PLUMBING

TYPE OF VENTS
BRANCH VENT A vent connecting one or more individual vents with a vent stack or stack vent

CIRCUIT VENT A branch vent that serves two or more traps and extends from in front of the last fixture
connection of a horizontal branch to the vent stack

COMMON VENT A vent connecting at the junction of two fixture drains and serving as a vent for both fixtures
A single vent that ventiliates multiple traps, in the case of back to back fixture

CONTINOUS VENT A vertical vent that is the continuation of the drain to which the vents connect

DRY VENT A vent that does not serve as drain and is located where if is not exposed to back up
of waste from a drainage pipe

DUAL VENT See common vent

GROUP VENT A branch vents that performs its functions for two or more traps

INDIVIDUAL VENT A pipe installed to vent, a fixture trap and w/c connects with the vent system above the fixture
served or terminates in the open air

LOOP or CIRCUIT VENT A circuit vent which loop backs to connect with a stack vent instead of a vent stack
Any vent connecting a horizontal branch or fixture drain with the stack vent of the
originating waste or soil stack

LOCAL VENT Is a pipe on the fixture side of the trap through which vapor or foul air is removed
from a room fixture

MAIN VENT The principal artery of the venting system to which vent branches may be connected

RELIEF VENT A vent installed so as to permit additional circulation of air between the drainage and vent
systems where the drainage systems might otherwise be air bound

UNIT VENT An arrangement of venting so installed that that one vent pipe will serve two traps

STACK VENT The extension of a soil or waste stack above the highest horizontal drain connected to the
stack horizontal drain, the uppermost end above the roof

WET VENT A vent which also serves as a drain

YOKE VENT A pipe connecting upward from a soil or waste stack to a vent stack for the purpose of
preventing pressure changes in the stack
NATIONAL PLUMBING CODE OF THE PHILIPPINES
BACKFLOW Is the flow of water or other liquids, mixtures or substances into the distributing pipes of a
supply of water from any source other than its intended source
BACK SIPHONAGE Is the backflow of used, contaminated or polluted water from a plumbing
fixture due to negative pressure
BATTERY OF FIXTURE Refers to any group of two or more similar adjacent fixtures which discharge into a common
horizontal waste or soil branch
BLANK FLANGE A flange that is not drilled
BLIND FLANGE A flange that closes the end of a pipe line used to discharge water
CAULKING Is plugging an opening with oakum, lead or other materials
COUPLING A short internally threaded section of pipe, used to join two pipes of conduits
UNION Used to connect the two ends of two pipes, neither of which can be turned
NIPPLE A short length of pipe with threads at each end; used to join couplings or fittings
DEAD END Is the extended portion of a pipe that is closed at one end to which no connections are made
on the extended portion
DEVELOPED LENGTH The length along the center of the pipe and fitting
DRAINAGE SYSTEM Includes all piping within public or private which conveys sewage, rain water or often liquid waste
to a legal point of disposal but does not include the main of a public sewer system or private or
or public sewerage treatment
FIXTURE BRANCH Is a pipe connecting several fixtures
FLOOD LEVEL Is a device located at the bottom of the tank for the purpose of flushing water closets and
and similar fixture
FERRULE A metallic sleeve, join to an opening of pipe, into which a plug is screwed
that can be removed for the purpose of cleaning
INVERT Is the lowest portion of the inside of any pipe or conduit that is not vertical
PLUMBING SYSTEM Includes water supply and distribution pipe; plumbing fixture and traps, soil
waste and vent pipes; house drain and house sewers including their respective connections
ROUGH IN Installation of all parts of the plumbing system which can be completed prior to the installation
of fixtures
SIAMESE CONNECTIONS A wye connections used on fire lines so that two lines of hose maybe connected to the hydrant
or to the same nozzle
SOIL PIPE Is any pipe which conveys the discharge of water closets of fixture having
similar function w/ or w/o the discharge of other fixtures to the building drain
TRAP SEAL Is the maximum vertical depth of liquid that a trap will retain measure between the crown weir
and the top of the dip of the trap
(PLUMBING)
WATER RESERVOIR Install to be able to meet the water requirements during peak demands from a low yielding
water well
SHOCK RELIEF AND EXPANSION The device being used to eliminate the noise cause by water hammer
CHAMBER
50 FEET OR MORE The location of water well to nearest septic vault
2 PERCENT Slope of house sewer connected from the building to the main sewer
CULVERT A passage under a road, embankment or canal which allow for the flow of water
BLACK WATER The third kind of water after the storm water and area water
RECESSED The type of bathtub oher than sunken, square, free standing
WHITE Color coding of high pressure steam
BLACK Color coding for fuel oil division
TRAP OR WATER SEAL The water column that seals the escape of unhealthy gases in the sanitary drainage system
2.50 M Service drop conductor clearance over the roof
COMPRESSION VALVE A valve which in the water flow is shut off by a flat disk that is screwed down onto its seat
CISTERN An underground tank reservoir to store water
OVERHEAD STORM DRAIN Another classification of storm drain, besides from inside drain and outside drain
PRESSURE COCK Tap used in high pressure water system with an interval valve to control the flow of water
PRESSURE REDUCING VALVE A valve which maintains uniform pressure on its outlet side regardless of its pressure fluctuations
on the inlet side above the pressure level
UNION PATENT A pipe fitting within the interconnection of pipes for the purpose of easy dismantling of
the connection when needed
FLUSHOMETER A device that discharge a predetermined volume of water to fixture for flushing purposes and
is activated by direct water pressure
CORPORATION STOP Another name for corporation cock
AIR TRAP A U-shaped pipe filled with water and located beneath the plumbing fixtures
to form a seal against the passages of gases and odors
ABSORPTION TRENCH A trench containing course aggregate and a distribution tile pipe through which septic tank
effluent may flow covered with earth
ILLUMINATION The luminous flux density incident on a surface
CATCH BASIN An underground structure for drainage into which water from the roof or floor will drain through
sewer
WYE FITTING A type of fitting for yoke bent
1 1/2" Minimum discharge pipe and fitting for bath tub
150mm DIAMETER Minimum size of building sewer; it should not be less than the building drain
TRAP SIZES OF FIXTURES
1 1/2" BATH FOOT
2" BATH SHOWER STALL
1 1/2" BATH SITZ
1 1/2" BATH TUB
1 1/2" BIDETS
1 1/2" COMBINATION FIXTURE
1 1/4" DRINKING FOUNTAIN
2" FLOOR DRAIN
1 1/4" FOUNTAIN CUPSIDERS
1 1/2" LAUNDRY TRAYS
1 1/2" SINKS (DISHWASHER)
2' SINKS (HOTEL OR PUBLIC)
1 1/2" SINKS (KITCHEN OR RESIDENCE)
1 1/4" SINKS (SMALL PANTRY OR BAR)
2" SLOP SINKS (ORDINARY)
3" SLOP SINKS (WITH COMBINE TRAP)
3" URINAL (PEDESTAL)
1 1/2" URINALS (LIP)
2" URINALS (STALL)
2" URINALS (THROUGH)
1 1/4" WASH BASIN (LAVATORIES)
3" WATER CLOSETS
TYPES OF WATER CLOSETS
SIPHON-VORTEX Quiet, extermely sanitary. Like the siphon jet but having the flushing water directed through the
rim to create a vortex that scours the bowl
SIPHON-JET Sanitary, efficient very quiet. A toilet bowl into which the flushing water enters through the rim and
siphonic action initiated by a water jet draws the contents of the bowl through the trapway
REVERSE TRAP Moderately noisy. Similar to siphon jet except that trap passageway and water surface area
are smaller
WASH DOWN Minimum cost. Least efficient subject to clogging, noisy. Simple washout and emptying through
small irregular passageway, prohibited by some health codes
BLOW OUT Noisy but highly efficient. Strong jet into leg forces contents out
URINALS
WALL HUNG
THROUGH
PEDESTAL
STALL
BIDET A basin like fixture design to be struddled for bathing the genitals and posterior parts of the body
NOTES
19.05mm or 3/4" No building supply pipe shall be less than WHAT size in diameter
46 mm. Minimum height of Fire Service Connection from the grade/floor
122mm Maximum height of Fire Service Connection from the grade/floor
61 mm. Minimum height of Dry Standpipe Outlet from the floor line
122 mm Maximum height of Dry Standpipe Outlet from the floor line
5 FEET Considered extension of bulding drain outside the building wall
1/4" BEND ? Fitting for base or soil stack and building drain
51mm or 2" Wet standpipe for a riser not more than 15m
64mm or 2 1/2" Wet standpipe for riser more than 15m
4" Dry standpipe for a riser below 23m
6" Dry standpipe for a riser more than 23m
RATIO OF 1:25 Ratio of water closets for female population for elementary and secondary school
RATIO OF 1:30 Ratio of water closets for male population for elementary and secondary school
RATIO OF 1:75 Ratio of urinals for elementary schools
RATIO OF 1:75 Ratio of water closets for female population for principal worship places
RATIO OF 1:5 Ratio of lavatory to number of occupants
4 CLOSETS Minimum number of water closet required for female office and public buildings
3 HEADS Minimum head of water required in section of plumbing for water test

