No PARAMETER REQUIREMENT
1 Type of Cooler Shell & Tube
2 No of Coolers Two Coolers in Duplex Arrangement
3 Mounting Vertical / Horizontal Mounting
4 Oil Flow Rate 300 LPM
Heat to be dissipated To be calculated
5 Medium to be cooled Lubricating oil, Oil Grade: ISO VG 46
6 Design Pressure of Shell (Oil side) 5 Kg/cm² (g)
7 Inlet Oil Temperature 60°C
8 Outlet Oil Temperature 40 °C
9 Coolant Water
10 Cooling Water Inlet Temperature 32
11 Design pressure on water side 5 Kg/cm² (g)
12 Tubes Material Admiralty Brass or SS as per Enquiry
13 Tube side fouling factor 0.0002 Hr.Sq.M.Deg.C/Kcal
14 Tubes Plugging Margin 20%
15 Pressure drop on water side < 1 kg/cm² (g)
16 Velocity of water in Tubes > 1.5 Metres/ Sec
17 Water side test pressure 1.5 x Rated water pressure
18 Oil side test pressure 1.5 x Rated Oil pressure