pound on the rectifier.
to measure the air gap as the rotor turns. Minimum air gap is
0.035 inch.
Mount the generator to the prime mover, and make the electrical
connections as described earlier.
Table 6: Troubleshooting
* Inch-pounds
SCREW Set Screws Brass Screws Stainless Screws Grade B Top Lock Nuts
SIZE Foot-Pounds Newton-Meter Foot-Pound Newton-Meter Foot-Pound Newton-Meter Foot-Pound Newton-Meter
Ft-Lbs Tol N-M Tol Ft-Lbs Tol N-M Tol Ft-Lbs Tol N-M Tol Ft-Lbs Tol N-M Tol
#4-40 4* 0.4 5* 0.6
#6-32 8* 0.9 10 * 1.1
#8-32 20 * 2.3 16 * 1.8 21 * 2.4
#10-24 18 * 2 24 * 2.7
#10-32 34 * 3.8 33 * 2.9 33 * 3.7
1/4-20 6 1 9 2 5 1 7 2 6 1 8 2 6 1 8 1
5/16-18 13 2 18 3 9 2 12 2 11 2 15 3 11 2 15 3
3/8-16 23 2 31 6 16 3 22 4 21 4 28 5 18 2 24 3
7/16-14 36 5.14 50 10 26 5 35 7 33 7 45 9 28 4 38 5
1/2-13 50 10 70 14 35 7 45 9 45 9 60 12 44 ** 6 60 12
9/16-12 55 10 70 13 60 11 80 15
5/8-11 110 18 145 24 85 14 115 19 100 17 140 23
3/4-10 180 35 240 46 120 23 160 31 130 25 180 35
7/8-9 430 60 580 82 205 30 280 40
1.0-8 580 70 790 90 300 35 400 45
1 1/8-7 430 45 590 60
1 1/4-7 550 60 750 80
1 3/8-6 700 70 950 100
1 1/2-6 930 100 1250 130
* Inch-pounds
** For Electrical Lugs use 44 Ft-lbs (60 N-M)
Chart 1: Torque Values
Grade 8.8
SCREW Grade 4.8 to 6.8 Grade 6.9 to 8.8 GASKETED COVERS Grade 10.9
SIZE Foot-Pounds Newton-Meter Foot-Pound Newton-Meter Foot-Pound Newton-Meter Foot-Pound Newton-Meter
Ft-Lbs Tol N-M Tol Ft-Lbs Tol N-M Tol Ft-Lbs Tol N-M Tol Ft-Lbs Tol N-M Tol
M4 x .70 1.1 1.5 2 2.7 2.9
M5 x .80 2.3 3.1 4 5.3 6
M6 x 1.00 4 1 5.2 1 7 1 9.3 2 4 1 5 1 10 2 14 3
M7 X 1.00 6.5 1 8.7 2 11 1 15 3 16 5 34 7
M8 x 1.25 10 2 13 3 18 2 24 5 11 2 15 4 25 10 54 14
M10 x 1.50 20 4 27 5 32 4 43 9 13 3 18 4 47 15 95 20
M12 x 1.75 34 7 45 9 58 7 77 15 19 4 26 5 83 20 135 27
M14 x 2.00 54 10 72 13 94 10 125 23 132 30 200 40
M16 x 2.00 80 13 108 18 144 13 192 32 196 40 275 55
M18 x 2.50 114 22 152 29 190 22 253 50 269 50 500 70
M20 x 2.50 162 23 216 30 260 23 347 50 366 60 800 80
M22 x 2.50 202 23 269 31 368 23 491 55 520 90 1200 120
M24 x 3.00 245 25 327 33 470 25 627 65 664 120 1650 160
M27 x 3.00 360 40 480 52 707 40 943 100 996 180 2400 250
M30 x 3.50 500 50 667 70 967 50 1289 130 1357 230 3100 300
Special tools
Bearing puller For changing bearing.
Exciter puller For pulling exciter armature
Standard tools
Cable tool Crimping
Flashlight As required
Grease gun For lubricating bearings
Hammer Soft-faced
Lamp (incandescent) Safety light
Screwdrivers Standard, sized as required
Screwdrivers Phillips, sized as required
Wrench Adjustable, 12-inch
Wrench Torque 0 to 100 ft-lb
Wrench set Allen, 1/8 to 1/2 inch
Wrench set Socket, 1/4 to 1 inch with 3/8 and 1/2 inch drive
Wrench set Standard, open-end/box-end combination sized 1/4 to 1 inch
Vacuum Electric with nonmetallic nozzle
Materials
Air Compressed, dry.
Corrosion inhibitor Nox-Rust VC #10 Oil or equivalent
Covering material Waterproof desiccant bags for protection from
moisture during long-term equipment storage
Detergent As required for cleaning
Gloves Chemical-protective
Gloves Electrical-protective
Heaters Space Heater, for eliminating excess moisture in damp areas and dry
out of motor or generator windings
Plastic Protection for long-term storage
Rags As required for cleaning
Water Warm and clean, for cleaning
Tags Warning and cautions
Page 1
Table of Contents
Note: Because of rapid changes in designs Introduction...................................................................... 4
and processes and the variability of Kato Foreword............................................................................................... 4
Engineering’s products, information in this Safety instructions................................................................................. 4
manual must not be regarded as binding Ratings/description............................................................................... 4
and is subject to change without notice. Features, options and specifications...........................4
Overview................................................................................................4
Standard features and options.............................................................. 5
Specifications........................................................................................ 7
Operating principles.......................................................10
Installation...................................................................... 16
Mounting..............................................................................................16
Interconnection....................................................................................16
Single phase 100 to 600 Vac sensing................................................. 16
Three-phase 100 to 600 Vac sensing..................................................16
Input power..........................................................................................20
Output power....................................................................................... 20
Grounding........................................................................................... 20
External voltage adjust rheostat.......................................................... 20
Connection to reactive voltage droop................................................. 21
UFL circuit 50/60 and 400 Hz selector J1........................................... 25
Voltage regulator fuse......................................................................... 25
Accessory items................................................................................. 25
Operation........................................................................ 30
Adjustments........................................................................................ 30
Field flashing....................................................................................... 30
Single unit initial operation.................................................................. 32
Parallel operation................................................................................ 34
Maintenance....................................................................37
Preventive maintenance......................................................................37
Corrective maintenance...................................................................... 37
Operational test...................................................................... 38
Troubleshooting...................................................................................38
Page 2
Figures and Tables
Figure 1: Standard UFL operational threshold for 50/60 Hz system.............9
Figure 2: Effect of timed gating signal on SCR phase angle...................... 13
Figure 3: Outline drawing............................................................................17
Figure 4: Single phase sensing schematic................................................. 18
Figure 5: Three-phase sensing schematic..................................................19
Figure 6: Interconnection............................................................................22
Figure 7: Parallel operation, reactive voltage droop mode......................... 23
Figure 8: Parallel operation, cross-current compensation mode................ 24
Figure 9: Circuit board schematic (with UFL or volts-per-Hz).................... 26
Figure 10: Circuit board schematic (with flat regulation option)................. 27
Figure 11: UFL electrical schematic........................................................... 28
Figure 12: Operational test........................................................................ 39
Page 3
Introduction
Foreword
This manual contains instructions for installing, operating and
maintaining Kato Engineering KCR 760 voltage regulators.
Please read this manual in its entirety before installing, operating, and
servicing your regulator.
Safety instructions
In order to prevent injury or equipment damage, everyone involved
in installation, operating and maintenance of the equipment described
in this manual must be qualified and informed of the current safety
standards that govern his or her work.
Page 4
Standard features and options
Features provided in standard KCR 760 voltage regulators, options
available in this series, and various accessories that can be supplied
with the generator set voltage regulating system are described in the
paragraphs that follow. Where options are specified in the purchase order,
the required circuitry changes are made within the regulator at the factory
while accessories are parts that mount external to the regulator.
Standard sensing: The basic KCR 760 regulator uses single phase 50/60
Hz sensing. The sensing transformer has a multi-tap primary permitting
operation at sensing voltages of 100 to 600 Vac. The standard regulator
includes an underfrequency limit circuit that decreases voltage in
proportion to the decrease in frequency when speed drops below the UFL
operational threshold. The UFL in standard 50/60 Hz sensing regulators
is adjusted with an operational threshold of 48 Hz for a 50 Hz application
and 58 Hz for a 60 Hz application.
- 400 Hz, single or three-phase, 100 to 600 Vac with 385 Hz UFL
operational threshold.
- 50/60 Hz or 400 Hz, single or three-phase 100 to 600 Vac with flat
regulation for a motor-generator set or variable frequency/constant
voltage applications. Regulators with flat regulation will not include
UFL or V/Hz circuitry.
Page 5
Field flashing: KCR 760 voltage regulators include solid-state field
flashing circuitry.
Optional fuse: In applications where the system does not include a field
circuit breaker and generator field protection is required, a smaller fuse
may be used. For generator field protection, fuse amperage should be one
and a half to two times the exciter field current with rated load connected
to the generator. Fuse amperage must not exceed 15 A or two thirds open
circuit forcing. The fuse must be normal blow type. Do not install a time-
delay type fuse.
