Professional Documents
Culture Documents
Installation Guide
3 Zone Mini Control
EN Panel
DS3MX-E-I | Installation Guide | 1.0 General Information EN | 2
2.0 Specifications 2
12.7 cm
Table 1: Specifications (5 in.)
3.0 Mounting
1. Mount the DS3MX in a convenient location for
operation and no higher than the shoulder height
of the shortest person operating the system.
2. Remove the chassis from the base by inserting a
small flathead screwdriver in the two slots at the
bottom of the housing. Press up while pulling the
rear chassis away from the front cover.
3.1 Wall Mount
Using the base as a guide, mark the location for the
three mounting holes and the wire/cable entry on the
wall.
4.0 Wiring
Be sure all wiring is un-powered (de-energized) before routing or connecting to the DS3MX.
1. Route all wiring for power, zone inputs, and multiplex bus through the rear chassis wire entry hole (see
Figure 1).
2. Make all necessary wire connections to the DS3MX terminals (see Figure 2).
If using as a Multiplex device, see Table 4.
6 6 6
5
2
O 1 2 3 4 5 6 7 8
N
P1 P2
P1 P2
1
1 - Address DIP switch setting
Program Description Factory Allowed Program Program Description Factory Allowed Program
Function Default Value Range Function Default Value Range
8 Zone 1 shunt 2 1 = Zone shunt 20 Panic keys 0 0 = Off
allowed 1 = On (enable)
2 = No zone shunt 21 Relay function 0 0 = Follows alarm
allowed 1 = Follows
9 Zone 2 type 4 1 = Instant unlock code
2 = Delay 22 Door unlock 0000 0000 to 9999
3 = 24-hour code (0000 = Disabled)
4 = Follower 23 Door unlock 000 000 to 999
10 Zone 2 2 1 = Bypass time (0 seconds to 999
bypass allowed seconds)
2 = No bypass 000 = disabled
allowed
11 Zone 2 shunt 2 1 = Zone shunt
allowed
2 = No zone shunt For each address, you must enter the
allowed allowable program value described in Table
12 Zone 3 type 3 1 = Instant 3. If an incorrect entry is made (not the
2 = Delay number length, only the value), you can
3 = 24-hour press [#] to clear your previous entry and
4 = Follower re-enter it again.
5 = Request to exit
5. After finishing the programming, press [*] for 3
(REX)
seconds to leave the Programming Mode. One
13 Zone 3 2 1 = Bypass
long beep and the three zones’ LEDs turn off
bypass allowed
2 = No bypass
indicating you left the Programming Mode.
allowed The DS3MX automatically exits the
14 Zone 3 shunt 2 1 = Zone shunt Programming Mode after 3 minutes if there
allowed is no activity (no key pressed).
2 = No zone shunt
allowed
15 Alarm piezo 1 0 = Off
1 = On
6.0 Zone Types
16 SS output 1 1 1 = Follows armed The DS3MX supports the following zone types and
state functions.
2 = Follows zone Instant: When the DS3MX is armed, violating an
alarm instant zone causes an immediate alarm.
17 SS output 2 1 1 = Follows fire
reset Delay: When the DS3MX is armed, violating this zone
2 = Follows zone causes an alarm after the entry or exit delay time
alarm expires.
3 = Follows door Follower: When the DS3MX is armed and the entry
unlock code
zone is violated first, a follower zone experiences the
18 Quick arm 2 1 = Quick arm on, same delay as the entry zone.
2 = Quick arm off
19 Keyswitch 1 1 = Allows arm 24-hour: Active at all times, DS3MX armed, or
input only disarmed. Any violation causes an alarm.
2 = Allows REX: Active at all times, armed, or disarmed.
arm/disarm Triggering this input activates the output programmed
to follow the unlock code and timer setting.
Bypass: If a zone is programmed to allow bypass, DS3MX devices can be powered directly from the
entering a user code, pressing the [Bypass] key, a zone DS7400Xi Aux Power Terminals. However, if
number, and the [On] key, bypasses the zone during connecting more than twelve DS3MX devices, a
this arming period. The zone bypass clears when the separate power supply(s) is needed. Each power
DS3MX is disarmed.
supply should have its 12 VDC output floating from
Shunt: If a zone is programmed for zone shunt, only ground to avoid a MUX bus fault and each should
the first zone trigger activates the DS3MX. All have its own internal battery back-up. See Figure 4 for
additional triggers during this armed period are power supply connections.
ignored. Shunt clears when the DS3MX is disarmed.
Each DS3MX must have a different address using the
DIP switch on the PCB. Follow standard DS7400Xi
7.0 Using the DS7400Xi Alarm multiplex point addressing guidelines and refer to Table
4 for the proper setting.
Control
When using the DS3MX on the DS7400Xi Multiplex
Bus, the maximum number of devices of all types is
240.
