You are on page 1of 7

Key Condenser Failure Mechanisms

Issue 4 and Volume 113.


4.1.09

  
  

Eight practical lessons highlight troublesome condenser tube corrosion issues.


By Brad Buecker, Contributing Editor
The steam surface condenser is an integral component at electric utilities and other
facilities that generate power. It is also the point where highly pure condensate can
potentially come in contact with very impure cooling water via a condenser tube leak.
The consequences literally can be catastrophic for plant operations.

During much of my career at two coal-fired utilities, I monitored condenser


performance for a number of units, where the condenser tube metallurgy ranged
from Admiralty brass to copper-nickel alloys to stainless steel. This article outlines
many of the factors that can influence condenser tube corrosion and the effects
contaminant in-leakage can have on steam generating units.

Figure 1 Hydrogen damage in a waterwall tube


Photo courtesy of the Nalco Co.  Click here to enlarge image

The literature contains many references to the problems caused by cooling water
infiltration into steam system condensate. We will examine a few of these problems
as a refresher on how impurities can affect boiler water chemistry.

Numerous authors have described water as the closest thing to a universal solvent.
While this is an oversimplification, water’s unique properties do give it powerful
solvating characteristics. Typical cooling waters, whether from a surface supply or
from wells, contain many compounds absorbed from the earth and the atmosphere.
Ground waters usually contain greater mineral concentrations than surface waters,
including calcium, magnesium and iron. These dissolve in water as it percolates
through the soil and underlying rock formations. Surface waters are often softer, but
contain many more suspended solids as well as organic compounds, the latter due
to decomposing leaves and plant material. Common organics include tannins and
lignins, whose rather complicated structures resemble the carbon-based plant
material from which they derive.

Figure 2 MIC in a stainless steel tube


Source: The Nalco Guide to Cooling Water Systems Failure Analysis.  Click here to
enlarge image

When contaminants enter a steam-generating system, the high temperatures will


initiate many reactions. Well known is the potential for scaling by calcium salts. Silica
may precipitate by itself to form a hard, insulating deposit. Or it may combine with
magnesium or other ions to form additional troublesome scales. Impurities,
particularly silica, will carry over with steam and precipitate in turbines and reheater
lines. Although boiler water treatment programs help mitigate these reactions, if an
upset is too severe the treatment may be overwhelmed, as the following lesson
illustrates.

Lesson No. 1
An 80 MW unit supplied by a 1,250 psig coal-fired, cyclone boiler had just been
returned to service from a scheduled outage. Laboratory personnel discovered a
condenser leak was allowing contaminants to enter the system, such that
condensate total-dissolved-solids (TDS) concentrations at times reached 0.75 ppm.
Although lab staff asked that the boiler be taken off line immediately, operations
managers declined due to load demand issues. The boiler was on phosphate
treatment, so lab staff increased monitoring frequency and attempted to maintain
phosphate and pH levels within recommended guidelines. After roughly three weeks,
operators discovered the source of the leak and corrected the problem.

Two months later, boiler waterwall tubes began to fail with alarming frequency. The
unit came off numerous times for tube repairs. In at least one instance it had only
been back on-line for a few hours when another tube failed. The failures happened
so regularly that plant management scheduled an emergency tube replacement
during an upcoming outage at a cost of over $2 million. The mechanism attributed to
these failures was under-deposit corrosion caused by excessive sludge and scale
formation. Interestingly, the leak was not from a failed condenser tube. The
condenser hotwell is equipped with a drain line that discharges to the cooling water
outlet tunnel. During the outage, an operator opened the line to drain the hotwell but
forgot to close the isolation valve before startup. Once the unit went on-line, the
strong condenser vacuum pulled cooling water into the hotwell.

Impurities can quickly initiate corrosion in a boiler. The reaction below outlines what
occurred in this case history.

MgCl 2 + 2H 2O + heat → Mg(OH) 2↓ + 2HCl

Magnesium chloride or sulfate salts react with water to produce a magnesium


hydroxide precipitate, plus acid. This can cause the boiler water pH to fall well below
neutral, which—given the harsh conditions inside a boiler —is potentially
catastrophic. Not only will acid cause general corrosion, but the hydrogen atoms
produced by the reaction form molecular hydrogen, which penetrates tube metal due
to the element’s small size. The hydrogen gas by itself induces internal pressure in
the steel that can cause metal cracking. It will also react with carbon to produce
methane (CH4), a larger molecule, which exacerbates the cracking mechanism.