GI PIPE SIZES
1/2", 3/4", 1", 1 1/4", 1 1/2", 2, 2 1/2"
3", 4", 6", 8", 10", 12"

(MECHANICAL)
AIR CONDITIONER An apparatus that can heat, cool, clean and circulate air
BUGLARS AND PROWLERS They were deter to the intrusion alarm system in residential signal system
AIR DUCT An air passage usually formed in sheet metal with insulation for ventilating on a building
DRAUGHT OR DRAFT The current of air or gases
4 STOREY Requirement for a dry standpipe
BLACK Color coding of piping for fuel oil division
DUMBWAITER A hoisting and lowering mechanism with a building equipped with relatively small car
excusively for carrying materials
HUMIDIFIER The device for maintaining desirable humidity conditons in the air supplied
50 GALS. The average consumption of water per capita
THERMOSTAT An automatic control of the operation of heating or cooling device responding to changes of
temperature of the space
BULLDOZER A tractor equipped with the blade attached by arms and bolted to its end, used in piling earth
ACOUSTICAL LAY IN PANEL The acoustical ceiling board design to be laid in an exposed grid suspension system
DECIBEL The total sound units provided by a given material
135-197 F Heat rating for a fixed temperature heat detector
REAR OR TOP Fire tube boliers shall be provide with sufficient room for removal or replacement of tube
either from these places
SOUND ABSORPTION The process of dissipating sound energy by converting it to heat
SOUND INSULATION The system of deadening sound materials to wall, ceiling, floors to prevent sound from passing
through the members into adjoining room
LUX The illuminance produce by luminous flux of the one lumen distributed uniformly over a one
square meter surface
WATER TABLE Level of subterrenean water
AIR HANDLING UNIT Package assembly of air conditioning components which provides for the treatment of the air
before it is distributed to an air conditioned space
TRAVEL TIME This is the criteria in selection of an elevator other than interval and average waiting time
CONCRETE CASING Protection of PVC pipe underground
CREEP Reflection of sound from curve surface
ESCALATOR AND ELEVATOR
TRAVEL TIME The criteria in the selection of an elevator other than interval and average waiting time
FREIGHT ELEVATOR Type of conveyor that transport packages equipment crates
BUFFER Important element of an elevator below the first level floor line that absorbs and minimize
building shocks to the car
PIT That portion of the hoistway in the elevator extending from the threshold level of the lowest landing
floor of the hoistway
WINDING DRUM MACHINE A geared drive machine in which the suspension ropes are fastened to and wind on a drum
GUIDE RAILS Vertical tracks that serves as a guide for the car and the counterweight
MECHANICAL REGULATIONS
ELEVATOR
600mm Car pit clearance depth from the bottom of the car
FOR REPAIR AND INSPECTION When machine room or penthouse is provided at the top of the hoistway, it shall have
a sufficient room for this
2 HOISTWAYS When 4 or more elevator serve all or the same portion of the bulding
4 ELEVATORS Shalll be located in any one hoistway
3 HOISTWAYS Minimum number of hoisting ropes for traction elevators
2 HOISTWAYS Minimum number of hoisting ropes for drum type elevators
30mm Minimum diameter of hoisting and counterweight ropes
OVER LOAD RELAY AND Provision for all elevators
REVERSE POLARITY RELAY
ESCALATOR
35 degrees Minimum angle of inclination of an escalator
558 mm Minimum width of balustrade
1.20 m Maximum width of balustrade
330 mm Maximum width of the steps
TEMPERED TYPE GLASS Kind of glass required in an escalator's balustrade
38 mpm Maximum rated speed measured along the angle of inclination
BOILERS
R.C CONCRETE OR MASONRY Provision for boiler rooms inside the building
3.00 mts. FROM OUTSIDE WALL Minimum distance if the building is not made of fire resistive materials
1 meter No part of the boiler shall be closer to this from the wall
5.00 mts Distance of the smokestacks above the building within 50 mts. radius
2 CHECK VALVES Provision between any feed pump and the boiler in addition to the regular shut-off valve
NON RETURN OR SHUT OFF VALVE Provision when two or more boilers are connected in parallel
ONE SAFETY VALVE Provision of every boiler
TWO SAFETY VALVE Provision for boilers having generating capacity exceeding 907 kg/hr
15 DAYS Notification in writing in advance for boiler's inspection
REFRIGERATION AND AIR CONDITIONING
68deg-74deg F Temperature and humidity of the air to be used for comfortable cooling
2.30 meters ABOVE THE FLOOR Minimum for refrigerant piping crossing a passageway in any building
STOP VALVES Provision of installation for refrigerant system containing more than 9 kgs.
2.13 meters Minimum for window type AC installed on ground floors
PIPING
GALVANIZED PIPING It should not be used for steam
STEAM DIVISION
WHITE High Pressure
BUFF Exhaust Fan
WATER DIVISION
BLUE Fresh Water, low pressure
BLUE Fresh Water, high pressure
GREEN Salt water piping
OIL DIVISION
BRASS OR BRONZE Delivery
YELLOW Discharge
GRAY PNEUMATIC DIVISION
BLACK GAS DIVISION
BLACK FUEL OIL DIVISION
BLACK REFRIGERATING DIVISION
ELECTRICAL TERMS
CIRCUIT BREAKER The part of the cut out that is design to open or break an electrical current under an
excessive load
WATTS Unit of power
AMPERE The unit used in the measure of the rate of flow of electricity
OBSERVATION STANDS This is where an electric service conductor can be installed
TOWER OR FLATFORM
KNIFE SWITCH A type of electric switch consisting of one or more movable copper blades which are hinged
and which make contact with stationary forked contract jaws being forced between them
TRANSFORMER VAULT Provision for building with an expected electric load demand of 200KVA
RECTIFIER The conversion of alternating current (AC) to direct current (DC)
RAPID START FLOURESCENT A kind of flourescent lamp that does not use starter element
LAMP
JUNCTION BOX An iron box or casing by which electrical conduit branches are formed
5 STOREYS A passenger elevator with a constant 24 hour service for residential condominum
3.00 m Minimum service drop of connection line above the ground and from the ground
500 mm Minimum distance of poles and transformer support located from the road right of way
AIR CURTAIN A vertical flow of air used to separate different function of spaces
GOOSENECK Original name of P-Trap
DISTRIBUTION LINE The main feed line of an electrical circuit to which branch circuits are connected
1.20m The minimum width of door in hospital housing unit
PLUG IN TYPE Another type of circuit breaker element other than bolt-on
COPPER WIRE The most practical conductor of electricity
RACEWAY A channel system in carrying electrical wire
CABLE WIRE An electric conductor consisting of a group of smaller diameter conductor strands twisted
together
DISTRIBUTION PANEL Another name for power panel
TRANSFORMER A device used to convert voltage from higher to lower or vise versa
NON FERROUS METAL Metal containing no iron such as copper, brass and aluminum
2.50m The minimum allowance clearance from the highest point of the roof to the service drop
conductor from NBC
STEP DOWN TRANSFORMER To bring down voltage
OPEN WIRING Wiring not concealed by the building sructure
AUTOMATIC TRANSFER SWITCH Transferring the power load from the building circuitry to standby generator or during brownout
AIR SWITCH One with contacts that separate in air
ARC VOLTAGE The voltage across the welding arc
ARMORED CABLE Cable provided in wrapping of metal usually steel wires or tapes, primarily for the purpose
of mechanical protection
ASKAREL A synthetic non-flammable insulating liquid which, when decomposed by an elctric arc
evolves only non-explosive gases
ASSEMBLY Is combination of all or a portion of component parts included in an electric apparatus,
mounted on a supporting frame or panel and properly interwined
BASE LOAD Minimum load over a given period of time
BRANCH CIRCUIT That portion of a wiring system extending beyond the final overcurrent device protecting
the current
BUS Is a conductor, or group of conductors, in switchgear assemblies which serves as a common
connection for two or more circuit
BUSWAY Approved assembly of insulated conductors with fitting and conductor terminations in a
completely enclosed, ventilated protective metal housing where the system is design to carry
fault current and to withstand the magnetic forces of the current
CAGE System of conductor forming an essentially continuous conducting network over the object
protected and including any conductors necessary for interconnections of the object protected
and an adequate ground
CIRCUIT BREAKER A device design to open under abnormal conditions a current carrying circuit without injury
itself
CONDUCTOR A wire or combination of wires not insulated from one another suitable for carrying electric
current
CONTROLLER A device or group of devices which serves to govern in some predetermined manner, the
electric power delivered to the apparatus to which it is connected
CORONA A luminous discharge due to ionization of the air surrounding a conductor caused by voltage
gradient exceeding a certain critical value
CUT OUT BOX A metal housing that houses the circuit breaker or fuses; surface mounted
DEMAND FACTOR Is the ratio of the maximum demand of the system or part of the system to the total connected
load of the system
DEVICE A unit of electrical system which is intended to carry but not utilize electrical energy
DUCT A single enclosed runway for conductor cables
ELECTRIC MOTOR Machine which transforms electric power into mechanical power
FEEDERS The circuit conductors between the service equipment or the generator switchboard of
an isolated plant and the branch circuit overcurrent device
FOOTCANDLE Unit of illumination when the foot is taken as the unit of length. It is the illumination on a surface
one square foot in area in which there is uniformly distributed flux of one lumen
FUSE An overcurrent protective device with a circuit opening fusible member which is heated and
severed by the passage of the overcurrent through it
GENERAL LIGHTING Types of lighting that deals with lighting relatively large area covered
ILLUMINATION Density of the luminous flux on a surface
KNIFE SWITCH Is a form of air switch in which the moving element is a hinge blade wedge between
stationary contact blades when closed
LAMP Artificial source of light
LAMPHOLDER Device for mechanical support of light
LIGHT A radiant energy
LIGHTNING ARRESTER Protective device for limitting surge voltage on equipment by discharging or by-passing
surge current
LIGHTNING SURGE Is a transient electric disturbance in an electric circuit caused by lightning
LINE TAP Is the radial branch connection to a main line
LOAD FACTOR Is the ratio of the average load over a designated period of time to the peak load occuring
in that period
LUMEN Unit of luminous flux
LUX A unit of illumination equal to one lumen per square meter
OUTLET Point of the wiring system at which current is taken to supply utilization equipment
OUTLET BOX A metal box at an outlet which encloses one or more receptacle
PEAK LOAD Maximum load consumed by a unit in a stated period of time
PENDENT Device or equipment which is supended from overhead either by means of the flexible cord
PILOT WIRE Auxillary conductor used in connection with remote measuring devices for operating
apparatus at a distant point
PULLBOX Box with a blank cover which is inserted in one or more runs of raceway to facilitate
pulling in the conductors and the distributing of the conductors
RACEWAY Any channel for holding wires, cables or busbars
RECEPTACLE Convinience Outlet; Contact device installed at an oulet for the connection of an attachment plug

