Applications for Thermal Imagers

Substations and Switchgear

Application Note

Substations call for a predictive approach to maintenance


because a failure can be costly for end users in terms of
lost production and revenues and lead to lower revenues
for the utility from lost sales due to unreliable service.
Since overheating as well as abnormally cool operating
temperatures may signal the degradation of an electrical
component, thermal imagers provide the predictive capa-
bilities required for substation and switchgear maintenance.

In the power generation and failure. The goal is to determine transformers, regulators, switches,
distribution industries, the term whether corrective action circuit breakers and capacitors
substation is used in many is required and, if so, to take that among other components.
ways. Various outdoor facilities action before equipment fails. The time of day is an important
ranging from switchyards at One set of tools for monitoring factor in collecting thermal images
generating stations to equip- equipment in substations is of substation components. Read-
ment at utilities or at industrial Fluke’s handheld thermal ings in the stillness of early morn-
facilities that switches or modi- imagers. Thermal imagers cap- ing may avoid the effects of solar
fies voltage, frequency or other ture two-dimensional represen- reflections and wind, which can
characteristics of primary power tations of the apparent surface skew temperature readings. How-
are called substations. temperatures of electrical ever, in pre-dawn hours loads are
Predictive maintenance (PdM) components and other objects. generally lighter and problems
helps ensure the quality of an end less detectable. The training and
user’s electricity by enhancing the What to check and experience of the thermographer
reliability of substations. PdM when? may also affect when outdoor IR
accomplishes this increased relia- scans should be performed.
For a detailed outline of main-
bility by monitoring equipment
taining substations and related
over time in order to isolate
switchgear assemblies, follow
What to look for?
conditions that indicate impending Following a thorough inventory of
NFPA Standard 70B, Recom-
mended Practice for Electrical the equipment in a substation, scan
Equipment Maintenance, Chap- the entire substation yard, saving
ter 8: “Substation and images of any known or possible
Switchgear Assemblies.” That anomalies. Look especially for simi-
standard explains that in trans- lar pieces of equipment under simi-
forming primary power, substa- lar loading that are clearly operating
tions may provide system at different temperatures.
protection, power-factor-correc- A good thermographic approach
tion metering and circuit to substation maintenance is to
switching in addition to chang- create inspection routes that
ing voltage. Substations and include all the substations owned
switchgear inherently operate by your utility or facility. On a
at high voltages. NFPA standard computer, save thermal images of
70E provides additional specific each substation component and
guidance on procedures and the track temperature measurements
level of personal protective over time. That way, you’ll have
equipment required when baseline images with which to
For equipment that always has a inspecting substations. Thermal compare later images. Doing this
high operating temperature, estab- inspectors typically inspect will help you determine if tempera-
lish a baseline or standard accept-
able temperature range to compare
readings to.

For more information on Thermal Imagers


go to www.fluke.com/thermography
monitor substation equipment for includes a digital, visual-light
specific degrees of temperature image of the equipment and a
rise above established reference corresponding thermal image.
points. Knowledgeable technical, That’s the best way to communi-
safety and maintenance personnel cate any problems you found and
might establish these limits to to make any suggestions for cor-
This thermal image shows hot secondary connections on the
range from “continue to monitor” recting them. Following corrective
transformer. to “correct immediately,” with action, a new thermal image can
other levels of action such as be used to assess the effective-
“schedule maintenance” or “repair ness of repairs and evaluate the
as soon as possible” in-between. materials and techniques used.
This approach has been suc- With this information, you can
cessful when reference points continuously improve your main-
take into account the differences tenance program for substations.
between line-of-sight scans
(e.g., metal-to-metal contacts in *IT Performance Engineering and Measure-
ment Strategies: Quantifying Performance
switchgear) and non-line-of- and Loss, Meta Group, Oct. 2000; Fibre
sight situations (e.g., the internal Channel Industry Association as found on the
Web site of the Association of Contingency
components of transformers), Planners, Washington State Chapter:
where heat is dissipated or www.acp-wa-state.org.
Examine transformers, comparing similar connections under obscured from the direct view of bag in place.
similar loads. the thermographer and the IR
camera. In a non-line-of-sight
scan, the actual operating tem-
ture levels are unusual and, fol- perature will be much higher
lowing corrective action, help you than the IR camera registers, so
determine if maintenance was the reference points that signal
successful. what corrective action to take
must be much lower. Also,
What represents a abnormally cool as well as
“red alert?” abnormally hot components
should be included in the mix.
Equipment conditions that pose a
safety risk should receive the What’s the potential cost
highest repair priority. Beyond of failure?
that, NETA (InterNational Electri-
cal Testing Association) guide- The costs associated with a failed
lines say that when the electrical substation depend upon
temperature difference (T) many factors including the num-
between similar components ber and types of customers
under similar loading exceeds affected. One source*, estimates
15 °C (27 °F) immediate repairs the average hourly cost of down-
should be performed. NETA also time across all industries at
recommends the same action nearly $950,000.
when the∆T between a compo-
nent and ambient air exceeds Follow-up actions Fluke. Keeping your world
40 °C (72 °F). Whenever you discover a problem up and running.
Following this line of thinking, using a thermal imager, use the
one way to categorize mainte- associated software to document
nance tasks and flag equipment Fluke Corporation
your findings in a report that PO Box 9090, Everett, WA USA 98206
urgently needing repairs is to
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
An imaging tip: For more information call:
In the U.S.A. (800) 443-5853 or
Consider performing IR scans of substations during the winter and early spring Fax (425) 446-5116
months rather than during the summer when loading is the highest. In the sum- In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
mer, it is more difficult for maintenance personnel to get authorization for shut- In Canada (800) 36-FLUKE or
downs for repairs. However, during peak loading in the summer is when Fax (905) 890-6866
equipment is most likely to fail. Repairs made in winter and spring will put From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
equipment in tiptop condition to meet the demands of summer. Web access: http://www.fluke.com
©2005 Fluke Corporation. All rights reserved.
Printed in U.S.A. 9/2005 2542593 A-EN-N Rev A