STRESSING REPORT

PROJECT : Park Land Condo TK DATE : 15/06/2020


FLOOR / ZONE : GF (+0.1m) / Zone 4 PAGE : 1 of 5
Theoretical [Left].Jack No. 15/70 [Right].Jack No. 34 Total After
Strand Slip
Elongation [Left].Pump No. 15/70 [Right].Pump No. 34 Elongation Tranfer
Remark
(mm.) Elongation At Scale Reading (mm.) (mm.) (mm.)
No. (mm.)
0.95 1.00 1.05 75.0% 80.0% 75.0% 80.0% L R
1 227 239 251 68 50 236 62 44 6 Checked
2 25 32 86 103 246 28 97 4 Checked
3 227 239 251 40 75 230 37 68 4 Checked
4 45 70 230 43 64 2 Checked
5 35 40 75 88 238 35 83 4 Checked
6 159 167 175 83 166 78 2 Checked
7 87 174 82 2 Checked
8 94 188 89 2 Re Stress
9 87 174 83 1 Checked
10 227 239 251 45 80 250 39 76 4 Checked
11 75 50 250 64 46 9 Checked
12 48 78 252 42 73 5 Checked
13 225 237 249 91 35 252 86 30 4 Checked
14 38 90 256 32 85 5 Checked
15 104 14 236 99 11 2 Checked
16 128 135 142 67 134 63 1 Checked
17 57 65 122 61 1 Checked
18 69 138 65 1 Checked
19 70 140 66 1 Checked
20 67 134 64 0 Checked
21 128 135 142 69 138 63 3 Checked
22 68 136 60 5 Checked
23 65 130 60 2 Checked
24 225 237 249 54 70 248 50 67 1 Checked
25 63 61 248 53 56 9 Checked
26 65 60 250 59 54 6 Checked
27 227 239 251 31 35 78 100 244 31 93 5 Checked
28 82 43 250 74 37 8 Checked
29 67 58 250 63 53 3 Checked
30 219 230 242 79 45 248 71 40 7 Checked
31 64 62 252 60 58 2 Checked
32 53 73 252 48 68 4 Checked
33 227 239 251 80 45 250 74 41 4 Checked
34 73 54 254 67 50 4 Checked
35 62 64 252 56 60 4 Checked

Checking By Site Engineer : SUPERVISED BY :


APPROVED BY :
STRESSING REPORT
PROJECT : Park Land Condo TK DATE : 15/06/2020
FLOOR / ZONE : GF (+0.1m) / Zone 4 PAGE : 2 of 5
Theoretical [Left].Jack No. 15/70 [Right].Jack No. 34 Total After
Strand Slip
Elongation [Left].Pump No. 15/70 [Right].Pump No. 34 Elongation Tranfer
Remark
(mm.) Elongation At Scale Reading (mm.) (mm.) (mm.)
No. (mm.)
0.95 1.00 1.05 75.0% 80.0% 75.0% 80.0% L R
36 180 189 198 111 222 107 1 Re Stress
37 102 204 97 2 Checked
38 98 196 93 2 Checked
39 103 206 97 3 Checked
40 100 200 96 1 Checked
41 227 239 251 66 54 240 61 50 3 Checked
42 52 80 264 48 75 3 Re Stress
43 91 100 16 22 229 96 15 5 Checked
44 90 43 266 83 37 7 Re Stress
45 135 142 149 68 136 64 1 Checked
46 71 142 64 4 Checked
47 71 142 65 3 Checked
48 37 39 41 22 44 18 1 Re Stress
49 20 40 15 2 Checked
50 20 40 14 3 Checked
51 37 39 41 20 40 14 3 Checked
52 21 42 16 2 Checked
53 20 40 16 1 Checked
54 39 41 43 22 44 18 1 Checked
55 22 44 16 3 Checked
56 23 46 19 1 Re Stress
57 72 76 80 30 35 65 30 2 Checked
58 32 38 70 33 2 Checked
59 34 40 74 35 2 Checked
60 32 38 70 33 2 Checked
61 33 41 74 36 2 Checked
62 72 76 80 37 74 32 2 Checked
63 40 80 35 2 Checked
64 38 76 33 2 Checked
65 39 78 34 2 Checked
66 39 78 35 1 Checked
67 72 76 80 39 78 35 1 Checked
68 40 80 35 2 Checked
69 101 106 111 56 112 52 1 Checked
70 54 108 49 2 Checked

Checking By Site Engineer : SUPERVISED BY :

