Manual ADMAG AXFA11


Magnetic Flowmeter
Remote Converter
PROFIBUS DP Communication Type
IM 01E20C01-20E

IM 01E20C01-20E
1st Edition
Contents
1. INTRODUCTION ....................................................................................... 3
1.1 Safe Use of This Product ....................................................................................................... 4
1.2 Warranty................................................................................................................................. 5

2. AMPLIFIER FOR PROFIBUS DP COMMUNICATION.............................. 6


3. ABOUT PROFIBUS DP............................................................................. 7
3.1 Outline ................................................................................................................................... 7
3.2 Internal Structure of ADMAG AXFA11 ................................................................................ 7
3.3 Logical Structure of Each Block ............................................................................................ 8
3.4 Wiring System Configuration ................................................................................................ 8

4. GETTING STARTED ................................................................................. 9


4.1 Connection of Devices ........................................................................................................... 9
4.2 Master Setting ...................................................................................................................... 11
4.3 Bus and ADMAG AXFA11 Power ON................................................................................ 12
4.4 Setting of Write Protect Switch............................................................................................ 13
4.5 Integration of GSD............................................................................................................... 14
4.6 Cyclic data exchange ........................................................................................................... 14

5. BLOCK Setting ....................................................................................... 15


5.1 AI Function Block Parameters ............................................................................................. 15
5.2 Transducer Block Parameters .............................................................................................. 17
5.3 Totalizer Function Block Parameters ................................................................................... 19
5.4 DI Function Block Parameters ............................................................................................. 21

6. IN-PROCESS OPERATION..................................................................... 23
6.1 Mode Transition ................................................................................................................... 23
6.2 Generation of Alarm ............................................................................................................ 23
6.2.1 Indication of Alarm................................................................................................... 23
6.2.2 Alarm and Event ....................................................................................................... 25
6.3 Simulation Function............................................................................................................. 25

7. DIAGNOSTIC INFORMATION ................................................................ 26


8. GENERAL SPECIFICATIONS................................................................. 27
APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE ADMAG
AXFA11.................................................................................................... 28
A1.1 Physical Block ..................................................................................................................... 28
A1.2 Al Function Block................................................................................................................ 30
A1.3 Totalizer Function Block...................................................................................................... 32
A1.4 Transducer Block ................................................................................................................. 34
A1.5 Discrete Input Function........................................................................................................ 37

APPENDIX 2. APPLICATION, SETTING AND CHANGE OF BASIC


PARAMETERS ........................................................................................ 38
A2.1 Applications and Selection of Basic Parameters.................................................................. 38
A2.2 Setting and Change of Basic Parameters ............................................................................. 39
A2.3 Setting the AI Function Block.............................................................................................. 40
A2.4 Setting the Transducer Block ............................................................................................... 41
A2.5 Setting the Totalizer Function Block.................................................................................... 42
A2.6 Setting the DI Function Block ............................................................................................. 43

-2- IM 01E20C01-20E
1. INTRODUCTION
This manual contains a description of the ADMAG AXFA11 Magnetic Flowmeter PROFIBUS DP Communication
Type.PROFIBUS DP communication type is similar to the BRAIN communication type in terms of basic performance
and operation. This manual describes only those topics that are required for operation of the PROFIBUS DP
communication type and that are not contained in the BRAIN communication type instruction manual. Refer to
ADMAG AXFA11 Magnetic Flowmeter instruction manual IM01E20C01-01E for topics common to the BRAIN
communication and PROFIBUS DP communication types.

■ Regarding This Manual


・ This manual should be passed on to the end user.
・ The contents of this manual are subject to change without prior notice.
・ All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
・ Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied
warranty of merchantability and fitness for a particular purpose.
・ If any question arises or errors are found, or if any information is missing from this manual, please inform the
nearest Yokogawa sales office.
・ The specifications covered by this manual are limited to those for the standard type under the specified model
number break-down and do not cover custom-made instruments.
・ Please note that changes in the specifications, construction, or component parts of the instrument may not
immediately be reflected in this manual at the time of change, provided that postponement of revisions will not
cause difficulty to the user from a functional or performance standpoint.
・ The following safety symbols are used in this manual:

WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It
may also be used to alert against unsafe practices.

IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.

NOTE
Draws attention to information essential for understanding the operation and features.

-3- IM 01E20C01-20E
1.1 Safe Use of This Product
For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety
instructions when handling this instrument. If these instructions are not heeded, the protection provided by this
instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please
pay special attention to the following points:

(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device.
Operators are not allowed to carry out installation unless they meet this condition.
• With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.
• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden,
explosive release of process fluids.
• When draining condensate from the pressure detector section, take appropriate precautions to prevent the
inhalation of harmful vapors and the contact of toxic process fluids with the skin or eyes.
• When removing the instrument from a hazardous process, avoid contact with the process fluid and the interior of
the meter.
• All installation work shall comply with local installation requirements and the local electrical code.

(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument.
Operators are not permitted to carry out wiring unless they meet this condition.
• Before connecting the power cables, please confirm that there is no current flowing through the cables and that
the power supply to the instrument is switched off.

(c) Operation
• Wait 5 min. after the power is turned off, before opening the covers.

(d) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require further assistance,
please contact the nearest Yokogawa office.
• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate.
To clean these surfaces, use a soft, dry cloth.

(e) Explosion Protected Type Instrument


• User of explosion proof instruments should refer first to section 2.1 (Installation of an Explosion Protected
Instrument) of this manual.
• The use of this instrument is restricted to those who have received appropriate training in the device.
• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.

(f) Modification
• Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument
by the customer.

-4- IM 01E20C01-20E
1.2 Warranty
・ The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase.
Problems occurring during the warranty period shall basically be repaired free of charge.
・ If any problems are experienced with this instrument, the customer should contact the Yokogawa representative
from which this instrument was purchased or the nearest Yokogawa office.
・ If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under
which it developed, including the model specification and serial number. Any diagrams, data and other information
you can include in your communication will also be helpful.
・ The party responsible for the cost of fixing the problem shall be determined by Yokogawa following an
investigation conducted by Yokogawa.
・ The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is
due to:
- Improper and/or inadequate maintenance by the purchaser.
- Malfunction or damage due to a failure to handle, use, or store the instrument in accordance with the design
specifications.
- Use of the product in question in a location not conforming to the standards specified by Yokogawa, or due to
improper maintenance of the installation location.
- Failure or damage due to modification or repair by any party except Yokogawa or an approved representative of
Yokogawa.
- Malfunction or damage from improper relocation of the product in question after delivery.
- Reason of force majeure such as fires, earthquakes, storms/floods, thunder/lightening, or other natural disasters, or
disturbances, riots, warfare, or radioactive contamination.

-5- IM 01E20C01-20E
2. AMPLIFIER FOR PROFIBUS DP
COMMUNICATION
Refer to the instruction manual for detailed descriptions of the parts. This section describes the topics applicable to the
PROFIBUS DP communication type.
(1) In the PROFIBUS DP communication type, there are no local key access function.
(2) ADMAG AXFA11 adjusting using AM012 calibrator must be done on off-line.

-6- IM 01E20C01-20E
3. ABOUT PROFIBUS DP
3.1 Outline
In addition to the AXFA11 magnetic flowmeter high grade remote converter which is a sophisticated product with
outstanding reliability and ease of operation, developed on the basis of decades of field-proven experience.
PROFIBUS DP is the international standards IEC61158 and IEC61784 and is a manufacturer-independent PROFIBUS
DP for applications in manufacturing, factory automation.
The enhanced functions of PROFIBUS DP/V1 are required to set parameters not only cyclically but also non-cyclically
and operate the system.
The combination of a replaceable electrode type flowtube and diagnostics to detect the adhesion level on the electrodes
dramatically improves maintainability.
The AXFA11 also employs the fluid noise free “Dual Frequency Excitation Method” and the newly added “Enhanced
Dual Frequency Excitation Method” as an option for more severe applications to ensure higher stability and quicker
response.

Note: The “Dual Frequency Excitation Method” is Yokogawa’s unique technology.

PROFIBUS is registered trademark of PROFIBUS Nutzerorganisation e.V., Karlsruhe, Germany.

3.2 Internal Structure of ADMAG AXFA11


ADMAG AXFA11 contains three function blocks which are implemented in accordance with Profile3.0.

(1) Physical block


• Manages the status of ADMAG AXFA11 hardware.
• Automatically informs the host of any detected faults or other problems.
(2) Transducer block
• Converts sensor output to flow rate signal and transfers to AI function block.
(3) AI function block
• Conditions raw data from the Transducer block.
• Outputs flow rate signals.
• Carries out scaling extraction.
(4) Totalizer function block
• Totalization of raw data from the Transducer block.
(5) DI function block
• Conditions discrete data from the Transducer block.

-7- IM 01E20C01-20E
3.3 Logical Structure of Each Block

ADMAG AXFA11 PROFIBUS DP

Device Management

Physical Block

AI Function Block
Output

Totalizer Function
Totalized value
Sensor Block 1
input
Totalizer Function
Transducer Block Totalized value
Sensor

Block 2

Totalizer Function
Totalized value
Block 3

DI Function Block 1 Discrete Output

DI Function Block 2 Discrete Output

Figure 3.1 Logical Structure of Each Block

Setting of various parameters and station addresses shown in Figure 3.1 is required before starting operation.

3.4 Wiring System Configuration


The number of devices that can be connected to a single bus and the cable length vary depending on system design.
When constructing systems, both the basic and overall design must be carefully considered to allow device performance
to be fully exhibited.

-8- IM 01E20C01-20E
4. GETTING STARTED
PROFIBUS DP is fully dependent upon digital communication protocol and differs in operation from conventional 4 to
20 mA transmission and the BRAIN communication protocol. It is recommended that novice users use PROFIBUS DP
devices in accordance with the procedures described in this section. The procedures assume that fieldbus devices will
be set up on a bench of an instrument shop.

4.1 Connection of Devices


The following instruments are required for use with PROFIBUS DP devices:

• Terminator:
PROFIBUS DP requires two terminators at the end of the segment.
Built-in terminator
ADMAG AXFA11 builds in the terminator for PROFIBUS communication. In order to confirm a built-in
terminator, SW2 slide switch is turned ON like the above-mentioned figure 5.1.

SW3

ADDRESS

SW3
SW1

O
N
Connector

WRITE_PROTECT
SIMULATE
2

1
20
2

O
N
19
1
SW1
CN4

SW2

TERMINATOR
2

1
O
N

SW2

SW2 SW2

OFF OFF
TERMINATOR

TERMINATOR
2

1
O

O
N

ON ON

Figure 4.1 Switch Configuration


• Segment Coupler:
PROFIBUS DP requires the segment coupler which adopts to the RS-485 signals to the IEC 61158-2 signal level.

• Field devices:
Connect PROFIBUS DP communication type ADMAG AXFA11. Two or more ADMAG AXFA11 devices or other
devices can be connected. Refer to Figure 4.1 Terminal Connection for ADMAG AXF.

-9- IM 01E20C01-20E
Remote Type Converter (AXFA11):

Terminal Symbols Description Terminal Symbols Description


SB EX2
EXCITATION Excitation current output
B EX1
SIGNAL A Flow signal input
L /+
SA POWER SUPPLY Power supply
N/-
C
Functional grounding
DP2+ Profibus communication
DP2- signal Protective grounding
PROFIBUS (Outside of the terminal)
DP1+ DP1+, DP2+ : B (RXD/TXD-P)
DP1- DP1-, DP2- : A (RXD/TXD-N)
DGND
TERMINATOR Terminator
5V

Figure 4.2 Terminal connection for ADMAG AXFA11

The power supply output for external terminators


The power supply for external terminators is provided. Terminal names are 5V and DGND. Since 10mA
is rating, please do not use current capacity other than the object for external terminators.

• Master:
Used for accessing field devices. A dedicated master (such as DCS or PLC) is used for an instrumentation line while
dedicated communication tools are used for experimental purposes. For operation of the master, refer to the
instruction manual for each master. No details of the master are explained in the rest of this material.
• Cable:
EN 50 170 specifies two types of bus cable. For transmission rates up to 1.5 Mbit/s, cable type A is recommended.
For ADMAG AXFA11, use an M4 screw terminal. Some hosts require a connector.

Connect the devices as shown in Figure 4.2. Connect the terminators at both ends of the trunk, with a minimum length
of the spur laid for connection.
The polarity of signal must be maintained.