Standard voltage adjust: KCR 760 voltage regulators are provided with
an internal voltage range adjust potentiometer and an auto voltage adjust
rheostat for remote mounting. The auto voltage adjust rheostat permits
adjustment of generator voltage approximately ±10% from the nominal
sensing voltage.
Page 6
such as 400 Hz motor-generator applications where regulator input power
is taken from 50/60 Hz motor-generator set input power lines. Voltage
matching transformers are available for applications where available
voltage is different from the voltage regulator rated input voltage.
Specifications
Power output:
Power input: Single phase, 50/60 Hz, 120 Vac ±10%; or single phase,
50/60 Hz, 240 Vac ±10%.
Sensing: Standard regulators are constructed for single phase 100 Vac to
600 Vac sensing. Three phase 100 Vac to 600 Vac available as optional
feature. Special voltage or frequency is available as an optional feature.
V/Hz sensing available as optional feature.
Page 7
Field resistance:
- Standard:
58 Hz for 60 Hz system
48 Hz for 50 Hz system
385 Hz for 400 Hz system
Thermal stability: Less than ±0.5 percent for 40° change in ambient
temperature.
Page 8
Figure 1: Standard UFL operational threshold for 50/60 Hz system
Dimensions: 11.5 in. (292 millimeters) x 8.5 in. (216 millimeters) x 4.75
in. (121 millimeters).
Page 9
Operating Principles
General: Parts comprising the KCR 760 voltage regulator are shown on
the electrical schematics.
- When the regulator is designed for flat regulation the regulator will
not have the UFL or V/Hz circuitry and the voltage applied to the
reference side of the first stage differential amplifier in the error
detector will be the voltage across Zener diode Z1.
Page 11
During parallel operation of two or more generators interconnected
for reactive voltage droop, if field excitation on one of the generators
becomes excessive and causes a circulating current to flow between the
generators, the circulating current will appear as an inductive load to the
generator with excessive excitation and a capacitive load to the other
generator(s). The parallel components R4 and T2 will cause the voltage
regulator of the generator with excessive field excitation to decrease the
generator voltage while the voltage regulators of the other generator(s)
will increase the generator voltage.
The first differential stage is comprised of transistors Q1, Q2, & Q12,
resistors R9 through R18, R21, R22, R23, R83, & R93, capacitors
C3, C23, C30, & C31, ferrite beads L2 & L3, Zener diode Z1, and the
circuitry within the underfrequency limit. Underfrequency limit (UFL)
provides a reference voltage to the base of transistor Q2 as described
in the UFL circuit description. During generator operation at rated
frequency the reference signal is constant and identical to the Zener
voltage. Voltage from the sensing circuit, which is proportional to the
generator voltage, is applied to the base of transistor Q1. When Q1 base
voltage is different from the reference voltage applied to the base of
Q2, there will be a difference in Q1 collector current with respect to Q2
collector current.
Phase control circuit: One of T1’s secondary windings, diodes D1, D2,
D21 & D22, resistors R87 & R88, capacitors C20, C21, & C22, supply
power to the first and second differential stage and the underfrequency
limit stage. The phase control circuit consists of diodes D5 and D6,
resistors R28 through R32, & R80, capacitors C20, C21, & C22, Zener
diode Z2, and programmable unijunction transistor (PUT) Q5.
ac input power to
the regulator
voltage required to
fire SCR
ramp voltage
Page 13
The amplitude of the pedestal voltage is determined by the collector
current of second stage differential amplifier transistor Q3. Zener
diode Z2 serves as a voltage clamp and resistors R31 and R32 are a
voltage divider, which determines the threshold of the programmable
unijunction transistor Q5. The output of PUT Q5 is applied to the gate
of the power controller SCRs through resistors R43 & R44 and didoes
D15 & D16 and an amplifying stage that is comprised of transistor Q11,
diode D10, resistors R46 & R81, and capacitor C24.
Power stage (power controller): The power stage supplies the generator
exciter field current. The power stage consists of an SCR/diode bridge
rectifier. The power stage input is either single phase 120 Vac or single
phase 240 Vac depending on regulator design. The output of the power
stage is regulated by the “turn on” gating signal that its SCRs receive
from the phase control circuit. The circuit includes a free wheeling diode
for field discharge of the inductive exciter field load and a fuse (Fl) in its
input power line.
Field flashing circuit: The field flashing circuit includes SCR1, field
effect transistor (FET) Q6, transistors Q7 through Q10, resistors R34
through R42, R82, and R85, Diodes D7, D11, & D29, and capacitors
C25 & C27. Transistors Q8 and Q9, diode D7, and resistors R36, R37,
R38, R40, & R41 comprise a Schmidt trigger circuit. The Schmidt
trigger turns on when an increasing voltage is present with magnitude
approximately 70% of the nominal 24 Vdc output of the sensing
rectifiers, and turns off when a decreasing voltage is present with
magnitude of approximately 30% of the nominal output of the sensing
rectifier.
When the Schmidt trigger is off, FET Q6 is on. This action turns
on transistors Q10 and Q7, which supply current to fire slave SCR1
located on the circuit board. Slave SCR1 fires the silicon controlled
rectifiers SCR1 and SCR2 in the regulator power controller circuit
which, when on, supply current to the exciter field. When the Schmidt
trigger turns on, FET Q6 turns off. This action turns off transistors Q10
and Q7, which removes the gating signal to slave SCR1 and in turn the
gating signal of the flashing circuit from the power controller SCRs.
Resistor R70 and capacitor C19 provide assistance in the firing of the
power stage SCRs. Capacitor C8 and resistor R45 assist in limiting
conducted EMI. Diodes D8, D9 and those in the power stage supply
power to the flashing and phase control circuits.
The voltage from the sensing transformer is rectified by diodes D19 and
D21, and the rectified signal is applied to a Schmidt trigger consisting
of operational amplifier IC2A, resistors R47 through R51, and capacitor
C29. A 24 Vdc peak-to-peak square wave is generated at the output of
IC2A at double the frequency of the sensing voltage.
The 24 Vdc square wave from the Schmidt trigger is fed to the first
stage of a two-stage monostable multivibrator IC1 and associated
parts, where it is decreased to a 5 Vdc peak-to-peak square wave at
double the frequency of the sensing voltage. The 5 Vdc square wave
is applied to the second stage of the monostable multivibrator. The
monostable multivibrator output pulse is uniform in amplitude and
duration for each input pulse. Thus, the average voltage level of the
collective pulses at the output of the monostable multivibrator is
directly proportional to the frequency of the pulses. The monostable
multivibrator output is fed into a four-pole Butterworth low pass filter
comprised of operational amplifier IC2B and IC2C, resistors R60
through R66, and capacitors C13 through C18. This filtering circuit
does the actual averaging of the collective pulses from the monostable
multivibrator. Amplifier gain is set at level where its output equals the
Zener reference at rated 60 Hz or 400 Hz operation by resistors R65,
R66, and capacitor C16. When operated at rated frequency of 50 Hz,
the circuit is set for 50 Hz operation by removing jumper J1. This
action adds R57 to the circuit.
Diode D12 and integrated circuit IC2D form a voltage clamping circuit.
If the voltage from the Butterworth filter is equal to that of the Zener
reference, the UFL output to the error detector will be the same as the
Zener reference and the UFL will have no effect on regulator operation.
However, when the voltage from the filter decreases as occurs during
underspeed operation of the generator, the reference voltage applied
to the error detector is less than the Zener reference. This action will
cause the error detector differential signal to proportionally increase
in a manner that results in a proportionally later turn-on signal to the
regulator output SCRs. The regulator then decreases excitation and a
lowering of generator output voltage occurs.
Resistors R54 & R56, potentiometer R55, and capacitor C12 determine
the underfrequency limit operational threshold. Zener diode Z3 and
capacitors C9 and C10 protect the integrated circuits from damage
should excessive voltage spikes occur.
Page 15
Installation
Mounting: The voltage regulator can be mounted in any position without
affecting its operating characteristics. The voltage regulator is convection
cooled. Retain sufficient space around the regulator for heat dissipation
and for making electrical connections and controls adjustments. Mount
the voltage regulator in any location where shock and vibration are not
excessive and the ambient temperature does not exceed its ambient
operational limits.
Warning: De-energize the generator set Interconnection: Connect the regulator to the generator system as
starting circuit before making repairs, instructed in this section and as shown in the connection diagram
connecting test instruments or removing or provided with the generator set. See Figure 3 for an overall outline
making connections to or within the voltage
drawing that shows the location of regulator mounting provision
regulator. Dangerous voltages are present
at the voltage regulator terminal boards and parts of the voltage regulator. See Figures 4 to 11 for a typical
and within the voltage regulator when the interconnection diagrams and electrical schematics of the voltage
generator set Is running. These include regulator. Use 14 gauge or larger wire for connections to the voltage
the sensing voltage, power to the voltage regulator.
regulator, and the voltage regulator output.
