1. Introduction
Power line communication (PLC) has been duplicate the power line characteristics.
available since October 2006 according to the The simulator consists of two analog units
official gazette in Japan. PLC is restricted to and one digital unit which can simulate PLC
use only indoors and in the frequency range transmission channel characteristics. Figure 1
of 2 to 30MHz. Normally Surge Protective shows the block diagram of it. The clock
Devices (SPD) are installed on a main power speed for 14 bit A/D and 16 bit D/A converter
distribution board or inside an electric is 125 MHz and FIR digital filter is 1024 tap.
apparatus. Because no investigations have The propagation delay is less than 1
been done on transmission characteristics of microsecond. It can duplicate the power line
PLC when using SPD, we examined several transmission characteristics whenever you
examples of PLC transmission configurations like. it is also possible to add more
using PLC transmission channel simulator. attenuation, white noise with Gaussian
From our experiments, we found that the distribution and synchronized noise
transmission rate degraded when using a generated by electric-equipment.
varistor-type SPD. When installing an SPD
for a PLC, it is necessary to only use a GDT
(Gas Discharge Tube) or connect a GDT with
a varistor in series.
219
was 11-15 Mbps degradation when installing
the varistor under flat line conditions. And
there was about 7-8 Mbps degradation when
installing the varistor under real power line
conditions.
The measured PLC modem rates with
multiple varistors under the condition of 60
dB flat attenuation are listed in Table 3.
220
From this experiment, we have greater series, the degradation of PLC modem rate is
infulence for PLC modem performance when
less than 1Mbps, which does not affect
transmission characteristics of PLC.
installing multiple varistors.
(3)When installing an SPD on a PLC circuit
Low impedance values of varistors
it is necessary to use a GDT only or
caused a PLC modem rate degradations. In
connecting a GDT with a varistor in series.
order to reduce the effect of Metal oxide
varistors, we propose to use a GDT (Gas
Discharge Tube) as well as varistors.
Reference
When a GDT was inserted in a varistor in
(1) Ministry of Internal Affairs and
series, the degradation of PLC modem rate is
less than 1Mbps under any conditions Communications,“Authorities Report”
mentioned above. We can achieve almost Oct.2006 (in Japanese)
ideal environment for PLC by using a GDT.
This is because the capacitance of a GDT as
low as several 10pF, and the impedance at
30MHz is comparatively as high as several
100 Ohm, which does not affect a
transmission characteristic of PLC.
When installing an SPD for a PLC circuit it
is necessary to use only a GDT or connect a
GDT with a varistor in series.
4. Conclusions
In this paper we investigated power line
simulation method using PLCS3000 which
can duplicate the real power line
characteristics efficiently. It was confirmed
that the influence on transmission
characteristics of PLC when using SPD.
(1)Impedance values of varistors at the
maximum frequency of 30MHz for PLC are
about 0.35 Ohm, and they are very low as
compared with those of commercial
frequencyies. This low impedance nealy
created short circuit conditions for PLC
trasmision signals and caused PLC modem rate
degradations.
(2)When a GDT was inserted in a varistor in
221