Class 1 Class 2
master master
PC
PLC

PROFIBUS-DP

PROFIBUS-DP slaves

Figure 4.3 Device Connection

- 10 - IM 01E20C01-20E
4.2 Master Setting
To activate PROFIBUS DP, the following bus parameters settings are required for the master.

IMPORTANT
Do not turn the power OFF immediately after parameter setting. When the parameters are saved to the
EEPROM, the redundant processing is executed for the improvement of reliability. If the power is turned
OFF within 60 seconds after setting of parameters, changed parameters are not saved and may return to
their original values.
When the consecutive parameter setting to the multiple parameters is not executed via the acyclic data
exchange, the time inverval between each parameter setting must not be within 2 seconds.
Changed parameters may not be written to the device.

Table 4.1 Bus Parameters

Symbol Parameter Description and Settings


transmission rate Transmission Rate The transmission rate of AXFA11 DP up to 1.5Mbps.
The maximum time a master station must wait for the complete
TSL Slot Time
reception of the first octet of a response (11 bits).
This is the quickest time a slave can send the first bit of a
min TSDR Min. Station Delay Timer
response back.
This is the quickest time a slave can send the first bit of a
max TSDR Max. Station Delay Time
response back.
Quiet Time controls the time when the bus electronics or software
TQUI Quiet Time of the sender are set to receive mode after a message has been
sent.
Setup Time is the waiting time which is started before a message
TSET Setup Time
is sent.
HSA Highest Station Address HSA set the highest station address in the network.
Gap update factor is set after how many token cycles the master
G Gap update factor
will search for a new master.
Max Retry Limit sets the number of retries which are taken when a
max. retry limit Max Retry Limit
receiver does not respond to a message.

- 11 - IM 01E20C01-20E
4.3 Bus and ADMAG AXFA11 Power ON
Turn on the power of the host, and ADMAG AXFA11.
Using the host device display function, check that the ADMAG AXFA11 is in operation on the bus. Unless otherwise
specified, the following settings are in effect when shipped from the factory.
bus address: 126 (hexadecimal 7E)

If no ADMAG AXFA11 is detected, check the available address range. If the bus address is not specified when
ordering, default value is factory set. If two or more ADMAG AXFA11s are connected at a time with default value,
only one ADMAG AXFA11 might be detected from master as ADMAG AXFA11s have the same initial address.
Separately connect each ADMAG AXFA11 and set a different address for each.

Address setting switch


A setup of bus address is possible by the change with a parameter, or the hardware slide switch.
In case of setting up with a parameter, the No. 8 switch of SW3 (below figure) is turned OFF first.
It sets up in SET_ADDRESS (Physical Block). Setting ranges are 0-126. In order to set up the
bus address by the hardware slide switches, the No. 8 switch of SW3 (below figure) is turned ON
first. Other seven switches of No.1 to No.7 on the SW3 are for setting address. No.1 switch of
SW3 is allocated for bit0 of address, and No.7 switch of SW3 is allocated for bit6 of address. The
below figure shows an example that the address setting of the hardware slide switch is effective,
and the address number sets 3.

ADDRESS

OFF
8
7
6
5
4
3
2
1

SW3
N
O

ON

MSB LSB
8 7 6 5 4 3 2 1
ON OFF OFF OFF OFF OFF ON ON
Figure 4.4 Address Switch

- 12 - IM 01E20C01-20E
4.4 Setting of Write Protect Switch
A write protection is a function to forbid changing of parameters. It is possible to set the software write protection by
parameter setup or the hardware write protection by the hardware slide switch. In case of the setting up by parameters, it
can set up in WRITE_LOCKING. When WRITE_LOCKING is “0: Lock”, the status of write protect becomes protected
mode. And when WRITE_LOCKING is “2457: Disabled”, the status becomes disable mode.
In case of the setting up by hardware switch, it can set up in No.1 switch of SW1. When the switch is turned on, the
status becomes protected mode, and when the switch is turned off, the status becomes disable mode. The state of the
hardware write-protection switch can be checked with the parameter "HW_WRITE_PROTECTION." As the
mentioned above, write protection is available by the setting either of software protection or hardware protection, one of
them is set to protect mode, the status becomes protected mode.

Table 4.2 Write Protect

Setting of Displaying of Setting of State of Protect


Hardware Write Protect SW HW_WRITE_PROTECTION WRITE_LOCKING Protect State

Enable 0:Unprotected 0: Lock Protect


Enable 0:Unprotected 2457: Disabled Enable
Protect 1:Protected 0: Lock Protect
Protect 1:Protected 2457: Disabled Protect
WRITE_PROTECT

OFF OFF WRITE_PROTECT


2
1

2
1
SIMULATE

SIMULATE
N
O

N
O

ON ON

SW1 SW1
Figure 4.5 Write Protect Switch

- 13 - IM 01E20C01-20E
4.5 Integration of GSD
PROFIBUS DP system requires GSD file which describes the device parameters such as the transmission rate
supported, input, output data, data format and data length.

The following GSD files in the following table are available to ADMAG AXFA11.

Table 4.3 GSD files

Profile Ident-Number 0x9740


Profile GSD file PA139740.GSD (AIx1, TOTx1)
Device Specific Ident-Number 0x084D
Device Specific GSD file YEC_084D.GSD

4.6 Cyclic data exchange


To send the volume flow or totalized value or to set the control variables for totalizer function block cyclically, the
cyclic data exchange service must be set. ADMAG AXFA11 transmits the following measured values on the cyclic data
exchange service.

Table 4.4 Cyclic data exchange

Parameter Input/Output Description


OUT(AI) Input Volumetric flow
TOTAL(TOT) Input Totalized value
Output Reset the initial value of the algorithm to zero or set this value to
PRESET to PRESET_TOT. The following selection are possible.
SET_TOT(TOT) 0: TOTALIZE
1: RESET
2: PRESET
Output Select the behavior of the totalization. The following selection are
possible.
0: BALANCED
MODE_TOT(TOT)
1: POS_ONLY
2: NEG_ONLY
3: HOLD
Input Set the status signal to LIMSW_1_TARGET and
LIMSW_2_TARGET in the transducer block respectively.
These status signal selected from the followings are reflected to
OUT_D.
OUT_D(DI)
0:H/L Alarm
1:HH/LL Alarm
2:Adhesion Alarm
3:Adhesion Warning
ZERO_POINT_ADJUST(TRA) Output Execute Auto Zero function.
SIGNAL_LOCK(TRA) Output Execute Signal Lock function.

- 14 - IM 01E20C01-20E
5. BLOCK Setting
This chapter contains information on how to adapt the function and performance of the ADMAG AXFA11 to suit
specific applications. Because two or more devices are connected to PROFIBUS DP, settings including the
requirements of all devices need to be determined. Practically, the following steps must be taken.
The following section describes each step of the procedure in the order given. Using a dedicated configuration tool
allows the procedure to be significantly simplified. This section describes the procedure to be assigned for a master
which has relatively simple functions.

5.1 AI Function Block Parameters


AI Function block parameters can be read or set from the host. For a list of the parameters of blocks held by the
ADMAG AXFA11, refer to "List of parameters for each block of the ADMAG AXFA11" in Appendix 1. The
following is a list of important parameters with a guide how to set them.
TARGET_MODE, MODE_BLK:
Indicates the three types of function block modes; Out_Of_Service, Manual, and Auto. TARGET_MODE indicates
what mode of operation is desired for AI Function block. In Out_Of_Service mode, the AI block does not operate.
The Manual mode does not allow values to be updated. The Auto mode causes the measured value to be updated.
Under normal circumstances, set the Auto mode to take effect. The Auto mode is the factory default.
CHANNEL:
This is the parameter of the transducer block to be input to the AI block. AI block is assigned flow rate.
OUT:
This parameter contains the current measurement value from Transducer Block or configuration adjusted engineering
unit and the belonging state in AUTO MODE. OUT contains the value and status set by an operator in MAN MODE.
Quality
Sub-status (bit 2-5) Limit (bit 0-1) Alarm Value
(bit 6-7)
2:Good (NC) Ok 0:Not limited
Update Event 1:low limited
Active Advisory Alarm 2:high limited
Active Critical Alarm 3:constant
Unack. Update Event
Unack. Advisory Alarm
Unack. Critical Alarm
9:Maintenance required 0:Not limited 80:Adhesion Wng
0xA4
81:Insu-Brk Wng(Reserved)
1:Uncertain 0:Non specific 0:Not limited 56:H/L HH/LL Set *1
73:Adh Set Err
0x40
74:Flow Limit Set(Reserved)
82:Auto Zero Wng
1:low limited or 85:Flow Vel Over 0x41
2:high limited 0x42
8:Simulated Value 0:Not limited 91:AI Sim. enabled 0x60
0:Bad 0:Non specific 3:constant 46:TB O/S Mode
50:Span > 10m/s
51:Span < 0.1m/s
56:H/L HH/LL Set *2
0x03
57:Dens Set Err
71:Meas Mod Set
72:Size Set Err
73:Adh Set Err
3:Device Failure 3:constant 10:uP Fault
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault 0x0F
16:EEPROM Dflt
17:Comm uP Fault
18:Comm EEPROM Fault
19:I/F Module Fault
0:Bad 4:Sensor Failure 3:constant 15:Coil Open
30:Sig Overflow
31:Empty Pipe 0x13
33:Adhesion Alm
34:Insulation Alm(Reserved)
7:Out of Service 3:constant 41:PB O/S Mode
0x1F
42:AI FB O/S Mode
*1: In case of the vale of (5,88):ALM_SETTING is No.
*2: In case of the vale of (5,88):ALM_SETTING is Yes.

- 15 - IM 01E20C01-20E
PV_SCALE:
Scale of input from the transducer block. The engineering unit of PV_SCALE high and low scale values are direct
related to the VOLUME_FLOW_UNIT of the Transducer block. Changing the unit (can be set only in flow rate)
also causes the unit within the transducer block to be automatically changed. (The unit is automatically changed
according to the unit selected by AI.)
OUT_SCALE:
Sets the range of output (from 0% to 100%). Available units for OUT_SCALE are the after-mentioned units for
VOLUME_FLOW_UNIT and the units shown below.
Table 5.1 OUT_FLOW_UNIT
d h min s
%(1342)
Ml/d(1355) Ml/h(1522) Ml/min(1521)
m3/d(1350) m3/h(1349) m3/min(1348) m3/s(1347)
kL/d(1520) kL/h(1519) kL/min(1518) kL/s(1523)
L/d(1354) L/h(1353) L/min(1352) L/s(1351)
cm3/d(1514) cm3/h(1513) cm3/min(1512) cm3/s(1511)
m/s(1061)
t/d(1329) t/h(1328) t/min(1327) t/s(1326)
kg/d(1325) kg/h(1324) kg/min(1323) kg/s(1322)
g/d(1321) g/h(1320) g/min(1319) g/s(1318)
kft3/d(1527) kCFH(1526) kCFM(1525) kCFS(1524)
ft3/d(1359) CFH(1358) CFM(1357) CFS(1356)
mft3/d(1531) mCFH(1530) mCFM(1529) mCFS(1528)
Mgal(US)/d(1366) Mgal(US)/h(1459) Mgal(US)/min(1455) Mgal(US)/s(1451)
kgal(US)/d(1462) kgal(US)/h(1458) kgal(US)/min(1454) kgal(US)/s(1450)
gal(US)/d(1365) gal(US)/h(1364) GPM(1363) gal(US)/s(1362)
mgal(US)/d(1461) mgal(US)/h(1457) mgal(US)/min(1453) mgal(US)/s(1449)
kbbl(US Oil)/d(1493) kbbl(US Oil)/h(1489) kbbl(US Oil)/min(1485) kbbl(US Oil)/s(1481)
bbl(US Oil)/d(1374) bbl(US Oil)/h(1373) bbl(US Oil)/min(1372) bbl(US Oil)/s(1371)
mbbl(US Oil)/d(1492) mbbl(US Oil)/h(1488) mbbl(US Oil)/min(1484) mbbl(US Oil)/s(1480)
ubbl(US Oil)/d(1491) ubbl(US Oil)/h(1487) ubbl(US Oil)/min(1483) ubbl(US Oil)/s(1479)
kbbl(US Beer)/d(1534) kbbl(US Beer)/h(1533) kbbl(US Beer)/min(1532)
bbl(US Beer)/d(1538) bbl(US Beer)/h(1537) bbl(US Beer)/min(1536) bbl(US Beer)/s(1535)
mbbl(US Beer)/d(1542) mbbl(US Beer)/h(1541) mbbl(US Beer)/min(1540) mbbl(US Beer)/s(1539)
ubbl(US Beer)/min(1544) ubbl(US Beer)/s(1543)
ft/s(1067)
klb(US)/d(1548) klb(US)/h(1547) klb(US)/min(1546) klb(US)/s(1545)
lb(US)/d(1333) lb(US)/h(1332) lb(US)/min(1331) lb(US)/s(1330)
STON/d(1337) STON/h(1336) STON/min(1335) STON/s(1334)
LTON/d(1341) LTON/h(1340) LTON/min(1339) LTON/s(1338)
MImpGal/d(1478) MImpGal/h(1474) MImpGal/min(1470) MImpGal/s(1466)
kImpGal/d(1477) kImpGal/h(1473) kImpGal/min(1469) kImpGal/s(1465)
ImpGal/d(1370) ImpGal/h(1369) ImpGal/min(1368) ImpGal/s(1367)
mImpGal/d(1476) mImpGal/h(1472) mImpGal/min(1468) mImpGal/s(1464)
If “1995” is set to OUT_SCALE.UnitsIndex, the contents in OUT_UNIT_TEXT is indicated on the display.