Accidental contact with live conductors Single-phase 100 to 600 Vac sensing (terminals El and E3): The
could result in serious electrical shock or standard KCR 760 voltage regulator designed for single phase sensing
electrocution. has an internal sensing transformer (T1) as shown in Figure 4. This
transformer is provided with taps on the primary winding for sensing
Caution: Do not use a megger or high
voltages of 100 to 139, 200 to 228, 216 to 265, 375 to 458, 432 to 528,
potential test equipment when testing
the voltage regulator. Disconnect
and 540 to 600 Vac. The transformer primary winding taps are identified
interconnecting conductors between the with the corresponding nominal voltages, which are 120, 208, 240, 416,
generator and voltage regulator when 480, and 600. Vac. To obtain proper operation the internal wire from
testing the generator or exciter with a voltage regulator terminal E3 must be connected onto the correct primary
megger or high potential test equipment. tap on transformer T1. Electrical wires within the regulator connect to
The high voltage developed by megger or the sensing transformer secondary winding as shown in Figure 4.
high potential test equipment will destroy the
solid state components within the voltage Three-phase 100 to 600 Vac sensing (terminals El, E2, and E3): When
regulator. the regulator is designed for three-phase sensing, it includes two sensing
transformers (T1 and T3) as shown in Figure 5.
Caution: Never open the regulator sensing
circuit while power is applied to the regulator
Except when otherwise specified in the purchase order, the regulator
input power terminals. Loss of sensing
voltage will result in maximum regulator
sensing transformers will both include multi-tap primary winding for
output. use with the sensing voltages described in the single phase 100 to 600
Vac sensing procedure.
Page 16
Figure 3: KCR 760 outline drawing
Page 17
Notes:
Sensing: Using sensing
terminals E1 and E3, the
internal wire form E3 must
connect to the tap on T1
that matches the genera-
tor voltage.
Parallel operation: An
external current trans-
former is required for
parallel operation. Where
the current transformer
has a 1 A secondary, con-
nect to terminals CT• and
CT1. Where the current
transformer has a 5 A
secondary, connect to ter-
minals CT• and CT5. For
single generator opera-
tion, remove the droop
signal by adjusting R4 to
0 resistance measured
across terminals CT• and
CT1.
Page 18
Notes:
Sensing: Uses terminals
E1, E2, E3 and sensing
transformers T1 and T3.
The wire from E2 must
connect to the tap on T3
that matches the generator
voltage. The wire from E3
must connect to the tap
on T1 that matches the
generator voltage.
Parallel operation: An
external current trans-
former is required for
parallel operation. Where
the current transformer
has a 1 A secondary, con-
nect to terminals CT• and
CT1. Where the current
transformer has a 5 A
secondary, connect to ter-
minals CT• and CT5. For
single generator operation,
remove the droop signal by
adjusting R4 to 0 resis-
tance measured across
terminals CT• and CT1.
Page 19
Note: Jumper wire J3 on the regulator Input power (terminal P1 and P2): Before making electrical
circuit board is installed when regulator input connections, refer to the wiring diagram provided with the generator.
power is 120 Vac ±10% and removed when Connect input power as follows.
input power is 240 Vac ±10%.
- When the regulator is designed for 120 Vac ±10% input power and
65 Vdc maximum continuous output, connect single-phase 120 Vac
power to terminals P1 and P2. Refer above for recommended use of
load isolation and voltage matching transformers.
- When the regulator is designed for 240 V ac ±10% input power and
125 Vdc maximum continuous output, connect single-phase 240 Vac
power to terminals P1 and P2. Refer above for recommended use of
load isolation and voltage matching transformers.
Maintain correct polarity between the regulator output and exciter field.
Make sure field resistance for the 65 Vdc regulator is not less than 6.5 Ω
and field resistance for the 125 Vdc regulator is not less than 12.5 Ω.
Make sure the field circuit is not grounded and/or opened or shorted
during operation of the generator set.
Because the regulator output leads are not connected to any part of
the system except the exciter field, they are not filtered. To minimize
conducted EMI the keep the leads as short as possible and shielded.
Effective shielding can be attained by routing both leads through 0.5
inch conduit. In general, do not leave unshielded more than 1 to 2 feet
of field leads. If the voltage regulator is installed within the generator
outlet box, it is possible to achieve satisfactory results with short
unshielded leads.
Page 20
nominal. It is provided as a separate item for panel mounting. Connecting
wires from the rheostat attach to terminals R1 and R2. A jumper wire
must be connected between rheostat terminal 2 and rheostat terminal 1 as
shown in Figure 6.
Page 21
Notes:
1) For single-phase sensing, terminals are E1 and E3. See Figures 2 and 3.
2) The field must not be opened, shorted or grounded while the generator is operat-
ing.
3) The external voltage adjust must have a jumper across its terminals 1 and 2.
4) Input power standard KCR 760 voltage is 120 Vac; optional 240 Vac. Maximum
continuous output is 65 Vdc for a 120 Vac input and 125 Vdc for a 240 Vac input. See
Figures 4 and 5.
Page 22
Regulator 1
Generator 1
Generator 2
Regulator 3
Generator 3
Page 23
Regulator 1
Generator 1
Generator 2
Regulator 3
Generator 3
Page 24
Generator operating singly: When generators are not operating parallel
and reactive voltage droop is not required, use one of the following
methods to eliminate the effect of the parallel operation transformer
within the voltage regulator.
UFL circuit 50/60 and 400 Hz selector J1: The underfrequency limit
components or V/Hz components are located on the voltage regulator
circuit board (see Figure 9). Parts comprising the UFL or V/Hz
components are shown in Figure 11. A jumper wire J1 eliminates the
effect of resistor R57. Removing the jumper J1 places R57 in the circuit.
Voltage regulator fuse: The voltage regulator contains a 15 A normal Warning: A fire hazard can exist if the
blow fuse in the voltage regulator input power circuit (see Fig. 1, 2 voltage regulator fuse is larger than 15 A or
and 3). In applications where voltage regulator power requirements are if a delay-type fuse is used.
reduced, as when used with small generators where excitation is less than
Note: On generator systems that include
given, a smaller fuse may be used. Never install a fuse larger than 15 A
the auto/manual voltage control option, the
and never install a delay-type fuse.
OFF position on the AUTO/OFF/MANUAL
selector switch provides voltage shutdown.
Accessory items: Accessory items provided with the generator system On generator systems that include a field
must be connected as shown on the wiring diagram provided with the circuit breaker, manually tripping the circuit
generator set and the accessory item drawing or instruction. Observe breaker OFF provides voltage shutdown.
the precautions and general procedures that follow when connecting
accessory items. Caution: Never install the voltage shutdown
switch in the exciter field circuit as the
Voltage shutdown (engine idle switch): The system can be equipped with voltage regulator dc output (terminals
a switch to allow removal of excitation in an emergency or when the F+ and F-) must not be opened during
operation. To do so would produce inductive
prime mover must be operated at reduced speeds. This switch must be
arcing that could destroy the exciter or
placed in the input power line to the regulator (terminal P1 or P2). voltage regulator output power bridge.
Field circuit breaker: The field circuit breaker must be of the type that Caution: Never open the dc output
has separate terminals for the thermal element and the contacts. (terminals F+ and F-) during operation.
The circuit breaker thermal element receives heat from either the field To do so would produce inductive arcing
current or generator line current. Where it is heated by field current, the that could destroy the exciter or voltage
thermal element connects between the voltage regulator output and the regulator. Therefore, never place circuit
breaker contacts in the exciter field circuit.
Page 25
240 Vac.
To voltage range
adjust and voltage {
adjust. See Figures
2 and 3.
Page 26
trol. See Figures 2 {
and 3. { To field F +. See
Figures 2 and 3.
From sensing
choke. See Figures { { To field F +. See
2 and 3. Figures 2 and 3.
Figure 9: KCR 760 (with UFL or volts-per Hz) circuit board schematic
{ To field F +. See
Figures 2 and 3.
To field F +. See
{
Figures 2 and 3.
From sensing
transformers. See
Figures 2 and 3.
{
To voltage range
adjust and voltage {
adjust. See Figures
2 and 3.
Page 27
choke. See Figures { { To field F +. See
2 and 3. Figures 2 and 3.
{ To field F +. See
Figures 2 and 3.
To field F +. See
{
Figures 2 and 3.
Figure 10: KCR 760 (with flat regulation option) circuit board schematic
input is 240 Vac.
Note: With jumper J3, install when
input is 120 Vac, and remove when
Figure 11: UFL electrical schematic
Page 28
exciter field. Where it is heated by generator line current, the thermal
element connects to a current transformer located in one of the generator
load lines.
Page 29
Operation
Caution: Before initial operation, verify Adjustments: The adjustments pertaining to the voltage regulator and
that the regulator is connected for the system operation are described in the paragraphs that follow and, except
application. See wiring diagram provided where noted, adjustment is made during initial operation and normally
with the generator set and review the does not have to be repeated during the life of the voltage regulator.
procedures given above.
Generator voltage adjust rheostat (VAR): This adjustment is
provided to control the generator voltage. When set to its maximum
counterclockwise position, minimum generator voltage is obtained.
Maximum generator voltage is obtained when the rheostat is set to its
maximum clockwise position.
This control is located on top of the cover, mounted below the heat
sink and above the RANGE adjust. Loosen the 9/16 inch hex-head
locknut that keeps the control shaft from turning due to vibration before
attempting to adjust R6 (with a screwdriver). Retighten the locknut after
adjustment is complete.