Hydrogen damage failures may result in a matter of days without any appreciable
metal loss following a significant condenser tube leak, particularly if the cooling water
is cycled up in a cooling tower or comes from brackish or ocean makeup sources.
The Electric Power Research Institute (EPRI) recommends immediate boiler
shutdown if the pH drops to 8.0. The following case history illustrates how rapidly
contaminant in-leakage can affect boiler water chemistry.

Lesson No. 2
This problem involved a 200 MW unit with a 2,400 psig, coal-fired tangential boiler.
The unit was on phosphate treatment with typical bulk water phosphate
concentrations of 2 to 6 ppm. At the time of this event, the unit’s only on-line
chemistry monitoring consisted of a sodium analyzer at the condensate pump
discharge (CPD). The monitor was not equipped with an alarm. On the morning of
the upset, a unit operator checked the monitor at 7:00 a.m. and found the sodium
concentration measured less than one part-per-billion (ppb). When lab chemists
checked at 7:45 a.m., the monitor needle was pegged beyond the upper limit of 100
ppb. Lab personnel took a boiler water sample and found that no phosphate
remained in the sample and that the pH had dropped to 5.8. The chemists notified
operations personnel, who took the unit off as quickly as possible. During this time
the chemists injected trisodium phosphate into the boiler water to stabilize the pH
and establish a phosphate residual. The operators opened the blowdown drains on
the lower headers to remove solids.

Once the unit came off-line, maintenance personnel discovered the problem. A plug
had fallen out of a topmost condenser tube, which had previously failed due to steam
erosion. (Another failure mechanism to inspect for during outages.) The tube had
massive failures across its length, so large quantities of cooling water poured into the
condenser. Even though this condenser is on a once-through cooling system
supplied with relatively soft lake water, the contaminants quickly consumed the
boiler’s phosphate. Quick action by plant staff prevented serious scale formation or
corrosion. The boiler was chemically cleaned at the earliest available opportunity and
no tube failures occurred. However, the event helped convince utility managers to
install a comprehensive on-line water chemistry monitoring system.

Lesson No. 3
A unit with a condenser tubed with 304 stainless steel came down for a scheduled
maintenance outage, but the waterside of the condenser was not drained. Many of
the tubes remained immersed in standing water for about a month. When the unit
came back on line, cooling water in-leakage to the condensate was severe. Upon
inspection, plant personnel discovered numerous pinhole failures in the tubes. The
failure mechanism was microbiologically induced corrosion (MIC) produced by the
stagnant conditions. When microbes attach to tubes, anaerobic bacteria will grow
and flourish underneath the overlying layer of slime. Anaerobic bacteria do not, as
the name implies, use oxygen in their metabolic processes. Rather, they use other
chemicals such as sulfate (SO4) for energy. Resulting byproducts include acid and
other compounds, including hydrogen sulfide (H 2S). These compounds then produce
pitting in the tube metal. Pitting is an insidious corrosion mechanism, as failures
result with little loss of tube material.

Figure 3 Sulfide pitting of a copper-alloy tube


Photo courtesy of the Nalco Co.  Click here to enlarge image

Underdeposit corrosion will also occur while units are in operation if scale or
microbiological deposits are allowed to accumulate on condenser tubes. These
deposits will also severely retard heat transfer, where loss of efficiency can cost a
large plant thousands of dollars a day making it important to implement and monitor
proper cooling water chemistry programs.

Lesson No. 4
Another condenser was originally equipped with Admiralty (70 percent copper and
30 percent zinc) tubes, which had begun to fail after 17 years due to steam-side
ammonia/oxygen attack (discussed below). Plant personnel decided to replace the
tubes with 90-10 copper-nickel, a material that had performed well in other
condensers. Within two years, the new tubes began to fail. When a tube was pulled
for examination, numerous pits were observable on its waterside. A single one-foot-
long half-section sample contained eight through-wall penetrations. The corrosion
was traced to the manufacturing process and a supplier that had used a lubricant
containing sulfide (S-2), which is a corrosive agent to copper. The supplier did not
clean the tubes before they were installed so the sulfide kept eating through the
tubes until they failed.

Lesson No. 5
The condenser outlined in lesson 4 had operated well. But without warning
numerous failures began to occur in the air-removal section. These failures caused a
number of forced outages. During one outage, maintenance personnel pulled four
tubes that previously had been plugged. Each of the four Admiralty brass tubes
showed circumferential gouges at interface points between the tubes and tube
support plates. The gouges showed many small cracks and one or more of the
gouges in each tube contained a through-wall penetration. The corrosion was
identified as ammonia-oxygen attack of the metal.

