1. MCU (Mode Control Unit)
1.1 Feature
Fine-tuned control
DVM S HR uses a Mode Change Unit (MCU) kit that is less than 32 percent the size of competitors’ products. The
MCU has an internal on/off valve that enables fine-tuned control via an electronic expansion valve (EEV) and sub-
cooler. Improved performance and reduced noise create a pleasant temperature-controlled environment.
Before installing MCU, refer to the compatible table below and find the model before installation.
MCU-S6NEE1N
MCU-S4NEE1N
MCU-S4NEE2N
MCU-S2NEK1N
đ७७७७ǹ७७७७ đ७७७७Ę७७७७
MCU-S6NEK2N
MCU-S4NEK3N
MCU-S2NEK2N
MCU-S1NEK1N
4
1. MCU (Mode Control Unit)
1.1 Feature - For DVM S Eco Only
Fine-tuned control
DVM S Eco uses a HR Changer that is less than 32 percent the size of competitors’ products. The MCU has an
internal on/off valve that enables fine-tuned control via an electronic expansion valve (EEV) and sub-cooler.
Improved performance and reduced noise create a pleasant temperature-controlled environment.
Before installing MCU, refer to the compatible table below and find the model before installation.
MCU-S6NEK3N
MCU-S6NEK2N
AM****XMD*R MCU-R4NEK0N MCU-S4NEK3N AM****N****
MCU-S2NEK2N
MCU-S1NEK1N
5
1. MCU (Mode Control Unit)
1.2. MCU indoor/outdoor unit compatible table
Before installing MCU, refer to the compatible table below and find the model before installation.
MCU-S6NEE1N
MCU-S4NEE1N
đ७७७७ǹ७७७७ MCU-S4NEE2N đ७७७७Ę७७७७
MCU-S2NEK1N
Unit: mm(inch)
6
1. MCU (Mode Control Unit)
1.2. MCU indoor/outdoor unit compatible table
Before installing MCU, refer to the compatible table below and find the model before installation.
MCU-S6NEK2N
MCU-S4NEK3N
đ७७७७ǹ७७७७ MCU-S2NEK2N đ७७७७Ę७७७७
MCU-S1NEK1N
Unit: mm(inch)
Liquid pipe connected to indoor unit
Gas pipe connected to indoor unit
7
1. MCU (Mode Control Unit)
1.2. HR Changer, MCU indoor/outdoor unit compatible table - For DVM S Eco Only
Before installing HR Changer and Sub MCU, refer to the compatible table below and find the model.
MCU-S6NEK3N
MCU-S6NEK2N
AM****XMD*R MCU-R4NEK0N MCU-S4NEK3N AM****N****
MCU-S2NEK2N
MCU-S1NEK1N
8
1. MCU (Mode Control Unit)
1.3. Spec Sheet
Type MCU
Model MCU-S6NEE1N MCU-S4NEE1N MCU-S4NEE2N MCU-S2NEK1N
Maximum number of connectable indoor
EA 6 4 2 2
units
Maximum capacity of connectable indoor KW 56 56 56 28
units MBH 192 192 192 96
Ø, #, 1/2/220-240/50
Power Supply
V, Hz 1/2/208-230/60
Mode - heat Recovery
Power Input Cooling 55 55 55 55
W
(Nominal) Heating 55 55 55 55
Current Cooling 0.5 0.5 0.5 0.5
Power Input A
Heating 0.5 0.5 0.5 0.5
(Nominal)
MCA A 0.63 0.63 0.63 0.63
MFA(MOP) A 15 15 15 15
9
1. MCU (Mode Control Unit)
1.3. Spec Sheet
10
1. MCU (Mode Control Unit)
1.3. Spec Sheet - For DVM S Eco Only
11
1. MCU (Mode Control Unit)
1.4. Technical drawings
Dimensional drawings
MCU-S2NEK1N
Unit: mm[inch]
816 [2’-8 1/8”]
764 [2’-6 1/16”]
727 [2’-4 5/8”]
66 [2 5/8”]
469 [1’-6 7/16”]
224 [8 13/16”]
100 [3 15/16”]
129 [5 1/16”]
94 [3 11/16”]
89 [3 1/2”]
28 [1 1/8”]
160 [6 5/16”]
97 [3 13/16”]
159 [6 1/4”]
61 [2 3/8”]
51 [2”]
12
1. MCU (Mode Control Unit)
1.4. Technical drawings
MCU-S4NEE1N / MCU-S4NEE2N
Unit: mm[inch]
66 [2 5/8”]
469 [1’-6 7/16”]
94 [3 11/16”] 224 [8 13/16”]
100 [3 15/16”]
129 [5 1/16”]
89 [3 1/2”]
27 [1 1/16”]
160 [6 5/16”]
159 [6 1/4”]
97 [3 13/16”]
61 [2 3/8”]
51 [2”]
16 [5/8”]
13
1. MCU (Mode Control Unit)
1.4. Technical drawings
MCU-S6NEE1N
Unit: mm[inch]
66 [2 5/8”]
93 [3 11/16”] 224 [8 13/16”]
100 [3 15/16”]
129 [5 1/16”]
89 [3 1/2”]
27 [1 1/16”]
120 [4 11/16”] 80 [3 1/8”] X 5 = 400 [1’-3 7/16”) 146 [5 3/4”] 128 [5 1/16”] 66 [2 5/8”]
100 [3 15/16”]
197 [7 3/4”]
198 [7 7/8”]
160 [6 5/16”]
159 [6 1/4”]
97 [3 13/16”]
61 [2 3/8”]
51 [2”]
16 [5/8”]
148 [5 13/16”]
14
1. MCU (Mode Control Unit)
1.4. Technical drawings
MCU-S1NEK1N
Unit: mm[inch]
66 [2 5/8”]
409 [1’-4”]
224 [8 13/16”]
100 [3 15/16”]
69 [2 3/4”]
137 [5 1/2”]
114 [4 1/2”]
34 [1 1/4”]
409 [1’-4”]
197 [7 3/4”]
160 [6 5/16”]
159 [6 1/4”]
68 [2 3/4”]
51 [2”]
15
1. MCU (Mode Control Unit)
1.4. Technical drawings
MCU-S2NEK2N
Unit: mm[inch]
66 [2 5/8”]
469 [1’-6 7/16”]
224 [8 13/16”]
100 [3 15/16”]
87 [3 1/2”]
129 [5 1/16”]
94 [3 11/16”]
68 [2 3/4”]
197 [7 3/4”]
159 [6 1/4”]
160 [6 5/16”]
51 [2”]
68 [2 3/4”]
97 [3 13/16”]
16
1. MCU (Mode Control Unit)
1.4. Technical drawings
MCU-S4NEK3N
Unit: mm[inch]
66 [2 5/8”]
469 [1’-6 7/16”]
100 [3 15/16”]
87 [3 1/2”]
129 [5 1/16”]
94 [3 11/16”]
68 [2 3/4”]
159 [6 1/4”]
51 [2”]
68 [2 3/4”]
240 [9 7/16”]
17
1. MCU (Mode Control Unit)
1.4. Technical drawings
MCU-S6NEK2N
Unit: mm[inch]
66 [2 5/8”]
469 [1’-6 7/16”]
224 [8 13/16”]
100 [3 15/16”]
87 [3 1/2”]
129 [5 1/16”]
68 [2 3/4”]
94 [3 11/16”]
18
1. MCU (Mode Control Unit)
1.4. Technical drawings- For DVM S Eco Only
MCU-R4NEK0N
66 [2 5/8"]
469 [1'-6 7/16"]
224 [8 13/16"]
100 [3 15/16"]
87 [3 1/2"]
130 [5 1/16"]
94 [3 11/16"]
160 [6 5/16"]
51 [2"]
68 [2 3/4"]
159 [6 1/4"]
100 [3 15/16"]
MCU-S6NEK3N
224 [8 13/16"]
100 [3 15/16"]
94 [3 11/16"]
129 [5 1/16"]
86 [3 3/8"]
88[3 7/16"]
119 [4 3/4"] 80[3 1/8"] X5 = 400 [1'-3 3/4"] 104 [4"] 128 [5 1/16"] 100 [3 15/16"] 66 [2 5/8"]
197 [7 3/4"]
199 [7 7/8"]
160 [6 5/16"]
50.6 [2"]
19
20
High Temperature & Pressure Gas
CheckValve- Ball Valve - High Temperature & Pressure Liquid
Discharge1 Outdoor Fan Motor 1 Outdoor Fan Motor 2 Gas pipe (BV_G)
(CV_D1) (OFM1) (OFM2) Low Temperature & Pressure Gas
SolenoidValve- Thermistor- Low Temperature & Pressure Liquid
MainEEV Ambient
(V_ME) (T_A) COOL
Thermistor-
Piping drawings Cooling mode
CondOut
FAN ON
CheckValve- (T_CO)
HeatRecovery
(CV_HR) Heat Exchanger - Main (HX_M)
Solenoid Valve -
Main EEV (V_ME) Electronic Solenoid
Expansion Valve-
Check Valve - Valve- HotGas COOL
Thermistor - bypass2
Suction pipe (T_S) EEV Bypass Main(E_M) FAN ON
(CV_EB) (V_HG2)
OilSeparator1 (OS2)
(OS1) Solenoid Valve - Thermistor -
Thermistor - EVI Bypass EVI Out OFF
Suction pipe2 (T_S2) (V_EB) (T_EO) FAN OFF
Pressure
Switch- Heat Exchanger -
(PW_H2) Thermistor - Intercooler
High1
(PW_H1) EVI In (T_EI) (HX_IC)
Thermistor-
Thermistor- Discharge (T_D2)
Compressor pipe1 (T_CT2)
Top1 (T_D1) Accumulator
(T_CT1) (AC) COOL
Pressure FAN ON
Sensor -
Compressor 1 Low Electronic
(COMP1) (COMP2) (PS_L) Expansion
Valve - EVI
(E_EVI)
Thermistor -
Liquid pipe
Solenoid (T_L) OFF
Valve - Solenoid Valve - FAN OFF
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
High Temperature & Pressure Gas
CheckValve- Ball Valve - High Temperature & Pressure Liquid
Discharge1 OutdoorFanMotor1 OutdoorFanMotor2 Gas pipe (BV_G)
(CV_D1) (OFM1) (OFM2) Low Temperature & Pressure Gas
SolenoidValve- Thermistor- Low Temperature & Pressure Liquid
MainEEV Ambient
(V_ME) (T_A) HEAT
Thermistor- FAN ON
Piping drawings Heating mode
CondOut
CheckValve- (T_CO)
HeatRecovery
(CV_HR) Heat Exchanger - Main (HX_M)
Solenoid Valve -
Main EEV (V_ME) Electronic Solenoid
Expansion Valve-
Check Valve - Valve- HotGas HEAT
Thermistor - bypass2
Suction pipe (T_S) EEV Bypass Main(E_M) FAN ON
(CV_EB) (V_HG2)
OilSeparator1 (OS2)
(OS1) Solenoid Valve - Thermistor -
Thermistor - EVI Bypass EVI Out OFF
Suction pipe2 (T_S2) (V_EB) (T_EO) FAN OFF