PV_FTIME:
Sets the time constant of the damping function within AI block (primary delay) in seconds.
FSAFE_TYPE:
This is the parameter which defines the operation of the function block if a fault is detected.
0: The value of FSAFE_VALUE is used as OUT. Status – Uncertain Initial Value
1: The last valid OUT value is used. Status – Uncertain LastUsableValue, if there is no valid value
available, then Uncertain Initial Value
2: OUT has the wrong calculated value and status. Status – Bad Sensor Failure
FSAFE_VALUE:
This is the parameter which sets the default value for the OUT parameter, if sensor or sensor electric fault is
detected.
15: Coil Open
16: EEPROM Dflt
31: Empty Pipe
33: Adhesion Alm
46: TB O/S mode

- 16 - IM 01E20C01-20E
5.2 Transducer Block Parameters
The transducer block sets functions specific to the flow rate measurement of the ADMAG AXFA11. For a list of the
parameters of each block of the ADMAG AXFA11, refer to “List of parameters for each block of the ADMAG
AXFA11” in Appendix 1. The following is a list of important parameters with a guide to how to set them.

NOMINAL_SIZE:
Sets the size of the flow tube.
NOMINAL_SIZE_UNIT:
Sets the unit of the flow tube size.
LOW_MF:
Sets the meter factor of low frequency side.
HIGH_MF:
Sets the meter factor of high frequency side.
LOW_MF(EDF):
Sets the meter factor of low frequency side under enhanced dual frequency mode.
HIGH_MF(EDF):
Sets the meter factor of high frequency side under enhanced dual frequency mode.
VOLUME_FLOW_UNIT:
Units which can be set by PV_SCALE are shown below.

Table 5.2 VOLUME_FLOW_UNIT


d h min s
Ml/d(1355) Ml/h(1522) Ml/min(1521)
m3/d(1350) m3/h(1349) m3/min(1348) m3/s(1347)
kL/d(1520) kL/h(1519) kL/min(1518) kL/s(1523)
L/d(1354) L/h(1353) L/min(1352) L/s(1351)
cm3/d(1514) cm3/h(1513) cm3/min(1512) cm3/s(1511)
m/s(1061)
t/d(1329) t/h(1328) t/min(1327) t/s(1326)
kg/d(1325) kg/h(1324) kg/min(1323) kg/s(1322)
g/d(1321) g/h(1320) g/min(1319) g/s(1318)
kft3/d(1527) kCFH(1526) kCFM(1525) kCFS(1524)
ft3/d(1359) CFH(1358) CFM(1357) CFS(1356)
mft3/d(1531) mCFH(1530) mCFM(1529) mCFS(1528)
Mgal/d(1366) Mgal/h(1459) Mgal/min(1455) Mgal/s(1451)
kgal/d(1462) kgal/h(1458) kgal/min(1454) kgal/s(1450)
gal/d(1365) gal/h(1364) GPM(1363) gal/s(1362)
mgal/d(1461) mgal/h(1457) mgal/min(1453) mgal/s(1449)
kbbl/d(1493) kbbl/h(1489) kbbl/min(1485) kbbl/s(1481)
bbl/d(1374) bbl/h(1373) bbl/min(1372) bbl/s(1371)
mbbl/d(1492) mbbl/h(1488) mbbl/min(1484) mbbl/s(1480)
ubbl/d(1491) ubbl/h(1487) ubbl/min(1483) ubbl/s(1479)
kbbl/d(1534) kbbl/h(1533) kbbl/min(1532)
bbl/d(1538) bbl/h(1537) bbl/min(1536) bbl/s(1535)
mbbl/d(1542) mbbl/h(1541) mbbl/min(1540) mbbl/s(1539)
ubbl/min(1544) ubbl/s(1543)
ft/s(1067)
klb/d(1548) klb/h(1547) klb/min(1546) klb/s(1545)
lb/d(1333) lb/h(1332) lb/min(1331) lb/s(1330)

VOLUME_FLOW_FTIME:
Sets output time constants. Setting range is 0.1 to 200sec. “ 3sec.” is factory set.
LOW_FLOW_CUTOFF:
Sets low cut range for output. Setting range is 0 to 10%. “ 0%” is factory set. The larger absolute value between
Array1 and Array2 is used for the scale.

- 17 - IM 01E20C01-20E
DISPLAY_SELECT1,2,3:
DISPLAY_SELECT 1 DISPLAY_SELECT 2 DISPLAY_SELECT 3
The display content for the display unit’s The display content for the display unit’s The display content for the display unit’s
first line. second line. third line.

0:Flow Rate(%) 0:Off 0:Off


1:Out Value 1:Flow Rate(%) 1:Flow Rate(%)
2:Totalized Flow Rate1 2:Out Value 2:Out Value
3:Totalized Flow Rate2 3:Flow Rate(Bar) 3:Flow Rate(Bar)
4:Totalized Flow Rate3 4:Totalized Flow Rate1 4:Totalized Flow Rate1
5:Totalized Flow Rate2 5:Totalized Flow Rate2
The factory default setting is 1. 6:Totalized Flow Rate3 6:Totalized Flow Rate3
7:Tag No 7:Tag No
8:Adhesion Check 8:Adhesion Check
9:Communication 9:Communication

The factory default setting is 0. The factory default setting is 0.

DISPLAY_CYCLE:
Sets the cycle of LCD display. The display cycle is 200ms * (setting). The factory default setting is 1, but if a low
temperature environment makes it difficult to view the display, it is recommended that you set a longer display
cycle.
VOLUME_FLOW:
Indicates the current measured value and status as the primary value (volumetric flow) This parameter is input to the
AI Function Block and the Totalizer Function Block.
This parameter contains the current measurement value from Transducer Block or configuration adjusted
engineering unit and the belonging state in AUTO MODE. OUT contains the value and status set by an operator in
MAN MODE.

Quality
Sub-status (bit 2-5) Limit (bit 0-1) Alarm
(bit 6-7)
2:Good (NC) 0:Ok 0:Not limited Normal condition
1:Update Event
9:Maintenance required 0:Not limited 80:Adhesion Wng
0xA4
81:Insu-Brk Wng(Reserved)
1:Uncertain 4:Sensor Conversion Not 1:low limited or 85:Flow Vel Over 0x49
Accurate 2:high limited 0x4A
5:Engineering Unit Violation 3:constant
7:Configuration Error 0:Not limited 56:H/L HH/LL Set *1
73:Adh Set Err
0x5C
74:Flow Limit Set(Reserved)
82:Auto Zero Wng
0:Bad 0:Non specific 3:constant 41:PB O/S Mode 0x03
1:Configuration Error 3:constant 50:Span > 10m/s
51:Span < 0.1m/s
56:H/L HH/LL Set *2
57:Dens Set Err 0x07
71:Meas Mod Set
72:Size Set Err
73:Adh Set Err
3:Device Failure 3:constant 10:uP Fault
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault 0x0F
16:EEPROM Dflt
17:Comm uP Fault
18:Comm EEPROM Fault
19:I/F Module Fault
4:Sensor Failure 3:constant 15:Coil Open
30:Sig Overflow
31:Empty Pipe 0x13
33:Adhesion Alm
34:Insulation Alm(Reserved)
7:Out of Service 3:constant 46:TB O/S Mode 0x1F
*1: In case of the vale of (5,88):ALM_SETTING is No.
*2: In case of the vale of (5,88):ALM_SETTING is Yes.

- 18 - IM 01E20C01-20E
5.3 Totalizer Function Block Parameters
Totalizer Function block parameters can be read or set from the host. ADMAG AXFA11 contains three Totalizer
function blocks. For a list of the parameters of blocks held by the ADMAG AXFA11, refer to "List of parameters for
each block of the ADMAG AXFA11" in Appendix 1. The following is a list of important parameters with a guide to
how to set them.

TARGET_MODE, MODE_BLK:
Indicates the three types of function block modes; Out_Of_Service, Manual, and Auto. TARGET_MODE indicates
what mode of operation is desired for Totalizer Function block. In Out_Of_Service mode, the AI block does not
operate. The Manual mode does not allow values to be updated. The Auto mode causes the measured value to be
updated. Under normal circumstances, set the Auto mode to take effect. The Auto mode is the factory default.
CHANNEL:
This is the parameter of the transducer block to be input to the Totalizer block. Totalizer block is assigned to flow
rate.
UNIT_TOT:
This is the parameter of the unit of the totalized value coming from the transducer block. Totalizer function block
doesn’t have the scaling which is similar to AI Function Block.
Available units for UNIT_TOT are the units shown below.

1549:Ml, 1034:m3 , 1035:dm3, 1550:kL, 1041:hL, 1038:L, 1040:mL,1036:cm3, 1092:t, 1091:Mg, 1088:kg, 1089:g,
1090:mg, 1043:CF, 1048:gallon, 1051:bbl, 1094:lb
FAIL_TOT:
This is the parameter which defines the fail safe mode of the Totalizer function block. This parameter determines the
operation of the Totalizer function block during the occurrence of input values with bas status.
0: RUN – Totalization is continued using the input values despite the bad status. The status is ignored.
1: HOLD – Totalization is stopped during occurrence of bad status of input values.
2: MEMORY – Totalization is continued based on the last input value with good status before the
first occurrence of bad status.

MODE_TOT:
This is the parameter which defines the direction of the totalization.
0: BALANCED – Forward and reverse measured value are counted up.
1: POS_ONLY – Forward measured value are only counted up.
2: NEG_ONLY – Reverse measured value are only counted up.
3: HOLD – Totalizer is stopped.
SET_TOT, PRESET_TOT:
SET_TOT is the parameter in order to reset TOTAL value to zero or preset to the specific value.
0: TOTAILIZE – Start the totalization.
1: RESET – Reset TOTAL value to zero.
2: PRESET – Set TOTAL value to the value set to PRESET_TOT.

- 19 - IM 01E20C01-20E
TOTAL:
This parameter contains the integrated quantity of the rate parameter provided by CHANNEL and the associated
status.
This parameter contains the current measurement value from Transducer Block or configuration adjusted
engineering unit and the belonging state in AUTO MODE. OUT contains the value and status set by an operator in
MAN MODE.

Quality
Sub-status (bit 2-5) Limit (bit 0-1) Alarm Value
(bit 6-7)
2:Good (NC) Ok 0:Not limited
Update Event 1:low limited
Active Advisory Alarm 2:high limited
Active Critical Alarm 3:constant
Unack. Update Event
Unack. Advisory Alarm
Unack. Critical Alarm
9:Maintenance required 0:Not limited 80:Adhesion Wng
0xA4
81:Insu-Brk Wng(Reserved)
1:Uncertain 0:Non specific 0:Not limited 56:H/L HH/LL Set *1
73:Adh Set Err
0x40
74:Flow Limit Set(Reserved)
82:Auto Zero Wng
1:low limited or 85:Flow Vel Over 0x41
2:high limited 0x42
5:Engineering Unit Violation 3:constant
0:Bad 0:Non specific 3:constant 46:TB O/S Mode
50:Span > 10m/s
51:Span < 0.1m/s
56:H/L HH/LL Set *2
0x03
57:Dens Set Err
71:Meas Mod Set
72:Size Set Err
73:Adh Set Err
1:Configuration Error 3:constant 75:Unit Set Err
3:Device Failure 3:constant 10:uP Fault
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault 0x0F
16:EEPROM Dflt
17:Comm uP Fault
18:Comm EEPROM Fault
19:I/F Module Fault
4:Sensor Failure 3:constant 15:Coil Open
30:Sig Overflow
31:Empty Pipe 0x13
33:Adhesion Alm
34:Insulation Alm(Reserved)
7:Out of Service 3:constant 41:PB O/S Mode
43:Total1 FB O/S Mode
0x1F
44:Total2 FB O/S Mode
45:Total3 FB O/S Mode
*1: In case of the vale of (5,88):ALM_SETTING is No.
*2: In case of the vale of (5,88):ALM_SETTING is Yes.

