Professional Documents
Culture Documents
Ice Plant and Cold Storage Design (120 Tons of Ice)
Ice Plant and Cold Storage Design (120 Tons of Ice)
MANILA CAMPUS
DEPARTMENT OF MECHANICAL ENGINEERING
Submitted By:
Lucidos, Marjohn E.
Submitted To:
Engr. Jorge B. Yasay
FREEZING TANK
Design Conditions:
Production Rate = 120 TOI per Day
Ice Temperature = -7.5°C = 18.5°F
Brine Temperature = -9.44°C = 15°F
Raw Water Temperature = 26°C
Freezing Time = 48 Hrs.
Standard Ice Can Dimension = 11” X 22” X 44”
Weight of Ice per Can = 300 lbs.
N=
(120TONS OF ICE) ( 2,000lb
TON )
( 48 hrs)
300 lb x 24 hrs
N = 1600 Cans
N (adjusted) = 1610 Cans
60 ft 3
V BRINE =TOR [ ]
1 TOR
60 ft 3
V BRINE =196.72 TOR[ ]
1TOR
V BRINE =11803.2 ft 3
44
V IC= [242+180+ 4 ( 211 ) ]
6
1 ft 3
V IC=9284 ¿ 3
123 ¿3( )
V IC=5.3727 ft 3 x 1610
V IC=8650.047 ft 3
V T =8650.047 ft 3 + 11803.2 ft 3
V T =20453.247 ft 3
V TOTAL 20453.247 ft 3
H= =
L1 L2 78.83 ft . x 58.83 ft .
H=4.4103 ft ¿)
H=52.9236∈¿
Height of Freezing Tank > Height of Ice Can
52.9236∈¿ 44 ∈¿
DESIGN IS OKAY!
Length
L = L1 +L (insulations)
L = 946 + 2(0.25 + 15 + 6); in
L = 988.5 in = 82.375 ft. = 25.1143 m
Width
W = L2 + L (insulations)
W = 706 + 2(0.25+15+6); in
W = 748.5 in. = 62.375 ft. = 19.0168 m
Height
H = H1 + Top Cover + Insulation
H = 53 + 4 + 7 + 6
H = 70 in. = 5.8333 ft. = 1.7784 m
Q p=Q 1+Q 2 +Q 3
kg kJ
Q1= (1.2598 )( 4.187 )(26-0)° C
s kg−° C
Q1=137.144 kW
For Q3 =( mH O )( C p ) ( t f −t ice )
2 ice
kg kJ
Q3= (1.2598 )(2.0935 )(0-(-7.5))° C
s kg−° C
Q 3=19.78 kW
For Qp= Q1 + Q2 + Q3
Q p=137.144 kW + 422.033 kW +19.78 kW
Q p=578.957 kW
1TOR
Q p=578.957 kW x
3.517 kW
Q p=164.617 TOR
TOI 120TOI
≥ TOR ; ≥ Qp
0.61 0.61
For Q1 = Q2 (Considering the width and height)
A ∆t
Q 1=
1 X 1 X2 X 3 1
+ + + +
ho k 1 k 2 k 3 h1
Q1=156.31 W
Q1 = Q2 = 0.15631 KW
Q3 = Q4 = 0.20642 KW
Q5 = 27.20473 KW
65 gpm
Brine Agitator Capacity = ( 164.617TOR)
TOR
Brine Agitator Capacity = 10700.11 gpm
1 hp
Brine Agitator Power= ¿
TONS )
17.5
DAY
Brine Agitator Power=6.86 hp
Use 7 Hp Motor for Each Brine Agitator.
Blower Power:
For Low Pressure Air Agitator, Approximately 0.5 cfm of Free Air is supplied at about 2 Psi per
300 lbs. per can.
0.5 cfm ( ft 3
V air = 1610 CANS =805
)
CAN min
3
lb ¿ 2 (805 ft )
Air Power=
( )2( ¿2
144 )
ft 2 min
= 7.03 hp
ft −lb
33,000
hp−min
Assuming Blower Efficiency = 80%
Blower Efficiency = Air Power / BPH
BPH = 7.03 hp. / .80
BPH = 8.79 hp
Use 9 Hp Driving Motor for Blower of Freezing Tank.
STORAGE CAPACITY:
Product: Brine Meat
Mass Capacity of Storage = 180,000kg
Mass of Meat per Day = 2.08 Kg/S
From Design Data from Meat Storage
Product Temperature = 37.76° C
Freezing Point Temperature = -0.5° C
Recommended Temperature = -0.5° C
C p =¿ 3.14 kJ/kg-K
a
C p =¿ 1.67 kJ/kg-K
b
h f =¿ 228 kJ/kg
i
Q C =[ ( m ) ( C p ) ( ∆ t ) ] + [ ( m ) ( h f
a ice
) ] + [ ( m) ( C p ) ( ∆ t ) ]
b
Q C =¿ 724.124 kW
Storage Area :
L = 50 ft.