Pressure
Switch- Heat Exchanger -
(PW_H2) Thermistor - Intercooler
High1
(PW_H1) EVI In (T_EI) (HX_IC)
Thermistor-
Thermistor- Discharge (T_D2)
Compressor pipe1 (T_CT2)
Top1 (T_D1) Accumulator
(T_CT1) (AC) HEAT
Pressure FAN ON
Sensor -
Compressor 1 Low Electronic
(COMP1) (COMP2) (PS_L) Expansion
Valve - EVI
(E_EVI)
Thermistor -
Liquid pipe
Solenoid (T_L) OFF
Valve - Solenoid Valve - FAN OFF
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
21
22
High Temperature & Pressure Gas
CheckValve- Ball Valve - High Temperature & Pressure Liquid
Discharge1 Outdoor Fan Motor 1 Outdoor Fan Motor 2 Gas pipe (BV_G)
(CV_D1) (OFM1) (OFM2) Low Temperature & Pressure Gas
SolenoidValve- Thermistor- Low Temperature & Pressure Liquid
MainEEV Ambient
(V_ME) (T_A) COOL
Thermistor- FAN ON
CondOut
CheckValve- (T_CO)
HeatRecovery
(CV_HR) Heat Exchanger - Main (HX_M)
Piping drawings Main Cooling mode
Solenoid Valve -
Main EEV (V_ME) Electronic Solenoid
Expansion Valve-
Check Valve - Valve- HotGas COOL
Thermistor - bypass2
Suction pipe (T_S) EEV Bypass Main(E_M) FAN ON
(CV_EB) (V_HG2)
OilSeparator1 (OS2)
(OS1) Solenoid Valve - Thermistor -
Thermistor - EVI Bypass EVI Out HEAT
Suction pipe2 (T_S2) (V_EB) (T_EO) FAN ON
Pressure
Switch- Heat Exchanger -
(PW_H2) Thermistor - Intercooler
High1
(PW_H1) EVI In (T_EI) (HX_IC)
Thermistor-
Thermistor- Discharge (T_D2)
Compressor pipe1 (T_CT2)
Top1 (T_D1) Accumulator
(T_CT1) (AC) COOL
Pressure FAN ON
Sensor -
Compressor 1 Low Electronic
(COMP1) (COMP2) (PS_L) Expansion
Valve - EVI
(E_EVI)
Thermistor -
Liquid pipe
Solenoid (T_L) HEAT
Valve - Solenoid Valve - FAN ON
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
High Temperature & Pressure Gas
CheckValve- Ball Valve - High Temperature & Pressure Liquid
Discharge1 Outdoor Fan Motor 1 Outdoor Fan Motor 2 Gas pipe (BV_G)
(CV_D1) (OFM1) (OFM2) Low Temperature & Pressure Gas
SolenoidValve- Thermistor- Low Temperature & Pressure Liquid
MainEEV Ambient
(V_ME) (T_A) HEAT
Thermistor- FAN ON
CondOut
CheckValve- (T_CO)
HeatRecovery
(CV_HR) Heat Exchanger - Main (HX_M)
Piping drawings Main Heating mode
Solenoid Valve -
Main EEV (V_ME) Electronic Solenoid
Expansion Valve-
Check Valve - Valve- HotGas HEAT
Thermistor - bypass2
Suction pipe (T_S) EEV Bypass Main(E_M) FAN ON
(CV_EB) (V_HG2)
OilSeparator1 (OS2)
(OS1) Solenoid Valve - Thermistor -
Thermistor - EVI Bypass EVI Out COOL
Suction pipe2 (T_S2) (V_EB) (T_EO) FAN ON
Pressure
Switch- Heat Exchanger -
(PW_H2) Thermistor - Intercooler
High1
(PW_H1) EVI In (T_EI) (HX_IC)
Thermistor-
Thermistor- Discharge (T_D2)
Compressor pipe1 (T_CT2)
Top1 (T_D1) Accumulator
(T_CT1) (AC) HEAT
Pressure FAN ON
Sensor -
Compressor 1 Low Electronic
(COMP1) (COMP2) (PS_L) Expansion
Valve - EVI
(E_EVI)
Thermistor -
Liquid pipe
Solenoid (T_L) COOL
Valve - Solenoid Valve - FAN ON
EVI 1 (V_EVI2)
Accumulator oil Return
(V_EVI1) (V_AR)
Ball Valve -
Liquid pipe (BV_L)
23
24
High Temperature & Pressure Gas
COOL COOL COOL COOL
High Temperature & Pressure Liquid
FAN ON FAN ON FAN ON FAN ON
Ball Valve - Low Temperature & Pressure Gas
Gas Pipe1
(BV_G1) Low Temperature & Pressure Liquid
• Cooling mode
Thermistor -
Cond Out
(T_CO)
Pressure Electronic
Switch- Expansion
High Valve - EVI
(PW_H) (E_EVI)
Thermistor -
Discharge
Thermistor - pipe
Compressor (T_D)
Top
(T_CT)
Accumulator
(AC)
Compressor Solenoid Valve - Thermistor -
(COMP) Accumulator Liquid pipe
oil Return (T_L)
(V_AR)
Service Valve -
Liquid Pipe
(SV_L)
1. MCU (Mode Control Unit)
Thermistor -
Cond Out
(T_CO)
Pressure Electronic
Switch- Expansion
High Valve - EVI
(PW_H) (E_EVI)
Thermistor -
Discharge
Thermistor - pipe
Compressor (T_D)
Top
(T_CT)
Accumulator
(AC)
Compressor Solenoid Valve - Thermistor -
(COMP) Accumulator Liquid pipe
oil Return (T_L)
(V_AR)
Service Valve -
Liquid Pipe
(SV_L)
High Temperature & Pressure Gas
COOL HEAT COOL COOL
High Temperature & Pressure Liquid
FAN ON FAN ON FAN ON FAN ON
Ball Valve - Low Temperature & Pressure Gas
Gas Pipe1
(BV_G1) Low Temperature & Pressure Liquid
Thermistor -
Cond Out
(T_CO)
Pressure Electronic
Switch- Expansion
High Valve - EVI
(PW_H) (E_EVI)
Thermistor -
Discharge
Thermistor - pipe
Compressor (T_D)
Top
(T_CT)
Accumulator
(AC)
Compressor Solenoid Valve - Thermistor -
(COMP) Accumulator Liquid pipe
oil Return (T_L)
(V_AR)
Service Valve -
Liquid Pipe
(SV_L)
1. MCU (Mode Control Unit)
Thermistor -
Cond Out
(T_CO)
Electronic
Solenoid Valve- Thermistor - Expansion
4Way (V_4W) Pressure Ambient1
Sensor- Valve - Main
Thermistor - Low (PS_L) (T_A1) Solenoid Valve - (E_M)
Suction pipe EVI Bypass
Check Valve - (T_S) (V_EB)
Discharge 1
(CV_D1) Heat Exchanger -
Intercooler
(HX_IC)
Oil
Separator
(OS)
Thermistor - Electronic
Pressure Ambient2 Expansion
Sensor- (T_A2) Valve - EVI
Hgh (PS_H) (E_EVI)
Pressure Electronic
Switch- Expansion
High Valve - EVI
(PW_H) (E_EVI)
Thermistor -
Discharge
Thermistor - pipe
Compressor (T_D)
Top
(T_CT)
Accumulator
(AC)
Compressor Solenoid Valve - Thermistor -
(COMP) Accumulator Liquid pipe
oil Return (T_L)
(V_AR)
Service Valve -
Liquid Pipe
(SV_L)
25
1. MCU (Mode Control Unit)
MCU Kit Wiring drawing
EEV1 electronic expansion valve EEV2 electronic expansion valve EEV3 electronic expansion valve
EEV4 electronic expansion valve EEV5 electronic expansion valve EEV6 electronic expansion valve
S/C EEV electronic expansion valve F100 FUSE
(Sub cooler)
NOTE
• This wiring diagram applies only to the MCU kits.
• Symbols show as follow : BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue:
GRN: green
• For connection wiring indoor-outdoor transmission F1-F2
• Protective earth(SCREW) ), CN *: connector, : The quantity
26
1. MCU (Mode Control Unit)
HR Changer Wiring drawing - For DMS S Eco Only
MCU-R4NEK0N
EEV1 electronic expansion valve EEV2 electronic expansion valve EEV3 electronic expansion valve
EEV4 electronic expansion valve S/C EEV electronic expansion valve F100 FUSE
(Sub cooler)
HR EEV electronic expansion valve
NOTE
• This wiring diagram applies only to the HR Changer
• Symbols show as follow : BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue:
GRN: green
• For connection wiring indoor-outdoor transmission F1-F2
• Protective earth(SCREW) ), CN *: connector, : The quantity
27
1. MCU (Mode Control Unit)
Wiring drawings
EEV1 electronic expansion valve EEV2 electronic expansion valve EEV3 electronic expansion valve
EEV4 electronic expansion valve EEV5 electronic expansion valve EEV6 electronic expansion valve
S/C EEV electronic expansion valve F100 FUSE
(Sub cooler)
NOTE
• This wiring diagram applies only to the MCU kits.
• Symbols show as follow : BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue:
GRN: green
• For connection wiring indoor-outdoor transmission F1-F2
• Protective earth(SCREW) ), CN *: connector, : The quantity
28
1. MCU (Mode Control Unit)
1.5. Sound pressure level
• This value was measured at steady state in anechoic chamber and may vary depending on operating condtion.
• Sound pressure level will vary depending on a range of factors such as the construction of the particular room
where the equipment is installed.