RIGID METAL CONDUIT A raceway especially constructed for the purpose of physical protection
of conductors, the pulling in or the withdrawing of wires or cables after the
conduit is in place and made of metal pipe of standard width and thickness
ROSETTE Enclosure of porcelain or other insulating material fitted with terminals and intended for
connecting the flexible cord carrying a pendent to permanent wiring
SERVICE DROP The overhead service conductor from the last pole or other aerial support to and including splices
if any connecting to the service entrance conductors at the building
SERVICE RACEWAY The raceway that encloses the service entrance conductors
SUBMARINE CABLE Cable designed for service under water
SURGE Is a transient variation in the current potential or power
5.5 mm2 Minimum wire size of THW stranded copper conductor in raceway for a branch circuit in a 30
ampere rating
HERTZ Unit of frequency equal to one cycle per seconds
PHON Unit of loudness of level
REVERBERATION Prolongation of sound as a result of succesive reflection
WAVELENGTH Distance sounds travels during each cycles of vibration
SOUND DIFFRACTION Acoustical phenomenon which causes sound wave to bend or scattered around
SOUND Fluctuation in pressure, a particle displaceent in elastic medium
PURE TONE Sound sensation in a single frequency
CANDELA A luminous intensity of light expressed in candela; Unit of luminous intensity
LUMINAIRE A lighting fixture
LAMBERT Unit of luminance equal to 1 candela per square meter
LUX Unit of illmination equal to one lumen per square meter
FOOT CANDLE Unit of illumination equal to one square foot
LUMINOUS FLUX Rate of flow of light through a surface
IMPEDANCE Resistance in AC system
CONDUCTANCE Reciprocal of resistance
SOUND INTENSITY Rate of flow of sound energy
ACCENT LIGTHING Lighting used primarily to draw attention to particular point of interests
HPS LAMP A type of HID lamp
CONNECTIONS
SINGLE PHASE TO SUPPLY This connetions is used where the load is comparatively small and
120 V LIGHTING LOAD the length of the secondary circuit is short

SINGLE PHASE TO SUPPLY This connections is used in most urban distribution circuits
120/240 3-WIRE LIGHTING
AND POWER LOAD

SINGLE PHASE FOR POWER The 120/240 volt winding is connected in series serving 240 volts on
a two wire system, this connection is used for small industrial applications

TWO PHASE CONNECTIONS Consist merely of two single phase transformers operated 90deg out
of phase, the common wire must carry /2 times the load current

DELTA-DELTA FOR POWER This is used to supply a single phase lighting load and three phase
AND LIGHTING power load simultaneously
OPEN DELTA FOR LIGHTING This connection is used when single phase lighting load is large as
AND POWER compared with the power load

Y DELTA FOR POWER Often it is desirable to increase the voltage of a circuit form a 2400 to 4160 volts to
increase its potential capacity

Y DELTA FOR LIGHTING This connection is similar to the delta-delta bank with only the primary connection changed
AND POWER The primary neutral should not be grounded or tied into the system neutral, since a single
phase ground fault may result in extensive blowing of fuses throughout the system
This connection requires special watt-hour metering

OPEN Y DELTA When operating Y delta and one service is disabled, service maybe maintained at reduced load

DELTA Y FOR LIGHTING The single phase lighting load is all on one phase resulting in unblanced primary currents
AND POWER in any one bank

Y-Y FOR LIGHTING AND The primary voltage was increased from 2400 to 4160 volts to increase the potential
POWER capacity of the system

Y-Y AUTO TRANSFORMER When the ratio of transformation from the primary to secondary voltage is small,
the most economical way of stepping down the voltage