- 20 - IM 01E20C01-20E
5.4 DI Function Block Parameters
DI Function block parameters can be read or set from the host. ADMAG AXFA11 contains two DI function blocks,
which individually transfer the “HH/LL Alarm” and “Adhesion Alarm” generated by the transducer block. For a list of
the parameters of blocks held by the ADMAG AXFA11, refer to "List of parameters for each block of the ADMAG
AXFA11" in Appendix 1. The following is a list of important parameters with a guide to how to set them.

TARGET_MODE, MODE_BLK:
Indicates the three types of function block modes; Out_Of_Service, Manual, and Auto. TARGET_MODE indicates
what mode of operation is desired for Totalizer Function block. In Out_Of_Service mode, the AI block does not
operate. The Manual mode does not allow values to be updated. The Auto mode causes the measured value to be
updated. Under normal circumstances, set the Auto mode to take effect. The Auto mode is the factory default.
CHANNEL:
This is the parameter to specify the value of the transducer block to be input to the DI block. Each DI block is
assigned to either “HH/LL Alarm” or “Adhesion Alarm”.
INVERT:
This is the parameter which indicates whether the input value from the transducer block should be logically inverted
before it is stored in the OUT_D.
0: Not inverted
1:invert
FSAFE_TYPE:
This is the parameter which defines the operation of the function block if a fault is detected.
0: The value of FSAFE_VAL_D is used as OUT_D. Status – Uncertain Initial Value
1: The last valid OUT_D value is used. Status – Uncertain LastUsableValue, if there is no valid value
available, then Uncertain Initial Value
2: OUT_D has the wrong calculated value and status. Status – Bad Sensor Failure
FSAFE_VAL_D:
This is the parameter which sets the default value for the OUT_D parameter, if sensor or sensor electric fault is
detected.
15: Coil Open
16: EEPROM Dflt
31: Empty Pipe
33: Adhesion Alm
46: TB O/S mode

- 21 - IM 01E20C01-20E
OUT_D:
This parameter contains the current measurement value from Transducer Block or configuration adjusted
engineering unit and the belonging state in AUTO MODE.
OUT contains the value and status set by an operator in MAN MODE.

Quality
Sub-status (bit 2-5) Limit (bit 0-1) Alarm Value
(bit 6-7)
2:Good (NC) Ok 0:Not limited
Update Event 1:low limited
Active Advisory Alarm 2:high limited
Active Critical Alarm 3:constant
Unack. Update Event
Unack. Advisory Alarm
Unack. Critical Alarm
9:Maintenance required 0:Not limited 80:Adhesion Wng
0xA4
81:Insu-Brk Wng(Reserved)
1:Uncertain 0:Non specific 0:Not limited 56:H/L HH/LL Set *1
73:Adh Set Err
0x40
74:Flow Limit Set(Reserved)
82:Auto Zero Wng
1:low limited or 85:Flow Vel Over 0x41
2:high limited 0x42
Simulated Value 0:Not limited 96:DI1 Sim. enabled
0x60
98:DI2 Sim. enabled
0:Bad 0:Non specific 3:constant 46:TB O/S Mode
50:Span > 10m/s
51:Span < 0.1m/s
56:H/L HH/LL Set *2
0x03
57:Dens Set Err
71:Meas Mod Set
72:Size Set Err
73:Adh Set Err
3:Device Failure 3:constant 10:uP Fault
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault 0x0F
16:EEPROM Dflt
17:Comm uP Fault
18:Comm EEPROM Fault
19:I/F Module Fault
4:Sensor Failure 3:constant 15:Coil Open
30:Sig Overflow
31:Empty Pipe 0x13
33:Adhesion Alm
34:Insulation Alm(Reserved)
7:Out of Service 3:constant 41:PB O/S Mode
47:DI1FB O/S Mode 0x1F
48:DI1FB O/S Mode
*1: In case of the vale of (5,88):ALM_SETTING is No.
*2: In case of the vale of (5,88):ALM_SETTING is Yes.

- 22 - IM 01E20C01-20E
6. IN-PROCESS OPERATION
This chapter describes the procedure performed when changing the operation of the function block of the ADMAG
AXFA11 in process.

6.1 Mode Transition


When the function block mode is changed to Out_Of_Service, the function block pauses and a block alarm is issued.

When the function block mode is changed to Manual, the function block suspends updating of output values. In this
case alone, it is possible to write a value to the OUT parameter of the block for output. Note that no parameter status
can be changed.

6.2 Generation of Alarm


6.2.1 Indication of Alarm
When the self-diagnostics function indicates that a device is faulty, a diagnostic message (DIAGNOSIS or
DIAGNOSIS_EXTENSION) is issued from the physical block. When a diagnostic message is detected in each function
block or an diagnostic message in the process value (process alarm) is detected, a diagnostic message is issued from
each block. If two or more alarms are issued, multiple error messages are displayed in 4-second intervals. (when "1" is
set to DISPLAY_CYCLE).
When an alarm has been occurred, the corresponding alarm name, description, and suitable countermeasure will be
displayed on the display unit. The normal Display Mode and Alarm Mode may be displayed alternatively. When a
warning has been issued, the corresponding content will be shown in the third line in the Display Mode.

Figure 6.1 Error Identification on Indicator

- 23 - IM 01E20C01-20E
Table 6.1 List of Error Messages
DIAGNOSIS_ Display Message Countermeasure Message Alarm description
Category
EXTENSION (21 characters OK)
1 0 10:uP Fault Contact nearest office or service Microprocessor error
1 11:EEPROM Fault center Hart EEPROM error
2 12:A/D(H) Fault A/D converter error
3 13:A/D(L) Fault
4 14:A/D(Z) Fault
System 5 15:Coil Open Cut the power and check coil & EX Flowtube coil open-circuit
Alarms cables
6 16:EEPROM Dflt Contact nearest office or service EEPROM default values
7 17:Comm uP Fault center FB Microprocessor error
2 0 18:Comm EEPROM Fault FB EEPROM error
1 19:I/F Module Fault Hart communication error
2 30:Sig Overflow Check signal cable and grounding Input signal error
3 31:Empty Pipe Fill flow tube with fluid Flowtube is not filled with fluid
Process 4 32:HH/LL Alm Check flow rate and setting value Flow rate alarm for greater than High-High limit
Alarms value or less than Low-Low limit value.
5 33:Adhesion Alm Clean electrodes Electrode adhesion alarm
6 34:Insulation Alm(Reserved) Insulation alarm
7 41:PB O/S Mode Physical Block is in O/S Mode. Output is hold.
3 0 42:AI FB O/S Mode Analog Input Function Block is in O/S Mode. Output
is hold.
1 43:Total1 FB O/S Mode Totalizer1 Function Block is in O/S Mode. Output is
hold.
2 44:Total2 FB O/S Mode Totalizer2 Function Block is in O/S Mode. Output is
O/S Mode hold.
Alarms 3 45:Total3 FB O/S Mode Totalizer3 Function Block is in O/S Mode. Output is
hold.
4 46:TB O/S Mode Transducer Block is in O/S Mode. Output is hold.
5 47:DI1 FB O/S Mode Discrete Input1 Function Block is in O/S Mode.
Output is hold.
6 48:DI2 FB O/S Mode Discrete Input2 Function Block is in O/S Mode.
Output is hold.
7 50:Span > 10m/s Check parameter 27 of AI and 34 of Span flow velocity setting is 11 m/s or more
4 0 51:Span < 0.1m/s TB Span flow velocity setting is 0.05 m/s or less
1 56:H/L HH/LL Set Check parameter 83 to 86 of TB The condition [High_Alarm - Low_Alarm >
H/L_Alarm_Hys] or the condition
[High_High_Alarm - Low_Low_Alarm >
H/L_Alarm_Hys] is not satisfied.
2 57:Dens Set Err Check parameter 34, 76 and 77 of Mass units have been selected for Base Flow Unit
TB but density is set to 0.

Setting 3 71:Meas Mod Set Check parameter 70 of TB Measure_Mode is set to Enhanced DF without
Alarms selecting an optional specification code /HF1 or
/HF2.
4 72:Size Set Err Check parameter 31 and 32 of TB A value of 3000.1 mm or more is set for
Nominal_Size.
5 73:Adh Set Err Check parameter 115 to 118 of TB The condition in Adhesion detection level,
Level:1<Level:2<Level:3<Level:4 is not satisfied.
6 74:Flow Limit Set(Reserved) Check parameter 35 and 36 of TB The condition [VOLUME_FLOW_LO_LIMIT <
VOLUME_FLOW_HI_LIMIT] is not satisfied.
7 75:Unit Set Err Check parameter 27 of TOT and 34 The mismatch of UNIT_TOT and
of TB VOLUME_FLOW_UNITS.
5 0 80:Adhesion Wng Slight adhesion to electrodes.

1 81:Insu-Brk Wng(Reserved) Insulation deteriorate.

2 82:Auto Zero Wng Results of automatic zero adjustment are higher


Warning than the rated values.
3 84:Display Over Wng Overflow in the display digits instantaneous
(Reserved) flow-rate display.
4 85:Flow Vel Over Flow velocity overflow.

5 91:AI Sim. enabled Simulation is enabled in AI Function Block.

6 92:AI FB Man Mode AI Function Block is in Man mode

7 93:Total1 FB Man Mode Totalizer1 Function Block is in Man mode


(Reserved)
6 0 94:Total2 FB Man Mode Totalizer2 Function Block is in Man mode
(Reserved)
1 95:Total3 FB Man Mode Totalizer3 Function Block is in Man mode
Warning (Reserved)
in FB
2 96:DI1 Sim. enabled Simulation is enabled in DI1 Function Block.

3 97:DI1 FB Man Mode DI1 Function Block is in Man mode

4 98:DI2 Sim. enabled Simulation is enabled in DI2 Function Block.

5 99:DI2 FB Man Mode DI2 Function Block is in Man mode

6 100:Sim. Jmpr On The simulation enable jumper pin is On.

- 24 - IM 01E20C01-20E
6.2.2 Alarm and Event
The parameter Alarm Summary summarizes the status of up to 16 block alarms. The current states is only supported.
Limit alarm bits will be set to 1 or 0 if the alarm reason occurs (1) or is gone (0).
The update event bit will be set to 1 after ST_REV increment and will be set to 0 after 10 s.
Bits of the Octet String are associated with the following alarms:
Octet 0
0: Discrete alarm (LSB) (only Function Blocks with discrete limit parameters)
1: HI_HI_Alarm (only Function Blocks with analog limit parameters)
2: HI_Alarm (only Function Blocks with analog limit parameters)
3: LO_LO_Alarm (only Function Blocks with analog limit parameters)
4: LO_Alarm (only Function Blocks with analog limit parameters)
5: reserved
6: reserved
7: Update Event (e.g. increment of ST_REV)

Octet 1
0 -7: reserved

6.3 Simulation Function


The simulation function simulates the input of a function block and let it operate as if the data was received from the
transducer block.
A SIMULATE_ENABLE slide switch is mounted in the ADMAG AXFA11 amplifier. This is to prevent the accidental
operation of this function. When switch is turned on, simulation is enabled. (See Figure 6.2.)
WRITE_PROTECT

WRITE_PROTECT

OFF OFF
2
1

2
1
SIMULATE

SIMULATE
N
O

N
O

ON ON

SW1 SW1
Figure 6.2 SIMULATE_ENABLE Switch Position

In simulation enabled status, an alarm is generated from the resource block, and other device alarms will be masked; for
this reason the simulation must be disabled immediately after using this function.
The SIMULATE parameter of AI block consists of the elements listed in Table 6.3 below.
Table 6.2 SIMULATE Parameter

Sub- index Parameters Description


1 Simulate Status Sets the data status to be simulated.
2 Simulate Value Sets the value of the data to be simulated.
Controls the simulation function of this block.
3 Simulate_Enabled 0: Disabled (standard)
1: Enabled(simulation)

When Simulate_Enabled in Table 6.3 above is set to "Enabled", the applicable function block uses the simulation value
set in this parameter instead of the data from the transducer block. This setting can be used for propagation of the status
to the trailing blocks, generation of a process alarm, and as an operation test for trailing blocks.
- 25 - IM 01E20C01-20E
7. DIAGNOSTIC INFORMATION
Diagnostic information and failures of ADMAG AXFA11 are indicated by using parameter DIAGNOSIS (slot 0, index
29) and DIAGNOSIS_EXTENSION (slot:0 index 30) in Physical Block. Each diagnostic information is supported
when the corresponding bit in DIAGNOSIS_MASK and DIAGNOSIS_EXTENSION is set.