NC curve
60 NR 65 60
55 NR 60 55
50 NR 55 50
Sound Pressure Level (dB)
45 Cooling NR 50 45
40 40
NR 45
35 35
NR 40
30 30
NR 35
25 25
NR 30
20 Hearing 20
NR 25
15 threshold 15
NR 20
10 10
NR 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)
29
1. MCU (Mode Control Unit)
1.5. Sound pressure level
NC curve
60 NR 65 60
55 NR 60 55
50 NR 55 50
Cooling
Sound Pressure Level (dB)
45 NR 50 45
40 40
NR 45
35 35
NR 40
30 30
NR 35
25 25
NR 30
20 Hearing 20
NR 25
15 threshold 15
NR 20
10 10
NR 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)
MCU-S1NEK1N
60 NR 65 60
55 NR 60 55
50 NR 55 50
Sound Pressure Level (dB)
45 NR 50 45
Cooling
40 40
NR 45
35 35
NR 40
30 30
NR 35
25 25
NR 30
20 Hearing 20
NR 25
15 threshold 15
NR 20
10 10
NR 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)
30
2. EEV (Electronic Expansion Valve ) kit
2.1 Feature
EEV kit
Control Layer
DMS 2.0
Set Layer
ODU
31
2. EEV (Electronic Expansion Valve ) kit
EEV
EEV connector
32
2. EEV (Electronic Expansion Valve ) kit
2.2. Line-up
Description
Model Quantity of
Connectable capacity of indoor
connectable Weight (Net) Indoor units Remarks
units
indoor units
MEV- E24SA Up to 3.6kW (12.0MBH) 1 1.1kg (2.2 lbs) Wall mounted units Extension wire
MEV- E32SA 4.5 ~ 9kW (15.5 ~ 31MBH) 1 1.1kg (2.2 lbs) Ceiling units included
33
2. EEV (Electronic Expansion Valve ) kit
2.3. Spec Sheet
Liquid Ø, mm - - - - 9.52
Pipe Ø, inch - - - - 3/8”
Outlet
Pipe 3 Ø, mm - - - - 15.88
Gas Pipe
Ø, inch - - - - 5/8”
Net Weight kg (lbs) 1.1 (2.4) 1.1 (2.4) 7 (15.4) 7 (15.4) 7.6 (16.8)
Shipping Weight kg (lbs) 1.4 (3.1) 1.6 (3.5) 8.8 (19.4) 8.8 (19.4) 9.4 (20.7)
External Net Dimensions mm 86X201X118 86X201X118 450X333X204 450X333X204 500X333X204
Dimension (WxHxD) (inch) (3 3/8x7 15/16x4 5/8) (3 3/8x7 15/16x4 5/8) (17 3/4 x 13 1/8 x 8) (17 3/4 x 13 1/8 x 8) (17 3/4 x 13 1/8 x 8)
Shipping Dimensions mm 226X306X134 226X306X134 596X382X276 596X382X276 596X382X276
(WxHxD) (inch) (8 7/8 x 12 x 5 1/4) (8 7/8 x 12 x 5 1/4) (23 1/2 x 15 x 10 7/8) (23 1/2 x 15 x 10 7/8) (23 1/2 x 15 x 10 7/8)
1 port kW Up to 3.6 4.5 ~ 9.0 2.0~3.6 2.0~3.6 2.0~3.6
Indoor
Installation unit’s 2 port kW - - 4.5~9.0 2.0~3.6 2.0~3.6
Capacity
3 port kW - - - - 4.5~9.0
34
2. EEV (Electronic Expansion Valve ) kit
2.3. Spec Sheet
35
2. EEV (Electronic Expansion Valve ) kit
2.4. Dimensional drawings
Dimensional drawings
Unit: mm[inch]
86 [3-3/8]
86 [3-3/8] 72 [2-7/8]
42 [1-5/8]
169 [6-5/8]
201 [7-7/8]
89 [3-1/2]
36
2. EEV (Electronic Expansion Valve ) kit
2.4. Dimensional drawings
02 Unit: mm[inch]
1
01
105 [4-1/8]
06
07
450 [17-3/4]
03
08
04
120 [4-3/4]
190 [7-1/2]
500 [19-5/8]
333 [13-1/8] 458 [18]
323 [12-3/4] 403 [15-7/8]
39 [1-4/8]
60 [2-3/8]
40 [1-5/8]
60 [2-3/8]
110 [4-3/8]
130 [5-1/8]
40 [1-5/8]
100 [3-15/16]
125 [4-3/4]
05
202 [7-15/16] 20 [3/4] 56 [2-1/4]
44 [1-3/4]
97 [3-7/8]
37
2. EEV (Electronic Expansion Valve ) kit
2.4. Dimensional drawings
105 [4-1/8] 02
Unit: mm[inch]
01
06
07
450 [17-3/4]
03
08
04
120 [4-3/4]
190 [7-1/2]
500 [19-5/8]
333 [13-1/8]
458 [18]
40 [1-5/8] 40 [1-5/8] 39 [1-4/8]
323 [12-3/4]
403 [15-7/8]
85 [3-3/8] 40 [1-5/8] 40 [1-5/8]
313 [12-3/8]
100 [3-15/16] 60 [2-3/8]
110 [4-3/8]
60 [2-3/8]
130 [5-1/8]
204 [8-1/16]
20 [3/4] 05
44 [1-3/4] 56 [2-1/4]
202 [ 7-15/16] 97 [3-7/8]
03 Liquid pipe connections to wall mounted/ceiling units 01 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
04 Gas pipe connections to wall mounted/ceiling units 02 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
38
2. EEV (Electronic Expansion Valve ) kit
2.4. Dimensional drawings
Wiring drawings
EEV1 electronic expansion valve EEV2 electronic expansion valve EEV3 electronic expansion valve
NOTE
• This wiring diagram applies only to the Three rooms EEV kits.
• Symbols show as follow : BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue:
GRN: green
• For connection wiring indoor-outdoor transmission F1-F2
• Protective earth(SCREW) ), CN *: connector, : The quantity
39
3. AHU (Air Handling Unit) kit
3.1 Feature (For VRF outdoor unit)
Outdoor unit
Communication F1, F2
EEV kit
EEV Control
Liquid Pipe
Room
Sensor
AHU Controller
(Optional)
Gas pipe
EVA. OUT Sensor
40
3. AHU (Air Handling Unit) kit
3.1 Feature (MXD-K100XN, for single outdoor unit)
Outdoor unit
Communication F1, F2
EEV Kit
LLiquid Pipe
A Eva. out
Sensor
AHU Controller
(Optional)
Gas pipe
41
3. AHU (Air Handling Unit) kit
3.1 Feature (MXD-K100XN, for single outdoor unit)
MXD-K***AN / MXD-X000AN
EEV kit
Lower insulation
Upper insulation
Holder
Cover
Clamp
Out In
Control kit
Controller board
Case
Cover
42
3. AHU (Air Handling Unit) kit
3.3. Spec Sheet
• Specifications may be subject to change without prior notice for product improvement.
• The AHU design SPEC are base on 10HP test result under Evaporating Temperature:
ߩઘAࡥƊЇΧʪθ˵ʪɇϩࡤߣઘAࡥ̈θϩʪ͔ΧʪθɇϩЇθʪࡤߤߩઘAU9ࢩߣ߫ઘAǮ9
• The EEV kit, Room/EVA. IN/EVA. OUT/Discharge sensors and Cable-nuts are not included in the Control kit
Model “MCM-D201N, MXD-X000AN”.
(Pipe inlet/outlet sensor is included in “MCM-D201N, MXD-X000AN”.)
• In case of MCM-D201N, EEV kit(Model name : MXD-A64K100E) is need to order 1ea per 10HP separately.
• In terms of AHU, there is a no limitation in capacity.
43
3. AHU (Air Handling Unit) kit
3.3. Spec Sheet
ƟцΧʪࢩף ߣߢߥ²Ǯࢩߨף
EVA. IN
m/mm² 10m/2 * 0.75mm²
ƟцΧʪࢩף ߣߢߥ²Ǯࢩߩף
Sensor EVA. Out
m/mm² 10m/2 * 0.75mm²
ƟцΧʪࢩף 103HW / Molding
Room
m/mm² 10m/2 * 0.75mm²
Refrigerant Type - R410A
mm 380 x 130 x 280
Dimensions Control Box (W x H x D)
inch 15.0 x 5.1 x 11.0
• Specifications may be subject to change without prior notice for product improvement.
• The AHU design SPEC are base on test result under Air temperature as below.
Aͱͱ̷̈͝˝ࡤÃ͝ʒͱͱθߤߩঙU9ࢩߣ߫ঙǮ9ࡥĮЇϩʒͱͱθߥߧঙU9ࢩߤߦঙǮ9
²ʪɇϩ̈͝˝ࡤÃ͝ʒͱͱθߤߢঙU9ࢩߣߧঙǮ9ࡥĮЇϩʒͱͱθߩঙU9ࢩߨঙǮ9
• The EEV kit, Room/EVA. IN/EVA. OUT/Discharge sensors and Cable-nuts are not included in the Control kit
Model “MCM-D201N, MXD-X000AN”.
(Pipe inlet/outlet sensor is included in “MCM-D201N, MXD-X000AN”.)
• In case of MCM-D201N, EEV kit(Model name : MXD-A64K100E) is need to order 1ea per 10HP separately.
• In terms of AHU, there is a no limitation in capacity.
44
3. AHU (Air Handling Unit) kit
3.3. Spec Sheet
ƟцΧʪࢩף ߣߢߥ²Ǯࢩߨף
EVA. IN
m/mm² 10m/2 * 0.75mm²
ƟцΧʪࢩף ߣߢߥ²Ǯࢩߩף
Sensor EVA. Out
m/mm² 10m/2 * 0.75mm²
ƟцΧʪࢩף 103HW / Molding
Room
m/mm² 10m/2 * 0.75mm²
Refrigerant Type - R410A
mm 380 x 130 x 280
Dimensions Control Box (W x H x D)
inch 15.0 x 5.1 x 11.0
• Specifications may be subject to change without prior notice for product improvement.
• The AHU design SPEC are base on test result under Air temperature as below.
Aͱͱ̷̈͝˝ࡤÃ͝ʒͱͱθߤߩঙU9ࢩߣ߫ঙǮ9ࡥĮЇϩʒͱͱθߥߧঙU9ࢩߤߦঙǮ9
²ʪɇϩ̈͝˝ࡤÃ͝ʒͱͱθߤߢঙU9ࢩߣߧঙǮ9ࡥĮЇϩʒͱͱθߩঙU9ࢩߨঙǮ9
• The EEV kit, Room/EVA. IN/EVA. OUT/Discharge sensors and Cable-nuts are not included in the Control kit
Model “MCM-D201N, MXD-X000AN”.
(Pipe inlet/outlet sensor is included in “MCM-D201N, MXD-X000AN”.)
• In case of MCM-D201N, EEV kit(Model name : MXD-A64K100E) is need to order 1ea per 10HP separately.
• In terms of AHU, there is a no limitation in capacity.
