EMEK ELEKTRIK
ENDUSTRISi A.S.TY PE sicnation
Inductive Voltage Transformers ; GT1-72.5
Inductive Voltage Transformers. : GT1-125
: GT1-145
Inductive Voltage Transformers : GT1-170
Inductive Voltage Transformers : GT41-245
Inductive Voltage Transformers : GT1-300
Inductive Voltage Transformers : GT1-362
Inductive Voltage Transformers : GT1-420
Inductive Voltage Transformers
DESCRIPTION
Production
EMEK voltage transformers are
manufactured in Ankara Turkey.
Special Design
Non standard core data, creepage, seismic, atc.
designs are available on request.
Standards
All transtormers are subjected to full routine tests as
describad in the relevant standards.
Type tests can also be performed In our own testing
laboratories but should be negotiated during the order
slage.
Quality Assurance
Emak is 1SO 9001 certified by both ABS Qual
Evaluation Inc. and TSE, Turkish Standards
Institute.
DAT Accauireo TO MAKE AN OFFER
———— General
+ Quantity * Insulation Level
+ Delivery Time: + Frequency
* Destination « Number of Windings
+ Service Conditions» Voltage Ratio
+ Others + Rated Burden
ElectriCal Data
+ Accuracy Class for Each Winding.
+ Standards
+ Voltage Rating Factor
+ Creepage Distance
for Each Winding
EE
General Description
* Primary and secondary windings are housed in a porcetain
bushing.
* Including and above 245 kV EMEK VT's are _twa piece
designs, commonly known as ‘Cascade’. These are
basically two independent VT'S connected in series. They
‘re named the top unit and bottom unl
+ Transformers are hermotically sealed.
Frequency
#50 Hz, 60 Hz
Rated Secondary Voltage
#11013, 10043 V'etc. in conformity with customer
requirement.
Rated Tertiary Voltage
#110/N3, 1003, 110/3, 100/3, 100, 140 V etc.
fn conformity with customer requirement,
Highest System Voltage
‘+ Highest system voltage from 72.5 te 420 KV.
Number of Secondary Windings
* In conformity with customer requirements.
Voltage factor
4.2.x Un continuous / 1.9 x Un for 30 sec,
‘Standards
IEC, BS, ANSI, AS, other standards on request
Hermetic Seal
* Oil volume variations are compensated with stainless steel
balinws placad in the head of the current transformers.
‘= With this facility there will be no contact between air and ol.
* The dielectric strength will remain unchanged for the life time
ofthe VT.a __—
Primary Terminals.
* Primary terminals are made from tin plated brass.
* Vertical and horizontal primary terminals are available.
* Dimensions of stud typa are 30x 80 im. Nema ped or
amp type primary terminals are avallable on request
Core
* High quality stieet sleet cores. are used.
Paper Insulation
" Olimpregnated peper high alecc tang, low delectic
losses.
Bushing =
** Brown glazed porcelain (other colours on request).
* Extra high creepage aistance is also possible on raquest.
Oil Insulation
** The insulating oi! is mineral oil in conformity with IEC 296.
Before impregnation, moisture and gases are removed
from the oll by special processes,
* Drain plug for taking samples and oll refiling facilities are,
provided on request.
* Floating type oll level indieatoris standard supply.
‘Oil Impregnation
* Heat and vacuumiare applied ta the fully insulated windings
afler assembly of the magritic unit for drying purposes,
followed inimédiately by oil impregnation procedure.
Accessories
* Fixing holes, lifting holes, secondary terminal box, name
Blate, warning plates are aso provided in our staridare
ign.
Secondary Terminal Box
* Hinged type boxes are Used and aré sealable on request
* Secondary terminals are-clamp type, other types are also
available on request
* Fuses or MB's are also available on request.
Name Plate
* Name plates are stainless stee! and weatherproof.
Primary Windings
+ Enameled electrolyte copper wire is used for pamary
windings of intermediate votlage transformer
Secondary Windings
+ Enamelied ‘copper wire is used for secondary
windings of intermediate voltage trafisformer.
External Binding Elements,
* All extemal bolts, nuts, washers atc: are either stainioss
steel or hot dip galvanised steel.
Painting
+ External surface of the transformers, which ara already
Corrosion protected (e.g. by galvanising), are additional
painted grey colour. Other colours are available on request,
Earthquake Design
+ Standard design is up to 0.69.
Mechanical Strength
+ Applied load to the primary terminal in horizontal and
vertical is in conformity with IEC 6004.42
Ambient Temperature
* Standard design is suitable for temperature range -25°C
to0 *C Other ranges on requast.
Altitude
* Standard dasign is suitable up to 1000 m above sea level.
Higher values on request,
Bracelet
* All bracelets used on transformers are made from aluminium
alloy.
‘Optional Accessories
» Steel support siructure
Primary connectors
* Marshailing box.
Storage
+ itis recommended to store the transformers in their factory
packed condition prior to installation.
Packing
* The transformers are packed in rugged wooden erates:
‘Which are suitable for transportation.
+ The transformers ore encapsulated in polyethylene covers
to keep them from environmental effects such as rain‘,
dust and sand etc. (during transport and storage)
+ Wooden crates can be lifted by elther a fork lit or by a
Grane with slings,
‘Spare Part
+ There are_no user serviceable par, therefore no spare
parts are required,
Maintenance:
‘+ Maintenance free, simple recommendations >
* A. Complete and thorough inspection should be carried out
invevery year
* Clean the porcelain bushiny al teyular intervals depending
On the dagres of potlution,
“Ensure that there is 110 oll ieakage.