SCOTT CONNECTION In some localities two phase power is required from three phase system
3PHASE TO 2PHASE

SCOTT CONNECTED If it should be necessary to supply three phase power from a two
2PHASE TO 3PHASE phase system, the special tap must be provided on the secondary side

T Thermoplastic
TW Moisture Temperature Resistant
UF Underground Feeder
FEPW Flourinated Ethylene Propylene Moisture Resistant
RH Heat Resitant Rubber
RHW Heat and Moisture Resistant Rubber
RUH Heat Resistant Latex Rubber
THW Moisture and Heat Resistant Thermoplastic
THWN Heat and Moisture Resistant Thermoplstic with Nylon
XHHW Moisture and Heat Resistant Cross Link Polymer
BX Armored Cable
THHN THERMOPLASTIC HEAT RESISTANT
PE POLYETHELENE
SA SILICON ASBESTOS
AVA ASBESTOS AND VARNISH CAMBRIC
HEAT DETECTOR
FIXED TEMPERATURE Use low melting point solders or metal the expand when exposed to heat to detect fire
HEAT DETECTOR 135deg-197deg F
PHOTO ELECTRIC DETECTOR Use of the scattering of light by smoke into view of photo cell through incandescent or diode
INFRARED FLAME DETECTOR It responds to the high-frequency radiant energy from flames. Alarm is only triggered when
IR energy flickers at rate which is chracteristics of flame
IONIZATION SMOKE HEAT Uses the interruption of small current flow between electrodes by smoke in ionized sampling
DETECTOR chamber to detect fire
TYPES OF CABLE
ARMOR CABLE (AC) Fabricated assembly of insulated conductors enclosed in flexible metal
sheath. It is used both on exposed and concealed work

METAL CLAD CABLE (MC) A factory assemble cable of one or more conductors each individualy
insulated and enclosed in a mettalic sheath of interlocking tape of smooth
or corrugated tube. This type of cable is especially used for service feeders,
branch circuit and for indoor, outdoor work

MINERAL INSULATED CABLE (MI) Is a factory assembly of one or more conductors insulated with highly
compressed refractory mineral insulation enclosed in a liquid and gas
tight continous copper sheath. This type of cable is used in dry, wet or
continously moist location as service feeders or branch circuit

NON METALLIC SHEATED Is a also a factory assembly of two or more insulated conductors having
CABLE (NM) a moisture resistant, flame retardant and non metallic material outer
sheath. This type is used specifically for one or two family dwellings not
exceeding 3 storey building

SHIELDED NON METALLIC This type of cable is factory assembly of two or more insulated conductors
SHEATED CABLE (SNM) in an extruded core of moisture resistant and flame retardant material
covered within an overlapping spiral metal tape. This type is used in
hazardous locations and in cable trays or in raceways

UNDERGROUND FEEDER AND Is a moisture resistant cable used for underground connections including
BRANCH CIRCUIT (UF) direct burial in the ground as feeder or branch circuit

POWER AND CONTROL TRAY This is factory assembled two or more insulated conductors with or without
CABLE (TC) associated bare or covered or grounding under a mettalic sheath, This is
used for installation of cable trays, raceways, or it is supported by messenger wire
FLAT CABLE ASSEMBLY (FC) Is an assembly of parallel conductors formed integrally with insulating
material web designed especially for field installation in metal surface or raceways

FLAT CONDUCTOR CABLE (FCC) Consist of three or more flat copper conductor placed edge to edge
separated and enclosed with an insulating assembly. This type of cable is
used for general purposes such as: appliance branch circuit, and for individual
branch circuits, especially in hard smooth continous floor surfaces and the like

MEDIUM VOLTAGE CABLE (MV) Is a single or multi conductor solid dielectric insulated cable rated at 2,000
volts or higher. This type is used for power system up to 35,000 volts
UTILITIES 1999
TELEPHONE TERMINAL CABINET Part of the facility which accept the house cable riser and house the
terminal block at each floor and at the highest or end of a feeder riser cable

TELECOMMUNICATION SYSTEM Is the simplest type of building automation system, which intercoms, PABX,
microwave links, analog and digital telephone system, video conferencing,
satellite links, structured cabling and similar devices

ON EVERY HOSE BIBB A full open type valve is used in several locations in a water distribution
system, which of the following does NOT require it?

DRY STANDPIPE A fireline system without a constant water supply and is equipped with a fire service
inlet and outlet connection installed exclusively for the use of Fire Service

WATER SERVICE PIPE Term used to main water pipe delivering portable water to a building

INSUFFICIENCY IN THE SIZE OF Which poor design in the plumbing system causes water supply drop
THE WATER SERVICE AND when the fixture is simultaneously opened?
DISTRIBUTION PIPE

1 ½" KITCHEN SINK TRAP SIZE


1 ¼" LAVATORY TRAP OR BRANCH SIZE
64mm or 2 ½" OUTLET OF DRY STANDPIPE
64mm or 2 ½" OUTLET OF WET STANDPIPE for riser of more than 15 mts

SLOPE OF THE DRAIN PIPE Not needed in sizing the vent pipe for individual branch and circuit vent
based on the total linear footage of the pipe making up the vent?

3 WAY VALVE DIVERTER A hot and cold water supply pipes, where it is mix manually in desired water temperature
temperature and direct the mixed water either at the shower head or at the fooe spout

BALL VALVE Principle where a single lever valve used in kitchen sink and lavatory, they are
beautiful and maintenance free

132 LITERS PER MINUTE Minimum water delivery in liters per minute for an outlet of a wet standpipe
at a residual pressure or 1.8 kilos per sq.mts

ELBOW REDUCER A female GI threaded pipe reducer fitting use to connect a reducing branch pipe at an angle

FLUSH VALVE FITTINGS General term used to described the fitting in the drawing

2" WYE AND 2 x 1/8 GI fitting used to accept the P trap assembly of the lavatory (drawing)
BEND COMBINATION

CIRCUIT VENT Type of vent applied on installations with multi branch interval where the vertical vent pipe
takes off in front of the first fixture and connects to a main vent stack

REVERSE OSMOSIS Stage in water purification which removes mineral deposits, slats, heavy metal, totally dissolves
solids while some useful minerals are retained

FIXED TEMPERATURE Fire detector installed in a fire alarm system, which uses low melting point
HEAT DETECTOR solders or metals that expand when exposed to heat to detect a fire, 135deg-197deg F

COUPLING GI fitting to join two threaded fittings as close as possible but not exceeding three inches

PRESSURE REGULATOR A device used to control an incoming high water pressure into the water distribution system
by mechanical means so as to bring it to a working pressure of 80 psi

WRONG CHOICE OF VENT TYPE A poor venting system caused by a slow draining of water from
a fixture down a plumbing system

SUBMERSIBLE PUMP A type of pump for driven well from 150 to 200 ft which work by a principle of venturi where
jet,jack,reciprocating water of high pressure is pump into the well to draw water upwards through the return pipe

AT EVERY BRANCH INTERVAL Which of the following does not require the installation of the cleanout?
OF SOIL STACK

5" Which is not a standard size of GI pipe for water supply? 2 1/2", 3",4",5"

URINAL FLASH VALVE ASSEMBLY Device in control valve which work by discharging instantaneous
volume of water at higher pressure
TAIL PIECE or DEAD END Term used for pipe extension of not more than 2 feet in length install in
any stack or branch of a plumbing rough in for the purpose of future trap

CHECK VALVE A full open valve located in a supply pipe to every water heater

120 LITERS For cold water, a family members of 12 needs a 3.6 cu.mts. of cold water.
What is the maximum hot water probable hour demand?
110 100 120 140 liters

AUTOMATED RETRACTABLE Parking management system for two types of vehicular deterrent either articulated arm type
PILLAR SYSTEM or straight beam type. It can be activated by means of radio frequency remote control, push
push button switch, photocell, magnetic loop or acces control