45
3. AHU (Air Handling Unit) kit
3.4. Dimensional drawings
Dimensional drawings
MCM-D201N
[Unitࡤ͔͔࣑̈͝ʀ˵࣒]
4 ߧࢩ .6
X ߪ
࣑ ף6
Ø8 ࣒
4 ࢩߣף
X ߦ
.2
࣑
Ø ࣒
ߤߩߧߢ࣑ߣߢࣛߣߥࢩߣߨ࣒
ߤߧߢߢ࣑߫ࣛߣߥࢩߣߨ࣒
ߣߩߧߢ࣑ߨࣛߩࢩߪ࣒
ߥߢߢߢ࣑ߣߢࣛߣߥࢩߣߨ࣒
ߥߧߨߢ࣑ߣߦ࣒
ߥߪߧߢ࣑ߣߧࣛߥࢩߣߨ࣒
ߨߧߣ࣑࣒߫
For detailed information of EEV installation, refer to the installation manual of ASS’Y EEV (MXD-A64K100E) which
you need to purchase additionally.
MXD-A64K100E
Filter
46
3. AHU (Air Handling Unit) kit
Wiring drawings
EEV Electronic Expansion Valve EEV1 Electronic Expansion Valve Vd Defrost Signal(AC)
TR Room Temperature TEI EVAP. IN Temperature TEO EVAP. OUT Temperature
Com/HP/CO/AV/OV Simple BMS
NOTE
• Symbols show as follow : BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue:
GRN: green
• Protective earth(SCREW) ), CN *: connector, : The quantity
47
3. AHU (Air Handling Unit) kit
Wiring drawings
MCM-D201N
NOTE
• Symbols show as follow : BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue:
GRN: green
• Protective earth(SCREW), CN *: connector, : The quantity
48
4. FCU kit
MIM-F00N
Features
Unit: mm(inch)
ՍՒՋطՌՋՑՍظ
ՍՋՋطՒՓՒظ
ՍՍՐطՓՓՐظ
ՓՒطՎՏՍظ
• Communication and control interfacing kit between 3rd • Provides external contact input
party FCU and Samsung control system. • Outputs control signal for FCU fan.
• Possible to use wired remote controller • Outputs control signal for Water valve .
• Possible to use DMS2.5, Touch centralized controller
Product specification
Europe
USA
49
4. FCU kit
MIM-F00N
Product specification
DC Wire
Compatible controller
Description of parts
ŵʪϑʪθЭʪʒ
ŵʪϑʪθЭʪʒ
ŵʪϑʪθЭʪʒ
ŵʪϑʪθЭʪʒ
50
4. FCU kit
MIM-F00N
Connection diagram
UđƊՍՐ ƟͱЇʀ˵ʀʪ͝ϩθɇ̷̈іʪʒʀͱ͝ϩθͱ̷̷ʪθ
ŵՌŵՍ
AƸ̈͝ϩʪθ˙ɇʀʪ͔ͱʒЇ̷ʪ AƸ̈͝ϩʪθ˙ɇʀʪ͔ͱʒЇ̷ʪ
طđÃđفՌՋĘظ طđÃđفՌՋĘظ
UǤđA²ÃøøkŵՌ UǤđA²ÃøøkŵՍ
ՌՍ
ՎՏ ՎՏ
ՌՍ
ՎՏ ՎՏ
đɇуՌՑAƸçÃƟϑ
ՎՏ ՎՏ
51
4. FCU kit
MIM-F00N
Ǯ̈θʪʒθʪ͔ͱϩʪʀͱ͝ϩθͱ̷̷ʪθ
ɇ͝Χͱиʪθ
AƸçÃƟ ɇ͝Χͱиʪθ
ǽفŵĘ
ŵkU
ǽkø
ǮɇϩʪθÃĘϑʪ͝ϑͱθ
9øç
AĘՍ
AĘՏ
ŵkU
AĘՎ
AƸ̈͝ϩʪθ˙ɇʀʪ͔ͱʒЇ̷ʪ ǮɇϩʪθÃĘϑʪ͝ϑͱθ
UđƊՍՐ
ɇ͝Χͱиʪθ ɇ͝Χͱиʪθ
ǮɇϩʪθÃĘϑʪ͝ϑͱθ ǮɇϩʪθÃĘϑʪ͝ϑͱθ
UǤđA²Ãøøkŵ
• Indoor temperature sensor must be installed to control FCU. Use either wired remote controller built-in sensor or
external room sensor (MRW-TA).
- Option setting value should be changed in service setting mode of wired remote controller after installing the
remote controller. (Main menu 1, Sub menu 1, SEG 1, value 1)
- In case of using external temperature sensor (optional), value of SEG24 (FCU KIT external indoor temperature
sensor) of 05 series installation option should be set as 1.
• Water sensor should be attached to inlet pipe (1) for 2 pipe system (Water In), and each inlet pipe (2) for 4 pipe
system (Cooling pipe in Heating pipe in.)
• Maximum number of FCU KITs that can be installed and controlled simultaneously by a wired remote controller
is 16.
52
4. FCU kit
MIM-F00N
UđƊ
ǽفŵĘ
ŵkU
ǽkø
AƸ̈͝ϩʪθ˙ɇʀʪ͔ͱʒЇ̷ʪ
9øç
AĘՍ
AĘՏ
UǤđA²Ãøøkŵ
ŵkU
AĘՎ
AǮɇϩʪθǤɇ̷ЭʪՋՐ
Ǯ̈θʪʒθʪ͔ͱϩʪ
ʀͱ͝ϩθͱ̷̷ʪθ đ
ǮɇϩʪθÃĘϑʪ͝ϑͱθ
AĮđđĮĘ
²Ã²
đÃU
øĮǮ Ɵʪθ͔̈͝ɇ̷ɵ̷ͱʀ̧
ŵʪ̷ɇц
AՍՋՓڬՍՎՋǤՑՋ²і
AՍՍՋڬՍՏՋǤՐՋ²і
AՍՋՓڬՍՎՋǤՑՋ²і
AՍՍՋڬՍՏՋǤՐՋ²і
• National electric appliance safety standard should be applied for relay installation and capacity and power cable
connection of FCU terminal block.
53
4. FCU kit
MIM-F00N
Wiring
Y-GRN
RED
YEL
Water-IN 1 sensor
Water-IN Room sensor
2 sensor (optional)
CN2
BLK
CN4
LED
CN3
RED
BLDC Fan
F1 Control
12V
F2
Modulating
Fan Motor power Valve 2
AC 208 - 230 V~ 60 Hz, 1 Ph, 1 A
AC 220 - 240 V~ 50 Hz, 1 Ph, 1 A Modulating
COMMON Valve 1
LOW
Fan MID
Motor HIGH External
contact
F4
M
Water Valve 1
F3
M
Water Valve 2
Water valve
AC 208 - 230 V~ 60 Hz, 1 Ph, 0.5 A
AC 220 - 240 V~ 50 Hz, 1 Ph, 0.5 A
ELCB
AC 208 - 230 V~ 60 Hz, 1 Ph
AC 220 - 240 V~ 50 Hz, 1 Ph
AC 220V 1A • For direct power supply from FCU KIT, fan motor must work at AC 208 - 230V ~ 60 Hz,
Ę
øĮǮ AC 220 - 240V ~ 50Hz and 1 A or low. Otherwise, install relay for external power
đÃU supply to the fan motor.
Ę ²Ã²
Water Valve: 2 Way or 3 Way solenoid valve
đ
ǮɇϩʪθǤɇ̷ЭʪՌ • 2/3 way solenoid value is a type that works at AC 208 - 230V ~ 60Hz,
AC 220 - 240V ~ 50Hz and supports product with 0.5 A or low.
đ
ǮɇϩʪθǤɇ̷ЭʪՍ Pipe Power output according to AC 220 V output
Note
type operation mode (Max 0.5 A)
Cooling/ Thermo ON 1-2 Normal Close Type
2-pipe
Heating Thermo OFF 1-3 Normal Open Type
Thermo ON 1-2 Normal Close Type
Cooling
Thermo OFF 1-3 Normal Open Type
4-pipe
Thermo ON 4-5 Normal Close Type
Heating
Thermo OFF 4-6 Normal Open Type
• Connect 3 Way valve power cable according to value of operation mode power output.
• Select each valve that is below 0.5 A of operation current.
• Installation option setting(05series, SEG 14) is required to define 2 pipe
or 4 pipe system.
54
4. FCU kit
MIM-F00N
Water IN sensor
55
4. FCU kit
MIM-F00N
kуϩʪθ͝ɇ̷
ʀͱ͝ϩɇʀϩ
ŵͱͱ͔ϑʪ͝ϑͱθͱطΧϩ̈ͱ͝ɇ̷ظ
CAUTION
• Use either wired remote controller with built-in room sensor or external room sensor (MRW-TA) must be installed.
kуϩʪθ͝ɇ̷ʀͱ͝ϩɇʀϩ̈͝ϩʪθ˙ɇʀʪ͔ͱʒЇ̷ʪ
࣑ĮΧϩ̈ͱ͝ɇ̷࣒
Y-GRN
RED
YEL
CN2
BLK
CN4
CN3
RED
w
56
5. Universal comm. kit
5.1. Feature
1 ťθͱӬʒʪϑɇʀͱ͔͔Ї̈͝ʀɇϩ̈ͱ̧̈͝ϩϩ˵ɇϩʪ͝ɇɵ̷ʪϑ͝ͱθ͔ɇ̷ͱΧʪθɇϩ̈ͱ͝и˵ʪ͝ʀͱ͝͝ʪʀϩ̈͝˝ऌɇ͝ͱЇϩʒͱͱθЇ̈͝ϩ࣑Ǥŵ࣒ϩͱɇ