W = 50 ft.
H = 20 ft.
92.96(32−(−0.5))
QL =
wall
1 0.0508 0.0508 6.35 x 10−3 1
+ + + +
9.37 0.043 .72 14.3 7.95
Q L =¿2034.609 W
wall
Q L =¿2.034609 kW
wall
QL FandC
=¿3.875912 kW
Q L=Q L ( 4 ) +Q L (2)
wall fandC
Q L=2.034609 ( 4 ) +3.875912(2)
Q L=15.89026 kW
QT =Qc + QL =724.124+15.89026
Q T =740.01426 kW
Compressor:
Q P , Tons of Refrigeration = 578.957 KW
Q S , Tons of Refrigeration = 740.01426 KW
Refrigerant = Ammonia
Storage Evaporating Temperature = -6° C
Ice Evaporating Temperature = -10° C
Condenser Temperature = 43° C
W C 1=m1 ( h2 +h1 )
Qp
m 1=
h1−h 8
578.957 kW
m 1=
kJ kJ
1450.22 −172.371
kg kg
kg
m 1=0.4531
s
kg kJ kJ
W C 1=0.4531
s (
1460 −1450.22
kg kg )
W C 1=¿ 4.4313 kW
W C 2=m 4 ( h4 −h3 )
m 4 =m 3+ m2
QS
m 3=
h3−h6
740.01426 kW
m 3=
kJ kJ
1455 −405.416
kg kg
kg
m 3=0.7051
s
m 2=?
Energy Balance
E¿ =EOUT
m 2 h6 +m 1 h2 =m 1 h7 +m2 h3
m1( h7−h2)
m 2=
h6−h 3
kg kJ kJ
0.4531 (172.371 −1460 )
s kg kg
m 2=
kJ kJ
405.416 −1455
kg kg
kg
m 2=0.5559
s
kg kg
m 4 =0.7051 +0.5559
s s
kg
m 4 =1.261
s
kg kJ kJ
W C 2=1.261
s(1691 −1455
kg kg )
W C 2=297.596 kW
W CT =4.4313+297.596
W CT =302.0273 kW
302.0273(1 hp)
W CT = =404.86 hp
0.746 kW
404.86 hp
Actual Power For EachCompressor =
2
Motor Hp=202.43∨203 Hp
Condenser:
Condenser Temperature = 40° C
Entering Water Temperature = 28° C
Leaving Water Temperature = 33° C
kg
m 4 =1.261
s
kJ
(
1621.1214 kW =m w 4.187
kg−° C )
( 33−28 ) ° C
kg
m w =77.44
s
gal m3
V LR=(164.617 TOR)(0.50 )(0.003785 )
TON OF REF . gal
V LR=0.3115 m3
Evaporator:
Ice Evaporator Temperature = -12° C
Brine Temperature = -9.44°C
A Ie =379.4548 M 2
Length of Rope, LR =5 m
Total Load, W
W = 315(5) = 1575 Lbs
Ft
(
W R=1.6 D R2 ( LR ) =1.6 D R 2 ( 5 m ) 3.28
M )
= 26.24 D R2
F=Ma
(W R + W )( A )
F T −W R −W =
G
M
(0.15 −0)
(V F −V O ) S
A= =
T 10 s
M Ft
A=0.015
S 2 (
3.28
M )
Ft
A=0.0492
S2
Ft =?
Ft
(26.24 D R2 +2,075 Lbs )( 0.0492 )
S2
F T −26.24 D R2−1575 Lbs=
Ft
32.174
S2
F T =26.28 D R2 +1577.41
Static Approach
A M (DW )( EW )
F B=
DS
Where:
Fb – Equivalent Bending Load
F B=26,800 D R2
F U −F B
N=
FT
Where:
N = 7 (Design Factor)
Fu – Breaking Strength = 42 Dr2
Ft - Rope Tensile Force
lb
42 D r2 (2,000 )−26,800 Dr2
ton
7=
Ft
F t=8,171.43 D r 2
Rope Diameter, D R
26.28 D R 2+1577.41=8,171.43 D R2
8,145.15 DR 2=1577.41
1
D R=0.50∈¿ ∈.
2
Hoist Power
D S =30 D R =30 ( 0.5 )=15∈.