Table 7.1 Contents of DIAGNOSIS

Octet Bit Mnemonic Description Remarks Mask


1 0 DIA_HW _ELECTR Hardware failure of the electronic 10:uP Fault 1
17:Comm uP Fault
19:I/F Module Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault
1 DIA_HW _MECH Hardware failure mechanics 15:Coil Open 1
2 DIA_TEMP_MOTOR Motor – temperature too high -- 0
3 DIA_TEMP_ELECTR Electronic temperature too high -- 0
4 DIA_MEM_CHKSUM Memory error 11:EEPROM Fault 1
18:Comm EEPROM Fault
5 DIA_MEASUREMENT Failure in 30:Sig Overflow 1
Measurement
6 DIA_NOT_INIT Device not initialized (No self 16:EEPROM Dflt 1
calibration)
7 DIA_INIT_ERR Self calibration failed -- 0
2 0 DIA_ZERRO_ERR Zero point error (limit position) 82:Auto Zero Wng 1
1 DIA_SUPPLY 1 DIA_SUPPLY Power supply failed -- 0
(electrical, pneumatic)

2 DIA_CONF_INVAL Configuration not valid 50:Span > 10m/s 1


51:Span < 0.1m/s
56:H/L HH/LL Set
57:Dens Set Err
71:Meas Mod Set
72:Size Set Err
73:Adh Set Err
74:Flow Limit Set (Reserved)
75:Unit Set Err
3 DIA_WARMSTART New-start-up (warm start up) hot start 0
carried out.
4 DIA_COLDSTART Re-start-up HW,SW,DL restart power fail 0
(cold start up) carried out.
5 DIA_MAINTENANCE Maintenance required 31:Empty Pipe 1
32:HH/LL Alm
33:Adhesion Alm
34:Insulation Alm(Reserved)
80:Adhesion Wng
81:Insu-Brk Wng(Reserved)
85:Flow Vel Over
90:Display SW(Reserved)
6 DIA_CHARACT Characterization invalid -- 0
7 IDENT_NUMBER_ Set to 1 (one), if the Ident_Number 1
Violation of the running cyclic data transfer
and the value of Physical Block
IDENT_NUMBER_SELECTOR
parameter are different.
3 0-7 Reserved Reserved for use within the PNO X
4 0-6 Reserved Reserved for use within the PNO X
7 EXTENSION_AVAILAB More diagnosis information is 1
LE available. Refer to Table 6.1.

- 26 - IM 01E20C01-20E
8. GENERAL SPECIFICATIONS
■ STANDARD SPECIFICATIONS
For items other than those described below, refer to GS 01E20C01-01E.
Function Blocks
One AI Function block, Three totalizer function blocks and two DI function blocks are available. (Profibus Profile
3.0 Compliant)
Output Signals:
・ Data transmission rate: 9.6k baud to 1.5M baud
・ Signal encoding: Asynchronous NRZ coding
Output data
Volumetric flow, Totalized value,
Status output (Adhesion alarm, HH/H/L/LL alarm)
Input data
Zero point adjustment
Totalized value reset
0% signal Lock
Alarm Selection Function:
These informations are indicated in DIAGNOSTICS parameter, which can be handled during normal operation.
(Note 1) The following functions aren't supported in the Profibus model.
- Pulse Output
- Multi-range Function
- Totalization Switch
- Alarm Output

■ MODEL AND SUFFIX CODE


AXFA11 Magnetic Flowmeter Remote Converter:
AXFA11G-H1-□1/□
“H” following the first dash indicates that the output is digital communication compliant with PROFIBUS DP/V1
protocol.

<Setting When Shipped>


Default (FT1002) for TAG_DESC,
Tag Number(TAG_DESC)*1
nothing for tag plate unless otherwise specified
Flow rate Range (PV_SCALE) ‘0 to 10m/s’ unless otherwise
Lower/Higher Range Value and Unit specified in order
Output Range (OUT_SCALE) Same data as ‘PV_SCALE’
Lower/Higher Range Value and Unit unless otherwise specified
Bus Address ‘0x7E(126)’ unless otherwise specified

*1: Specified Tag Number is entered in the amplifier memory and also engraved on the stainless steel plate.
- For entry in the amplifier memory,
Up to 32 letters using any of alphanumereics and symbols, - and x.
- For engraving on the stainless steel plate,
Up to 16 letters using any of alphanumerics and symbols.
*2 Bus Address; Set by remote configurator or at factory.
Explanation of parameters listed above:
(1) PV_SCALE: Set the input value from Transducer block (input range of sensor) which corresponds to 0%
value and 100% value of the calculation in the AI function block. In the case of ADMAG
AXFA11, the value set as flow span should be entered to this parameter.
(2) OUT_SCALE: Output scaling parameter. Set the output value which corresponds to 0% value and 100% value
of the calculation in the AI function block.

- 27 - IM 01E20C01-20E
APPENDIX 1. LIST OF PARAMETERS FOR
EACH BLOCK OF THE ADMAG AXFA11
Note: The Write Mode column contains the modes in which each parameter is write enabled. O/S: Write enabled in O/S
mode.
MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.

A1.1 Physical Block


Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
0 16 BLOCK_OBJECT -- Information on this block such as Block Tag, DD Revision,
(DS-32) Execution Time etc.

0 17 ST_REV -- 0 The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static
parameter value in the block is changed.
0 18 TAG_DESC Auto “Specified at the The user description of the intended application of the block
time of order”
0 19 STRATEGY Auto 0 to 65535 0 The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
0 20 ALERT_KEY Auto 0 to 255 0 The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
0 21 TARGET_MODE Auto The permitted Auto Set the Target of block mode (MODE_BLK) to Auto or O/S
bit is only according to the Write Mode of the parameter to be set or
available. changed.
0 22 MODE_BLK Actual -- Auto The mode parameter is a structured parameter composed of
(DS-37) the actual mode, the normal mode and the permitted mode.
Actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block is
allowed to take.
Normal: Indicates the operating condition that the block will
usually take.
Permitted -- O/S, Auto bit

Normal -- The permitted


bit is only
available.
0 23 ALARM_SUM Current -- Bit7 is only 0 The current alert status, unacknowledged status, unreported
(DS-42) available. status and disabled status of the alarms associated with the
function block.
Unacknowledged -- for future use 0

Unreported -- for future use 0

Disabled -- for future use 0

0 24 SOFTWARE_REVISION -- -- Revision-number of the software of the field device.

0 25 HARDWARE_REVISION -- -- Revision-number of the hardware of the field device.


0 26 DEVICE_MAN_ID -- 55(0x37) Identification code of the manufacturer of the field device.

0 27 DEVICE_ID -- ADMAG AXFA11 Manufacturer specific identification of the field device.

0 28 DEVICE_SER_NUM Auto Serial No. Serial number of the field device.

0 29 DIAGNOSIS -- Variable Detailed information of the device, bitwise coded. More than
one message possible at once.
0 30 DIAGNOSIS_EXTENSION -- Variable Additional manufacturer-specific information of the device,
bitwise coded.
0 31 DIAGNOSIS_MASK -- Supported Definition of supported DIAGNOSIS information-bits.
0: Not supported
1: Supported
0 32 DIAGNOSIS_MASK_EXTENSION -- Definition of supported DIAGNOSIS_EXTENSION
information-bits.
Supported
0: Not supported
1: Supported
0 33 DEVICE_CERTIFICATION -- No information Space Not used for AXFA11

0 34 WRITE_LOCKING Auto 0: Lock 2457 (0x999) If set, no writes from anywhere are allowed, except to clear
2457: Disabled WRITE_LOCKING.
0 35 FACTORY_RESET O/S 2506:Warmstart 0 Allows a manual restart to be initiated.
2712:reset 2506: Warm start of the device. All parameterization
Adrs(126) only remains
unchanged.
2712: Reset the bus address only.
54081: Resetting device. The bus address setting is
changed by
SET_ADDRESS.

- 28 - IM 01E20C01-20E
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
0 36 DESCRIPTOR Auto Space User definition text (a string) to describe the device within the
application
0 37 DEVICE_MESSAGE Auto Space User definable MESSAGE (a string) to describe the device
within the application or in the plant.
0 38 DEVICE_INSTAL_DATE Auto Space Date of installation of the device.

0 40 IDENT_NUMBER_SELECTOR Auto 0:PROFILE ID 1 Each PROFIBUS-DP device shall have an Ident_Number


1:Device provided by the PNO.
Specific ID 0: PROFILE ID
1: device specific ID
0 41 HW_WRITE_PROTECTION -- 0:Unprotected 0 Not used for AXFA11
1:Protected
42-48 reserved by PNO
0 49 SOFT_DESC -- Uncertain Yokogawa internal use.

0 50 SET_ADDRESS O/S 0 to 126 0 This parameter is used in order to set or change the station
address.
0 52 VIEW_PHYSICAL_BLOCK -- View objects allow the following groups of physical block
parameter values to be read with one read request.
ST_REV, MODE_BLK, ALARM_SUM, DIAGNOSIS

- 29 - IM 01E20C01-20E
A1.2 Al Function Block
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
1 16 BLOCK_OBJECT -- Information on this block such as Block Tag, DD Revision,
(DS-32) Execution Time etc.
1 17 ST_REV -- 0 The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
1 18 TAG_DESC Auto Space The user description of the intended application of the block
1 19 STRATEGY Auto 0 to 65535 0 The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
1 20 ALERT_KEY Auto 0 to 255 0 The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
1 21 TARGET_MODE Auto The permitted bit Auto Set the Target of block mode (MODE_BLK) to Auto or O/S
is only available. according to the Write Mode of the parameter to be set or
changed.
1 22 MODE_BLK Actual -- Auto The mode parameter is a structured parameter composed of
(DS-37) the actual mode, the normal mode and the permitted mode.
Actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block is
allowed to take.
Normal: Indicates the operating condition that the block will
usually take.
Permitted -- O/S bit, Man bit, O/S,Man,Auto
Auto bit
Normal -- The permitted bit Auto
is only available.
1 23 ALARM_SUM Current -- Bit1, Bit2, Bit3, 0 The current alert status, unacknowledged status, unreported
(DS-42) Bit4, Bit7 are status and disabled status of the alarms associated with the
available. function block.
Unacknowledged -- for future use 0
Unreported -- for future use 0
Disabled -- for future use 0
1 24 BATCH BATCH_ID Auto 0 This parameter is intended to be used in Batch applications in
(DS-67) line with IEC 61512 .
RUP Auto 0
OPERATION Auto 0
PHASE Auto 0
1 25 Not used
1 26 OUT Value -- 0 This parameter contains the current measurement value from
(DS-33) Transducer Block or configuration adjusted engineering unit
and the belonging state in AUTO MODE.
OUT contains the value and status set by an operator in MAN
MODE.
Status -- 0
1 27 PV_SCALE Array1 O/S 0.00001 to 32000 Specified at the Conversion of the Process Variable into percent using the
(Array) time of order high and low scale values.
The engineering unit of PV_SCALE high and low scale values
are direct related to the PRIMARY_VALUE_UNIT of the
configured
Transducer Block (configured via Channel parameter).
The PV_SCALE high and low scale values follow the changes
of the PRIMARY_VALUE_UNIT of the related Transducer
Block
automatically, i.e. a change of the Transducer Block
PRIMARY_VALUE_Unit causes no bump at OUT from AI.
Array2 O/S 0.00001 to 32000 “Specified at
the time of
order”
1 28 OUT_SCALE EU at 100% O/S “Specified at Scale of the Process Variable
(DS-68) the time of This parameter contains the values of the lower limit and
order” upper limit effective range, the code number of the
engineering unit of Process Variable and the number of digits
on the right hand side of the decimal point.
EU at 0% O/S “Specified at
the time of
order”
Units Index O/S 1342:% “Specified at
1355:Ml/d the time of
1522:Ml/h order”
1521:Ml/min , etc
Decimal Point O/S “Specified at
the time of
order”
1 29 LIN_TYPE O/S 0:No 0 Not used for AXFA11
Linearisation
250:Not used
251:None
1 30 CHANNEL O/S 0x0111(1, 17) Reference to the active Transducer Block which provides the
measurement value to the Function Block.
1 31 Not used
1 32 PV_FTIME Auto more than 0sec 0.000 Time constant of a single exponential filter for the PV, in
seconds.