ߥθʒऌΧɇθϩц̈͝ʒͱͱθЇ̈͝ϩ
Components: Control kit + EEV kit
2 k͝˵ɇ͝ʀʪϑϩ˵ʪʀͱ͔Χɇϩ̈ɵ̷̈̈ϩцӥϩ˵ɇߥθʒऌΧɇθϩц̈͝ʒͱͱθЇ̈͝ϩɇ͝ʒΧθͱӬʒʪϑɇʒЭɇ͝ʀʪʒ˙Ї͝ʀϩ̈ͱ͝ϑ
3 System Diagram
Simple BMS
Control Economizer
Wired
Remote 1 Control Kit Ventilation
Control Damper
EEV Kit /
2 Temp.
Temp Sensor
Senso
Outdoor Enthalpy
Unit Sensor
Upper
controller
DMS 2.5/
BACnet/
Lonwork
Indoor Unit
(Ex: Unit Ventilator)
57
5. Universal comm. kit
5.2. Combination & Line-up Table
Reated
Capacity Range Heat Exchanger Number of Number of
Display Capacity Control kit EEV kit
(Btu/h) (Btu/h) Volume(in3) Control kit EEV kit
0 12k 7k to 18k 28 to 71 1 1
MXD-A24K100E
1 12k 7k to 18k 28 to 71 1 1
2 24k 7k to 30k 71 to 118 1 MXD-A32K100E 1
3 36k 30k to 42k 118 to 165 1 1
MXD-A40K100E
4 48k 42k to 60k 165 to 236 1 1
5 60k 60k to 72k 236 to 283 1 1
6 72k 72k to 96k 283 to 378 1 1
MCM-D211UN
7 96k 96k to 144k 378 to 566 1 1
8 144k 144k to 192k 566 to 755 1 2
9 192k 192k to 240k 755 to 944 1 MXD-A64K100E 2
A 240k 240k to 288k 944 to 1133 1 3
B 288k 288k to 336k 1133 to 1322 1 3
C 336k 336k to 384k 1322 to 1510 1 4
D 384k 384k 1510 to 1725 1 4
DVM S
DVM S water
DVM S Eco
3 Part combination
58
5. Universal comm. kit
5.3. Product Specification
Type Control Kit EEV Kit EEV Kit EEV Kit EEV Kit
Model Name MCM-D211UN MXD-A24K100E MXD-A32K100E MXD-A40K100E MXD-A64K100E
ࡥ࢈ࡥף
Power Supply 24VAC - - - -
V, Hz
Heat Pump / Heat Heat Pump / Heat Heat Pump / Heat Heat Pump / Heat Heat Pump / Heat
Applied outdoor unit Type -
Recovery Recovery Recovery Recovery Recovery
EEV(EDM) - - ͔͔ߦߤף ͔͔ߤߥף ͔͔ߢߦף ͔͔ߦߨף
Cooling kW - - - - -
(Min) Btu/h 7000 7000 18000 30000 60000
Performance Cooling kW - - - - -
(Max) Btu/h 384000 18000 30000 60000 144000
Capacity
Heating kW - - - - -
(Min) Btu/h 8500 8500 22000 34000 64000
Heating kW - - - - -
(Max) Btu/h 432000 22000 34000 64000 108000
AHU Internal
Heat Exchanger Min in3 28 28 71 118 236
Volume
Allowance Max in3 1725 71 118 236 566
EEV in/out Liquid Pipe ̈͝ࡥףʀ˵ - 3/8 1/2 3/8 1/2
Connection Gas Pipe ̈͝ࡥףʀ˵ - 3/8 1/2 3/8 1/2
Power Source Wire mm2 - - - - -
Field Wiring
Transmission Cable mm2 - - - - -
59
5. Universal comm. kit
5.4. Technical drawings
Dimensional Drawings
1 Control Kit
Uniϩ: mm[inʀ˵ࣉ
56 [2-1/4”]
385 [1’3-3/6”]
50 [1-15/16”]
ߦࣛ˵࣒ߦࢩߣף࣑ߨߨףɇ̷˙ϑ̷ͱϩϑ
ߦ̷ࣛͱ˵࣒ߨߣࢩߧף࣑ߥߪףʪϑ
275 [10-13/16”]
175 [6-7/8”]
ߣߦߤࣈ߫ࢩߣߨ࣭ࣉ
50 [1-15/16”]
ߣߤߧࣈߣࢩߤ࣭ࣉ
ߦߤߧࣈߣࣛߣߣࢩߣߨ࣭ࣉ ߦߤߧࣈߣࣛߣߣࢩߣߨ࣭ࣉ
300 [11-15/16”]
60
5. Universal comm. kit
5.4. Technical drawings
MXD-A64K100E MXD-A40K100E
MXD-A32K100E MXD-A24K100E
EEV EEV
(D)
(D)
(B)
(B)
61
5. Universal comm. kit
5.4. Technical drawings
Piping Drawings
1 Cooling operation
COOL
FAN ON Outdoor Fan Motor
(OFM) Thermistor -
Thermistor - Room Temperature
EVA Out (T_RT)
(T_EO) Thermistor -
EVA In
(T_EI)
Ball Valve -
Gas pipe (BV_G)
Heat Exchanger - Main (HX_M)
Thermistor -
Discharge air Temperature
(T_DT)
62
5. Universal comm. kit
5.4. Technical drawings
Piping Drawings
1 Heating operation
HEAT
FAN ON Outdoor Fan Motor
(OFM) Thermistor -
Thermistor - Room Temperature
EVA Out (T_RT)
(T_EO) Thermistor -
EVA In
(T_EI)
Ball Valve -
Gas pipe (BV_G)
Heat Exchanger - Main (HX_M)
Thermistor -
Discharge air Temperature
(T_DT)
63
5. Universal comm. kit
5.4. Technical drawings
Piping Drawings
COOL
FAN ON Outdoor Fan Motor
(OFM) Thermistor -
Thermistor - Room Temperature
EVA Out (T_RT)
(T_EO) Thermistor -
EVA In
(T_EI)
Ball Valve -
Gas pipe (BV_G)
Heat Exchanger - Main (HX_M)
Thermistor -
Discharge air Temperature
(T_DT)
64
5. Universal comm. kit
5.4. Technical drawings
Wiring Drawings
EEV Electric expansion valve FAN MID FAN Output(Step Mid ON) NC NO CONNECTION
Checking fan operation status of input
AIR (10K) Thermistor () FAN LOW FAN-Output(Step Low ON) FAN CHECK
signal
FREE
EVA-OUT (10K) Thermistor (EVA.-OUT_10K) FAN OUT FAN-Output(ON/OFF) Blowing wind from outside(Input)
COOL_IN
EVA-IN (10K) Thermistor (EVA.-IN_10K) HEATER Heater-Output(ON/OFF) PT1000 ťƟߣߢߢߢצϑʪ͝ϑͱθ࣑Ã͝ΧЇϩ࣒
DISCHARGE
Thermistor (Discharge_10K) DEFROST Defrost-Output(ON/OFF) TB100 Terminal Block100(Power)
(10K)
EXT CTRL EXTERNAL CONTROL COOL_T Coolling Thermo-Output(ON/OFF) TB800 Terminal Block800(control/Dry Contact)
COMP ERROR Error check output THERMO Thermo-Output(ON/OFF) F100 Fuse
FAN HIGH FAN-Output (Step High ON) OPERATION O(ON/OFF)
NOTE
• This wiring diagram applies only to Universal Comm. Kit
• Colors BLK: black, RED: red, BLU: blue, WHT: white, YEL: yellow, BRN: brown, SKY: skyblue , ORG: orange,
GRN: green
• When operating, don’t short circuit the protection device (High Pressure switch)
• Protective earth(screw), : connector, : The wire quantity
65
5. Universal comm. kit
5.5. Installation
Outdoor unit
EEV Control
Liquid valve
Communication cable:
F3,F4
* Room Temperature
Gas pipe
Wired remote controller
OUT sensor
66
5. Universal comm. kit
5.5. Installation
10.5. Installation
PBA
12 11 10 9 8
(+) (COM)
DIS EXT-CTRL COMP/ERROR EEV1 EEV2 EEV3 EEV4 COOL HEAT AUTO COM TEMP COM ENTHALPY
DAMPER
(COM)
7
(+)
6
AIR
EVA-OUT
5
EVA-IN
4
F1 F2 V1 V2 F3 F4
AC 24V B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
B16
B17
B18
B19
B20
B21
B22
B23
B24
B25
B26
1 2 3
67
5. Universal comm. kit
5.5. Installation
* Use the rated current capacity for the dry contact within AC 250 V/1 A.
* Use the ring terminal that fits the screw.
68
6. Drain Pumps
6.1. Feature
Drip-free operation
The check valve on the drain pump prevents drained water from
flowing backward into the drain pan. This minimizes the drain pan’s Check valve:
Prevents drain water
water level, eliminating the worry and hassle of water stagnation or from reversing
69
6. Drain Pumps
6.1. Feature
Plug-and-connect drainage
The optional Plug and Connect External Type drain pump takes the
hassle out of draining the unit. Simply plug it in and connect it, and
with the single drain pump, maintaining all the building’s Duct S units
is easier than ever.
6.2. Line-up
Model Application Product Mounting Type Remark
ADP-M075SGC MA-0,1 Internal Type
ADP-M075SGC1 MA-2 Internal Type
MDP-M075SGK1 MA-0,1 Internal Type
MDP-M075SGK2 MA-2 Internal Type
MDP-M075SGU1 MA-0,1 Internal Type
MDP-M075SGU2 MA-2 Internal Type
MDP-M075SGU3 MA-S Internal Type
ADP-M075SEC0 MA-S Internal Type
ADP-N047SNK1 HSP(MA2) Internal Type
MDP-N047SNC1 HSP(MA2) Internal Type
MDP-E075SEC3 SLIM1,2,3 Internal Type
MDP-E075SEE3 SLIM1,2,3 Internal Type
ADP-E075SEK3 SLIM1,2,3 Internal Type
MDP-E075SEC4A SLIM DUCT HOME Internal Type
MDP-N047SNC1D BIG DUCT Internal Type
MDP-M075SGU2D MA2 DUCT Internal Type
MDP-M075SGU1D MA1 DUCT Internal Type
MDP-M075SGU3D MAS DUCT Internal Type
MDP-E075SEE3D SLIM DUCT Internal Type
ADP-N047SNK1D BIG DUCT Internal Type
MDP-M075SGK2D MA2 DUCT Internal Type
MDP-M075SGK1D MA1 DUCT Internal Type
ADP-E075SEK3D SLIM DUCT Internal Type
MDP-G075SP GLOBAL DUCT External Type
MDP-G075SQ GLOBAL DUCT Internal Type
70
6. Drain Pumps
6.3. Spec Sheet
1 Discharge fluid volume : 1200mm lift 10mm water level rated voltage
2 Noise : AC Motor - 1meter distance from drive motor head empty operating, 1200mm lift 10mm water level rated voltage
DC Motor - 1meter distance from drive motor head ( 300mm Head, 5mm water level, rated voltage
71
6. Drain Pumps
6.3. Spec Sheet
1 Discharge fluid volume : 1200mm lift 10mm water level rated voltage
2 Noise : AC Motor - 1meter distance from drive motor head empty operating, 1200mm lift 10mm water level rated voltage
DC Motor - 1meter distance from drive motor head ( 300mm Head, 5mm water level, rated voltage
72
6. Drain Pumps
6.4. Technical drawings
Dimensional drawings
MDP-E075SEE3
Unit: mm(inch)
141.7(5-9/16")
11.0(7/16")
100.7(3-15/16")
63.5(2-1/2")
155.0(6-1/8")
115.5(4-9/16")
85.2(3-3/8")
52.0(2")
154.0(6")
85.0(3-3/8")
73
6. Drain Pumps
6.4. Technical drawings
MDP-G075SP
Unit: mm(inch)
167.0(6-9/16") 145.0(5-11/16" )
144.0(5-11/16") 118.4(4-11/16" )
105.5(4-1/8") 63.0(2-1/2" )
99.6(3-15/16")
26.6
(1-1/16" )
114.0(4-1/2")
175.9(6-15/16")
111.0(4-3/8")
40.2(1-9/16" ) 69.1(2-3/4" )
7.4(5/16" )
84.1(3-5/16" )
15.0(9/16" )
76.6(3" )
74
6. Drain Pumps
6.4. Technical drawings
MDP-G075SQ
Unit: mm(inch)
116.8(4-5/8" )
85.6(3-3/8" )
69.0(2-11/16" )
95.2(3-3/4" )
122.2(4-13/16" )
123.3(6-11/16" )
164.3(6-7/16" )
69.3(4-7/8" )
47.5(1-7/8" )
50.3(2" )
95.3(3-3/4" )
75
6. Drain Pumps
6.4. Technical drawings
MDP-E075SEC4A
Unit: mm(inch)
138.2 [5-7/16”]
96.2 [3-3/4”]
3.4 [1/8”]
156.0 [6-1/8”]
115.5 [4-9/16”]
31.1 [1-1/4”]
148.0 [5-13/16”]
85.0 [3-3/8”]
76
6. Drain Pumps
6.4. Technical drawings
Unit: mm(inch)
138.0 [5-7/16”]
97.0 [3-13/16”]
11.5 [7/16”]
115.5 [6-1/8”]
85.2 [3-3/8”]
77
6. Drain Pumps
6.4. Technical drawings
Unit: mm(inch)
141.7 [5-5/8”]
100.7 [3-15/16”]
13.5 [1/2”]
115.5 [6-1/8”]
85.2 [3-3/8”]
78
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.1. Part Names and Components
01 MAIN PBA
01
02 SMPS PBA
03 TERMINAL BLOCK
02
03
Components
Amount 1 1 1
Shape
Amount 5 1 1 2
Shape
79
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.2 Electrical Wiring Diagram
Connect it after
removing the
wire coating.