3
2
4 4
2 5 6
3
9
7 8
11
12
10
1- 12 VDC Power Supply 5- MUX – CMS-70009-
2- 12 VDC @ 2 A supply 20 pieces DS3MX 6- MUX + DS7412 10 -
3- DS3MX 7- DS7400Xi RS-232 11-
4- Up to 240 DS3MX maximum 8- DS7430/DS7436 12 -
Central monitoring
software
The DS3MX can send the following information to the DS7400Xi: arm, disarm, alarm, tamper, and trouble.
Additionally, this information can be reported from the DS7400Xi to the CMS7000
multi-panel monitoring software. Refer to the CMS7000 documents for more information.
See the following sections in the DS7400xi Reference Guide (Ver. 4+ [P/N: 40816]) for more information:
• Programming Section: Control/Communicator and Address 0419 to 0538 (requires the DS7400Xi China ROM
version 4.03a or later).
• Zone Programming Section if using a zone type of DS3MX = “6.”
If we set the DS3MX as a single point mode device, the Zone type is programmed as “0”, the same as
DS7457 Module. Only if set the DS3MX in the DS3MX expanded mode should the zone type be set to
“6”!
• Zone Function Programming Section for more information on the 24-hour zone function. The zone function of
DS3MX can only be programmed as 24-hour (value = 2), interior (value = 7), and fire zone without
verification (value = 1).
Other programming options are the same as standard device zone types.
179 ● ● ● ● ●
Table 4: continued
Table 4: continued
Zone ● = Switch On
(Point) (Closed) Zone ● = Switch On
Address 1 2 3 4 5 6 7 8 (Point) (Closed)
140 ● ● ● Address 1 2 3 4 5 6 7 8
141 ● ● ● ● 180 ● ● ● ●
142 ● ● ● ● 181 ● ● ● ● ●
143 ● ● ● ● ● 182 ● ● ● ● ●
144 ● ● 183 ● ● ● ● ● ●
145 ● ● ● 184 ● ● ● ●
146 ● ● ● 185 ● ● ● ● ●
147 ● ● ● ● 186 ● ● ● ● ●
148 ● ● ● 187 ● ● ● ● ● ●
149 ● ● ● ● 188 ● ● ● ● ●
150 ● ● ● ● 189 ● ● ● ● ● ●
151 ● ● ● ● ● 190 ● ● ● ● ● ●
152 ● ● ● 191 ● ● ● ● ● ● ●
153 ● ● ● ● 192 ● ●
154 ● ● ● ● 193 ● ● ●
155 ● ● ● ● ● 194 ● ● ●
156 ● ● ● ● 195 ● ● ● ●
157 ● ● ● ● ● 196 ● ● ●
158 ● ● ● ● ● 197 ● ● ● ●
159 ● ● ● ● ● ● 198 ● ● ● ●
160 ● ● 199 ● ● ● ● ●
161 ● ● ● 200 ● ● ●
162 ● ● ● 201 ● ● ● ●
163 ● ● ● ● 202 ● ● ● ●
164 ● ● ● 203 ● ● ● ● ●
165 ● ● ● ● 204 ● ● ● ●
166 ● ● ● ● 205 ● ● ● ● ●
167 ● ● ● ● ● 206 ● ● ● ● ●
168 ● ● ● 207 ● ● ● ● ● ●
169 ● ● ● ● 208 ● ● ●
170 ● ● ● ● 209 ● ● ● ●
171 ● ● ● ● ● 210 ● ● ● ●
172 ● ● ● ● 211 ● ● ● ● ●
173 ● ● ● ● ● 212 ● ● ● ●
174 ● ● ● ● ● 213 ● ● ● ● ●
175 ● ● ● ● ● ● 214 ● ● ● ● ●
176 ● ● ● 215 ● ● ● ● ● ●
177 ● ● ● ● 216 ● ● ● ●
178 ● ● ● ● 217 ● ● ● ● ●
218 ● ● ● ● ●
219 ● ● ● ● ● ●
Table 4: continued
Zone ● = Switch On
(Point) (Closed)
Address 1 2 3 4 5 6 7 8
220 ● ● ● ● ●
221 ● ● ● ● ● ●
222 ● ● ● ● ● ●
223 ● ● ● ● ● ● ●
224 ● ● ●
225 ● ● ● ●
226 ● ● ● ●
227 ● ● ● ● ●
228 ● ● ● ●
229 ● ● ● ● ●
230 ● ● ● ● ●
231 ● ● ● ● ● ●
232 ● ● ● ●
233 ● ● ● ● ●
234 ● ● ● ● ●
235 ● ● ● ● ● ●
236 ● ● ● ● ●
237 ● ● ● ● ● ●
238 ● ● ● ● ● ●
239 ● ● ● ● ● ● ●
240 ● ● ● ●
241 ● ● ● ● ●
242 ● ● ● ● ●
243 ● ● ● ● ● ●
244 ● ● ● ● ●
245 ● ● ● ● ● ●
246 ● ● ● ● ● ●
247 ● ● ● ● ● ● ●
248 ● ● ● ● ●
2 2 2
3
4
5 6 7