THREE FIXTURES Exception of fixture to be connected into a single trap

DRY STANDPIPE The presence of Fire Service Connection

POLTYBUTELENE PIPE Pipes and fittings which can exclusively be used for cold water lines for
AND FITTINGS potable main distribution water service, sprinkler and irrigation system. It
could be ½", ¾", 1", 1 ½", 1 ¼" and 2"

UPVC DWV SANITARY Orange or brown in color with sizes of 4" and 3 meter in lengths of pipes
PIPES AND FITTINGS and fittings, ASTM 2729 standards

ASBESTOS PIPE Least popular and not recommended use as potable water distribution pipe

SINGLE LEVER BATH FAUCET Shower set for bath (drawing)


WITH HAND SHOWER-
TELEPHONE SHOWER

FIBER CEMENT PIPE Pipe not used as water service pipe

GATE VALVE A cut off valve installed in the service piping system

64mm or 2 1/2" Minimum size of wet standpipe for a riser more than 15 meters from the source

61 cms Minimum height of dry standpipe outlet from the floor line

AIR CHAMBER Device used to prevent water hammering

VENT SIZE IS AT LEAST 1/2 THE Rule of tumb in sizing an individual vent
DRAIN IT SERVES BUT NOT LESS
THAN THE REQUIRED MINIMUM
W/C EVER IS LARGER

FAN COIL UNIT Mechanical equipment coupled with a central air conditioning system used
to dehumidify and cool the airstream injected to the conditioned space

1.5 TIMES MORE THAN THE Spacing provided for elevator with single bank in a non residential building
ELEVATOR CAR DEPTH

DOWN COLLECTIVE CONTROL Recording calls even when car is in use. It answer calls starting from the
highest and so on while descending

UP COLLECTIVE CONTROL Recording calls even when car is in use. It answer calls starting
from the lowest and so on while ascending

GOVERNOR Safety device of a passenger elevator which activates if the car travels faster
safety gear, safety shoe than its rated speed by grasping the guide rail to stop the car safely
magnetic break

main drive chain, step chain, handrail ESCALATOR'S PART


drive chain, bottom sprocket

PORTABLE GAS HOT FIRED WATER BOILER PARTS

ONE IN FRONT OF THE OTHER When planning a multiple system of elevator layout where four or
more elevator are arrange in banks

1120;980;800;760 Nominal size of an escalator; escalator's width like those in Japanese brand

1150;1100;1000;900 Nominal size of an escalator; escalator's step like those in Japanese brand

105 mts per min. Which is not the standard speed of electric traction type passenger
elevators for low to medium rise buildings

ADJUSTABLE LOCKING Type of dampers installed at supply ducts, which are electro-mechanically
DAMPERS activated by building automation system to close in case of fire within the area

AT THE ESCALATOR Location of Control System or computer brain of the escalator


MACHINE ROOM
12 to 14 SQ.MT PER TON OF This is a guide for the initial estimate per Ton of Refrigeration per sq.mts. of a standard
REFRIGERATION room of normal condition without external solar heat gain and excessive internal heat gain

International Standard and EN 81.1 Code in designing a machine room


PIPING OR DUCT BELONGING TO OTHER SYSTEM SHOULD NOT RUN
THROUGH THE MACHINE ROOM
OPENING BETWEEN HE MACHINE ROOM AND THE SHAFT MUST BE FULLY OPENED
TO ALLOW EASY ACCESS
VENTILATION MUST BE SUFFICIENT IN ORDER TO MAINTAIN INDOOR TEMPERATURE
OF 5 TO 40 DEGREES
ONLY HOIST MACHINE MOTOR ASSEMBLY, CONTROL PANEL AND AUXILLARY
EQUIPMENT FOR FIRE FIGHTING ARE ALLOWED INSIDE

STANDARD INSTALLATION OF ESCALATOR NOT EXCEEDING 4.50 MTS./ TRUSS


THE TOP CHORD OF THE TRUSS IS WITH A STEEL ANGLE SUPERIMPOSED
ON THE BUILDING'S STRUCTURAL BEAM

COUNTERWEIGHT BUFFER Main purpose of pit of the elevator shaft space

PRESSURE RELIEF VALVE Safety device caused by insufficient water flow on heater when brown out

EXPANDED POLYTHELYNE Vital part of Solar Water heater to keep the heat in and cold out
FOAM INSULATION

KNOCKDOWN BY MAJOR Packaging and assembly of elevator as it arrives on the site


COMPONENT PART

GOODS WITH PERSON Category of the elevator ISO 4190.1


SERVICE LIFTS FOR GOOD
PASSENGER ONLY
TRANSPORTS OF BED

COOLING TOWER Cool the condenser unit in a central conditioning system

SINGLE POLE SWITCH AT START, Two lights in a long hallway connected in parallel are to be controlled simultaneously at
3-WAY SWITCH AT MIDPOINT AND three points
SINGLE POINT SWITCH AT END

POWER AND CONTROL TRAY Factory assembled of two or more insulated conductors w/ or w/o
CABLE TYPE associated bare cover ground conductor under a non metallic sheath
approved forr installation in cable trays, in raceways or in supported by a messenger wire

RH Heat Resistant Rubber / 75 degrees

METAL HALIDE Light source used in lighting fixtures best specified in areas such as those requiring high illumination
levels for detailed work such as needle work

SCOTT CONNECTION 2 PHASE A transformer location required in some localities, where a three phase
TO 3 PHASE power is required from a two phase system

TW Moisture Resistant Thermoplastic / 60 degrees

ILLUMINATED SWITCH Type of switch where pilot light inside a lit to guide the person inside

85 amperes Ampacity of an insulated copper conductor, based on ambient temperature of 30degrees


w/a 22 sq.m cross sectional area in size for USE

LOW SWITCH EMITTING DIODE Switch wiring device; Identify all (Brochure)
4-WAY NON APPELATION SWITCH

DRAWINGS Main power supply and wiring system for 110/220 volt line; which wiring diagram fits (drawing)

7500mm to 9000mm What is the maximum horizontal range between two or more air terminal for lightning
5000mm to 6000mm arrest for an effective disaster prevention in building
10000mm to 12000mm
6000mm to 7600mm

550mm; 700mm An air terminal for lighting arrest is distanced at 7600mm. What must be the least height of the
600mm; 850mm air terminal above the building part being protected for disaster prevention

15 amperes Ampacity of an insulated copper conductor, based on ambient temperature of 30degrees


w/a 2.0 sq.m cross sectional area in size for TW

PVC IS ALLOWED FOR AS LONG AS Best suited for Rigid Nonmetallic Conduit like PVC for underground installation in buildings
BOTH BURIAL DEPTH OF NO LESS
460mm AND CONCRETE
ENCASEMENT IS PROVIDED

ULTRASONIC Higher than 20,000 Hertz

SABINS Unit of acoustic absorption equivalent ot absorption by one square root


of a perfect absorber
AVOIDING ZONES OF DIRECT First defense method from external noise by site selection and site
SOUND planning for quiet internal acoustic environment

INSTALL ABSORBENT MATERIALS The effective method can be employed to reduce direct noise, which is transmitted airborne,
WITHIN THE WALL OF THE for noise reduction within a space
ENCLOSURE

SOUND TRAVELS SLIGHTLY LOWERThis does not describe the velocity of sound correctly
(FASTER)MOIST AIR THAN IN
DRY AIR

7,380 fps Sound with a wavelength of 1.50 m at Frequency 1,500 Hz

INTENSITY Perceptual characteristic of sound which is the average rate of flow of


energy per unit area perpendicular to the direction of propagation

UTILITIES

VENT PIPE It ventilates a house drainage system and prevent siphonage and back pressure

3/8" It is the size of supply valve tank type for water closet

6 FEET The maximum horizontal developed length between the trap seal and the
vertical vent inlet at the trap

2x2" WYE WITH 2" CO AND Combination fitting between the vertical waste branch and the horizontal waste branch
2 X 1/8 BEND