- 30 - IM 01E20C01-20E
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
1 33 FSAFE_TYPE Auto 0:Failsafe Value 1: Last Valid Defines reaction of device, if a fault is detected.
1:Last Valid OUT OUT Value 0: VALUE= FSAFE_VALUE
Value 1: VALUE= Stored last valid OUT VALUE
2:Wrong 2: VALUE= Wrong calculated
Calculated Value
1 34 FSAFE_VALUE Auto 0.000 Default value for the OUT parameter, if sensor or sensor
electronic fault is detected. The unit of this parameter is the
same like the OUT one.
1 35 ALARM_HYS Auto OUT_SCALE*0.5 0.5% of Amount the PV must return within the alarm limits before the
OUT_SCALE alarm condition clears. Alarm Hysteresis is expressed as
engineering units of the PV span.
1 37 HI_HI_LIM Auto +INF The setting for high high alarm in engineering units.

1 39 HI_LIM Auto +INF


The setting for high alarm in engineering units.
1 41 LO_LIM Auto -INF
The setting of the low alarm in engineering units.

1 43 LO_LO_LIM Auto -INF


The setting of the low low alarm in engineering units.
1 46 HI_HI_ALM Alarm State -- 0: No Alarm 0: No Alarm 0:Clear alarm
(DS-39) 1: Alarm Active 1:active alarm
-- Out value at the time the alarm was detected or cleared.
Value
1 47 HI_ALM Alarm State -- 0: No Alarm 0: No Alarm Same as HI_HI_ALM.
(DS-39) 1: Alarm Active
--
Value

1 48 LO_ALM Alarm State -- 0: No Alarm 0: No Alarm Same as HI_HI_ALM.


(DS-39) 1: Alarm Active
--
Value

1 49 LO_LO_ALM Alarm State -- 0: No Alarm 0: No Alarm Same as HI_HI_ALM.


(DS-39) 1: Alarm Active
--
Value
1 50 SIMULATE Simulate_Status Auto 0 For commissioning and test purposes the input value from the
(DS-50) Transducer Block in the Analog Input Function Block AI-FB
can be modified. That means that the Transducer and AI-FB
will be
disconnected.
Simulate_Value Auto 0

Simulate_Enabled Auto 0:Disabled, 0:Disabled Simulate_Enable = 0:Disabled 1: Enabled


1:Enable
1 51 OUT_UNIT_TEXT Auto Character Space If a specific unit of OUT parameter is not in the code list the
user has the possibility to write the specific text in this
parameter. The unit code is then equal “textual unit definition”.
1 52-60 reserved by PNO
1 61 VELOCITY_CHECK -- 0 to 99.999 This parameter is used in order to display the span
velocity corresponding to PV_SCALE.EU100 (EU0).
1 63 VIEW_ANALOG_INPUT_FB -- View objects allow the following groups of physical block
parameter values to be read with one read request.
ST_REV, MODE_BLK, ALARM_SUM,
OUT,VELOCITY_CHECK

- 31 - IM 01E20C01-20E
A1.3 Totalizer Function Block
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
2/3/4 16 BLOCK_OBJECT -- Information on this block such as Block Tag, DD Revision,
(DS-32) Execution Time etc.
2/3/4 17 ST_REV -- 0 The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
2/3/4 18 TAG_DESC Auto Space The user description of the intended application of the block
2/3/4 19 STRATEGY Auto 0 to 65535 0 The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
2/3/4 20 ALERT_KEY Auto 0 to 255 0 The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
2/3/4 21 TARGET_MODE Auto The permitted bit Set the Target Auto, Man or O/S according to the Write Mode
is only available. of the parameter to be set or changed.
2/3/4 22 MODE_BLK Actual -- Auto The mode parameter is a structured parameter composed of
(DS-37) the actual mode, the normal mode and the permitted mode.
Actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block is
allowed to take.
Normal: Indicates the operating condition that the block will
usually take.
Permitted -- O/S bit, Auto bit O/S,Auto
Normal -- The permitted bit Auto
is only available.
2/3/4 23 ALARM_SUM Current -- Bit1, Bit2, Bit3, 0 The current alert status, unacknowledged status, unreported
(DS-42) Bit4, Bit7 are status and disabled status of the alarms associated with the
available. function block.
Unacknowledged -- for future use 0
Unreported -- for future use 0
Disabled -- for future use 0
2/3/4 24 BATCH BATCH_ID Auto 0 This parameter is intended to be used in Batch applications
(DS-67) in line with IEC 61512 .
RUP Auto 0
OPERATION Auto 0
PHASE Auto 0
2/3/4 25 Not used
2/3/4 26 TOTAL Value -- -99999999 to 0 This parameter contains the integrated quantity of the rate
(DS-33) 99999999 parameter provided by CHANNEL and the associated
status.
Status -- 0
2/3/4 27 UNIT_TOT O/S 1549:Ml, 1034:m3 This parameter is used in order to set the unit of the totalized
1034:m3, quantity.
1550:kL,
1038:L,
1036:cm3,
1092:t,
1088:kg,
1089:g,
1043:CF,
1048:gallon
1051:bbl,
1094:lb
1035:dm3
1040:mL
1041:hL
1091:Mg
1090:mg
2/3/4 28 CHANNEL O/S 0x0111(1, 17) Reference to the active Transducer Block which provides the
measurement value to the Function Block.
2/3/4 29 SET_TOT Auto 0:Totalize 0:Totalize This parameter is used in order to assign the condition to the
1:Reset totalizer.
2:Preset
2/3/4 30 MODE_TOT O/S 0:Balanced 0:Balanced This parameter is used in order to define how the totalizer
1:Positive Only counts.
2:Negative Only
3:Hold
2/3/4 31 FAIL_TOT O/S 0:Run 0:Run This parameter is used in order to define error response in
1:Hold the event of the device error or bad measured value.
2:Memory
2/3/4 32 PRESET_TOT Auto -99999999~ 0.000 This parameter is used in order to define the starting value to
99999999 the totalizer.
2/3/4 33 ALARM_HYS Auto 0.000 Amount the PV must return within the alarm limits before the
alarm condition clears. Alarm Hysteresis is expressed as a
percent of the PV span.
2/3/4 34 HI_HI_LIM Auto +INF The setting for high high alarm in engineering units.
2/3/4 35 HI_LIM Auto +INF The setting for high alarm in engineering units.
2/3/4 36 LO_LIM Auto -INF The setting of the low alarm in engineering units.
2/3/4 37 LO_LO_LIM Auto -INF The setting of the low low alarm in engineering units.
2/3/4 38 HI_HI_ALM Alarm State -- 0: No Alarm 0: No Alarm 0:Clear alarm
(DS-39) 1: Alarm Active 1:active alarm
Value -- Out value at the time the alarm was detected or cleared.

- 32 - IM 01E20C01-20E
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
2/3/4 39 HI_ALM Alarm State -- 0: No Alarm 0: No Alarm Same as HI_HI_ALM.
(DS-39) 1: Alarm Active
Value --
2/3/4 40 LO_ALM Alarm State -- 0: No Alarm 0: No Alarm Same as HI_HI_ALM.
(DS-39) 1: Alarm Active
Value --
2/3/4 41 LO_LO_ALM Alarm State -- 0: No Alarm 0: No Alarm Same as HI_HI_ALM.
(DS-39) 1: Alarm Active
Value --
2/3/4 42-51 reserved by PNO
2/3/4 53 VIEW_TOTALIZER_FB -- View objects allow the following groups of physical block
parameter values to be read with one read request.
ST_REV, MODE_BLK, ALARM_SUM, TOTAL

- 33 - IM 01E20C01-20E
A1.4 Transducer Block
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
5 16 BLOCK_OBJECT -- Information on this block such as Block Tag, DD Revision,
(DS-32) Execution Time etc.
5 17 ST_REV -- 0 The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.
5 18 TAG_DESC Auto Space The user description of the intended application of the block.
5 19 STRATEGY Auto 0 to 65535 0 The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
5 20 ALERT_KEY Auto 0 to 255 0 The identification number of the plant unit. This information may
be used in the host for sorting alarms, etc.
5 21 TARGET_MODE Auto The permitted bit is Auto Set the Target of block mode (MODE_BLK) to Auto or O/S
only available. according to the Write Mode of the parameter to be set or
changed.
5 22 MODE_BLK Actual -- Auto The mode parameter is a structured parameter composed of
(DS-37) the actual mode, the normal mode and the permitted mode.
Actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block is
allowed to take.
Normal: Indicates the operating condition that the block will
usually take.
Permitted -- O/S bit, Auto bit O/S,
Auto
Normal -- The permitted bit is Auto
only available.
5 23 ALARM_SUM Current -- Bit7 is only 0 The current alert status, unacknowledged status, unreported
(DS-42) available. status and disabled status of the alarms associated with the
function block.
Unacknowledged -- for future use 0 0
Unreported -- for future use 0 0
Disabled -- for future use 0 0
5 24 CALIBR_FACTOR O/S 0.01 to 3.0000 1.0000 Gain compensation value for the detector, so that flow
indication is accurate.
This parameter means the meter factor of low frequency side
(LOW_MF).
This parameter must not be downloaded by the operator.
5 25 LOW_FLOW_CUTOFF O/S The value which 0 Set the low cut range corresponding 0 to 10 % of the large
corresponds to 0 to absolute value between PV_SCALE.Array1 and
10% of PV_SCALE PV_SCALE.Array2.
is permitted. This value must be set to the lower switching point because this
function has a hysterisis.
5 26 MEASUREMENT_MODE O/S 0:Unidirectional 0:Unidirectional Set the mode of the flow measurement,either unidirectional or
1:Bidirectional bidirectional.
5 27 FLOW_DIRECTION O/S 0:Positive 0:Positive Assign an arbitrary positive or negative sign to the measured
1:Negative PV value.
5 28 ZERO_POINT O/S -999.99 to 999.99 0.00 This function shows the current zero point compensation value
for the sensor.
This parameter is used to display the results obtained from
ZERO_POINT_ADJUST . Specifically, the correction values
displayed, and it is also possible to directly enter correction
values.
This parameter must not be downloaded by the operator.
5 29 ZERO_POINT_ADJUST Auto 0:Cancel 0:Cancel This parameter executes the automatic zero adjustment
1:Execute function: If “Execute” is selected, this function will be started.
“Now Auto Zero Executing...” is indicated while the Auto Zero
function is being carried out and After finishing the adjustment,
this parameter is set to “Cancel”. The result of the automatic
zero adjustment is confirmed using ZERO_POINT , and if the
result exceeds the rated value, the warning “82: Auto Zero Wng”
will be displayed.
5 30 ZERO_POINT_UNIT O/S 1062:mm/s 1062:mm/s This parameter is used in order to select the unit for zero point.
5 31 NOMINAL_SIZE O/S 0.99 to 100 This parameter is used in order to set the size (diameter) of the
3000.10(mm) sensor (flow tube).
0.01 to If the setting value exceeds the valid range, the warning
120.10(inch) “72:Size Set Err" will be displayed.
5 32 NOMINAL_SIZE_UNITS O/S 1013:mm, 1013:mm This parameter is used in order to select the unit of size
1019:inch (diameter) of the sensor (flow tube).
5 33 VOLUME_FLOW Value -- Indicates the current measured value and status as the primary
(DS-33) value (volumetric flow) This parameter is input to the AI
Function Block and the Totalizer Function Block.
Status -- Good
5 34 VOLUME_FLOW_UNITS O/S 1349:m3/h 1349:m3/h This parameter is used in order to select the unit for
1351:L/s VOLUME_FLOW, VOLUME_FLOW_LO_LIMIT and
1357:CFM VOLUME_FLOW_HI_LIMIT parameters.
1363:GPM, etc
5 35 VOLUME_FLOW_LO_LIMIT -- -11.88 to 11.88 m/s -335.8991 This parameter is used in order to enter the lower range value
or -22.68 to 22.68 for volumetric flow.
m/s
The value depends
on a volume flow
unit.