Operate the generator at rated frequency, no load, the point at which the
stability adjustment is most critical. Adjust STABILITY by first rotating
the control fully clockwise with screwdriver. One end of the screwdriver
slot will point to 2 o’clock; this end is the pointer. Set the STABILITY
by rotating pointer counterclockwise to 10 o’clock. This setting normally
ensures good stability, but may not provide optimum response time for
the generator.
If the generator voltage oscillates (hunts), turn the control clockwise past
the point where oscillation stops. If faster response is required, rotate
the control counterclockwise until the voltage becomes unstable, and
then rotate clockwise until the voltage is stable. Optimum adjustment
is attained when generator voltage is stable and response is satisfactory
at no-load and also during operation under any load up to the full load
rating of the generator.
Page 30
Parallel voltage droop potentiometer (R4): This adjustment is provided Note: Where the generator will be
to control the voltage droop signal of generators operating parallel. It operating singly and use of reactive voltage
is located on the regulator chassis. Maximum voltage droop is attained droop circuitry is not desired, either set R4
when the potentiometer is set to its maximum clockwise position. Adjust to the minimum droop position or install
each generator that will be operated parallel for identical voltage droop a jumper or unit/parallel switch across
as described in the parallel operation procedure that follows. Make the terminals CT• and CT1.
adjustment by loosening the locknut with a 1/2 inch wrench, adjusting
the droop with a screwdriver and then tightening the locknut after the
adjustment has been made.
- Adjusting the underfrequency limit when generator Note: The jumper wire must be across
frequency can not be adjusted. J1 on a 60 Hz system. Measured voltage
1. Connect a voltmeter between the circuit board must be negative. Slight variation in
operating threshold may exist due to
terminals TP1 (negative) and TP2 (positive).
circuit and meter tolerances.
2. Run the generator at rated speed and voltage.
3. Determine the desired underfrequency limit setting voltage
from Table 1 for 60 Hz generators or Table 2 for 50 Hz
generators. Operational dc voltage
4. Adjust R55 until the voltage between TP1-TP2 equals the test threshold TP1-TP2
voltage given in the appropriate table. EXAMPLE: With unit 50 Hz 0.000
running at 60 Hz and where limiting is desired at about 55 Hz, 49 Hz -0.107
the voltage across TP1-TP2 should be -0.438 Vdc. 48 Hz -0.210
47 Hz -0.315
46 Hz -0.425
Manual voltage control variac: This control is included in generators 45 Hz -0.553
equipped with the automatic/manual voltage control option. During
generator operation using the manual voltage control mode, the mode Table 2: Voltage across under-
selector is set to MAN and generator voltage output is controlled by the frequency limit terminals TP1-
manual voltage control variac. In order to maintain generator output TP2 with a 50 Hz generator
voltage at a constant level during operation in the manual voltage control and rated sensing voltage
mode, adjust the manual voltage control variac each time a change in Note: The jumper wire J1 must be
load occurs (either added or shed). removed during 50 Hz operation.
Measured voltage must be negative.
Slight variation in operating threshold
may exist due to circuit and meter
tolerances.
Page 31
Field flashing: The voltage regulator contains an internal solid state field
Caution: Do not attempt to flash the exciter flashing circuit. A minimum of about 6 Vac at the regulator input power
field while the generator set is running. Be terminals is required for operation of the flashing circuit. Usually the
careful to observe polarity when connecting exciter field poles retain sufficient magnetism to allow circuit operation
flashing source. Accidental polarity reversal and generator voltage buildup However, if flashing is required, stop the
will destroy the voltage regulator power generator, and then flash the field as given in the procedure that follows:
stage.
1. Connect the negative lead of a 12 or 24 Vdc flashing source onto
regulator terminal F-. Do not remove any other wires from terminal
F-.
2. Slide the positive lead of the flashing source onto the regulator
terminal F+. Only a few seconds flashing should be necessary.
3. Slide the flashing source positive lead off terminal F+. Then remove
the flashing source negative lead from terminal F-, and tighten the
terminal.
4. Start the generator, and check for satisfactory voltage buildup.
Caution: Before operating the generator for Single unit initial operation: When the generator set is equipped with
the first time, double check to make certain the automatic/manual voltage control option, normal operation of the
all wiring connections are made correctly. generator set is the automatic voltage control mode. During generator
Review the wiring diagrams provided set operation in the automatic voltage control mode, generator output
with the generator set, the installation voltage is pre-established during no-load operation by adjustment of
instructions above and the preceding the external voltage adjust rheostat and automatically maintained at the
adjustment procedures.
amplitude under all load conditions from no-load to full rated load by the
voltage regulator.
Note: Deviation in generator output voltage Automatic mode operation: Review the preceding adjustment and
approximately ±10% of rated can be single unit operation procedures. The general procedure for single unit
corrected by adjusting the voltage adjust automatic mode operation is as given in the procedure that follows:
rheostat and if necessary, the voltage range 1. If the generator set is equipped with the auto/manual control option,
set adjust. set the selector switch to AUTO.
2. Turn the voltage adjust rheostat to about one-half of the way
between the maximum counterclockwise and maximum clockwise
positions.
3. Open the output circuit breaker. Do not apply load until satisfactory
no-load operation is attained.
4. If a voltage shutdown switch or field circuit breaker is used, close
the switch to connect input power to the voltage regulator.
5. On generators that will be operated parallel and if the sets are
equipped with unit/parallel switches, close the switch on all
generators.
6. Start the prime mover and bring up to rated speed.
7. Verify generator voltage. Any of the following conditions can occur.
- No voltage buildup: If this condition exists, the exciter may not
have sufficient residual magnetism. Residual magnetism may be
restored by flashing the field as described in the “Field Flashing”
instructions.
- Overvoltage (+15% or more): If this condition occurs, open
the shutdown switch immediately and/or stop the prime mover.
Determine the cause of overvoltage.
Page 32
- Undervoltage (-15% or more): If this condition occurs, open
the shutdown switch immediately and/or shut down the prime
mover. Determine the cause of undervoltage.
- Undervoltage by operation of the underfrequency limit circuit
(UFL): Undervoltage by operation of the underfrequency
circuit can occur if the prime mover governor is not adjusted to
maintain rated speed or when the underfrequency limit circuit is
adjusted to operate at a frequency that is very close to the rated
frequency of the generator.
- Voltage begins to build up and then collapses: If this condition
exists, stop the prime mover and determine the cause of collapse.
If necessary refer to troubleshooting procedure.
- Oscillating voltage (hunting): If this condition occurs, be sure
prime mover speed is not fluctuating. Then, if this condition
persists, adjust the stability adjust (R6) as given in the stability
adjustment section above.
8. Operate the generator set for about 1/2 hour.
9. After about 1/2 hour of satisfactory operation, close the output circuit
breaker and connect the load.
10. Be sure the generator output voltage is correct and stable. Verify that
steady voltage regulation is satisfactory.
11. Remove the load.
12. If the generator will be operating parallel, adjust the parallel
operation potentiometer R4 as given in the steps that follow. To stop
the unit see step 19.
13. If the generator set is equipped with a unit/parallel switch, open the
switch.
14. Monitor no-load voltage.
15. Apply inductive load, and note the droop in generator voltage.
A droop of about 6% is attained when R4 is turned to complete
clockwise position for maximum resistance and the current
transformer secondary current is one ampere connected to terminals
CT• and CT1 or 5 amperes connected to terminals CT• and CT5.
16. If droop is more than is required, turn R4 counterclockwise. If droop
is less than is required, turn R4 clockwise.
17. Repeat steps 14 through 16 as necessary to obtain required droop
signal.
18. To stop the unit, remove the load, open the output circuit breaker,
and then stop the prime mover.
Page 33
1. Perform the preceding automatic mode operating procedure.
2. Open the output circuit breaker and, if it is running, stop the prime
mover.
3. If it is included, close the unit/parallel switch.
4. Set the auto/off/manual selector switch to MAN.
5. Set manual voltage adjust variac to the complete counterclockwise
position.
6. Start the prime mover, and bring it up to rated speed.
7. Turn the manual voltage adjust variac to the position where the
correct generator voltage is measured by the generator voltmeter.
8. Turn the manual voltage adjust variac to the position where
voltmeter indicates generator voltage is about 5% higher than rated.
9. Close the output circuit breaker, and apply load.
10. Measure the output voltage. If it is not correct, adjust the manual
voltage adjust variac.
11. Repeat steps 8 and 10 each time the load is increased.
12. Before shedding load, decrease generator voltage about 5% below
rated.
13. Adjust manual voltage adjust variac to position where the voltmeter
indicates generator is producing required voltage.
14. Repeat steps 12 and 13 each time any part of the load is shed.
15. Remove the load and open generator circuit breaker.
16. Set voltage adjust rheostat for rated generator output voltage.
17. Stop the prime mover.
18. Set the auto/off/manual switch to AUTO.
Caution: In generating systems equipped Parallel operation: The paragraphs that follow describe the procedures
with the automatic/manual voltage control to operate two or more generators in parallel.
option, always make parallel operation in
the automatic voltage control mode. Never Metering: In order to attain satisfactory paralleling and to check for
attempt to parallel generators when the proper parallel operation all generators should be equipped with the
mode switch is set to MAN. following monitoring equipment:
1. ac voltmeter to measure generator output voltage (one per set)
2. ac voltmeter to measure bus voltage (one per system)
3. ac ammeter (one per set)
4. Power factor or kVAR meter (one per set)
5. kW meter (one per set)
6. Exciter field current dc ammeters (one per set)
7. Synchroscope or a set of lights to indicate when units are in phase
Page 34
voltage at terminals El and E3. In applications where units are
connected for reactive voltage droop, verify that the connection is
made as shown in Figure 7. Cross-current compensation application
requires interconnection of the system as shown in Figure 8.