Π ( D S)( N S )
V=
12
Π (15)(N S)
( 0.15 ) (3.28)=
12(60)
N S =7.517 Rpm
DS
Hoist Power=2 π ( N S )( FT )( )
2
F T =8,171.43(0.5)2=2,042.86 Lbs
M W =( M W )Condenser
Kg
M W =77.44
S
Air Properties: Using Psychometric Chart
@ 26° C, 65% Rh
Kj
H 3=61 ; Hr3=0.0136
Kg
@ 32° C, 98% Rh
Kj
H 4 =108 ; Hr 4 =0.0297
Kg
Mass of Air, M A
Heat Balance on the Cooling Water,
M 1=M 2=M W And M 3=M 4 =M A
( M ¿¿ W ) ( C P ) ( T 1−T 2 )+ ( M W )( C P ) ( T 5 ) =( M A ) ( H 4 −H 3 ) ¿
W 5 W
[( M ¿¿ W ) ( C P ) ( T 1 −T 2 ) ]
M W =[ ( M A ) ( H 4 −H 3 ) ]−
W
¿
5
( C P ) (T 5)
W
MW =
[ ( M A ) ( 108−61 ) ]−[(77.44) ( 4.187 ) ( 33−28 ) ]
5
( 4.187 )( 27+ 273 )
M W =0.0374 m A −1.2907
5
M W =M A ( Hr 4 −Hr3 ) =M A (0.0297−0.0136)
5
M W =0.0161 M A
5
Therefore;
0.0374 m A −1.2907=0.0161 M A
Kg
M A =60.5962 Of Water
S
Kg
M W =0.9756 Of Water
5
S
Pv = mrt
Kg Kj
V A=
M A RA T A
=
60.5962
S (
0.287085
Kg−K )
( 26+273 ) K
PT −PV Kn
(101.325−2.186) 2
m
M3
V A =52.4666 Of Air
S
28+33 Kg
T= =30.5 ° C ; D W =996.283 3
2 m
Kg
(77.44 )(1Gal )(60 s)
M S
VW= W =
DW Kg
( 996.283 3
)(0.003785 m 3)(1 min)
m
V W =1232.1625Gpm
1232.1625 Gpm M2
Cooling Tower Area= X
3
Gpm ( 3.28)2 Ft 2
Ft 2
Area 38.1768 m 2
Width= = =7.6354 m
Length 5m
FAN:
Wheel Diameter = 60 In. = 5ft.
Static Pressure = 15 In. WATER
Total Head
H T =H V
A A
Ρ V2
HT = +
A
W 2g
m3
52.4666
Q S m
Velocity Of Air= = 2
=28.7475
A Π 2 m S
( ) ( 5 ft ) ( 2 2
)
4 3.28 Ft
m 2
( 28.7475
)
V2 S
= =41.3265 m of air
2g m
2(9.81 2 )
S
Ft M 1000 kg
(15∈. H 2 O)( )( )( 3 )
Ρ 12∈. 3.28 Ft M H 2 O
= =317.58 m
W Kg
1.2 3
M
H T =358.91 mof air
A
Fan Power
Kg N
H T (M A ) 358.91 M (60.5962 S )(9.81 Kg )
Fan Power= A
= =213.3536 Kw
FC W
1,000
Kw
1 Hp
Fan Power=213.3536 Kw X
0.746 kw
FAN POWER=285.9968 hp∨286 hp
DAY TANK:
Suction Pressure = 60kpa
Allowance for Fittings and Friction Loss = 5m
Elevation of Tank
Kn
)(1000 N )(1kg )
(60
M2
Elevation= +5 m
Kg
(1000 3 )(1 kn)(9.81 N)
M
Elevation=11.12 M
TONS 2,000 Lb 1 kg m3 m3
V 1=120 X X X =108.8435
Day TON 2.205 Lb 1,000 kg Day
Kg m3 3,600 s 24 Hrs . m3
V 2=0.9756 X X X =84.2918
S 1,000 kg 1 hr 1 Day Day
m3
V 3=20
Day
V T =V 1 +V 2+ V 3
m3
V T =(108.8435+ 84.2918+ 20)
Day
m3
V T =213.1353
day
Dimensions of Tank
Use H = 8m
Π
V T= ( D )2 ( H )
4
m 3 Π ( )2 (
213.1353 = D 8 m)
Day 4
D = 5.8242 m
Fm = 0.92 ; Fs = 0.25
SS =SU (F M )(F S )
Kn 1000 mm
78.48 (5.8242 m)( )
M 2
1m
t=
Kn Kn
( )
2 79.29 X 103 2 ( 0.80 )−78.48 2
M M
t=¿3.6052 mm
USE, t = ½ In.
Refrigerant: Ammonia
43oC
-6oC
-10oC
STANDARD ICE CAN DIMENSION
11”x22”x44”
FREEZING TANKS
FLOOR PLAN
1. Cooling Tower 9. Main Office
2. Day Tank 10. Engineering Office
3. Condenser 11. Thaw Tank
4. Compressor 12. Dump and Refill
5. Liquid Receiver 13. Ice Storage
6. Freezing Tank 14. Control Board
7. Cold Storage 15. Loading Platform
8. Tool Room