+ Periodical measurement of capacitance and power factor
are recommended,
Special Tools
+ No special tools are required for the maintenance.
Assembly
€ Foes assembly, the following visual chacks should be
m
‘There are no oll leaks
‘+The poteelain is not damaged
‘There is no damage'on the primary terminals
+ The oll level indicator indicates sufficient oil evel
+ Lifting holes are provided on the base plate. These should
be used for iting and assembly.TRANSPORTATION
‘Transportation is only possible in the
upright (vertical) position. The VT should
never be transported or stored in the
horizontal position. The crates should not
be put on top of each other. Attention
should be paid to the red "UP" arrows on
the crate.
HANDLING
For transformers which have been
transported and/or stored in horizontal
position for any reason, fectory level re-
conditioning and testing is necessary.
‘The vehicle used for transportation must
be of adequate size. The packing must
be tightly secured to the chassis of the
transportation vehicle.
Hfunpaved and rough roads are to be
travelled, care should be given to prevent
rigorous vibration, Prolonged and rough
vibration may lead to oil disturbances
CORRECT MAX INCLINATION WRONG.
ASSEMBLY
NEVER
Use the primary
terminals,
bracelets or porcelain
bushing
forlifting the
transformers
Lift the transformers d
by using the holes :
provided on the base.
TE
WRONG CORRECT |
fMAIN FEATURES OF
NOUC NOETAGr.
245 - 420 kV
Cascade type inductive voltage transformers are made up from two individual and
independent VT's which are connected in series.
The upper and lower part have independent oll compartments therefore no oil connection
is made between the units.
Each unit has its own stainless steel bellow for compensating the change in the oil volume
due to temperature variation.
The height of the units is suitable for upright (vertical) transport on normal trucks and
they will pass under standard bridges. This way complications of horizontal transport are
avoided.
Both units are assembled on site. Simple electrical connection is made between the
upper part and the lower part. No special tools are required for connection.
The line (and test) voliage is shared equally by both units. The insulation task of each
unit is actually half of the task of a single piece unit. Therefore there \s considerably less
strain on the insulation. Less insulation strain means longer life.
Minimum ferrous surfaces are subjected to the environment to minimise corrosion.
Ferrous surfaces are hot dip galvanised and painted.
A
&
&
- <
Single line | .
diagram ue
of 5
cascade j iE
a
inductive voltage t i <
transformer 2a
mn 2CROSS SECTION,
INDUCTIVE VOLTA
420 kV VT
4
12
13.
14,
18.
TRANSFORMERS
72.5-170 kV VT
as
10]
1) Filing Tap
‘Aluminium Cover
Stainless Steel Bellows
Oi Laval indicator
Primary Terminals
Heac
oi
Primary Winding and Paper Insulation
Magnetic Core
Winding and Paper Insulation,
Porcelain Bushing.
‘Secondary terminal box
Lifing holes
il Sampling Vave
BaseDATA, wes
Desenation arts | ati25 | orttas | atia70
Highest System Votlage | WV | 726 | 123 [tas] 170
Rated Frequency Hz 50 or 60 |
Fated primary Volage Kv ‘fom 60 KV up to 54K
Rated Secondary Votage_| V | _100N6, 110A, 1008, 1108, 100,170 6a
Test votages iy | wa0es [220860 | arseso | sesran
Reted Votage Facior A | 4.2 Un Gontinicusri ox Un for30 sec
Type of cannetion Phase to Ground
Greopane isancet) | am | 160] paco [6600] a,
Dimensions ~_[ mm | 1336 40 | _vea0 | 2205
B [mn] tao | 1640 | 1500 | 1908
& [mn | 900 | 1300 | 100 | ase ;
o [mm] ms [7s [ae | avs
(")Highor creepage distance are also avaliable on request
ae
Saati es Ee
Highest System Voltage 300, 362] 420
Rated Frequency [ve 50 or 60
ates pray Votage [wv TORE Vip w OT
Rated Secondary Voltage v 110W3, 100/V3, 10073, 110/3, 100, ect
Test Vato hey faeonoso [siomt76 | sronaoo | esaraes
fied Youge Fee 2 Conncue
Creepage distance(") [mm | 4800 ‘6000 7240 Ea
ar Aelia meas Soo [om | a
aid iene aa [S|
Galleri aoa | exces | neaeoe fear
‘00 [7600 | 800
(() Higher creepage distance are also avaliable on ales!
eeBLES
DATA, |
PACKING DETIALS (Approximate values) “The eennicatanterane
Diecsion ern) Weight imensions provided in
Gross
this document aro for
ee | wef | wis ai
GT1-72.5 ‘The exact data and
GT1-125, dimensions can be
GT1-145 verified once the client's
GT1-170 fal specs are known,
GT1-245 Upper Furthermore as efforts
Lower are constantly made to
GT1-300 Upper improve design and
Lower methods of manufacture,
GT1-362 Upper the equipment offered
ese say difer fom the
GT1-420 Upper equipment described in
te this document,
EMEK ELEKTRIK ENDUSTRISi A.S.
Post Address: P.O Box 648, Ulus 08044, Ankara Turkey
Factory Address : Esenboga Yolu 23 Km Cubuk Ankara Turkey
Phone + 90312 398 07 95
398 07 96
398 05 05
Fax :+90312 398 07 58
e-mail emekeeas@ada.nettr
web site :www.emek.com.tr September, 2004