4. Prior to operation, set the parallel voltage droop potentiometer R4
on all regulators for identical droop. This can be accomplished by
individually testing each generator set, one at a time, as given in the
single unit initial operation procedure.
Page 35
11. Observing the synchroscope (or lights), when generator No. 2 is in
phase with generator No. 1, close the circuit breaker for generator
No. 2.
12. Immediately after closing the circuit breaker, measure the line
current of generator No. 2. It should be well within the rating of
the generator. Also, immediately after closing the circuit breaker,
observe the kW or power factor meters. The following conditions
could occur:
- A high ammeter reading accompanied by a large kW unbalance:
When this condition exists, the speed governor is either not
adjusted correctly or is faulty.
- A high ammeter reading accompanied by a large kVAR
unbalance: When this condition exists, the voltage regulating
system is either not adjusted correctly or is faulty.
13. Adjust the speed of generator set No. 2 to the point where each
generator is carrying the desired share of kW load.
Note: If kVAR or power factor meters 14. Adjust the voltage of generator No. 2 until the ammeter readings of
are available, adjust the voltage adjust both generators are near minimum.
rheostats for equal or proportional kVAR 15. With full load applied, readjust the speed and voltage of generator
or power factor readings. If the generators No. 2 until the desired load division is obtained.
are equipped with power factor meters, 16. In applications where three or more generators are to be operated
alternately adjust the speed and voltage parallel, repeat preceding steps 7 through 15 for generator set No. 3,
on No. 2 until the ammeter readings are then No. 4, etc.
proportional and the power factor readings
are equal.
Shutting down one or more generators operating in parallel: Before
Note: To obtain best results, make final
dropping one or more generators operating parallel from the line bus,
adjustments with full load on the bus. reduce the total load on the bus to equal to or less than the combined
capacity of the generators remaining on the bus. Shut down one or more
Note: The best adjustment is obtained of generator sets operating parallel as follows:
when each generator supplies the same 1. Reduce load to combined capacity of generators remaining on the
percent of its rated current, the power bus.
factor readings are equal, or the sum of the 2. On systems where the prime mover governor is equipped with a
ammeter currents is minimum. manual speed adjust, shift the load to generators remaining on the
bus by reducing the speed of the generator set being dropped from
the bus.
3. Close its unit/parallel switch (on generator sets equipped with a unit/
parallel switch).
4. Shutdown the prime mover.
5. In applications where three or more generators are operated parallel,
repeat preceding steps 1 through 4 for each generator set being taken
off the bus.
Page 36
Maintenance
Preventive maintenance: Inspect the regulator periodically to ensure
that air flow is not restricted. Dirt, dust, and other foreign material may
be removed using low pressure (25 to 50 PSI) compressed air. Check the
connections between the regulator and system periodically to ensure they
are tight and free of corrosion.
Page 37
Voltage regulator operational test: Use the following test procedure to
determine if the regulator is basically operational:
1. Connect regulator as shown in Figure 12.
2. Connect internal wire from terminal E3 to the tap on the sensing
transformer T1 that matches the input power described in step 6.
3. Connect jumper across terminals CT• and CT1.
4. Adjust the external voltage adjust for maximum resistance (complete
counterclockwise position). If the light is on when voltage adjust
is turned to its complete counterclockwise position, the problem is
likely in the regulator.
5. Connect light bulb across terminals F+ and F- and wires to terminals
E1, E3, P1, and P2 as shown in Figure 12.
6. Connect to 120 Vac power source when regulator full load output
rating is 65 Vdc. Connect to 240 Vac power source when regulator
full load output rating is 125 Vdc.
7. Turn the external voltage adjust clockwise. Before reaching the
maximum clockwise position, the bulb should come on to near full
brilliance.
8. At the regulating point a small change in adjustment of the external
voltage adjust rheostat should turn the light on or off. If the light does
not come on, the problem is likely in the regulator.
9. Before installing back in the generating system, connect the regulator
as it was before steps 2 through 7.
Note: Incorrect electrical connections Troubleshooting: Between regular preventive maintenance inspections,
between the generator system and the be alert for any signs of trouble. Correct any trouble immediately. See
regulator and poor electrical connections Table 4 for typical symptoms, causes, and remedies.
are often the cause of system malfunction.
Before assuming a failure of the generator
or regulator has occurred, check wiring
against the wiring diagrams provided with
the generator set and the instructions given
above. Also make certain all connections
are tight and free of corrosion.
Page 38
Note: The internal wire from E3 must
connect to the 120 Vac tap on transformer
T1.
Jumper
Light bulb
External voltage
adjust
Page 39
Symptom Cause Remedy
Voltage does Shutdown switch is open Close the switch.
not built Fuse is blown Replace the fuse. If the fuse blows repeatedly,
up to rated determine the cause of the overload.
value
Auto/off/manual switch is on OFF Set to the switch to AUTO.
Field circuit breaker is open Close the circuit breaker.
No input power to terminals P1 and P2 Verify wiring.
Inaccurate generator voltmeter Verify using a test voltmeter. Calibrate or replace
a faulty meter.
Voltage too low at terminals P1 and P2 Verify wiring.
Low residual voltage (or reverse residual) Flash the field per the procedure.
Internal wire from the sensing terminals on Verify wiring.
the regulator is not connected to the correct
tap on the sensing transformer(s)
No connection or poor connection between Correct the wiring, and check the connections.
the exciter field and the regulator terminals
F+ and F-
Prime mover not up to rated speed Bring the prime mover up to rated speed.
Open or incorrectly connected external Verify wiring.
voltage adjust rheostat
Voltage range adjust R2 is set too low Refer to the setting procedure.
Potentiometer R89 out of adjustment The adjustment is factory set. If it is accidently
adjusted during operation, contact Kato
Engineering.
Faulty regulator power stage Test. If it is faulty, replace the voltage regulator or
power module.
Faulty printed circuit board Replace the voltage regulator.
Defective rectifiers in the exciter, defective Verify operation of the exciter and/or the
exciter windings, or defective generator generator. Refer to the generator instruction
manual for additional information.
Generator output heavily loaded Remove excessive load.
Voltage Faulty printed circuit board Replace voltage regulator.
builds up
until flash-
ing circuitry
operates
and then
oscillates
between
approxi-
mately 1/3
to 2/3 rated
voltage
Voltage is No voltage to sensing terminals on the Verify wiring.
high and not regulator
controllable
with the volt-
age adjust
rheostat
Page 40
Voltage is Open sensing transformer Verify wiring, and check for open windings.
high and not Automatic/off/manual switch set to MAN Set to Auto for automatic voltage regulation.
controllable
External voltage adjust rheostat shorted Verify wiring. Use an ohmmeter to test resistance
with the volt-
across the rheostat. Replace shorted rheostat.
age adjust
rheostat Internal wire from sensing terminals on the Verify the nominal sensing voltage from the
(cont.) regulator is not connected to the correct tap generator and wiring to the sensing transformers.
on the sensing transformer(s)
Faulty regulator circuit board Replace the voltage regulator.
Faulty regulator power stage SCRs or diodes Replace the power module or the voltage
regulator.
Voltage high, Internal wire from terminals) E2 and E3 to Verify the nominal generator voltage. Correct the
controllable the wrong tap on the sensing transformer(s) wiring.
with volt- T1 and T3
age adjust Improper connection of the sensing to the Verify wiring to the voltage regulator.
rheostat regulator sensing terminals
Single-phase sensing applied to a regulator Connect three-phase sensing.
designed for three-phase sensing
Voltage range adjust R2 set too high Adjust R2 per the procedure.
R89 adjustment is off Factory set. If accidently turned, contact Kato
Engineering.
Generator voltmeter is inaccurate Connect a test voltmeter to check operation of
the generator output. Calibrate or replace the
meter.
Faulty regulator power stage Replace the voltage regulator or power module.
Faulty regulator circuit board Replace the voltage regulator.
Poor regula- Voltage at regulator terminals P1 and P2 are Input voltage for standard KCR 760 voltage
tion too low at the nominal generator voltage regulators is 100 to 139 Vac for a unit with 65
Vdc output and 200 to 240 Vac for a unit with 125
Vdc output.
Jumper not installed across terminals CT• Install a jumper.
and CT1 while the generator is operating
singly
Unit/parallel switch in PARALLEL during Switch to UNIT.
single generator operation
Unit/parallel switch of the generator not on Set the switch of the generators not on the bus to
the bus set to PAR position UNIT.
The prime mover is not up to rated speed, or Bring the prime mover up to rated speed and/or
the prime mover speed is fluctuating adjust the governor.
Unbalanced load Balance the load.
Exciter field resistance is too low and /or the Add a series resistor. Resistance must not be
exciter field volts are too low less than 6.5 Ω for a 65 Vdc continuous full-load
rated regulator or 12.5 Ω for a 125 Vdc regulator.
