Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
This manual concerns the alternator AVR which you have just purchased.
We wish to draw your attention to the contents of this maintenance manual.
SAFETY MEASURES
2
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
CONTENTS
2 - POWER SUPPLY................................................................................................................ 5
2.1 - AREP excitation system................................................................................................5
2.2 - PMG excitation system..................................................................................................6
2.3 - SHUNT or separate excitation system...........................................................................7
3 - TECHNICAL CHARACTERISTICS.....................................................................................8
3.1 - Electrical characteristics................................................................................................8
3.2 - Configurations............................................................................................................... 8
3.3 - U/F and LAM functions................................................................................................12
3.4 - Typical effects of the LAM with a diesel engine with or without a LAM (U/F only)......... 12
3.5 - AVR options ................................................................................................................ 13
4 - INSTALLATION - COMMISSIONING................................................................................14
4.1 - Electrical checks on the AVR.......................................................................................14
4.2 - Setting up.................................................................................................................... 14
4.3 - Electrical faults............................................................................................................ 17
5 - SPARE PARTS.................................................................................................................. 18
5.1 - Designation................................................................................................................. 18
5.2 - Technical support service............................................................................................18
3
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
1 - GENERAL INFORMATION 1.2 - Identification
1.1 - Description There are 2 different versions available:
The R450 AVR is supplied in a casing - R450 M: single-phase sensing
designed to be mounted on a panel with - R450 T: three-phase sensing
dampers. These 2 AVRs are exactly identical in terms
- Operating temperature: - 40°C to + 65°C of characteristics and dimensions with
- Storage temperature: - 55°C to + 85°C “Mate N Lok™” connectors.
- Shocks on the base: 9 g depending on the
3 axes. 1.3 - Tools
- Vibrations: less than 10 Hz, 2 mm The “Mate N Lok™” connectors tools
half-peak amplitude. references are the following:
10 Hz to 100 Hz: 100 mm/s, above 100 Hz: - Crimping pliers: Ref TYCO 654.149.1
8 g. - Extractor: Ref TYCO 539.972.1
WARNING
WARNING
The AVR is IP00, it must be incorporated
in an environment which ensures it a Connectors must be unlocked before
IP20 protection. unpluging.
140 mm
R450 M DETECT. 1 PH
1 PH. SENSING
50 Hz EXT FREQ
60 Hz SETTING R450 T DETECT. 3 PH
3 PH. SENSING
50 Hz EXT FREQ
60 Hz SETTING
P1 Voltage
Rotating switch
VOLT.
VOLT.
ONLY FOR
ONLY FOR
65Hz
65Hz
SPECIAL
SPECIAL
CONFIG.
CONFIG.
EXT.FREQ.
EXT.FREQ.
LSA 49 / 50
LSA 49 / 50
LSA 49 / 50
LSA 49 / 50
7000 / 8000 2
7000 / 8000
7000 / 8000 2
7000 / 8000
LAM OFF
LAM OFF
RAPIDE
RAPIDE 3
RAPIDE
RAPIDE 3
LAM
LAM
LAM
LAM
OFF
OFF
VOLTAGE 320V ~ 530V
KNEE
ON
ON
P2
FAST 2
FAST
FAST 2
FAST
VOLTAGE 80V ~ 320V
SERIES
SERIES
SERIES
SHUNT
SHUNT // AREP
7
7
8
8
SET.
SET.
9
- Voltage
3
3
6
78 78
STAB. I EXC
STAB. I EXC
PMG
PMG
PMG
3
3
3
3
2
2
2
- Excitation
90 1
90 1
56
56
0 0 0 0
5
0
50Hz
50Hz
60Hz
60Hz
4
1 1 23 1 1 23
AREP
1k
1k
1 5000 / 6000
1 5000 / 6000
0 NORMAL
0 LSA 46 / 47
0 NORMAL
0 LSA 46 / 47
1 NORMAL
1 NORMAL
4
4
1
1
NORMAL
NORMAL
NORMAL
NORMAL
3
2
3
2
LSA 46 / 47
LSA 46 / 47
5000 / 6000
5000 / 6000
SERIES
SERIES
SERIES
SERIES
MODE 1
MODE 1
MODE 1
MODE 1
MODE 2
MODE 2
MODE 2
MODE 2
LAM
LAM
LAM
LAM
LAM
LAM
LAM
LAM
LAM
LAM
LAM
LAM
OFF
OFF
OFF
OFF
S1
S1
P3
S2
S2
Excitation
200 mm
175 mm
STAT.