- 34 - IM 01E20C01-20E
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
5 36 VOLUME_FLOW_HI_LIMIT -- -11.88 to 11.88 m/s -335.8991 This parameter is used in order to enter the upper range value
or -22.68 to 22.68 for volumetric flow.
m/s
The value depends
on a volume flow
unit.
5 57 SAMPLING_FREQ Value -- 75 This parameter is used in order to indicates the field frequency
(DS-33) of the sensor (Sensor specific, must not be downloaded).

Status -- Good
5 58 SAMPLING_FREQ_UNITS O/S 1077:Hz 1077:Hz This parameter is used in order to selected unit code for
SAMPLING_FREQ parameter.
5 59-68 reserved by PNO
5 69 VOLUME_FLOW_FTIME O/S 0.1 to 200.0 3.0 Setting of the damping time constant to VOLUME_FLOW. The
output to reach 63.2% from 0%.

5 70 DUAL_FREQUENCY_MODE O/S 0:Standerd DF 0:Standard DF Selection of excitation mode.


1:Enhanced DF This parameter is effective when FLOW_TUBE is "ADMAG
AXF" and NOMINAL_SIZE is in between 25mm to 200mm.
Outside the field of that condition, the warning "71:Meas Mod
Set" will be displayed.
5 71 LOW_MF O/S 0.01 to 3.0000 1.0000 This parameter is used in order to set the low-frequency meter
factor.
This setting is linked with that of parameter CALIBR_FACTOR.

5 72 HIGH_MF O/S 0.01 to 3.0000 1.0000 This parameter is used in order to set the high-frequency meter
factor.
5 73 LOW_MF(EDF) O/S 0 to 3.0000 1.0000 This parameter is used in order to set the low-frequency meter
factor as required when Enhanced DF (i.e., enhanced dual
frequency excitation) is selected. If “Standard DF” has been
selected for Measure_Mode, neither Low_MF(EDF) nor
High_MF(EDF) is displayed.

5 74 HIGH_MF(EDF) O/S 0 to 3.0000 1.0000 This parameter is used in order to set the high-frequency meter
factor as required when Enhanced DF (i.e., enhanced dual
frequency excitation) is selected.
5 75 SELECT_FLOW_TUBE O/S 0:ADMAG AXF 0:ADMAG AXF This parameter is used in order to set the types of flow tube.
1:ADMAG When combining this product with an AXF Remote Flow tube,
2:ADMAG AE “ADMAG AXF” should be selected.
3:ADMAG SE
4:YEWMAG
5:Calibrator
6:Other
5 76 DENSITY_UNIT O/S 0:kg/m3 1:lb/gal 0:kg/m3 This parameter selects the units for density as required when
2:lb/cf making settings using Mass_Density.
5 77 MASS_FLOW_DENSITY O/S 0 to 32000 0 Setting of the density for mass-flow rate. This parameter is
necessary in situations where t, kg, g, klb or lb has been
selected as the mass unit in VOLUME_FLOW_UNITS. If a
mass unit is selected in VOLUME_FLOW_UNITS and a value
of 0 is set for this parameter, the setting alarm “57: Density
SetErr.” will be displayed. In such a case, ensure that the
density is set correctly.
5 78 LIMSW_1_VALUE_D Value -- 0: Good 0 This parameter is used in order to indicate the current input
(DS-34) 1: Alarm value selected LIMSW_1_TARGET. If the target alarm occured
the value is set 1. Refore to LIMSW_1_TARGET.
Status -- Good
5 79 LIMSW_1_TARGET O/S 0:H/L Alarm 0 This parameter selects the input channel used to
1:HH/LL Alarm LIMSW_1_VALUE_D.
2:Adhesion Alarm
3:Adhesion
Warning
5 80 LIMSW_2_VALUE_D Value -- 0: Good 0 This parameter is used in order to indicate the current input
(DS-34) 1: Alarm value selected LIMSW_2_TARGET. If the target alarm occured
the value is set 1. Refore to LIMSW_2_TARGET.
Status -- Good
5 81 LIMSW_2_TARGET O/S 0:H/L Alarm 2:Adhesion This parameter selects the input channel used to
1:HH/LL Alarm Alarm LIMSW_2_VALUE_D.
2:Adhesion Alarm
3:Adhesion
Warning
5 82 SIGNAL_LOCK Auto 0:Unlock 0:Unlock This parameter executes the signal lock function: If “Lock” is
1:Lock selected, this function will be started.
5 83 LOW_ALARM O/S -110 to 110 -110 This parameter is used in order to set the low limit (L) alarm
value, and this is done using a % value of the maximum span.
A setting value of -110% indicates that the alarm is disabled.

5 84 HIGH_ALARM -- -110 to 110 110 This parameter is used in order to set the high limit (H) alarm
value, and this is done using a % value of PV_SCALE.
A setting value of 110% indicates that the alarm is disabled.
5 85 LOW_LOW_ALARM -- -110 to 110 -110 This parameter is used in order to set the low-low limit (LL)
alarm value, and this is done using a % value of PV_SCALE.
A setting value of -110% indicates that the alarm is disabled.
5 86 HIGH_HIGH_ALARM O/S -110 to 110 110 This parameter is used in order to set the high-high limit (HH)
alarm value, and this is done using a % value of PV_SCALE.
A setting value of 110% indicates that the alarm is disabled.
- 35 - IM 01E20C01-20E
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
5 87 H/L_ALARM_HYS O/S 0 to 10 5 This parameter is used in order to set the hysteresis width for
upper and lower alarm value, using a % value of PV_SCALE.
5 88 ALM_SETTING O/S 0:No 1:Yes 1:Yes This parameter specifies whether the setting alarm will be
recognized as an alarm.
5 89 ALM_SIG_OVER O/S 0:No 1:Yes 1:Yes This parameter specifies whether the signal overflow process
alarm will be recognized as an alarm. A signal overflow occurs
when there is an error in the input signal.
5 90 ALM_EMP_PIPE O/S 0:No 1:Yes 1:Yes This parameter specifies whether the empty pipe (flowtube is
not filled with fluid) process alarm will be recognized as an
alarm.
5 91 ALM_HH/LL O/S 0:No 1:Yes 0:No This parameter specifies whether HH/LL alarm process alarm
will be recognized as an alarm.
5 92 ALM_ADHESION O/S 0:No 1:Yes 0:No This parameter specifies whether the electrode adhesion alarm
will be recognized as an alarm.
5 94 OPERATION_TIME -- 0D 00:00 to 0D 00:00 This parameter is used to display the operation time. For
99999D 23:59 example, “1D23:45” indicates an operation time of 1 day, 23
hours, and 45 minutes.
5 95 ALM_RECORD1 -- 0 to 14 Space This parameter is used to display the most-recent alarm.
5 96 ALM_RECORD_TIME1 -- 0D 00:00 to 0D 00:00 This parameter is used to display the operation time at which
99999D 23:59 the alarm indicated by Alm_Record1 was occurred. For
example, “1D23:45” indicates that an alarm was triggered at the
operation time of 1 day, 23 hours, and 45 minutes.
5 97 ALM_RECORD2 -- 0 to 14 Space This parameter is used to display the second most recent
alarm.
5 98 ALM_RECORD_TIME2 -- 0D 00:00 to 0D 00:00 This parameter is used to display the operation time at which
99999D 23:59 the alarm indicated by Alm_Record2 was occurred.
5 99 ALM_RECORD3 -- 0 to 14 Space This parameter is used to display the third most recent alarm.
5 100 ALM_RECORD_TIME3 -- 0D 00:00 to 0D 00:00 This parameter is used to display the operation time at which
99999D 23:59 the alarm indicated by Alm_Record3 was occurred.
5 101 ALM_RECORD4 -- 0 to 14 Space This parameter is used to display the fourth most recent alarm.
5 102 ALM_RECORD_TIME4 -- 0D 00:00 to 0D 00:00 This parameter is used to display the operation time at which
99999D 23:59 the alarm indicated by Alm_Record4 was occurred.
5 103 DISPLAY_SELECT1 Auto 0 to 4 1:Out Value This parameter is used in order to set the LCD display mode.
5 104 DISPLAY_SELECT2 Auto 0 to 9 0:Off
5 105 DISPLAY_SELECT3 Auto 0 to 9 0:Off
5 106 DISPLAY_CYCLE Auto 0:200ms 1:400ms This parameter is used in order to set the renewal cycle of LCD
1:400ms display.
2:1s 3:2s Renewal cycle: 200 msec*DISPLAY_CYCLE
4:4s 5:8s
5 107 LANGUAGE Auto 0:English 0:English

5 108 RATE_LIMIT O/S 0 to 10 5 This parameter is used in order to set the rate limit value.
5 109 DEAD_TIME O/S 0 to 15 0 This parameter is used in order to set the time for application of
the rate limit, and if a value of 0 is set, the rate limit function will
be terminated.
5 110 PULSING_FLOW O/S 0:No 1:Yes 0:No This parameter is used in order to set the pulsing flow support.
5 111 POWER_SYNCH O/S 0:No 1:Yes 1:Yes This parameter is used in order to indicate whether or not the
internal frequency is to be synchronized with that of the power
supply.
5 112 POWER_FREQUENCY O/S 47.00 to 63.00 50.00 This parameter is used in order to set the power frequency.

5 113 SOFTWARE_REV_NO -- Uncertain -- This parameter is used to display the software revision number.
5 114 ADHESION_CHECK O/S 0:No 1:Yes 0:No This parameter selects whether or not the adhesion diagnostic
function will be carried out.
NOTE If the judgment value for Level 3 is exceeded, a warning
is displayed; and if the value for Level 4 is exceeded, an alarm
is displayed.
5 115 ADHESION_LEVEL1 O/S 0.00 to 100.00 0.10 This parameter is used in order to set the resistance value for
judgment of Level 1.
5 116 ADHESION_LEVEL2 O/S 0.00 to 100.00 0.50 This parameter is used in order to set the resistance value for
judgment of Level 2.
5 117 ADHESION_LEVEL3 O/S 0.00 to 100.00 1.00 This parameter is used in order to set the resistance value for
judgment of Level 3.
5 118 ADHESION_LEVEL4 O/S 0.00 to 100.00 3.00 This parameter is used in order to set the resistance value for
judgment of Level 4.
5 119 ADH_MEASURE_VALUE -- 0.00 to 1000.00 - This parameter displays the value measured using the
adhesion diagnostic function.
5 210 VIEW_TRANSDUCER_BLOCK -- View objects allow the following groups of physical block
parameter values to be read with one read request.
ST_REV, MODE_BLK, ALARM_SUM, VOLUME_FLOW,
SAMPLING_FREQ, LIMSW_1_VALUE_D,
LIMSW_2_VALUE_D, OPERATION_TIME, ALM_RECORD1,
ALM_RECORD2, ALM_RECORD3, ALM_RECORD4,
ALM_RECORD_TIME1, ALM_RECORD_TIME2,
ALM_RECORD_TIME3, ALM_RECORD_TIME4,
ADH_MEASURE_VALUE

