Earth Leakage Monitor
Earth Leakage Monitor is one important device used in DC power systems like battery chargers AC-DC
converter systems, DC-DC converter systems and DCDBs. Where an independent DC power source is
used, the connections between transducers, control units and DC power source are very important.
Monitoring and signalling of earth faults is essential in these situations, HBL ELM enables quick
detection of earth faults so prompt corrective action can be taken.
————
Earth leakage current monitoring and protection
‘of DC power supply systems and wiring with
local and remote alarm / annunciation
Every outgoing feeder can be monitored
individually
Reliable and rugged as any short circuit at load
end will not affect the system configuration
Low power consumption
‘Compact
| Princip! fo) ole) ola) |
HBL make ELM (Earth Leakage Monitor)
works on the residual or differential magnetising
current induced in a current transformer.
The two current carrying conductors (positive
and negative) are passed through a ring type
current transformer. Under normal conditions
there is no residual current in the CT as the
current flow in the two conductors is in opposite
direction.
In the event of earth-fault the current flowing
through the conductors will be different and this
difference gives rise to a residual / magnetizing
Current in the CT. The CT forms a part of
magnetic oscillator which would oscillate
symmetrically when there is no magnetizing
current in core.
‘The magnetizing current which is proportional to
the fault leakage current is sensed and used to
drive an LED and a relay through a comparator
for local and remote (potential free contacts)
annunciation.
‘The ELM is provided with a test button which can
be used to check the correct functioning of the
device during operation. HBLTechnical Specifications
11
20V ELCM|
DC system voltage 24-48V 110-220v
Auxiliary voltage Not required Not required
Current rating 258 25a
Sensitivity mA /20MA (+/-3mA) ‘5mA/20mA (+/-3MA)
Power consumption 2.5W 2.5W
Operating temperature -25 to +60t -25 to +60
Relay output Potential free Potential free
SPOT Contacts SPDT Contacts
rated 24V, 124 DC rated 24V, 12A DC
250V, 108 AC 250v, 108 AC
Local LED LeD
Extendable Relay contacts Relay contacts
Reset Manual (factory Manual (factory
settable auto settable auto
reset is available) reset Is available)
Physical Dimensions &
Mounting.
‘Mounting Suitable for top hat rail Suitable for top hat rail
Dimensions
(Height, Width, Depth in mm) 70 x 50 x 112 70 x 50 x 112
NOTE: 63A/10mA, 1254/20mA, 200A/20mA also supplied on special case based on customer request
Applications
HBL’s Earth Leakage Monitors can be widely used in Petro-chemical industries, Chemical,
Process industries and Substations.
Installation Requirements
‘Systems with floating power supply or centre of power supply grounded / earthed are compatible
with these ELMs. Systems with either positive and negative earthing are not compatible.
untrations, data, menses and weaghls gen mths rochure ae for glance ony and cant be hel ingame company.
HBL
HBL Power Systems Limited
#8-2-601, Road No.: 10, Banjara Hills, Hyderabad - 500034, TG, INDIA
website : www.hbl.in
e-mail : contact@hbl.in