Air enters a steam-generating system at points around the condenser due to the
strong vacuum generated within. Prime spots for in-leakage include the expansion
joint between the turbine and the condenser, penetrations of heater drips lines into
the condenser shell, turbine seals and explosion diaphragms and condensate pump
seals. Air in-leakage is almost impossible to prevent, but the effects are manageable
under normal conditions. Most condensers are equipped with one or more air-
removal compartments in which a mechanical vacuum is applied to pull in gases
from the condenser and exhaust them to the atmosphere. However, this process
also concentrates chemicals in the air removal zone, including oxygen and ammonia,
the latter generated by feedwater chemistry treatment. Concentrations of ammonia
are typically high in condensate that collects on tube support sheets and flows
downwards and around the tubes to the hotwell below. Oxygen converts the
protective cuprous oxide (Cu2O) film on the tube surfaces to cupric oxide (CuO),
after which the ammonia complexes the copper and puts it in solution.

Cu +2 + 4NH 3 → Cu(NH 3) 4+2


Lesson No. 6
An interesting cooling water in-leakage problem occurred on one of the condensers
outlined above. The condensate pump discharge (CPD) is equipped with on-line
sodium and cation conductivity monitors. Sodium concentrations typically range
between 0.5 and 0.9 ppb. During one three-week stretch of baseload operation,
condensate sodium levels periodically increased to a range of 1 to 2 ppb, where they
remained for anywhere from several hours to as long as a day before returning to
normal. The sodium fluctuations could not be traced to operational factors such as
load changes or soot blowing, so plant chemists concluded that a condenser tube
leak had developed. At the earliest opportunity, operators took the unit off line.
Maintenance personnel using the dye-check method found a small leak in one tube
which, once plugged, made the problem disappear. However, the question remained
as to why the contamination appeared and then disappeared with regularity. What
seems certain is that the pinhole periodically plugged with debris that entered with
the cooling water.

Lessons Nos. 7 and No. 8


In a 1992 Power Engineering article, I reported on a condenser performance
program that proved excellent for monitoring heat transfer and troubleshooting
problems.1 Subsequent work produced several lessons learned, two of which are
outlined below.

Figure 4 Ammonia-oxygen attack of a copper alloy tube


Source: The Nalco Guide to Cooling Water Systems Failure Analysis.  Click here to
enlarge image

I had been performing thrice-weekly cleanliness factor analyses on a condenser


rated at 1 million lb/hr of steam flow. The values remained very steady in the mid 70
percent range for several months, but dropped within two days to 45 percent.
Waterside fouling does not occur this rapidly and such drastic changes are more
indicative of excess air in-leakage. The maintenance department was notified and
when they inspected the condenser they discovered a crack in the condenser shell
where a heater drips line penetrates. Once maintenance workers sealed this crack,
the cleanliness factors returned to previous values where they remained for another
two months until suddenly dropping again. The seal had failed. This time the
maintenance crew welded a collar around the drips line, which sealed the crack
entirely and solved the problem.

In another instance, I had been collecting thrice-weekly readings on two, 690,000


lb/hr. condensers when one condenser suddenly began performing erratically. At
maximum unit loads, the cleanliness factors ranged between 70 percent and 75
percent. At low loads, however, the factor dropped as low as 18 percent. Here, too,
such fluctuations could not have been the result of waterside fouling. Utility
managers brought in a leak detection firm to look for air leaks using helium leak
detection to completely check the condenser and low-pressure end of the turbine.
The inspectors classified leaks as large, medium and small, and found over a dozen
leaks, including two large leaks (one of which was caused by a crack in the
expansion joint between the turbine exhaust and condenser). Maintenance crews
repaired all leaks, but this did not solve the problem.

Finally, an operator discovered that a trap on a line from the gland steam exhauster
was sticking open at low loads. The trap and line are designed to return condensed
gland steam from the condensate subcooler to the condenser, but vent gases to the
atmosphere. When the trap stuck open, the strong condenser vacuum pulled outside
air in through the vent. Once maintenance personnel replaced the trap, the
condenser performance problems disappeared. This example illustrates how
complex the task can sometimes be to identify sources of air in-leakage.

Reference
1. B. Buecker, “Computer Program Predicts Condenser Cleanliness”; Power
Engineering, Vol. 96, No. 6, June 1992.

You might also like