STAT.
LEDS
LEDS
Overrun indications
P4
Quad
FUSIBLES / FUSES
FUSIBLES / FUSES
droop
Fuses 10A
SEE NOTICE
VOIR NOTICE
SEE NOTICE
VOIR NOTICE
F- X2 Z1 F- X2 Z1
nc V W F+ Z2 X1 C US U V W F+ Z2 X1 C US
R450 M R450 T
4
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
2 - POWER SUPPLY to the alternator main voltage (Shunt
Both the AREP & PMG excitation systems characteristic), the second one has a
are controlled by the AVR. voltage proportional to the stator current
(compound characteristic : Booster effect).
2.1 - AREP excitation system The power supply voltage is rectified and
With AREP excitation, the electronic AVR is filtered before being used by the AVR
powered by two auxiliary windings which monitoring transistor.
are independent of the voltage sensing The rotating switch should be in the AREP
circuit. position (see 3.2.3).
The first winding has a voltage proportional
Field
5+ 6-
T5 T11
10 Yellow
R450 T DETECT. 3 PH
3 PH. SENSING
50 Hz EXT FREQ
60 Hz SETTING
P1 Voltage
VOLT.
ONLY FOR
65Hz
SPECIAL
CONFIG.
EXT.FREQ.
LSA 49 / 50
LSA 49 / 50
7000/ 8000 2
7000/ 8000
LAM OFF
RAPIDE
RAPIDE 3
P2
LAM
LAM
OFF
VOLTAGE 320V ~ 530V
KNEE
ON
FAST 2
FAST
SERIES
SERIES
Stability
SHUNT / AREP
SET.
9
3
78
STAB. I EXC
PMG
3
3
2
2
90 1
56
0 0
5
0
50Hz
60Hz
1 1 23
P3
1k
1 5000 /6000
0 NORMAL
0 LSA 46 / 47
1 NORMAL
Excitation
NORMAL
NORMAL
3
2
LSA 46 / 47
5000 /6000
SERIES
SERIES
MODE 1
MODE 1
MODE 2
MODE 2
LAM
LAM
LAM
LAM
LAM
LAM
OFF
OFF
S1
S2
P4 Quad
droop
STAT.
LEDS
FUSIBLES / FUSES
SEE NOTICE
VOIR NOTICE
F- X2 Z1
U V W F+ Z2 X1 C US
X2 10 Yellow
(*) Z1 11 Red
Z2 12 Black
X1 9 Green
(*) same connection for R450 M: W -> T3, V -> T2, nc -> T1
5
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
2.2 - PMG excitation system The AVR monitors the alternator output
With PMG excitation, a permanent magnet voltage by adjusting the excitation current.
generator (PMG) added to the alternator The rotating switch should be in the PMG
supplies the AVR with voltage which is position (see 3.2.3).
independent of the main alternator winding.
These two excitation principles provide the
machine with a short-circuit current overload
capacity of 3 IN for 10 s.
PMG
Field
5+ 6-
T4 T10 T5 T11 T6 T12
15
16
R450 T DETECT. 3 PH
3 PH. SENSING
50 Hz EXT FREQ
60 Hz SETTING
14 P1 Voltage
VOLT.
ONLY FOR
65Hz
SPECIAL
CONFIG.
EXT.FREQ.
LSA 49 / 50
LSA 49 / 50
7000/ 8000 2
7000/ 8000
LAM OFF
P2
RAPIDE
RAPIDE 3
LAM
LAM
OFF
VOLTAGE 320V ~ 530V
KNEE
ON
FAST 2
FAST
SERIES
SERIES
Stability
SHUNT / AREP
SET.
9
3
78
STAB. I EXC
PMG
3
3
2
2
90 1
56
0 0
5
0
50Hz
60Hz
1 1 23
P3
1k
1 5000 /6000
0 NORMAL
0 LSA 46 / 47
1 NORMAL
Excitation
NORMAL
NORMAL
3
2
LSA 46 / 47
5000 /6000
SERIES
SERIES
MODE 1
MODE 1
MODE 2
MODE 2
LAM
LAM
LAM
LAM
LAM
LAM
OFF
OFF
S1
S2
P4 Quad
droop
STAT.