with the
OPEN finish
Connect it after
removing the
wire coating.
with the
OPEN finish
Connect it after
removing the
wire coating.
80
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.3 Assembling
8 13/16
7 5/8
10 3/8
9 5/8
1 13/16
2 3 1/2
CW
FULL OPEN
Damper
LOUVER
SHAFT
NUT
Louver
WARNING
• When assembling the damper and Assy control box, be sure to fix the shaft and actuator (Nut x2) in the
louver in fully open state.
81
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.4 Combination unit
Model Number
Required Model Number per chassis
Left Right Back Front Top
LACKD-1
DVM S Small chassis LACH-SL LACH-SR LACH-R1 -
(= LACH-1)
LACKD-2
DVM Large A type chassis LACH-SL LACH-SR LACH-R2 -
(= LACH-2)
LACKD-2
DVM Large B type chassis LACH-SLR LACH-SLR LACH-R3 LACH-F1
(= LACH-2)
CAUTION
• When installing the components in the outdoor unit, be careful for screws not to touch the heat exchanger
pin.
82
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.5 Dimensions
UNIT : inch
LACH-SR LACH-SL
23 11/16 18 3/4
8 1/8
8 1/8
6 15/16
16 3/8
2 15/16
6 15/16
49 9/16
49 9/16
41 7/16
41 7/16
22
22
LACH-R1 LACH-R2
31 1/16
47 1/2
8 1/8
28 11/16 8 1/8
6 15/16
6 15/16
45 1/8
49 9/16
49 9/16
41 7/16
41 7/16
22 22
83
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.5 Dimensions
UNIT : inch
LACH-SLR LACH-R3
27 11/16
49 3/8
1 3/8
1 3/8
6 11/16
25 5/16 47
6 11/16
53 5/16
53 5/16
46 11/16
46 11/16
22
22
LACH-F1
16 7/8
9/16
15 1/16 1 15/16
6 11/16
46 11/16
15 7/8 22 5/8
84
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.5 Dimensions
UNIT : inch
35
5/8"
3 15/16"
35
25 3/16"
28 3/8"
23 7/8"
1 1/4"
3 3/16"
29 3/4" 5/8"
51 1/4"
5/8"
3 15/16"
51 1/4"
25 3/16"
28 3/8"
23 7/8"
1 1/4"
3 1/16"
29 3/4" 5/8"
85
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.6 Installation
12
Wind
direction
86
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.6 Installation
87
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.6 Installation
Grounding between
the outdoor unit and LAC kit
(Use the provided grounding screws.)
Mount Tie
88
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.6 Installation
89
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.6 Installation
Configuring the options of the outdoor unit for installation of LAC kit
When installing LAC kit, be sure to enable the LAC kit function for the outdoor unit.
When installing the modules, enable the function on the main outdoor unit.
1 Press and hold K2 to enter the setup. (Available in operation stop status)
- The following appears. (In case of compressor cut-off setting, 1 or 2 appears in Seg4.)
2 In the option setup menu, when you shortly press the K1 switch, the values for Seg1 and Seg2 change. You can
select the desired option.
(e.g. The value for Seg1 is 2 and the value for Seg2 is 1.)
90
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.6 Installation
1 In the desired option, if you shortly press the K2 switch, the values for Seg3 and Seg4 change. You can select the
desired option.
(e.g. The value for Seg3 is 0 and the value for Seg4 is 1.)
2 After selecting an option, if you press the K2 switch for 2 seconds, all 7-segment displays blink. If you enter the
tracking mode, the option setting is saved.
CAUTION
• If not normally processed as mentioned above, the option setting is not saved.
• Before entry of the mode, if you want to return to the setting, press and hold the K1 switch to cancel the
setting.
• If you want to reset to the factory defaults, in the option setting mode, press and hold the K4 switch.
- If you press and hold the K4 switch, all the settings are reset to the factory defaults but the values are not
saved yet. Only when the 7-segment display goes to the tracking mode by pressing and holding the K2
switch, the setting is saved.
Option Entry Unit SEG1 SEG2 SEG3 SEG4 Function Remarks
91
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.6 Installation
• Ã˙øÄ̧ϩ̈ϑ̈͝ϑϩɇ̷̷ʪʒࡥϩ˵ʪʀͱͱ̷̈͝˝ͱΧʪθɇϩ̈ͱ̈͝ϑΧͱϑϑ̈ɵ̷ʪЇΧϩͱࣛߣߥঌ
• For more information about cooling performance of LAC kit, see the following table:
Outdoor Temperature (°F, DB)
Performance Correction
Less than 23 Less than 99 Less than 107 Greater than 107
Dip S/W
• Prior to power supply to the outdoor unit, set the switches. When address recognition is impossible after power
supply, press the Reset button (K3 switch) on the outdoor unit.
Dip S/W
Function Remarks 7-Segment
#1 #2
ON (Default) ON (Default) Outdoor unit address: No.1 Connection to Main outdoor unit
OFF OFF Outdoor unit address: No.4 Connection to Sub3 outdoor unit
• After setup, check the LAC kit 7-segment display for normal address setup.
92
7. Low Ambient Cooling kit (This optional kit is sold only in North America.)
7.6 Installation
Dip S/W
• To see the version of LAC kit, change to the dip switch #4.
Dip S/W
Function Remarks
#4
• Error code
Communication error between Upon LAC kit 7-Segment Error Display Error, the state is
E203
LAC kit and outdoor unit changed to LCA KIT Full Open.
93
8. PDM (Pressure Drop Modulation) Kit
8.1. Part Names and Components
Dimensional drawings
KIT model
MXD-A38K2A MXD-A12K2A MXD-A58K2A
name
Uǹߢߪߢ७७ड़ߣߤߢ७७ Uǹߣߦߢ७७ड़ߣߨߢ७७ Uǹߣߪߢ७७ड़ߤߢߢ७७
SET đߢߪߢ७७ड़ߣߤߢ७७ đߣߦߢ७७ड़ߣߨߢ७७ đߣߪߢ७७ड़ߥߢߢ७७
application
model name đߢߩߤ७७ࢩड़ߣߤߢ७७ࢩ đߣߦߦ७७ࢩ đߣߨߪ७७ࢩड़ߤߣߨ७७ࢩ
ߦƟǤ७ߢߢߩߤ७७ड़ߢߣߤߢ७७ ߦƟǤ७ߢߣߦߦ७७ ߦƟǤ७ߢߣߨߪ७७ड़ߢߤߣߨ७७
500(1' 7-11/16")
500(1' 7-11/16")
262(10-5/16" )
217(8-9/16" )
142(4-7/8" )
12.7
(1/2") 12.7 15.88
* CTF “A” *CTF “B” (5/8")
(1/2" ) 129
120 ± 3 35 ± 3 89 89
135 (5")
(4-3/4" ) (5-5/16") (3-1/2") (3-1/2")
94
9. Branch kit
9.1. Y-joint
Dimensional drawing
(Unit : mm)
Model MXJ-YA1509M MXJ-YA2512M
Port
ID Ø12.9
ID Ø9.7
ID Ø12.9
ID Ø9.7
255 255
127 127
Liquid side
80
80
ID Ø12.9
ID Ø12.9
127 127
ID Ø12.9
ID Ø25.6 ID Ø12.9
x 2 EA x 2 EA
ID Ø19.2
ID Ø16.1
282 364
147 172
Gas side
80
80
ID Ø22.4
ID Ø25.6
ID Ø19.2
ID Ø19.2
147 172
ID Ø25.6
ID Ø19.2
x 2 EA
x 2 EA x 2 EA
255
ID Ø9.7