- 36 - IM 01E20C01-20E
A1.5 Discrete Input Function
Write
Slot Index Parameter Mnemonic Valid Range Initial Value Description
Mode
6/7 16 BLOCK_OBJECT -- Information on this block such as Block Tag, DD Revision,
(DS-32) Execution Time etc.
6/7 17 ST_REV -- 0 The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.
6/7 18 TAG_DESC Auto Space The user description of the intended application of the block
6/7 19 STRATEGY Auto 0 to 65535 0 The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
6/7 20 ALERT_KEY Auto 0 to 255 0 The identification number of the plant unit. This information may
be used in the host for sorting alarms, etc.
6/7 21 TARGET_MODE Auto The permitted bit Set the Target of block mode (MODE_BLK) to Auto, Man or O/S
is only available. according to the Write Mode of the parameter to be set or
changed.
6/7 22 MODE_BLK Actual -- Auto The mode parameter is a structured parameter composed of
(DS-37) the actual mode, the normal mode and the permitted mode.
Actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block is
allowed to take.
Normal: Indicates the operating condition that the block will
usually take.
Permitted -- O/S bit, Man bit, O/S,Man,Auto
Auto bit
Normal -- The permitted bit Auto
is only available.
6/7 23 ALARM_SUM Current -- Bit0,Bit7 are 0 The current alert status, unacknowledged status, unreported
(DS-42) available. status and disabled status of the alarms associated with the
function block.
Unacknowledged -- for future use 0
Unreported -- for future use 0 0
Disabled -- for future use 0 0
6/7 24 BATCH BATCH_ID Auto 0 This parameter is intended to be used in Batch applications in
(DS-67) line with IEC 61512 .
RUP Auto 0
OPERATION Auto 0
PHASE Auto 0
6/7 25 Not used
6/7 26 OUT_D Value -- 0 This parameter contains the current measurement value from
(DS-34) Transducer Block or configuration adjusted engineering unit
and the belonging state in AUTO MODE.
OUT contains the value and status set by an operator in MAN
MODE.
Status -- 0
6/7 30 CHANNEL O/S 0x013E(1, 62) Reference to the active Transducer Block which provides the
/ 0x0140(1, 64) measurement value to the Function Block.
6/7 31 INVERT Auto 0:Not Inverted 0 Indicates whether the input value of the PV_D should be
1:Invert logically inverted before it is stored in the OUT_D.
6/7 36 FSAFE_TYPE Auto 0:Failsafe Value 1 Defines reaction of device, if a fault is detected.
1:Last Valid
OUT Value
2:Wrong
Calculated
Value
6/7 37 FSAFE_VAL_D Auto 0 Default value for the OUT_D parameter, if sensor or sensor
electronic fault is detected.
6/7 40 SIMULATE Simulate_Status Auto 0 For commissioning and test purposes the input value from the
(DS-51) Transducer Block in the Discrete Input Function Block DI-FB
can be modified. That means that the Transducer and DI-FB will
be disconnected.
Simulate_Value Auto 0 0
Simulate_Enabled Auto 0:Disabled, 0:Disabled Simulate_Enable = 0:Disabled 1: Enabled
1: Enable
6/7 4-50 reserved by PNO
6/7 52 VIEW_DI_FB -- View objects allow the following groups of physical block
parameter values to be read with one read request.
ST_REV, MODE_BLK, ALARM_SUM, OUT_D

- 37 - IM 01E20C01-20E
APPENDIX 2. APPLICATION, SETTING
AND CHANGE OF BASIC PARAMETERS
A2.1 Applications and Selection of Basic Parameters

Setting Item (applicable parameters) Summary


Sets Tag_DESC and each block tag.
Tag No. Up to 32 alphanumeric characters can be set for both tags.
Refer to “Tag and address” in Section 5.
Sets the range of input from the transducer block corresponding to the 0% and 100%
points in operation within the AI1 function block. The calibrated range (0% and 100%) is
Calibration range setup
the factory default setting.
(PV_SCALE)
Sets the range unit, input value of the 0% point (in case of ADMAG AXFA11, 0), input
value of the 100% point (correspond to flow rate span).
Sets the scale of output corresponding to the 0% and 100% points in operation within the
AI function block. It is possible to set a unit and scale that differs from the measurement
Output scale setup
range.
(OUT_SCALE)
Sets the range unit, input value of the 0% point (lower bound of output scale), input value
of the 100% point (upper bound of output scale), and the 4 data at the decimal point.
Performs simulation of the AI function block.
Simulation setup The input value and status for the calibration range can also be set.
(SIMULATE) It is recommended that this parameter be used for loop checks and other purposes. Refer
to “Simulation Function” in Section 6.3.
Sets the time constant of damping function in seconds.
Damping time constant setup The setting of VOLUME_FLOW_FTIME affects not only flow rate but internal totalization.
(VOLUME_FLOW_FTIME) PV_FTIME of Al function block is a parameter for damping the value of Al OUT. It is
recommended to use PRIMARY_VALUE_FTIME for flowmeter's damping function.
Sets the low cut value which corresponds to the percent against the large absolute value of
PV_SCALE. The hysteresis is 0.5% when the low cut functions and also is released.
LOW_CUT of Al function block is a parameter for low cut of Al OUT. It has 1% hysteresis
Output signal low cut mode setup
when the low cut is released. Do not make LOW_CUT functioned when flow measuring in
(LOW_FLOW_LOWCUT)
reverse direction, or the output is zero at any flow rate because the flow rate is always
regarded as under zero. It is recommended to use LOW_FLOW_CUTOFF for
flowmeter's low cut function.
LCD display setup Sets the unit to be displayed on the LCD and the display speed.
(DISPLAY_SELECT1-3, Adjust display speed if a low temperature environment causes a poor LCD display quality.
DISPLAY_CYCLE)
Performs zero-point adjustment.
Zero-point adjustment
Zero-point adjustment should be done only when the fluid is filled in the flow tube and the
(ZERO_POINT, ZERO_POINT_ADJUST)
fluid velocity is completely zero.

- 38 - IM 01E20C01-20E
A2.2 Setting and Change of Basic Parameters
This section describes the procedure taken to set and change the parameters for each block. Obtaining access to each
parameter differs depending on the configuration system used. For details, refer to the instruction manual for each
configuration system.

Access the block mode (TARGET_MODE) of each block.

(*Note 1) (*Note 2)
Set the TARGET_MODE to Auto, Man or O/S according to
the Write Mode of the parameter to be set or changed.

Access the parameter to be set or changed.

Make setting or change in accordance with each parameter.

(*Note 2)
Set the Target of block mode (TARGET_MODE) back to Auto .

IMPORTANT
Do not turn the power OFF immediately after parameter setting. When the parameters are saved to the
EEPROM, the redundant processing is executed for the improvement of reliability. If the power is turned
OFF within 60 seconds after setting of parameters, changed parameters are not saved and may return to
their original values.
When the consecutive parameter setting to the multiple parameters is not executed via the acyclic data
exchange, the time inverval between each parameter setting must not be within 2 seconds.
Changed parameters may not be written to the device.

Note 1: Block mode consists of the following four modes that are controlled by the universal parameter that displays the running condition of each
block.
TARGET_MODE: Sets the operating condition of the block.
Actual: Indicates the current operating condition.
Permit: Indicates the operating condition that the block is allowed to take.
Normal: Indicates the operating condition that the block will usually take.
Note 2: The followings are the operating conditions which the individual blocks will take.

Totalizer DI
AI Function Transducer Physical
Function Function
Block Block Block
Block Block
Automatic (Auto) Yes Yes Yes Yes Yes
Manual (Man) Yes Yes Yes
Out of Service (O/S) Yes Yes Yes Yes Yes

Refer to the “List of parameters for each block of the ADMAG AXFA11” for details of the Write Mode for each block.

- 39 - IM 01E20C01-20E
A2.3 Setting the AI Function Block
The AI function block outputs the flow rate signals.

(1)Setting the calibration range

Access the PV_SCALE parameter.


Set the necessary unit to VOLUME_FLOW_UNITS in
Transducer Block.
Set the higher range value to Array1 on PV_SCALE.
Set the lower range value to Array2 on PV_SCALE.

Example:
To measure 0 to 100m3/h,
Set m3/h (1349)* to VOLUME_FLOW_UNITS in Transducer Block,
Set 100 to Array1 on PV_SCALE, and
Set 0 to Array2 on PV_SCALE.

(2)Setting the output scale

Access the OUT_SCALE parameter.


Set the necessary unit of output to Units Index on
OUT_SCALE.
Set an output value corresponding to the higher range
value to EU at 100% on OUT_SCALE. Set an output value
corresponding to the lower range value to EU at 0% on
OUT_SCALE. Set the decimal position to Decimal Point.

Example:
To set the output to 0.00 to 100.00kg/h,
Set 100 to EU at 100% on OUT_SCALE,
Set 0 to EU at 0% on OUT_SCALE, and
Set kg/h(1324)* to Units Index on OUT_SCALE,
Set 2 to Decimal Point on OUT_SCALE.

* Each unit is expressed using a 4-digit numeric code.


Refer to Section AI Function Block Parameters.

(3)Setting the fail safe mode

Access the FSAFE_TYPE parameter and set the necessary


fail safe mode.
0: FSAFE_VALUE is used as OUT
Status – Uncertain Initial value
1: The last valid OUT value is used.
Status – Uncertain LastUsebleValue
-- Uncertain Initial value, if no valid value
2: OUT has the wrong calculated value and status.
When FSAFE_TYPE is set to “0”, FSAFE_VALUE must be
set.

- 40 - IM 01E20C01-20E
(4)Simulation
By optionally setting the input value to the calibration range and status, perform simulation of the AI function block.

Access the Simulate Status parameter.


Set the status code.

Access the Simulate Value parameter.


Set an optional input value.

Access the Simulate En/Disable parameter.


Set whether Simulation is enabled or disabled.
Disabled(0) = disabled
Enable(Not 0) = enabled

If simulation is enabled, AI block uses Simulate Status and Simulate Value as the input, and if disabled, the AI block
uses Transducer Status and Transducer Value as input.
Refer to Section 6.3 Simulation Function.

A2.4 Setting the Transducer Block


(1)Setting the damping time constant
Access the VOLUME_FLOW_FTIME parameter.
Set the damping time (in seconds).

(2)Setting the output signal Low Cut


Set the low cut flow rate.

Access the LOW_FLOW_CUTOFF parameter.


Set the value subject to low cut.

(3)Setting the LCD display

Access the DISPLAY_SELECT1-3 parameter and set the


item of display.
ex. DISPLAY_SELECT1
0:Flow Rate(%)
1:Out Value
2:Totalized Flow Rate1
3:Totalized Flow Rate2
4:Totalized Flow Rate3

Access the DISPLAY_CYCLE parameter and set display


cycle.
The display cycle is 200 ms(setting). It defaults to 1(400
ms), but if the LCD display looks unclear when used in lower
temperature environments, increase the value as required.

- 41 - IM 01E20C01-20E
A2.5 Setting the Totalizer Function Block
The Totalizer function block outputs the flow rate signals.

(1)Setting the unit of totalization

Access the UNIT_TOT parameter and set the necessary unit.

(2)Setting the direction of the totalization


Access the MODE_TOT parameter and set the item of the
direction of the totalization.
0: Balanced (Positive and Negative)
1: Positive Only
2: Negative Only
3: Hold

(3)Setting the fail safe mode


Access the FAIL_TOT parameter and set the item of the fail
safe mde.
0: Run
1: Hold
2: Memory

(4)Resetting or presetting TOTAL value


By optionally setting the input value to the calibra-tion range and status, perform simulation of the AI function
block.

Access PRESET_TOT and set the specific value if necessary.

Access SET_TOT and set the item of the operation.


0: Totalize
1: Reset
2: Preset

SET_TOT is returned to “0: Totalizer” automatically. This


means the totalizer function block starts to count up again
immediately after setting.

- 42 - IM 01E20C01-20E
A2.6 Setting the DI Function Block
The DI function block outputs the status generated by the transducer block.

(1)Selection of the status


Access the LIMSW_1_VALUE_D and LIMSW_2_VALUE_D
in the transducer block and set the necessary status.
0: H/L Alarm
1: HH/LL Alarm
2: Adhesion Alarm
3: Adhesion Warning

(2)Selection of the channel

Access the CHANNEL parameter set the necessary channel


shown as below.
0x013E: LIMSW_1_VALUE_D
0x0140: LIMSW_2_VALUE_D

(3)Setting the invert

Access the INVERT parameter and set whether the input


value from the transducer block should be logically inverted.
0: Not inverted
1: Invert

(4)Setting the fail safe mode

Access the FSAFE_TYPE parameter and set the necessary


fail safe mode.
0: FSAFE_VAL_D is used as OUT_D
Status – Uncertain Initial value
1: The last valid OUT_D value is used.
Status – Uncertain LastUsebleValue
-- Uncertain Initial value, if no valid value
2: OUT_D has the wrong calculated value and status.
When FSAFE_TYPE is set to “0”, FSAFE_VAL_D must be
set.

- 43 - IM 01E20C01-20E
(5)Simulation
By optionally setting the input value to the calibration range and status, perform simulation of the DI function block.

Access the Simulate Status parameter.


Set the status code.

Access the Simulate Value parameter.


Set an optional input value.

Access the Simulate En/Disable parameter.


Set whether Simulation is enabled or disabled.
Disabled(0) = disabled
Enable(Not 0) = enabled

If simulation is enabled, DI block uses Simulate Status and Simulate Value as the input, and if disabled, the DI block
uses Transducer Status and Transducer Value as input.
Refer to Section 6.3 Simulation Function.

- 44 - IM 01E20C01-20E