The voltage applied to the exciter field at no load
must not be less than 10 Vdc. Best operation
occurs when the voltage is about 20 Vdc during
no-load operation. The resistor must not limit
regulator output during full load operation.
Page 41
Poor regula- Faulty regulator circuit board Replace the circuit board.
tion (cont.)
Faulty regulator power stage diodes or SCRs Replace the voltage regulator or power module.
Poor voltage Stability adjust R6 not adjusted to provide Adjust R6 per the procedure.
stability sufficient stabilizing signal.
Frequency unstable. Adjust the prime mover or the governor.
No-load field voltage and/or resistance is too Add a series resistor. Resistance must not be
low less than 6.5 Ω for a 65 Vdc continuous full-load
rated regulator or 12.5 Ω for a 125 Vdc regulator.
The voltage applied to the exciter field at no load
must not be less than 10 Vdc. Best operation
occurs when the voltage is about 20 Vdc during
no-load operation. The resistor must not limit
regulator output during full-load operation.
Voltage at regulator input power terminals P1 Input voltage for standard KCR 760 voltage
and P2 is too low regulators is 100 to 139 Vac for a unit with 65
Vdc output and 200 to 240 Vac for a unit with 125
Vdc output.
Voltage fluctuated to a point where flashing Replace the circuit board or the voltage regulator.
circuit energizes or de-energizes
Fault in the exciter or generator Verify the exciter and generator operation.
Page 42
No droop Unit/parallel switch closed (set to UNIT) Set the switch on the generator sets to PAR.
compensa- Leave the switch on UNIT on any generators that
tion can be will remain shutdown.
obtained Parallel droop adjust R4 set to minimum Turn R4 clockwise to increase droop.
for parallel droop
generators
Parallel CT does not supply the correct When a 1 A CT is used, connect to the regulator
(cont.)
secondary current terminals CT• and CT1. Terminals CT• and CT5
are for use with a 5 A CT. Determine rated line
current and voltage, and consult the factory.
Verify the number of turns on the generator line
through transformer are correct.
Voltage rises Wrong polarity between the parallel CT Interchange leads at terminals CT• and CT1.
instead of secondary leads and the regulator terminals Where a 5 A CT is used, terminals will be CT•
droops on and CT5.
application
of inductive
load
Parallel Terminals CT• and CT1 or CT5 shorted by Remove the jumper. Set the unit/parallel switch
generators jumper or unit/parallel switch to PAR.
do not divide
reactive
kVAR load
equally
resulting in
circulating
reactive
current
between
generators
Unequal adjustment of voltage droop Adjust for equal droop
potentiometers
Droop potentiometers on generators Adjust R4 on all generators for identical droop
operating parallel are set at different droop per the procedure.
positions
Wrong parallel CT or wrong ampere turns Consult Kato Engineering.
through the CT primary
Parallel CT is not in the correct generator Verify the wiring.
line
Parallel CT polarity is reversed Interchange the CT secondary leads at the
regulators terminals. CT• and CT1 are for use
with a 1 A CT. CT• and CT5 are for use with a 5
A CT.
Parallel Improper setting of the governor power Adjust the governor.
generators sensing
do not evenly
divide kW
load
Table 3: Troubleshooting
Page 43
Manual #: 351-07001-00
Date: July 2010
General
If your generator is equipped with air filters, it may have an optional differential pressure
switch. This switch senses the pressure differential between the two sides of the filter,
and as dust and dirt accumulate in the filter, the pressure differential increases. When
the pressure differential reaches the set point, the switch actuates. The switch may be
connected to an alarm, indicator lights, or shutdown circuitry. See your wiring diagram
for details.
Application
This instruction applies to all generators with inlet filter and cooling fan on the exhaust
side of the filter.
Generator air filters are stainless steel and can be removed from the generator and
cleaned. Filters may be cleaned with steam, soapy water or cleaning solution. Following
cleaning the filter, it should be thoroughly rinsed with either water or steam and dried.
The air pressure switch contacts are mechanically operated when air pressure expands
a sealed diaphragm assembly. The pressure switch includes an actuating pressure set
point adjusting screw, normally open contact and normally closed contact. The set point
adjusting screw and the contact terminals are located under the switch terminal box
cover. Normally open contact terminals are marked N.O. and common while normally
closed contact terminals are marked N.C. and common.
Turn the slotted screw clockwise to raise the differential pressure to where the switch will
actuate and counterclockwise to lower the set point pressure difference. Allowable static
pressure drop in air filters above clean condition is given on Table A.
The switch high-pressure port is at the atmospheric pressure outside of the generator
while the low-pressure port connects to the lower pressure ·that exists within the sheet
metal housing located between the generator and the air filter.
Calibration should be made by using a manometer to measure the static pressure drop.
Connect its low-pressure port to the air outlet side of the filter and high-pressure port to
atmospheric pressure.
Calibrate and adjust the pressure switch as detailed in the paragraph that follows.
Make certain the air filter is clean. Then operate generator at no-load, rated rpm and
measure the pressure drop. Slowly cover inlet side of the air filter using metal, plywood
or cardboard strips.
Observe when manometer indicates that pressure drop is equal to the sum of the clean
filter pressure drop plus the allowable static pressure drop. (See Table A). Keeping this
area of the filter blocked, adjust set point adjusting screw. The switch may be adjusted to
actuate when less static pressure drop exists. However, too low a pressure difference
may result in actuation of the warning or shutdown circuit before the filter is clogged to
extent where cleaning is necessary.
NOTE:
1. Use U tube manometer to measure pressure drop. Partially cover the filter face to
simulate a dirty filter.
2. The shutdown pressure drop will result in about a 10% reduction in air flow.
3. Frame number is 3rd and 4th digits in generator code number given on generator
nameplate.
Table A
GE Capacitors
DIELEKTROL Non-PCB Dielectric Protective Capacitors
With Internal Discharge Resistors - Indoor or Outdoor Mounting
Vo lta g e M a xi m um A pprox
P o le s Ne t
Ra ti ng Vo lta g e Mi crofarads F i g ur e
Cat #'s per W e i g ht
rms rms p e r P o le #
Uni t
Vo lts L -L Vo lts L -L Lb Kg
9L18BBB301 0-650 715 3 1 4 1.8
18L0015WH 2400 2640 3 0.5 36 16.4 4
18L0015WH 4160 4576 3 0.5 36 16.4 4
18L0019WH 6900 7590 1 0.5 29 13.1 1
18L0065WH 7200 7960 3 0.5 35 15.8 5
18L0009WH 13800 15180 1 0.25 33 14.9 2
18L0012WH 13800 15180 3 0.25 66 29.7 6
18L0010WH 24000 26400 1 0.125 57 22.7 3
Figure 1: Single-pole, 6900 volts Figure 2: Single-pole, 13,800 Figure 3: Single-pole, 24,000 volts
volts
Figure 4: Three-poles, 2400 & Figure 5: Three-poles, 7200 volts Figure 6: Three-poles, 13,800 volts
4160 volts
g GE Capacitors
GE Transmission, Distribution & Industrial Systems
DEA-224 381 Broadway, Ft. Edward, NY, 12828
(6/99) www.ge.com/capacitor
© 1999 General Electric Corporation
Type POLIM-S Surge Arresters
Maximum System Voltage 2.52 to 245 kV
POLIM-S Metal Oxide Gapless Surge Arresters
Application
The POLIM-S Surge Arrester has been verified to meet Station Class
requirements of IEEE C62.11 (IEEE Standard for Metal-Oxide
Surge Arresters for AC Power Circuits) and Line Discharge Class 3
requirements of IEC 60099-4 (IEC Standard for Metal-Oxide Surge
Arresters without gaps for AC Systems). The POLIM-S Surge Arrester is
designed to meet the following performance data:
Performance data
Maximum system voltages (Vm) 2.52 - 245 kVrms
Energy capability:
2 impulses, (IEC CI. 7.5.5) 9.8 kJ / kV of MCOV
Fullfills requirements of IEEE
transmission-line discharge
test for 24 kV systems
Notes:
1 The POLIM-S has demonstrated values of 80 kArms sym short circuit to IEEE C62-11 (1993)
Standard.