LEDS
FUSIBLES / FUSES
SEE NOTICE
VOIR NOTICE
F- X2 Z1
U V W F+ Z2 X1 C US
(*)
16
15
14
(*) same connection for R450 M: W -> T3, V -> T2, nc -> T1
6
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
2.3 - SHUNT or separate excitation
system
With SHUNT excitation, the AVR is powered
by the main winding (100V to 140V - 50/60
Hz ) by using X1, X2 on the AVR.
The rotating switch should be in the AREP
position (see 3.2.3).
Field
5+ 6-
T4 T10 T5 T11 T6 T12
R450 T DETECT. 3 PH
3 PH. SENSING
50 Hz EXT FREQ
60 Hz SETTING
P1 Voltage
VOLT.
ONLY FOR
65Hz
P2
SPECIAL
CONFIG.
EXT.FREQ.
LSA 49 / 50
LSA 49 / 50
7000/ 8000 2
7000/ 8000
LAM OFF
RAPIDE
RAPIDE 3
LAM
LAM
OFF
VOLTAGE 320V ~ 530V
KNEE
ON
FAST 2
FAST
SERIES
SERIES
Stability
SHUNT / AREP
SET.
9
3
78
STAB. I EXC
PMG
3
3
2
2
90 1
56
0 0
5
0
50Hz
60Hz
1 1 23
P3
1k
1 5000 /6000
0 NORMAL
0 LSA 46 / 47
1 NORMAL
Excitation
NORMAL
NORMAL
3
2
LSA 46 / 47
5000 /6000
SERIES
SERIES
MODE 1
MODE 1
MODE 2
MODE 2
LAM
LAM
LAM
LAM
LAM
LAM
OFF
OFF
S1
S2
P4 Quad
droop
STAT.
LEDS
FUSIBLES / FUSES
SEE NOTICE
VOIR NOTICE
F- X2 Z1
U V W F+ Z2 X1 C US
(*)
X1
X2
(*) same connection for R450 M: W -> T3, V -> T2, nc -> T1
7
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
3 - TECHNICAL CHARACTERISTICS 3.2.1.2 - Quadrature droop:
3.1 - Electrical characteristics Quadrature droop adjustment via
- Maximum power supply: 150V - 50/60 Hz potentiometer P4 within a range:
- Rated overload current: 10 A - 10 s - From 0 to 8% with a PF=0.8 for 400V
- Electronic protection: applications.
- in the case of a short-circuit, the excitation - From 0 to 14% with a PF=0.8 for 240V
current is reduced to a value less than 1A applications.
after 10 s - From 0 to 8% for 110V applications with a
- in the event of loss of voltage reference, step-up transformer (ratio of 4) placed on
the excitation current is reduced to a value
the voltage reference.
less than 1A after 1s for AREP/SHUNT, 10s
for PMG The potentiometer P4 has a non linear
- in the event of overexcitation, the current response. Then, when a 1A secondary CT is
is reduced as indicated in the next diagram connected the effective range starts from
(see 3.2.1.4) the the second 1/3 of P4 range and in the
- Fast acting fuses: F1 on X1 and F2 on Z2 case of a 5A secondary CT the effective
10A, 250V range starts from the first 1/3.
- Voltage sensing When a 5A CT is used, the adjustment range
R450 M: single-phase connection to V and is higher, so P4 must be set to the first 1/4
W. “80V-320V” or “320V-530V” according to (anti-clockwise) and then progressively
the rotating switch position. increase it.
R450 T: three-phase connection to U, V and
W. “80V-320V” or “320V-530V” according to WARNING
the rotating switch position.
For other voltages, a transformer should be The CT must be connected.
used (or two for R450 T). 3.2.1.3 - Stability:
- Voltage regulation:± 0.5% Stability adjustment via potentiometer P2.
- Current sensing: (parallel operation): input Selection of rotating switch according to the
S1, S2 intended for 1 C.T. > 2.5 VA cl1, machine type and the response time as
secondary 1 A or 5 A indicated in paragraph 3.2.3.
3.2 - Configurations 3.2.1.4 - Excitation limitation:
3.2.1 - Settings Excitation limitation adjustment via
3.2.1.1 - Voltage potentiometer P3 as described below.
Voltage adjustment via potentiometer P1 in The excitation current limitation threshold in
the ranges described in the table below: steady state is set by a potentiometer at
For 50 and 60 Hz Max.
110% of the rated value. The adjustment is
High range 320 V < Un ≤ 530 V
made by the operator during the on-load test
Medium range 80 V ≤ Un ≤ 320 V
at rated power by tuning the potentiometer.
