BEF Calculation - Part 5
BEF Calculation - Part 5
Settings Requirements
Rated current = VA / (¥3 x VL)
Rated current = 10 x 106 / (¥3 x 11000) = 525A
Assigned through fault current (rated stability limit) = 16 x load current = 8.4kA. See section 2.2.1
Required Primary Operate Current (Fault Setting)
10 – 25% of protected winding rated current, or as specified by the user.
POCprov (10 – 25% of Irated) = 52.5 - 131A. Say 60A. (0.1A secondary). See section 2.2.2
Metrosil Specification
For values < 8kW/s the integral 75mm Metrosil is suitably rated.
VFint 2
P1SEC t Where: VFint t 4 (VK 3 x Rshunt x IFint) x 1.3
Rstab
2800
IFint 14A
200
VFint t 4 (VK 3 u Rshunt u IFint) x 1.3
VFint t 4 (450 3 x 2200 x 14 u 1.3 1683 V
2
1683
P1SEC t 1287 W
2200
Vs = 120V
10MVA
11kV
1/600
1/600
27
7PG23
Rshunt
28
Settings Requirements
Rated current = VA / (¥3 x VL)
Rated current = 10 x 106 / (¥3 x 11000) = 525A
Assigned through fault current (rated stability limit) = 16 x rated current = 8.4kA. See section 2.2.1
Required Primary Operate Current (Fault Setting)
10 – 25% of protected winding rated current, or as specified by the user.
POCprov (10 – 25% of Irated) = 52.5 - 131A. Say 60A. (0.1A secondary). See section 2.2.2
Metrosil Specification
For values < 8kW/s the integral 75mm Metrosil is suitably rated.
VFint 2
P1SEC t Where: VFint t 4 (VK 3 x Rshunt x IFint) x 1.3
Rstab
2800
IFint 14A
200
VFint t 4 (VK 3 u Rshunt u IFint) x 1.3
VFint t 4 (450 3 x 2700 x 14 u 1.3 1771V
2
1771
P1SEC t 1161W
2700
Vs = 120V