APPROVED BY :
STRESSING REPORT
PROJECT : Park Land Condo TK DATE : 15/06/2020
FLOOR / ZONE : GF (+0.1m) / Zone 4 PAGE : 3 of 5
Theoretical [Left].Jack No. 15/70 [Right].Jack No. 34 Total After
Strand Slip
Elongation [Left].Pump No. 15/70 [Right].Pump No. 34 Elongation Tranfer
Remark
(mm.) Elongation At Scale Reading (mm.) (mm.) (mm.)
No. (mm.)
0.95 1.00 1.05 75.0% 80.0% 75.0% 80.0% L R
71 56 112 51 2 Checked
72 0 0 56 112 52 1 Checked
73 0 0 45 60 90 55 2 Checked
74 101 106 111 49 53 102 48 2 Checked
75 0 0 48 54 102 50 1 Checked
76 101 106 111 51 102 48 0 Checked
77 0 0 47 55 102 50 2 Checked
78 0 0 48 60 108 54 3 Checked
79 0 0 48 53 101 50 0 Checked
80 0 0 53 106 50 0 Checked
81 104 109 114 50 54 104 50 1 Checked
82 0 0 51 60 111 55 2 Checked
83 0 0 55 110 50 2 Checked
84 0 0 55 110 50 2 Checked
85 0 0 50 57 107 54 0 Checked
86 104 109 114 53 106 49 1 Checked
87 0 0 56 112 51 2 Checked
88 0 0 62 124 55 4 Re Stress
89 0 0 55 110 49 3 Checked
90 0 0 53 106 49 1 Checked
91 104 109 114 50 56 106 51 2 Checked
92 0 0 50 57 107 52 2 Checked
93 0 0 49 57 106 52 2 Checked
94 0 0 50 59 109 54 2 Checked
95 0 0 53 106 50 0 Checked
96 78 82 86 38 43 81 40 0 Checked
97 0 0 39 78 35 1 Checked
98 0 0 42 84 38 1 Checked
99 0 0 38 43 81 38 2 Checked
100 0 0 40 80 36 1 Checked
101 81 85 89 40 46 86 39 4 Checked
102 0 0 40 46 86 40 3 Checked
103 81 85 89 37 44 81 41 0 Checked
104 0 0 36 41 77 37 1 Checked
105 0 0 44 88 41 0 Checked

Checking By Site Engineer : SUPERVISED BY :

APPROVED BY :
STRESSING REPORT
PROJECT : Park Land Condo TK DATE : 15/06/2020
FLOOR / ZONE : GF (+0.1m) / Zone 4 PAGE : 4 of 5
Theoretical [Left].Jack No. 15/70 [Right].Jack No. 34 Total After
Strand Slip
Elongation [Left].Pump No. 15/70 [Right].Pump No. 34 Elongation Tranfer
Remark
(mm.) Elongation At Scale Reading (mm.) (mm.) (mm.)
No. (mm.)
0.95 1.00 1.05 75.0% 80.0% 75.0% 80.0% L R
106 0 0 0 44 88 41 0 Checked
107 0 0 34 50 84 45 2 Checked
108 81 85 89 45 90 41 1 Checked
109 0 0 42 84 39 0 Checked
110 0 0 43 86 38 2 Checked
111 0 0 40 45 85 40 2 Checked
112 0 0 44 88 40 1 Checked
113 81 85 89 37 46 83 43 0 Checked
114 0 0 41 82 38 0 Checked
115 0 0 39 47 86 42 2 Checked
116 0 0 39 44 83 39 2 Checked
117 0 0 40 44 84 40 1 Checked
118 81 85 89 40 46 86 43 0 Checked
119 0 0 39 45 84 41 1 Checked
120 0 0 39 48 87 43 2 Checked
121 0 0 40 49 89 46 0 Checked
122 0 0 41 82 36 2 Checked
123 81 85 89 48 96 43 2 Re Stress
124 0 0 46 92 42 1 Checked
125 0 0 43 86 38 2 Checked
126 0 0 45 90 40 2 Checked
127 0 0 36 47 83 40 4 Checked
128 81 85 89 34 48 82 40 5 Checked
129 0 0 38 44 82 41 0 Checked
130 0 0 38 46 84 43 0 Checked
131 0 0 39 45 84 41 1 Checked
132 0 0 38 44 82 40 1 Checked
133 79 83 87 40 80 34 3 Checked
134 0 0 39 45 84 39 3 Checked
135 0 0 40 80 36 1 Checked
136 79 83 87 43 86 39 1 Checked
137 0 0 44 88 38 3 Checked
138 0 0 40 80 35 2 Checked
139 0 0 44 88 41 0 Checked
140 0 0 38 43 81 40 0 Checked

Checking By Site Engineer : SUPERVISED BY :


APPROVED BY :
STRESSING REPORT
PROJECT : Park Land Condo TK DATE : 15/06/2020
FLOOR / ZONE : GF (+0.1m) / Zone 4 PAGE : 5 of 5
Theoretical [Left].Jack No. 15/70 [Right].Jack No. 34 Total After
Strand Slip
Elongation [Left].Pump No. 15/70 [Right].Pump No. 34 Elongation Tranfer Remark
(mm.) Elongation At Scale Reading (mm.) (mm.) (mm.)
No. (mm.)
0.95 1.00 1.05 75.0% 80.0% 75.0% 80.0% L R
141 79 83 87 40 80 36 1 Checked
142 0 0 44 88 38 3 Checked
143 0 0 38 43 81 39 1 Checked
144 0 0 35 39 74 32 4 Checked
145 0 0 38 42 80 36 3 Checked
146 79 83 87 37 44 81 40 1 Checked
147 0 0 40 80 35 2 Checked
148 0 0 41 82 36 2 Checked
149 0 0 38 44 82 39 2 Checked
150 0 0 40 80 37 0 Checked
151 72 76 80 38 76 34 1 Checked
152 0 0 34 41 75 36 2 Checked
153 72 76 80 32 38 70 31 4 Checked
154 0 0 34 37 71 33 1 Checked
155 0 0 35 39 74 35 1 Checked
156 0 0 34 38 72 32 3 Checked
157 0 0 34 38 72 34 1 Checked
158 72 76 80 38 76 35 Checked
159 0 0 35 38 73 34 1 Checked
160 0 0 36 72 33 0 Checked
161 0 0 34 36 70 34 -1 Checked
162 0 0 44 88 41 0 Re Stress

Checking By Site Engineer : SUPERVISED BY :

APPROVED BY :