When the excitation current exceeds this
value, a counter is activated at the speed of
WARNING one record per second for 90 s. When this
time is elapsed, the current is reduced to the
The allowed adjustment range is ±5%; value of the rated excitation current. If in the
when the setting exceeds these limits, meantime the excitation current drops
please check that it is conform with the below the threshold value, the counter
power table. counts down at the same speed.
8
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
current. In all operating conditions the
WARNING maximum excitation current is clamped to
9.5 A ± 0.5 A.
The limitation threshold must be
Overrun indications:
adjustable between 1 and 5.5 A. The
genset breaker must be open during the One green LED:
short circuit. If the genset is restarted in - Lights up when the excitation current is
short circuit, there is a excitation build below the continuous operation threshold
up during 10s again at the maximum It signals the AVR normal operation.
value. - Turns off when the excitation current ceiling
used to obtain short-circuit operation is
Operation between 3 and 6 In when reached and when the excitation current is
short-circuited: reduced to the shutdown value.
The excitation current ceiling during a - Flashes when the over excitation timer is
short-circuit equals 2.9 times the fixed decrementing.
threshold when setting the permitted
excitation ceiling in continuous operation. NB: After the short circuit is cleared, the
When the threshold is exceeded for a period output voltage is limited to about 70% of the
= 10 s the current is reduced to a value rated voltage. This avoids no load
between 0.5 and 0.7 A (shutdown). overvoltage for machine which no load
NB: Even if the AVR is limiting the exciter exciter current is less than the shutdown
current (only in AREP).
field current to a value less than 1A, the
generator will continue to supply the fault
I exc(A)
Diagram 1
2.9x I threshold 9.5
(Maximum current I exc)
(max. 9.5 A)
P3
I threshold
(1...5.5A)
t(s)
Shutdown Activation of
Activation of
0.5 ~ 0.7 90 s tempo. Decrease of
Activation of 10 s tempo. 10s tempo. elapsed :
90 s tempo.
90 s tempo. shutdown apllication
Red led
Green led
9
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
I exc(A)
Diagram 2
2.9x I threshold (Maximum current I exc)
(max. 9.5 A) 9.5
P3
I threshold
(1...5.5A)
t(s)
Shutdown
Activation of 90 s. tempo elapsed : application
0.5 ~ 0.7 90 s. tempo of permanent limitation
Red led
Green led
Red LED:
- Lights up simultaneously with the green led
when the continuous operation threshold is WARNING
reached for more than 90 s and the excitation
current is reduced to the continuous In the case of overload protection
operation threshold. It is used to set the activation, a voltage drop will appear
excitation current ceiling with a value sometimes higher than 10%
- Turns off when the excitation current is less of the reference voltage.
than the setting value
The UnderVoltage protection is not
- Flashes when the excitation current is
achieved by the AVR. Customer must
above the continuous operation threshold
ensure that his installation load is
during less than 90 s.
correctlyprotectedagainstundervoltage.
When the green led is off: During load rejection, the overvoltage is
-flashes in a case of loss of voltage sensing observed and takes a few seconds to be
<1s or 10s for PMG excitation. cleared.
-turns on if Iex= Ishutdown.
10
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
3.2.2 - Rotating switch selection: LAM 3.2.3 Rotating switch: excitation type
and U/F and time response
EXT.FREQ. 50Hz
SHUNT/AREP
LAM
LAM SET. 0 OFF
ON 9 LAM
1 MODE 1 RAPIDE 3 0 NORMAL
LAM 8 90 1 2 LAM
OFF MODE 2 FAST NORMAL
3
23
78
LAM
0
ONLY FOR 3
7 OFF
4 56
SPECIAL
CONFIG. LAM
1
4
2
KNEE 6
MODE 1 RAPIDE NORMAL
5 LAM
1 NORMAL
65Hz 60Hz
MODE 2 FAST 2
PMG
LAM OFF
SERIES
2 SERIES
LSA 49 / 50 LSA 46 / 47
(Tractelec application and variable speed 7000 /8000 2 1 5000 /6000
above 1800 rpm). VOLTAGE 80V ~ 320V
- Pos 7: Special (not used).
- Pos 8: Change in the voltage according to 0: Voltage from 320 to 530V
the U/F ratio, knee-point position at 48 Hz or - LSA 46/47 - 5000 / 6000 series
58 Hz according to selection of the frequency
by an external contact. 3: Voltage from 320 to 530V
- Pos 9: Change in the voltage according to - LSA 49/50 - 7000 / 8000 series
LAM 1, knee-point position at 48 Hz or 58 Hz
1: Voltage from 80 to 320V
according to selection of the frequency by - LSA 46/47 - 5000 / 6000 series
an external contact.