COUPLING REDUCER A female GI pipe reducer fitting used in straight connection, both are threaded inside

CIRCUIT VENT A vent use in battery of plumbing fixture where the vent is installed in front
of the last fixture of the battery

JET, SUBMERSIBLE A water pump for a 200ft driven well to deliver 10gpm against 200ft. It is
TURBINE, SUMP located at the surface

RECIPROCATING A pump motor installed on the surface attached to a lift and push a rod to
CENTRIFUGAL, PISTON, TURBINE activate a submerge piston

TO FACILITATE AIR MOVEMENT The purpose of a branch vent slope of 1/4"


WITH LESSER RESISTANCE

RECIPROCATING A pump with an impeller enclose in a housing coupled with the pump motor
CENTRIFUGAL, PISTON, TURBINE Its principle is to add a velocity to already flowing liquid

CENTRIFUGAL, SUBMERSIBLE A pump which delivers high water discharge with high water pressure drawn
JET, TURBINE from a shallow source like cistern, best suited as fire or transfer pump.
The motor is placed at the surface with shaft to turn the impellers below

46 mm Minimum height of Fire Service station rom the grade

BELL REDUCER A female GI pipe reducer fitting use to connect a reducing branch from
a main water distribution

POLYETHELENE PIPE PE

WATER DISTRIBUTION PIPES General term for hot or cold water pipes containing portable water supplying
different plumbing fixture

AT BRANCH SUPPLY DUCT AS Where are dampers install to regulate the amount of cool air fo an even
FAR AS PRACTICAL FROM THE distribution of outlets
OUTLET

SEASONAL ENERGY EFFICIENCY Rating index of an air conditioning system which rate the number for the unit
of BTU heat moved per watt of electrical input energy

TONS OF REFRIGERATION Standard unit rating to describe the capacity of the cooling tower

BOTTOM SPROCKET Prime movers that drives the escalator parts


GEARED HOIST
HELICAL GEARED MOTOR WITH
TRANSMISSION REDUCTION
CONTROL SYSTEM-PROGRAM
MABLE UNIT

STANDARD ISO 4190.1 ELEVATOR CATEGORY


Pasenger use in which goods may be carried
Goods accompanied by persons
Passenger elevator
Service elevator for goods only
A European brand of elevator
GOLDSTAR-KOREA
KOPPEL A.W.
DOVER
OTIS-U.S.

5.500 mm Required minimum vertical clearance of an overhead service drop measured from the ground
over residential and comercial properties and driveways not subjected to truck traffic and over
600 volts to ground

Required minimum vertical clearance of an overhead service drop measured from the ground
over public streets, alleys, roads, parking areas subjected to truck traffic, driveways on other
than residential property, and other land traveresed by vehicular such as cultivated, grazing
forest and courtyards

BUSWAYS Approved assembly of insulated conductors with fitting and conductor


terminations in a completely enclosed, ventilated protective metal housing
where the system is design to carry fault current and to withstand the
magnetic forces of such current

RIGID STEEL CONDUIT A raceway especially constructed for the purpose of physical protection
of conductors, the pulling in or the withdrawing of wires or cables after the
conduit is in place and made of metal pipe of standard width and thickness

120/240 VOLTS System of voltage used for computing branch circuits and feeder load

WINDMILL Natural energy source derived from force of wind acting on oblique blades
that radiates froma shaft attached to a dynamo to produce electricity

PANEL BOARD A point in th electrical system where the electrical load of a given area
is assumed to concentrate

SINGLE PHASE ALTERNATING Alternating current generated by the alternator where its wave rises to the
CURRENT peak, sinks to zero, drops to the negative peak and rises again to zero a
number of times each second depending on the frequency for which the
machine is designed

TWO PHASE ALTERNATING Alternating current where the alternator comprises of windings mounted
CURRENT at right angles to each other and provided with separate external connections
current waves will be produced and each of which will be at its maximum
when the other is zero

2.2, 30, 8, 14 Minimum conductor size for for overhead service drop for copper wire or cable

UF Underground Feeder, 60-75 degrees C

THW Moisture and Heat Resistant Thermoplastic used for dry and wet locations

REFRACTION The physical behavior of sound when travelling forward in a straight path
changes in direction as it passes through different densities and causes
the sound waves to bend

UTILITIES
38 mm (1 1/2") Standard size of wet standpipe outlet for each floor

WYE FITTING A type of pipe fitting for yoke vent

6" The minimum horizontal clearance of vent branch immediately above the flood
level rim of the fixture

THERMOSTAT A device installed on electric water heater used to detect the working temperature to
to activate a switch

1 1/2" The minimum size or trap of a bidet

3/8" Supply valve tank type for water closet

COUPLING A threaded fitting to join two threaded fittings as closed as possible but
not exceeding 3 inches

AT EVERY BRANCH INTERVAL OF Location that does not require installation of clean out
A SOIL STACK

BATTERY OF FIXTURE Interconnection of the same fixture in one soil or waste branch with one branch vent

COMMON VENT A single vent that ventiliates multiple traps, in the case of back to back fixture

NUMBER OF FIXTURE A parameter in sizing the drainage pipe

SOIL PIPE Conveys a discharge of solid and liquid wastes closets with or without the
discharged from other fixture to the house drain
102 mm (4") Minimum size of standpipe for a building in which the highest outlet is 23 m
or less from the Fire service Connection

UPFEED OR DIRECT METHOD In water distributon system which constantly rely its pressure from the main water pipe apply only
if the main fixture is supply continously with the flow rate and minimum required working pressure

PLUMBING SYSTEM System of building which includes the water supply distribution pipes the
fixture and fixture traps, the soil waste and the vent pipes, the house drain
and the house sewer, the storm water drainage with their devices

64 mm (2 1/2") Minimum size of wet standpipe for riser of more than 15 mts from source

6" Minimum height of a branch vent above the fixture it is venting

SIAMESE CONNECTIONS Common term for a two way service connections

BALL Single level valve used in kichen sink, lavatory faucets or at shower valve

NUMBER OF BRANCH VENTS A parameter in sizing a horizontal soil branch pipe

1/4", WYE and 1/8" BEND, LONG Fitting installed at the base of the soil stack and a building drain
SWEEP, 1/8" and 1/8" COMBINATION

12 TO 14 SQ.MTR/TR Guide for initial estimate of Ton of refrigeration

JET PUMP WITH INJECTOR A suitable type of water pump for deep well 4" or 6' casing to deliver
JACK, CENTRIFUGAL 35gpm against 450 ft. total develop height
SUBMERSIBLE

ZEOLITE Passing on it can treat hardwater

CIRCUIT VENT Vertical vent pipes take in front of the last fixture and connects to its soil
stack which acts as a vent

BUFFER A safety device of a passenger elevator which reduces the collision shock
of a car or counterweight due to over travel beyond the lowest stop. It
It stops the car or counterweight safely

SEASONAL ENERGY ENERGY Rating index of an air conditioning system which rates the unit for the number
EFFICIENCY RATING for BTU of heat moved per watt of electrical input energy

PHASE FAILURE RELAY Internal electronic safety features of an escalator. They function as a
DRIVECHAIN AND HANDRAIL GOV safety switches or detectors which monitors internal mechanical or
SKIRTING PANEL SWITCH electrical abnormalities and shuts down the system in any eventuality
MONITORING CONTACTS ON
STEP CHAIN

CIRCUIT BREAKER A passenger elevator safety device which protects the motor and its
ELECTRICAL PANEL BOX electrical parts from over current
PULL BOX
ELECTRONIC CONTROL PANEL

SAFETY SHOE The elevator door components that detect the obstacle during the door closing and re opens
SAFETY GEAR the door
OUTSIDE DOOR LATCH
DOOR LOCK SWITCH

AIR CURTAIN Mechanical equipment install on top of the main doors used to retain cold in the interiors