ID Ø19.2
282
ID Ø16.1
127
147
80
Liquid side
80
ID Ø12.9
ID Ø19.2
127
ID Ø19.2
ID Ø12.9
147
x 2 EA
x 2 EA
ID Ø31.9
ID Ø28.7
ID Ø28.7
ID Ø31.9
387 387
195 195
Gas side
80
80
ID Ø31.9
ID Ø31.9
195
ID Ø25.6
ID Ø25.6
x 1 EA 195 x 1 EA
x 1 EA x 1 EA
95
96
Port
Reducer
OD Ø34.9
OD Ø12.7
Gas side
40
OD Ø38.1
Liquid side
9.1. Y-joint
Model
ID Ø31.9
75
85
ID Ø31.9 ID Ø31.9 ID Ø16.1
110
130
140
ID Ø28.7
120
140
ID Ø28.7 ID Ø35.1
90
ID Ø9.7 ID Ø38.3 ID Ø19.2
55
ID Ø25.6
ID Ø25.6 ID Ø6.5
20
419
282
9. Branch kit
147
147
199
ID Ø19.2 ID Ø19.2
OD Ø28.58 ID Ø28.7 ID Ø35.1
80 80
MXJ-YA3419M
OD Ø41.28
45
OD Ø19.05
ID Ø25.6
(5)
80
ID Ø22.4 ID Ø44.6 ID Ø16.1
x 2 EA
x 2 EA
x 1 EA
x 1 EA
x 1 EA
115
210
105
150
ID Ø19.2
170
ID Ø12.9
70
160
ID Ø54.1
125
ID Ø16.1 ID Ø9.7
30
90
55
ID Ø12.9 ID Ø6.5 ID Ø41.4 ID Ø16.1
ID Ø38.3
ID Ø12.9
20
282
438
62 99
147
147
267
OD Ø31.75
OD Ø25.4 ID Ø19.2 ID Ø19.2
ID Ø35.1
40
OD Ø19.05 80
110 ID Ø38.3
MXJ-YA4119M
ID Ø28.7
75
ID Ø25.6 ID Ø22.4
20
170
110
60
125
ID Ø22.4 ID Ø19.2
145
90
165
x 2 EA
x 2 EA
x 1 EA
x 1 EA
x 1 EA
x 1 EA
55
ID Ø16.1
ID Ø22.4 ID Ø16.1
20
ID Ø12.9
ID Ø41.4 ID Ø19.2
ID Ø44.6 ID Ø22.4
ID Ø54.1 ID Ø25.6
475
364
172
244
OD Ø41.28
172
OD Ø38.1
OD Ø28.7
25
ID Ø25.6 ID Ø25.6
45
ID Ø38.3 ID Ø41.4
20
ID Ø38.3 110
80
MXJ-YA4422M
60 80
60
115
140
ID Ø25.4 ID Ø31.9
ID Ø41.4
ID Ø28.7
x 1 EA
x 1 EA
x 2 EA
x 1 EA
x 1 EA
x 1 EA
(Unit : mm)
(Unit : mm)
9. Branch kit
9.2. Y-joint for HR (High pressure gas)
Dimensional drawing
(Unit : mm)
MXJ-YA1500M MXJ-YA2500M
ID Ø19.2
ID Ø22.4
ID Ø16.1
ID Ø22.4
ID Ø25.6
ID Ø19.2
80
80
149 173
ID Ø22.4
ID Ø16.1
284 365 x 2 EA
x 1 EA
MXJ-YA3100M MXJ-YA3800M
ID Ø35.1
ID Ø35.1
ID Ø28.8
ID Ø22.4
ID Ø35.1
472
241
80
110
ID Ø44.6
ID Ø41.4
ID Ø35.1
194
ID Ø35.1
x 1 EA
ID Ø28.7
407
x 1 EA x 2 EA
Reducer
(Unit : mm)
60 145 145
OD Ø22.2
25
ID Ø19.2
ID Ø16.1
120 120
85 85
50 50
OD Ø25.4
ID Ø28.7
OD Ø28.58
20
OD Ø34.9
ID Ø22.4
ID Ø19.2
ID Ø16.1
ID Ø22.4
ID Ø28.7
ID Ø19.2
55
90
97
9. Branch kit
9.3. Header joint
Dimensional drawing
(Unit : mm)
Model MXJ-HA2512M MXJ-HA3115M
Port
265 60 425 60
ID Ø9.7
ID Ø9.7
ID Ø16.1
ID Ø12.9
57.2
55.6
ID Ø16.9
ID Ø19.2
Liquid side
85 40 40 40 85 40404040404040
x 4 EA x 1 EA a x 1 EA x 8 EA x 1 EA b x 1 EA
305
445
ID Ø28.7
80.9
ID Ø28.7
77.7
ID Ø31.9
ID Ø31.9
Gas side
ID Ø16.1 95 40404040404040 ID Ø16.1
90 40 40 40
x 4 EA x 1 EA x 1 EA x 8 EA x 1 EA x 2 EA
Model MXJ-HA3819M
Port
425 60
ID Ø9.7
58.8
ID Ø19.2
ID Ø22.4
Liquid side
85 404040 40 404040
x 8 EA c x 1 EA
445
ID Ø35.1
84.0
ID Ø38.3
Reducer
(Unit : mm)
60 100
60 60
15 15 50
15 15
OD Ø15.88
OD Ø12.7
OD Ø9.52
OD Ø15.88
ID Ø12.9
ID Ø6.5
ID Ø9.7
ID Ø12.9
ID Ø9.7
210
140 50 50
a b 55 c
ID Ø22.4
160
ID Ø19.2
90
125 55 20
90
OD Ø19.05
OD Ø15.88
55
OD Ø12.7
20
OD Ø28.58
20
ID Ø16.1
OD Ø28.58
ID Ø25.6
ID Ø22.4
OD Ø15.9
55
ID Ø22.4
ID Ø12.9
ID Ø25.6
ID Ø19.2
ID Ø16.1
90
98
9. Branch kit
9.4. Out door joint
Dimensional drawing
(Unit : mm)
Model MXJ-TA3819M MXJ-TA3419M
Port
ID Ø19.2
ID Ø19.2
ID Ø16.1
282
ID Ø16.1
282
147 147
Liquid side
80
80
ID Ø19.2
ID Ø19.2
147
ID Ø19.2
ID Ø19.2
147 x 2 EA x 2 EA
x 1 EA x 1 EA
ID Ø22.4
479 ID Ø28.8
251±2
ID Ø38.3
ID Ø35.1
ID Ø41.4
240 ID Ø35.1
Gas side
ID Ø35.1
ID Ø35.1
ID Ø38.3
262
ID Ø41.4
ID Ø28.8
ID Ø25.6 x 1 EA ID Ø35.1 240 x 1 EA
ID Ø22.4 x 1 EA 479±2
ID Ø19.2 x 1 EA
ID Ø25.6
ID Ø25.6
ID Ø19.2
364 364
ID Ø19.2
172 172
80
80
Liquid side
ID Ø22.4
ID Ø25.6
ID Ø22.4
ID Ø25.6
172 172
ID Ø25.6
ID Ø25.6
x 2 EA x 2 EA
ID Ø22.4
470
ID Ø41.4
ID Ø28.8
ID Ø54.1
334 ID Ø35.1
266
ID Ø41.4
Gas side
ID Ø41.4
ID Ø54.1
272
ID Ø28.8 334
ID Ø41.4
ID Ø25.6 470 x 1 EA
ID Ø22.4
ID Ø19.2 x 1 EA
Reducer
(Unit : mm)
145 105
OD Ø19.05
ID Ø16.1
ID Ø12.9
120
ID Ø9.7
85
85
50 50
20
OD Ø34.9
OD Ø34.9
ID Ø28.7
ID Ø31.9
ID Ø19.2 ID Ø28.7
ID Ø16.1 ID Ø22.4
ID Ø12.9 ID Ø19.2
55
95
145
OD Ø25.4
ID Ø22.4
60 70
20 35
40
OD Ø19.05
ID Ø22.4
OD Ø41.3
75
ID Ø35.1
110
145
165
99
9. Branch kit
9.5. Out door joint for HR (High pressure gas)
Dimensional drawing
(Unit : mm)
MXJ-TA3100M MXJ-TA3800M
422 423
264 266
ID Ø34.9
ID Ø41.4
ID Ø28.8
ID Ø41.4
ID Ø44.6
ID Ø35.1
173
173
x 1 EA
x 1 EA x 1 EA
ID Ø28.8 x 1 EA ID Ø28.8 x 2 EA
Reducer
(Unit : mm)
180
OD Ø41.28
407 70
ID Ø28.7
ID Ø38.3
ID Ø31.9
125 327
90 35
220
55 160
20 125
45 90
55
OD Ø41.3
80 20
OD Ø34.9
ID Ø35.1
ID Ø22.4
ID Ø28.7
ID Ø19.2
ID Ø16.1
59
115
140
ID Ø22.4
ID Ø25.6
ID Ø28.7
ID Ø19.2
ID Ø16.1
OD Ø28.6
100
10. ERVKit (Interface Module, ForNorthAmerica only)
10.1. Feature
Upper Controller
DVM
CASSETTE DUCT
- The local ERV product and Samsung communication system are linked through the ERV kit.
Shape
CN4
CN3 CN2
RED BLK
101
10. ERVKit (Interface Module, ForNorthAmerica only)
10.2. Spec sheet
(unit : mm)
Open
Close
102
10. ERVKit (Interface Module, ForNorthAmerica only)
10.4. Wiring Diagram
9̷ͱʀ̧
Mark S+ S- B A T+ T- W W D+ D-
Note - - BLU RED GND - - - - +12V -
SKY BLUE
BROWN
0;'.91
(MIM-N10)
BROWN
CN4
CN4
SKY BLUE
S-NET3
CN4
CN3
RED
ERV KIT
(Max 16)
CN2
CN2
CN2
BLK
BLK
BLK
F1-F2
CN3
CN3
CN3
RED
RED
RED
(&2728&+&RQWUROOHU
2SWLRQDORQHSHU(59
103
10. ERVKit (Interface Module, ForNorthAmerica only)
10.5. Install
1 After attaching a case to the side of the Fresh Access™ ERV, install the ERV KIT.
2 Connect the power cable and communication cable of the ERV KIT.
• When a ERV KIT is installed, you can perform a centralised control of DMS.
9̷ͱʀ̧
Mark S+ S- B A T+ T- W W D+ D-
Note - - BLU RED GND - - - - +12V -
SKY BLUE
BROWN
0;'.91
(MIM-N10)
BROWN
CN4
CN4
SKY BLUE
CAUTION
• You should switch off the power supply and disconnect the power cable.
(Abnormal operation of the product may occur due to the electric problem.)
104
10. ERVKit (Interface Module, ForNorthAmerica only)
10.5. Install
SW 4 SW 5
ON
CN3 CN2
RED BLK
• ƊǮߣࡑʒʒθʪϑϑϑӥϩʀ˵ࡥϑʪϩϩ˵ʪɇʒʒθʪϑϑӥϩ˵̈͝ߢड़࣑ߢड़ߣߧ࣒࣑ʒʒθʪϑϑɵʪϩиʪʪ͝ʪɇʀ˵kŵǤç̈ϩϑ˵ͱЇ̷ʒɵʪϑʪϩʒ̈˙˙ʪθʪ͝ϩ̷ц࣒
• ƊǮߦ࢈ߣࡑĮΧϩ̈ͱ͝ϑӥϩʀ˵ࡥи˵̈ʀ˵ϑʪϩϑɇЇϩͱ͔ɇϩ̈ʀࢩ͔ɇ͝Їɇ̷ɇʒʒθʪϑϑϑʪϩϩ̈͝˝и˵ʪ͝kŵǤç̈ϩɇ͝ʒθʪϑ˵ʀʀʪϑϑঊkŵǤ˵ɇЭʪ
been installed.