2: Voltage from 80 to 320V
- LSA 49/50 - 7000 / 8000 series
WARNING
For Pavers and hydraulic applications,
select positions 0 (50 Hz) or 3 (60 Hz).
11
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
3.3 - U/F and LAM function 3.3.2.2 - Soft voltage recovery function
During load impacts, the function helps the
3.3.1 - Frequency variation compared
genset to return to its rated speed faster with
with voltage (without LAM) a gradual increase in voltage according to
Voltage Bend 57.5 Hz the principle:
48 Hz
100 % - If the speed drops between 46 and 50 Hz
U/UN 50 Hz (in 50Hz operation), the rated voltage is
60 Hz recovered by following a fast gradient.
- If the speed drops below 46 Hz, since the
Frequency engine needs more help, the voltage follows
50 Hz 60 Hz
Hz
a slow gradient as it returns to the reference
value.
3.3.2 - LAM (Load Acceptance Module)
characteristics
U
3.3.2.1 - Voltage drop
The LAM system is integrated in the AVR. As Drop N 46 Hz
standard it is active. Drop N > 46 Hz
Time
0
Role of the LAM:
On application of a load, the genset rotation
speed decreases. When it falls below the 3.4 - Typical effects of the LAM with a
preset frequency threshold, the LAM causes diesel engine with or without a LAM
the voltage to drop proportionately to the (U/F only)
frequency (LAM1) or to the active power
(LAM2) depending the the rotating switch 3.4.1 - Voltage
position. This reduces the active load scale
applied until the speed returns to its rated Transient voltage drop
value. UN
Hence the LAM can be used either to reduce
the speed variation (frequency) and its 0,9
duration for a given applied load, or to (U/f)
increase the applied load possible for one 0,8
with without LAM
LAM
speed variation (turbo-charged engine). Time
Voltage fN LAM
Voltage
UN
0,9
without
U/f
LAM LAM
0,85 UN 0,8 Time
0 1s 2s 3s
48 or 58 Hz 50 or 60 Hz
0 fC
ST3 fN
12
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
3.4.3 - Power - R729 module: same as R726 with
additional functions.
LAM • Detection of a diode fault
• 4-20 mA input
Load on the
- Voltage transformer
(adaptation)
13
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
4-INSTALLATION-COMMISSIONING a) Initial potentiometer settings (see table
below).
4.1 - Electrical checks on the AVR
- Check that all connections have been Action Factory setting Pot.
made properly as shown in the attached Voltage
minimum fully 400 V - 50 Hz
wiring diagram anti-clockwise P1
- Check the rotating switches selections:
- Frequency Stability Not set
P2
(centre position)
- Type of alternator
- Nnormal position (response time) Excitation ceiling 10 A
- Factory-sealed maximum P3
- External potentiometer
- Rated voltage Voltage quadrature droop
Not set
- Secondary current of the CT used (// operation with C.T.)
- 0 quadrature droop fully (fully
P4
anti-clockwise)
- Type of excitation anti-clockwise
14
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
h) Check LAM operation: depending on the 4.2.2 - Max. excitation adjustment
rotating switch selection. (excitation ceiling)
In standard setting, the potentiometer P3 is
i) Vary the frequency (speed) around 48 or in maximum position.
58 Hz according to the operating frequency, However, for applications requiring an
and check the change in voltage from that overload protection (see 3.2.1.4), the
observed previously (~ 15%). excitation ceiling must be adjusted by using
the following procedures in AREP and PMG.
j) Readjust the speed of the genset to its
rated no-load value. Method 1 :
Adjustments in parallel operation -Connect the AVR to the alternator
Before starting work on the alternator, make -Apply load to 110% of rated machine rated
sure that the speed droop is identical for all at PF=0.8, the green led is on and the red
engines. one is off.
-Record the excitation current value
k) Preset for parallel operation (with C.T. -adjust P3 until obtaining the red led flashing,
connected to S1, S2)
the green one is always on.
- Potentiometer P4 (quadrature droop) in
1/4 position in the case of 5A CT and at 1/2 -Decrease the load to 100% and make sure
position in the case of 1A CT. that the red led is off.
Apply the rated load (PF = 0.8 inductive). - Increase the load at 115%, check that the
The voltage should drop by 2 to 3% (400 V). red LED flashes during 90 seconds and that
If it increases, check that neither V and W the excitation current is brought back to the
nor S1 and S2 have been reversed. above adjusted value (Iex adjusted).