WAIT INTERVAL Dividing the travel length by the rated speed

EVAPORATORS CANNOT BE Major physical restriction does a split type air conditioner system have which restricts
LOCATED AT CEILING its efficiency and performance

CONDENSER AND EVAPORATOR Not ideal physical installation of a split type air condition
ARE INSTALLED AT THE SAME
LEVEL W/ 15 MTS. DEVT. DISTANCE

EMERGENCY STOP SWITCH Activate by preventing the door to open during elevator car run,
SAFETY SHOE the door elevator will open only when the car stops at the floor
OUTSIDE DOOR LATCH
DOOR LOCK SWITCH

SAFETY SHOE Opening of door for passenger in case of power failure in the elevator
OUTSIDE DOOR LATCH
DOOR LOCK SWITCH
SAFETY GEAR

MAGNETIC BREAK Activate if the car travel faster than its travel speed, the power will turn off,
SAFETY SHOE and grasp the rope to operate the safety gear
CIRCUIT BREAKER
GOVERNOR
FOR CAR OVERRUN Main purpose of shafts overhead space

LIMIT SWITCH Device that open and closes the electric current in an elevator when it has reached the
EMERGENCY SWITCH designated end of travel course
TRAVEL SWITCH
MOTOR CONTROL SWITCH

FAN COIL UNIT Coupled with central air conditioning system, used to dehumidify and cool
the air stream injected into the conditioned space

CIRCUIT BREAKER A device designed to open and close a circuit by non automatic means
and to open the circuit automatically on predetermined over current
without damaged to itself when properly applied within its rating

SERVICE RACEWAY The raceway that encloses the service entrance conductors

Y-Y FOR LIGHTING AND POWER A transformer connection which is ideal in the event of change of primary
voltage from 2400 volts to 4160 volts to increase the potential capacity of
the system

24 AMPERE Maximum allowed ampere rating of one chord or plug utilization equipment connected in a 30
ampere branch circuit for lighting or utilization equipment

5.5 sq.mm Minimum wire size in sq.mm type THW stranded copper conductor in raceway for a branch
circuit with 30 ampere rating

3500mm Minimum vertical clearance of an overhead service drop measured from the ground, at the
electrical service entrance or above areas or sidewalks accesible only to pedestrian lanes,
measure from final grade line or other accesible surface only for service drop cabled together
with a grounded bare messenger wire and limited to 300 volts to ground

30 amperes Minimum ampacity of feeder conductor with a load of more than two wire branch circuit supplied
by a 3-wire feeder but not exceed the computed branch circuit load

3.5 sq.m Minimum wire size in sq.mm type TW copper conductor in raceway for a branch circuit with 20
ampere rating

45 Amperes Ampacity of an insulated copper conductor, based on ambient temperature of 30degrees


w/a 8 sq.m cross sectional area in size for THW

MULTI WIRE BRANCH CIRCUIT A branch circuit consisting of two or more grounded conductors having a potential difference
between them, and a grounded conductor having equal potential difference between it

A CLEARANCE OF NOT LESS THAN Pre requisite in use of split knob and tube wiring
76mm SHALL BE MAINTAINED
BETWEEN CONDUCTORS AND NOT
LESS THAN 26mm

PRESSURIZED WATER REACTOR A type of water coolant operates at a pressure of about 150 atmospheres

DEVICE A unit of electrical system which is intended to carry but not utilize electrical energy

BUSWAYS Approved assembly of insulated conductors with fitting and conductor


terminations in a completely enclosed, ventilated protective metal housing
where the system is design to carry fault current and to withstand the
magnetic forces of such current

60 CYCLES Standard frequency of water supply by the company like Meralco

USE Underground Service Entrance / 75degrees

SERVICE DROP The overhead service conductor from the last pole or other aerial support
to and including the splices, if any connecting to te service entrance
conductors at the building

BOILING WATER REACTOR A type of nuclear reactor where the water coolant is permitted to boil
within the core by operating at somewhat low pressure

BALANCE LOADING In a 240V, a three phase 3-wire service, branch cicuits are loaded and distributed to each
of the three phase with this objective to attain

CABLE TRAYS Unit or assembly of unit sections and associated fittings forming a rigid structural system
used to support cables

OPEN DELTA FOR LIGHTING A transformer connection where the secondary load is a combination of
AND POWER lighting and power. This connection is used when the single phase lighting
is large as compared with the power load

DELTA Y FOR LIGHTING AND A useful transformer connection applied when single phase lighting load is
POWER all on one phase resulting into unbalanced primary

ARMOR CABLE TYPE ACL Type of flexible cable which is a fabricated assembly of insulated conductors
which permit its use at exposed weather or excessive moisture
THREE PHASE ALTERNATING A type of alternating current where the alternator comprises the three
CURRENT armature windings set at 120 degrees to each other, current will be
produced in the form of triple wave

30 amperes Minimum branch circuit rating for household ranges and cooking appliance

POROUS ABSORBENT Type of sound absorbent best for lower band frequencies

HERTZ Unit of frequency which is equal to one cycle per second

SINGLE PHASE ALTERNATING A type of alternating current generated by alternator, where its wave rises to
CURRENT its peak, sinks to zero, drop to a negative peak and rises again to zero
a number of times each seconds depending on the frequency of the
machine is designed
MORE STUDIES INTERNET
LABEL OF DRAWINGS
CATEGORIES OF ELEVATOR
ELEVATOR
ESCALATOR
PUMPS
VALVES
LIGHTNING ARRESTER
SERVICE DROPS
NBC
NPCP
FORMULA OF TL
CYCLE OF FAN COIL UNIT

NEED TO BE RESEARCHED (SUMMARIZED)


NATIONAL PLUMBING CODE
Combination fitting between the vertical waste branch and the horizontal waste branch
2 x 2 WYE WITH 2" CO AND 2 x 1/8 BEND
2 x 1/4 BEND
4 x 2 WYE WITH 2" CO AND 2 x 1/4 BEND
2 x 2 TEE WITH 2" CO

LOCATION 8 Fitting in water closet in its order of sequence from the floor drain to the soil branch
2" P-TRAP 2x1/4 BEND 4x2 TEE
2" P-TRAP 2x1/16 BEND 4x2 TEE
2" P-TRAP 2x1/8 BEND 4x2 TEE
2" P-TRAP 2x1/4 BEND 2x1/8 BEND 4x2 WYE

Fitting installed at the branching tee from a horizontal soil branch to a horizonal waste branch
4 x 2 WYE AND 2" 1/8 BEND COMBINATION
4 x 4 TEE
4 x 2 TEE
4 x 4 WYE AND 4" 1/8 BEND COMBINATION

LOCATION 13 Fitting assembly joining the bare lavatory and the 2" tapped tee
1 1/4" DIAMETER STRAINER WITH POP UP VALVE
1 1/2" DIAMETER TAIL PIECE WITH POP UP VALVE
1 1/2" DIAMETER P-TRAP WITH POP UP VALVE
1 1/4" DIAMETER P-TRAP WITH POP UP VALVE

LOCATION 12 Use to accept the P-trap assembly of the lavatory


2" SANITARY TEE
2" TEE
2" TAPPED TEE
2" WYE AND 2 x 1/8 BEND COMBINATION

Fitting installed at the base of the soil stack and a building rain
1/4 BEND
LONG SWEEP BEND
WYE AND 1/8 BEND COMBINATON
1/8 BEND AND 1/8 BEND COMBINATION

A parameter in sizing horizontal branch pipe


NUMBER OF SOIL OR WASTE BRANCH
AMOUNT OF FALL OF THE PIPE
NUMBER OF BRANCH VENTS
TYPE OF VENTING SYSTEM
PUMPS
SUBMERSIBLE PUMP A type of pump for driven well from 150 to 200 ft which work by a principle of venturi where
jet,jack,reciprocating water of high pressure is pump into the well to draw water upwards through the return pipe

RECIPROCATING,TURBINE A pump motor installed on the surface attached to a lift and push a rod to
CENTRIFUGAL, PISTON activate a submerge piston