2 Higher strength designs available on request
3 Higher altitude designs available on request
Standard (Mylar)
WT. DATE
4F4002H02
MADE IN USA
(Example: Q015SA012ASN)
Four-Wire
Four-Wire
Grounded High
Maximum Three-Wire Four-Wire Three-Wire Grounded
Impedance
Vm Vn Vn Vr / VMCOV Vr / VMCOV
Vr / VMCOV
(kVrms) (kVrms) (kVrms) (kVrms) (kVrms)
(kVrms)
Medium Voltage 2.52 2.4 3 / 2.55
4.37Y / 2.52 4.16Y / 2.4 3 / 2.55 5 / 4.25
4.37 4.16 5 / 4.25
5.04 4.8 6 / 5.1
7.24 6.9 9 / 7.65
8.73Y / 5.04 8.32Y / 4.8 6 / 5.1 12 / 10.2
12.6Y / 7.27 12.0Y / 6.93 9 / 7.65 15 / 12.7
13.09Y / 7.56 12.47Y / 7.2 9 / 7.65 18 / 15.3
13.86Y / 8.0 13.2Y / 7.62 10 / 8.4 18 / 15.3
14.49Y / 8.37 13.8Y / 7.97 10 / 8.4 18 / 15.3
14.49 13.8 18 / 15.3
21.82Y / 12.6 20.78Y / 12.0 15 / 12.7 27/ 22
24.0Y / 13.86 22.86Y / 13.2 18 / 15.3 30 / 24.4
24.15 23.0 30 / 24.4
26.19Y / 15.12 24.94Y / 14.4 21 / 17 33 / 27
36.23Y / 20.92 34.5Y / 19.92 27 / 22 42 / 34
36.23 34.5
High Voltage 48.30 46 36 / 29
72.50 69 60 / 48
123 115 96 / 76
145 138 120 / 98
170 161 144 / 115
245 230 192 / 152
Key
Vn Nominal System Voltage per NEMA C84.1
Vm Maximum System Voltage per NEMA C84.1
Vr Duty Cycle Rated Voltage per IEEE C62.11
MCOV Maximum Continuous Operating Voltage per IEEE C62.11
TOV Temporary Overvoltage
SPL Switching Protective Level
500 A 3-132 Vr (kVrms)
1000 A 144-198 Vr (kVrms)
LPL Lightning Protective Level
FOW Front of Wave
Electrical characteristics
Ratings (kVrms) TOV (kVrms) Maximum residual voltage with current wave, (kVpeak)
with prior energy SPL (SIPL) LPL (LIPL) FOW
Voltage MCOV single impulse of 4.5 kJ/kVr 30/60 µS 8/20 µs 0.5 µs
Vr VMCOV 1 sec 10 sec 500 A 1.5 kA 3 kA 5 kA 10 kA 20 kA 40 kA 10 kA
3.0 2.55 5.15 4.93 9.77 10.5 10.9 11.2 11.3 12.9 14.4 12.8
4.0 3.40 5.15 4.93 10.0 10.8 11.2 11.5 11.6 13.3 14.8 13.1
5.0 4.25 6.87 6.57 12.3 13.2 13.7 14.2 14.4 16.3 18.2 16.1
6.0 5.10 6.87 6.57 12.8 13.8 14.3 14.8 15.0 17.0 19.0 16.8
7.0 5.95 10.3 9.86 17.7 19.1 19.8 20.5 21.0 23.6 26.3 23.3
8.0 6.80 10.3 9.86 18.5 20.0 20.7 21.4 22.0 24.7 27.6 24.4
9.0 7.65 10.3 9.86 19.0 20.5 21.3 22.0 22.6 25.4 28.3 25.0
10 8.40 11.5 11.0 21.0 22.6 23.5 24.3 25.0 28.0 31.3 27.6
12 10.2 13.7 13.1 25.1 27.1 28.1 29.0 30.0 33.5 37.4 33.1
15 12.7 17.2 16.4 31.3 33.7 35.0 36.1 37.5 41.8 46.6 41.2
18 15.3 20.6 19.7 37.4 40.3 41.9 43.3 45.0 50.0 55.9 49.3
21 17.0 24.0 23.0 41.8 45.1 46.9 48.4 50.4 55.9 62.5 55.2
24 19.5 27.5 26.3 47.7 51.5 53.5 55.2 57.6 63.9 71.3 63.0
27 22.0 30.9 29.6 53.6 57.8 60.1 62.1 64.8 71.8 80.2 70.8
30 24.4 34.4 32.9 59.5 64.2 66.7 68.9 72.0 79.7 89.1 78.6
33 27.0 37.8 36.1 65.4 70.6 73.4 75.7 79.2 87.6 97.9 86.4
36 29.0 41.2 39.4 71.3 77.0 80.0 82.6 86.4 95.5 107 94.2
39 31.5 44.7 42.7 77.3 83.3 86.6 89.4 93.6 103 116 102
42 34.0 48.1 46.0 83.3 89.9 93.4 96.5 101 112 125 110
45 36.5 51.5 49.3 89.1 96.1 99.9 103 108 119 133 118
48 39 55.0 52.6 95.6 103 107 111 116 128 143 126
51 41 58.4 55.8 101 109 114 117 123 136 152 134
54 42 61.8 59.1 107 116 120 124 130 144 160 142
55 44 63.0 60.2 109 117 122 126 132 146 163 144
60 48 68.7 65.7 119 128 133 137 144 159 178 157
66 53 75.6 72.3 131 141 147 152 159 175 196 173
72 57 82.4 78.8 142 153 159 165 173 191 213 188
75 60 85.9 82.1 148 160 166 172 180 199 222 196
78 63 89.3 85.4 155 167 173 179 188 207 232 204
81 65 92.7 88.7 160 173 180 186 195 215 240 212
84 68 96.2 92.0 166 179 186 192 202 223 249 220
90 70 103 98.6 178 192 199 206 216 238 266 235
94 73 108 103 186 201 208 215 226 249 278 246
96 76 110 105 190 205 213 220 231 255 285 251
102 82 117 112 201 217 226 233 245 270 302 266
108 84 124 118 214 231 240 248 260 287 320 283
108 88 124 118 214 231 240 248 260 287 320 283
114 92 131 125 225 243 253 261 274 302 338 298
120 98 137 131 237 255 265 274 288 317 355 313
129 104 148 141 255 275 286 295 310 342 382 337
132 106 151 145 260 281 292 302 317 349 390 344
138 111 158 151 273 294 306 316 332 366 409 361
144 115 165 158 284 307 319 329 346 381 426 376
150 121 172 164 296 319 332 343 360 397 443 391
168 131 192 184 332 358 372 384 404 445 497 439
172 140 197 188 339 366 380 393 413 455 508 448
180 144 206 197 355 383 398 411 432 476 532 469
192 152 220 210 379 408 425 438 461 508 568 501
198 160 227 217 391 422 438 453 476 524 586 517
4.0 / 3.40 Q004SA003A 11.2 (284) 7.7 (197) 120 18 (8.2) 14.42 (367) 1
5.0 / 4.25 Q005SA004A 11.2 (284) 7.7 (197) 120 18 (8.2) 14.42 (367) 1
6.0 / 5.10 Q006SA005A 11.2 (284) 7.7 (197) 120 18 (8.2) 14.42 (367) 1
7.0 / 5.95 Q007SA006A 11.2 (284) 7.7 (197) 120 18 (8.2) 14.42 (367) 1
8.0 / 6.80 Q008SA007A 11.2 (284) 7.7 (197) 120 18 (8.2) 14.42 (367) 1
9.0 / 7.65 Q009SA008B 11.2 (284) 7.7 (197) 120 18 (8.2) 14.42 (367) 1
10 / 8.40 Q010SA008B 11.2 (284) 7.7 (197) 120 18 (8.2) 14.42 (367) 1
12 / 10.2. Q012SA010A 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
15 / 12.7 Q015SA012A 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
18 / 15.3 Q018SA015A 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
21 / 17.0 Q021SA017B 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
45 / 36.5 Q045SA037A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
48 / 39.0 Q048SA039A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
51 / 41.0 Q051SA041A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
54 / 42.0 Q054SA042A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
55 / 44.0 Q055SA044A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
60 / 48.0 Q060SA048A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
66 / 53.0 Q066SA053A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
90 / 70.0 Q090SA070A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
94 / 73.0 Q094SA073A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
96 / 76.0 Q096SA076B 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
102 / 82.0 Q102SA082B 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
108 / 84.0 Q108SA084D 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
108 / 88.0 Q108SA088B 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
114 / 92.0 Q114SA092B 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
120 / 98.0 Q120SA098D 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
129 / 104 Q129SA104B 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
132 / 106 Q132SA106D1 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
132 / 106 Q132SA106E 133.4 (3388) 39.7 (1009) 700 94 (43) 58.62 (1489) 3
138 / 111 Q138SA111B 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
144 / 115 Q144SA115C 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
150 / 121 Q150SA121B 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
168 / 131 Q168SA131C 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
172 / 140 Q172SA140C 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
180 / 144 Q180SA144B 200.1 (5082) 65.7 (1669) 1050 137 (63) 84.61 (2149) 4
192 / 152 Q192SA152C 200.1 (5082) 65.7 (1669) 1050 137 (63) 84.61 (2149) 4
198 / 160 Q198SA160B 200.1 (5082) 65.7 (1669) 1050 137 (63) 84.61 (2149) 4
4.0 / 3.40 Q004SB003A 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
5.0 / 4.25 Q005SB004A 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
6.0 / 5.10 Q006SB005A 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
7.0 / 5.95 Q007SB006A 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
8.0 / 6.80 Q008SB007A 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
9.0 / 7.65 Q009SB008B 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
10 / 8.40 Q010SB008B 23.6 (599) 11.6 (297) 175 22 (10) 18.36 (466) 1
24 / 19.5 Q024SB019A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
27 / 22.0 Q027SB022A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
30 / 24.4 Q030SB024A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
33 / 27.0 Q033SB027A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
36 / 29.0 Q036SB029A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
39 / 31.5 Q039SB031B 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
42 / 34.0 Q042SB034B 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
72 / 57.0 Q072SB057A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
75 / 60.0 Q075SB060A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
78 / 63.0 Q078SB063A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
81 / 65.0 Q081SB065A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
84 / 68.0 Q084SB068A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
90 / 70.0 Q090SB070A 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
94 / 73.0 Q094SB073A 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
96 / 76.0 Q096SB076B 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
102 / 82.0 Q102SB082B 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
108 / 84.0 Q108SB084D 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