- To set automatic/manual address setting, set as in the following table. (Default: automatic address setting)
(This function is only applicable when new communication upper level controller is connected.)
1 2 SW4 SW5
ON OFF ON OFF
• When connecting a 485 communication cable between the ERV Kit and the DMS, be sure to match the polarity. If
the polarity does not match, communication is impossible.
CAUTION
• Both distances from the ERV Kit to the DMS must be within 3,280 feet.
• You should switch off the power supply before installation.
• The wiring should be installed in accordance with electric wiring regulations and should be placed inside the
wall so that users cannot touch them.
105
10. ERVKit (Interface Module, ForNorthAmerica only)
10.5. Install
Checking Operation
LED indication
1 When communication between the ERV Kit and an ERV(3rd party) is proceeding, the Y-GRN LED blinks.
2 When communication between the ERV Kit and DMS or ERV Interface module(MIM-N10), RED LED blinks.
LED
Y-GRN
RED
YEL
7-SEGMENT indication
Address SEGMENT
00 Ad 00
15
• The address of the ERV KIT can be set to a value from 0 to 15.
E101
106
10. ERVKit (Interface Module, ForNorthAmerica only)
10.5. Install
1RWHRQ0;'.91(59.LWDQG'06RSHUDWLRQ
• Set remote controller settings.
Error Codes
E109 Communication error due to ERV KIT address incomplete. ERV KIT
communication error
E111 ERV Kit Fresh Access™ ERV
(when COMM KIT cannot receive signals)
107
10. ERVKit (Interface Module, ForNorthAmerica only)
10.6. Compatible model
)UHVK$FFHVVw(59
Model Type
108
11. Differential Pressure Switch(This optional kit is sold only in Europe.)
11.1. Feature
࢜Ǯ˵ʪ͝ĘуууâƊçøçĘࢩkƸ̈ϑ̈͝ϑϩɇ̷̷ʪʒ̈͝ɇʀͱЇ͝ϩθци˵̈ʀ˵̈ϑϑЇɵ̟ʪʀϩϩͱAͱ͔͔̈ϑϑ̈ͱ͝θʪ˝Ї̷ɇϩ̈ͱ࣑͝kƸ࣒Ęͱߣߤߧߥࢩߤߢߣߦ
implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to Ecodesign
requirements for ventilation units, be sure to install a differential pressure switch (MOS-P1050), which can
measure pressures at the front and back of the filter, together with the product.
Name Differential Pressure Switch Plastic Tube PVC Tube Screw (PH, M4, L10)
Shape
Name Screw (PH, M3, L10) Screw (TH, M4, L8) Pin-terminal connector Holder Wire
Shape
109
11. Differential Pressure Switch(This optional kit is sold only in Europe.)
11.2. Spec sheet
Pin-terminal No.2
Pressure adjustment
dial
65.0mm
Pin-terminal No.3
Cover
ע6
57.5mm
110
11. Differential Pressure Switch(This optional kit is sold only in Europe.)
11.4. Wiring Diagram
- Connect the connecting wires to the pin-terminals No. 2 and No. 3 located on both sides to the differential
pressure switch dial, and then connect the opposite ends of the connecting wires to the HOOD terminals on the
ERV PBA.
11.5. Install
1 Connect the PVC tubes to the two sockets on the side of the differential pressure switch, and connect the plastic
tubes to the opposite side as shown in the figure.
• Connect the low pressure side PVC tube to the socket P2 (upper socket) and the high pressure side PVC tube to
the socket P1 (lower socket).
• Cut the PVC tube to fit the size of the product.
111
11. Differential Pressure Switch(This optional kit is sold only in Europe.)
11.5. Install
2 Untighten the screws on the ERV, as marked in the figure, and then assemble the differential pressure switch
using screws (PH, M4, and L10).
• AN026**
CAUTION
• When installing the differential pressure switch, make sure that its sockets to which the tubes are connected
face downward (based on product installation). Failure to do so may cause moisture to enter the switch or
errors to occur in differential pressure measurement.
3 Disassemble the circular cover next to the electrical control part of the ERV, and then assemble the low pressure
plastic tube connected to the differential pressure switch socket P2. Then, fix the low pressure PVC tube to the
product using the holder wire as shown in the figure.
• Disassembling the circular cover and assembling the plastic tube
NOTE
• Make sure that the direction of the plastic tube as indicated by the arrow in the figure is identical with the air
112 flow direction.
11. Differential Pressure Switch(This optional kit is sold only in Europe.)
11.5. Install
• AN026**
CAUTION
• In any case, be careful not to twist or press the PVC tube. Failure to do so may cause errors in pressure
measurement, leading to product malfunction.
• If the direction of the plastic tube is not identical with the air flow direction, errors may occur in pressure
measurement, leading to product malfunction.
113
11. Differential Pressure Switch(This optional kit is sold only in Europe.)
11.5. Install
4 Assemble the high pressure plastic tube(P1) to the OA duct installed on site, and then fix the high pressure PVC
tube using the holder wire.
• Assemble the plastic tube so that its direction is identical with the air flow direction in the OA duct.
• Assemble the plastic tube at a position which is 300 to 500 mm away from the product.
- Assemble the plastic tube to a side of the OA duct.
• AN026**
- Assemble the holder wire to the inspection cover assembly screw on the top of the product, and then fix the
PVC tube.
- Assemble the plastic tube to the external OA duct, and then fix the PVC tube using the holder wire.
Plastic tube
direction
ע2.5
ע7.5
ע2.5
CAUTION
• In any case, be careful not to twist or press the PVC tube. Failure to do so may cause errors in pressure
measurement, leading to product malfunction.
• If the direction of the plastic tube is not identical with the air flow direction, errors may occur in pressure
measurement, leading to product malfunction.
• If the plastic tube is assembled below the OA duct, the plastic tube can be blocked by dirt or dust. Be careful
not to assemble the plastic tube below the OA duct.
114
11. Differential Pressure Switch(This optional kit is sold only in Europe.)
11.5. Install - Wire
Connecting the connecting wires between the differential pressure switch and the ERV PBA
1 Untighten the screw (1 EA) of the differential pressure switch, disassemble the cover, and then pass the cable
through the screw type cable connection part.
3 Connect the connecting wires to the pin-terminals No. 2 and No. 3 located on both sides to the differential pressure
switch dial, and then connect the opposite ends of the connecting wires to the HOOD terminals on the ERV PBA.
CAUTION
• Be sure to switch off the power supply before installation. (Failure to do so may cause electrical problems,
leading to abnormal operation of the product.)
• The wiring must be installed in compliance with electrical wiring regulations.
• If the diameter of the connecting wire is less than 5mm, the sealing of the screw type cable connection part
may not be complete.
115
11. Differential Pressure Switch(This optional kit is sold only in Europe.)
11.5. Install - Wire
1 Rotate the dial located at the center of the differential pressure switch until the number pointed by the yellow
arrow becomes equal to the differential pressure setting value of the product.
(Refer to the following table for the setting values by model.)
AN026JSKLKN/EU 220
AN035JSKLKN/EU 200
50
50
10
0
0
150
AN050JSKLKN/EU 250
450
200
400
AN080JSKLKN/EU 280
0
35
0
300
25
AN100JSKLKN/EU 310
NOTE
• When rotating the dial to set the differential pressure, be sure to rotate it in the direction that the number
increases from the minimum value to the setting value. If you rotate the dial in the direction that the number
decreases to the setting value, errors may occur in differential pressure measurement.
WARNING
• Be sure to set the differential pressure while the product is turned off. If it is not turned off, an electric shock
may occur due to your contact with a peripheral wire.
2 Close the cover of the differential pressure switch, and then tighten the screw.
3 Set SEG17 of the installation option 1 (02 mode) of the product to 1. (The ANxxxJSKLKN / EU models ship with being set to
the factory default 1.).
࢜Ǯ˵ʪ͝ĘуууâƊçøçĘࢩkƸ̈ϑ̈͝ϑϩɇ̷̷ʪʒ̈͝ɇʀͱЇ͝ϩθци˵̈ʀ˵̈ϑϑЇɵ̟ʪʀϩϩͱAͱ͔͔̈ϑϑ̈ͱ͝θʪ˝Ї̷ɇϩ̈ͱ࣑͝kƸ࣒Ęͱߣߤߧߥࢩߤߢߣߦ
implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to Ecodesign
requirements for ventilation units, be sure to install a differential pressure switch (MOS-P1050), which can
measure pressures at the front and back of the filter, together with the product.
116
12. Accessory
12.1. Indoor Unit's Accessory Compatibility
OAP
1 way MSP Duct
(North America)
Floor Standing
Mini 4way
Slim duct
B-Ceiling
ERV Plus
DUCT
Big Duct
Console
Local ERV
Ceiling
Duct-S
4 way
2 way
AHU
RAC
PAC
360
Product Model Remark
8,10HP
MSP-0
MSP-S
MSP-2
MSP-1
JSF-0
JSF-2
JSF-1
5HP
Below 6 indoor
MCU-S6NEE1N
units, below 56 kW
O O O O O O O O O O O O O O O O O O O O O
Below 4 indoor
MCU-S4NEE1N
units, below 56 kW
O O O O O O O O O O O O O O O O O O O O O
MCU-KIT Below 2 large
MCU-S4NEE2N capacity indoor O O O O O O O O O O O O O O O O O O O O O
unit, below 56 kW
Below 2 indoor
MCU-S2NEK1N
units, below 28 kW
O O O O O O O O O O O O O O O O O O O O O
MEV-E**SA 1 Indoor O
EEV KITS
MXD-E**K***A 2,3 Indoor O
only for 2.5Hp's
MXD-K025AN
AHU
O
MXD-K050AN only for 5Hp's AHU O
only for 7.5Hp's
AHU-KIT MXD-K075AN
AHU
O
MXD-K100AN only for10Hp's AHU O
only for 10~40Hp's
MCM-D201N
AHU
O
MDP-
N047SNC0D
- O
MDP-
N047SNC1D
- O
MDP-
M075SGU1D
- O O
DRAIN MDP-
M075SGU2D
- O
PUMP
MDP-
M075SGU3D
- O
MDP-E075SEE3D - O
External, All
MDP-G075SP
Capacities
O
MDP-G075SQ Internal O
Motion
No technical data
detect MCR-SMA
provided
O
Sensor
No technical data
MSD-CAN1
provided
O O
S-Plasma
Ion KIT No technical data
MSD-EAN1
provided
O
ERV CO2 No technical data
Sensor
MOS-C1
provided
O
ERV Kit MXD-K200VN O
Diffrencial
Pressure MOS-P1050 O
Switch
NOTE
• In case you want to konw information the accessories, please refer to the control and accessories TDB on pvi.
samsung.com site.