JET, SUBMERSIBLE A water pump for a 200ft driven well to deliver 10gpm against 200ft. It is
TURBINE, SUMP located at the surface

RECIPROCATING,TURBINE A pump motor installed on the surface attached to a lift and push a rod to
CENTRIFUGAL, PISTON activate a submerge piston
RECIPROCATING A pump with an impeller enclose in a housing coupled with the pump motor
CENTRIFUGAL, PISTON, TURBINE Its principle is to add a velocity to already flowing liquid

CENTRIFUGAL, SUBMERSIBLE A pump which delivers high water discharge with high water pressure drawn
JET, TURBINE from a shallow source like cistern, best suited as fire or transfer pump.
The motor is placed at the surface with shaft to turn the impellers below

JET PUMP WITH INJECTOR A suitable type of water pump for deep well 4' or 6' casing to deliver
JACK, CENTRIFUGAL 35gpm against 450 ft. total develop height
SUBMERSIBLE
ELEVATOR
BUFFER A safety device of a passenger elevator which reduces the collision shock of a car or
counterweight due to over travel beyond the lowest stop. It stops the car or counterweight safely

PHASE FAILURE RELAY Internal electronic safety features of an escalator. They function as a
DRIVECHAIN AND HANDRAIL GOV safety switches or detectors which monitors internal mechanical or
SKIRTING PANEL SWITCH electrical abnormalities and shuts down the system in any eventuality
MONITORING CONTACTS ON
STEP CHAIN

CIRCUIT BREAKER A passenger elevator safety device which protects the motor and its
ELECTRICAL PANEL BOX electrical parts from over current
PULL BOX
ELECTRONIC CONTROL PANEL

OUTSIDE DOOR LATCH During elevator emergency to rescue passenger, this type of elevator is used to open the door
from the outside

SAFETY SHOE The elevator door components that detect the obstacle during the door closing and re opens
SAFETY GEAR the door
OUTSIDE DOOR LATCH
DOOR LOCK SWITCH

WAIT INTERVAL Dividing the travel length by the rated speed

EMERGENCY STOP SWITCH Activate by preventing the door to open during elevator car run,
SAFETY SHOE the door elevator will open only when the car stops at the floor
OUTSIDE DOOR LATCH
DOOR LOCK SWITCH

SAFETY SHOE Opening of door for passenger in case of power failure in the elevator
OUTSIDE DOOR LATCH
DOOR LOCK SWITCH
SAFETY GEAR

MAGNETIC BREAK Activate if the car travel faster than its travel speed, the power will turn off,
SAFETY SHOE and grasp the rope to operate the safety gear
CIRCUIT BREAKER
GOVERNOR

FOR CAR OVERRUN Main purpose of shafts overhead space

LIMIT SWITCH Device that open and closes the electric current in an elevator when it has reached the
EMERGENCY SWITCH designated end of travel course
TRAVEL SWITCH
MOTOR CONTROL SWITCH

GOVERNOR Safety device of a passenger elevator which activates if the car travels faster
SAFETY GEAR than its rated speed by grasping the guide rail to stop the car safely
SAFETY SHOE
MAGNETIC BREAK

International Standard and EN 81.1 Code in designing a machine room


PIPING OR DUCT BELONGING TO OTHER SYSTEM SHOULD NOT RUN THROUGH
THE MACHINE ROOM
OPENING BETWEEN HE MACHINE ROOM AND THE SHAFT MUST BE FULLY OPENED
TO ALLOW EASY ACCESS
VENTILATION MUST BE SUFFICIENT IN ORDER TO MAINTAIN INDOOR TEMPERATURE
OF 5 TO 40 DEGREES
ONLY HOIST MACHINE MOTOR ASSEMBLY, CONTROL PANEL AND AUXILLARY
EQUIPMENT FOR FIRE FIGHTING ARE ALLOWED INSIDE

STANDARD INSTALLATION OF ESCALATOR NOT EXCEEDING 4.50 MTS./ TRUSS


THE TOP CHORD OF THE TRUSS IS WITH A STEEL ANGLE SUPERIMPOSED ON THE
BULDING'S STRUCTURAL BEAM

STANDARD ISO 4190.1 ELEVATOR CATEGORY


Pasenger use in which goods may be carried
Goods accompanied by persons
Passenger elevator
Service elevator for goods only
Transports of bed

A European brand of elevator


GOLDSTAR-KOREA
KOPPEL A.W.
DOVER
OTIS-U.S.

ESCALATOR
BOTTOM SPROCKET Prime movers that drives the escalator parts
GEARED HOIST
HELICAL GEARED MOTOR WITH
TRANSMISSION REDUCTION
CONTROL SYSTEM-PROGRAM
MABLE UNIT

AT THE ESCALATOR Location of Control System or computer brain of the escalator


MACHINE ROOM

main drive chain, step chain, handrail ESCALATOR'S PART


drive chain, bottom sprocket

1120;980;800;760 Nominal size of an escalator; escalator's width like those in Japanese brand

1150;1100;1000;900 Nominal size of an escalator; escalator's step like those in Japanese brand
ELECTRICAL
SINGLE POLE SWITCH AT START, Two lights in a long hallway connected in parallel are to be controlled simultaneously at
3-WAY SWITCH AT MIDPOINT AND three points
SINGLE POINT SWITCH AT END

DRAWINGS Main power supply and wiring system for 110/220 volt line; which wiring diagram fits (drawing)

A CLEARANCE OF NOT LESS THAN Pre requisite in use of split knob and tube wiring
76mm SHALL BE MAINTAINED
BETWEEN CONDUCTORS AND NOT
LESS THAN 26mm

MULTI WIRE BRANCH CIRCUIT A branch circuit consisting of two or more grounded conductors having a potential
difference between them, and a grounded conductor having equal potential difference between it

550mm; 700mm An air terminal for lighting arrest is distanced at 7600mm. What must be the least height of the
600mm; 850mm air terminal above the building part being protected for disaster prevention

7500mm to 9000mm What is the maximum horizontal range between two or more air terminal for lightning
5000mm to 6000mm arrest for an effective disaster prevention in building
10000mm to 12000mm
6000mm to 7600mm

5500 mm Required minimum vertical clearance of an overhead service drop measured from the ground
over residential and comercial properties and driveways not subjected to truck traffic
and over 600 volts to ground

Required minimum vertical clearance of an overhead service drop measured from the ground
over public streets, alleys, roads, parking areas subjected to truck traffic, driveways on other
than residential property, and other land traveresed by vehicular such as cultivated, grazing
forest and courtyards

3500mm Minimum vertical clearance of an overhead service drop measured from the ground, at the
electrical service entrance or above areas or sidewalks accesible only to pedestrian lanes,
measure from final grade line or other accesible surface only for service drop cabled together
with a grounded bare messenger wire and limited to 300 volts to ground

24 amperes Maximum allowed ampere rating of one chord or plug utilization equipment connected in a 30
ampere branch circuit for lighting or utilization equipment
30 amperes Minimum ampacity of feeder conductor with a load of more than two wire branch circuit
supplied by a 3-wire feeder but not exceed the computed branch circuit load
85 amperes Ampacity of an insulated copper conductor, based on ambient temperature of 30degrees
w/a 22 sq.m cross sectional area in size for USE
45 amperes Ampacity of an insulated copper conductor, based on ambient temperature of 30degrees
w/a 8.0 sq.m cross sectional area in size for THW
15 amperes Ampacity of an insulated copper conductor, based on ambient temperature of 30degrees
w/a 2.0 sq.m cross sectional area in size for TW
5.5 sq.mm Minimum wire size in sq.mm type THW stranded copper conductor in raceway for a branch
circuit with 30 ampere rating
3.5 sq.m Minimum wire size in sq.mm type TW copper conductor in raceway for a branch circuit with
20 ampere rating
30 amperes Minimum branch circuit rating for household ranges and cooking appliance