108 / 88.0 Q108SB088B 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
114 / 92.0 Q114SB092B 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
120 / 98.0 Q120SB098D 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
129 / 104 Q129SB104B 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
132 / 106 Q132SB106D 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
138 / 111 Q138SB111B 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
144 / 115 Q144SB115C 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
150 / 121 Q150SB121B 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
168 / 131 Q168SB131C 200.1 (5082) 65.7 (1669) 1050 137 (63) 84.61 (2149) 4
172 / 140 Q172SB140C 200.1 (5082) 65.7 (1669) 1050 137 (63) 84.61 (2149) 4
4.0 / 3.40 Q004SC003A 42 (1067) 17.6 (447) 250 33 (15) 24.27 (616) 1
5.0 / 4.25 Q005SC004A 42 (1067) 17.6 (447) 250 33 (15) 24.27 (616) 1
6.0 / 5.10 Q006SC005A 42 (1067) 17.6 (447) 250 33 (15) 24.27 (616) 1
7.0 / 5.95 Q007SC006A 42 (1067) 17.6 (447) 250 33 (15) 24.27 (616) 1
8.0 / 6.80 Q008SC007A 42 (1067) 17.6 (447) 250 33 (15) 24.27 (616) 1
9.0 / 7.65 Q009SC008B 42 (1067) 17.6 (447) 250 33 (15) 24.27 (616) 1
12 / 10.2. Q012SC010A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
15 / 12.7 Q015SC012A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
18 / 15.3 Q018SC015A 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
21 / 17.0 Q021SC017B 66.7 (1694) 25.5 (647) 350 47 (22) 32.14 (816) 1
45 / 36.5 Q045SC037A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
48 / 39.0 Q048SC039A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
51 / 41.0 Q051SC041A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
54 / 42.0 Q054SC042A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
55 / 44.0 Q055SC044A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
60 / 48.0 Q060SC048A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
66 / 53.0 Q066SC053A 108.7 (2761) 43.6 (1107) 600 76 (35) 50.25 (1276) 2
72 / 57.0 Q072SC057A 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
75 / 60.0 Q075SC060A 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
78 / 63.0 Q078SC063A 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
81 / 65.0 Q081SC065A 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
84 / 68.0 Q084SC068A 133.4 (3388) 51.5 (1307) 700 90 (41) 58.12 (1476) 2
90 / 70.0 Q090SC070A 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
94 / 73.0 Q094SC073A 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
96 / 76.0 Q096SC076B 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
102 / 82.0 Q102SC082B 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
108 / 84.0 Q108SC084D 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
108 / 88.0 Q108SC088B 150.7 (3828) 50.0 (1269) 850 109 (50) 68.86 (1749) 4
114 / 92.0 Q114SC092B 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
120 / 98.0 Q120SC098D 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
129 / 104 Q129SC104B 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
132 / 106 Q132SC106D 175.4 (4455) 57.8 (1469) 950 123 (56) 76.73 (1949) 4
138 / 111 Q138SC111B 200.1 (5082) 65.7 (1669) 1050 137 (63) 86.41 (2149) 4
144 / 115 Q144SC115C 200.1 (5082) 65.7 (1669) 1050 137 (63) 86.41 (2149) 4
150 / 121 Q150SC121B 200.1 (5082) 65.7 (1669) 1050 137 (63) 86.41 (2149) 4
(Example: 5 kV Q015SA012AUH)
(Example: 15 kV Q015SA012ASAA6)
DATE U.S.A.
STYLE NO. SERIAL NO.
Galvanized steel
Aluminum
Note: Line and ground terminals can accommodate copper or aluminum cable size Number 2 to 1000 MCM / 0.25 to 1.15 in. diameter. Ground terminal can be located on any lug.
The phase-to-ground clearance in substations is usually based The Adjusted Protective Level to be used in Figure 1, is defined
on the selected standard rated lightning and switching impulse as:
withstand voltages. International standards, e.g. IEC 60071-2, - For lightning impulse:
recommend minimum clearances. Lpl x 1.15 x eH/8150
- For switching impulse:
In general, the clearance between a grounded object and a surge Spl x 1.10 x eH/8150
arrester should be the same as the phase-to-ground clearance
selected for other high voltage equipment in a substation. If it H is the altitude in meters above sea level.
is not possible to use the normal phase-to-ground clearance
in special applications of POLIM-S Surge Arresters, a smaller Lpl and Spl are the lightning and switching impulse protective
clearance may be chosen, considering the protective levels for the selected POLIM-S Surge Arresters at the respective
characteristics of the arrester. At system voltages 24 kV and coordinating currents.
below, the margin between the rated withstand voltage of the
substation and the protective level of the surge arrester is large. The minimum clearance is determined either by lightning or
Furthermore, distance effects by fast transients do not exist in the switching impulse withstand, whichever renders a larger value.
immediate vicinity of the surge arrester.
(cm) 200
Switching impulse
150
Lightning impulse
100
50
0
0 100 200 300 400 500 600 700 800 900 1000
Adjusted Protective Level (kV)
The phase-to-phase clearance for high voltage equipment in The Adjusted Protective Level shown in Figure 2 is based on the
a substation is normally based on the selected standard rated lightning protective characteristics of the selected POLIM-S Surge
lightning and switching impulse phase-to-phase withstand voltages. Arresters. It includes safety margin and altitude correction factors and
International standards, e.g. IEC 60071-3 recommend minimum is defined as:
phase-to-phase clearances. Note that the normal election of surge Lpl x 1.15 x eH/8150 + Vm x √2 / √3
arrester protective levels does not directly protect the phase-to-phase
insulation. - Vm is the highest voltage for equipment according to IEC 60071-1,
which is usually equal to the highest system voltage.
In general, the clearance between surge arresters in adjacent phases - Lpl is the lightning impulse protective level for the selected POLIM-S
should be the same as the phase-to-phase clearance selected for Surge Arrester.
other high voltage equipment in the substation. If it is not possible
to use the normal phse-to-phase clearance in a special application The minimum phase-to-phase clearance for arresters with respect
of POLIM-S Surge Arresters, the minimum clearance with regard to to switching overvoltages should always be based on the selected
lightning overvoltages can be derived from Figure 2. standard rated switching impulse phase-to-phase withstand voltage
for the substation. Consequently, the clearances specified in IEC
The clearances shown in Figure 2 are based on the assumption that 60071-3, Table VI, are valid for most applications of arresters. If a
one phase is subjected to a lightning overvoltage, while the voltage on special application requires a minimized phase spacing, the favorable
the adjacent phase is at the peak of the maximum power frequency electrode configuration established by the grading rings on POLIM-S
operating voltage (opposite polarity). Obviously, these clearances Surge Arresters may permit a further reduction of the phase-to-phase
will also cover the case of lightning overvoltages of the same polarity clearance.
appearing simultaneously on two or three phases.
(cm) 250
200
150
100
50
0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200
Adjusted Protective Level (kV)
ABB Inc.
www.abb.us
3/13/2013 CERTIFIED FOR: CATERPILLAR INC; PO #: ; PROJECT NAME: VMSC; KATO SN: 31065;
3/13/2013 CERTIFIED FOR: CATERPILLAR INC; PO #: ; PROJECT NAME: VMSC; KATO SN: 31065;
3/13/2013 CERTIFIED FOR: CATERPILLAR INC; PO #: ; PROJECT NAME: VMSC; KATO SN: 31065;
.500 X .250 KST 2.000 X .375 KST 2.000 X .750 KST
Step Diameter Length WK² Weight Added WK² Added Weight DESCRIPTION
(Inches) (Inches) (lb in²) (lbs) (lb in²) (lbs)
1 5.75 6.00 182.23 44.1
2 5.75 6.00 182.23 44.1 9879.80 502.1 EXCITER, PMG
3 7.87 5.19 553.16 71.4
4 7.08 3.56 248.38 39.7
3.00 6.50 6.50 9.00
5 7.08 3.56 248.38 39.7 BRG CENTERLINE
6 7.87 2.94 313.35 40.5
7 8.49 2.50 361.56 40.1 1 2 3 4 5 6 7 8 9 10 11 12 131415 16 17 18 19 20 21
8 10.50 2.38 803.75 58.3
9 11.25 13.62 6061.41 383.1
10 11.51 21.88 10654.45 643.8
11 11.51 21.00 10225.94 617.9 1860713.00 10666.0 ROTOR
12 12.00 8.12 4678.08 259.9
13 11.25 1.62 720.96 45.6
14 10.50 2.38 803.75 58.3
15 8.49 2.50 361.56 40.1
16 7.87 3.34 355.99 46.0
17 7.08 3.16 220.48 35.2
18 7.08 3.16 220.48 35.2 BRG CENTERLINE
19 7.87 3.84 409.28 52.9
20 7.75 7.50 751.72 100.1
21 7.75 3.00 300.69 40.0 14749.00 328.0 COUPLING HUB
Kato Engineering
TOTAL WK² (lb ft²) 13361.11 TITLE
TORSIONAL DATA
Kato Engineering
TITLE
TORSIONAL DATA