Method 2 :
l) The no-load voltages should be identical
The rated excitation current (see machine
for all the alternators intended to run in
plate) must be multiplied by 1.1 and the
parallel.
obtained value is used to set the
- Couple the machines in parallel.
potentiometer P3 at the right position. The
- By adjusting the speed, try to obtain 0 kW
following table must be used.
power exchange.
- By altering the voltage setting P1 on one of Position of P3 I exc (A)
the machines, try to cancel (or minimise) the 8h 1
current circulating between the machines.
- From now on, do not touch the voltage
9h 1.55 12H
10h 1.95
settings.
11h 2.5
P3
only correct if a reactive load is available) 13h 3.65
- By altering the speed, match the kW (or 14h 4.25
divide the rated power of the units 15h 4.7
proportionally). 16h 5.15
- By altering the quadrature droop
potentiometer P4, match or divide the NB: In the case of a permanent short-circuit,
currents. the excitation current must reach 2.9 x Iex
adjusted, during 1 second in AREP or 10
seconds in PMG and shuts down to a value
less than 1A.
15
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
The exciter is switched off by disconnecting
the AVR power supply (1 wire on each
auxiliary winding) - contact rating 16 A -
250 V A.C.
When the excitation current is set to the Connection is identical for resetting the AVR
rated value, a voltage dip is observed in internal protection.
excitation current limit when the
limitation is activated and the current
limit is reached.
F+
F- Exciter field winding
US
Field forcing
C
B Volt
X1
F- X2 Z1
F+ Z2 X1
t
X2
Time
X1
F- X2 Z1
F+ Z2 X1
Z2
16
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
4.3 - Electrical faults
Fault Action Measurements Check/Cause
The alternator builds up and its - Lack of residual magnetism
voltage is still correct when the
battery is removed
No voltage at Connect a new battery The alternator builds up but its - Check the connection of the voltage
no load on of 4 to 12 V to terminals voltage does not reach the rated reference to the AVR
start-up E- and E+, respecting value when the battery is removed - Faulty diodes
the polarity, for 2 to 3 - Armature short-circuit
seconds
The alternator builds up but its - Faulty AVR
voltage disappears when the - Field windings disconnected
battery is removed - Revolving field coil open circuit. Check the
resistance
Check the AVR connections (AVR may be
faulty)
Correct speed - Field windings short-circuited
Voltage too Check the drive speed - Rotating diodes burnt out
low - Revolving field coil short-circuited
- Check the resistance
Increase the drive speed
Speed too low (Do not touch the AVR voltage pot. (P1)
before running at the correct speed)
Voltage Adjust AVR stability If no effect: try normal/fast - Check the speed: possibility of cyclic
oscillations potentiometer recovery modes irregularity
- Loose connections
- Faulty AVR
- Speed too low when on load
(or U/F knee-point set too high)
Voltage between E+ and E- - Check the speed
Voltage Run at no load and AREP/PMG < 10 V (or U/F knee-point set too high)
correct at no check the voltage Voltage between E+ and E- - Faulty rotating diodes
load and too between E+ and E- on AREP/PMG > 15 V - Short-circuit in the revolving field coil.
low when on the AVR Check the resistance
load (*) - Faulty exciter armature
(*) Caution: For single-phase operation, check that the sensing wires coming from the AVR are correctly connected to
the operating terminals.
Voltage Check the AVR, the The voltage does not return to the - Exciter winding open circuit
disappears surge suppressor, the rated value - Faulty exciter armature
during rotating diodes, and - Faulty AVR
operation (**) replace any defective - Revolving field coil open circuit or
components short-circuited
(**) Caution: Internal protection may be activated (overload, open circuit, short-circuit)
17
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
5 - SPARE PARTS
5.1 - Designation
Description Type Code
Voltage regulator R450 M AEM 110 RE 032
(AVR)
18
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
Disposal and recycling instructions
We are committed limiting the
environmental impact of our activity. We
continuously monitor our production
processes, material sourcing and products
design to improve recyclability and minimise
our environmental footprint.
These instructions are for information
purposes only. It is the user’s responsibility
to comply with local legislation regarding
product disposal and recycling.
19
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
20
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
21
Electric Power Generation Installation and maintenance 4342 en - 2020.05 / l
R450 M & T
AVR
22
Service & Support
Life Extension
•Reconditioning Start-up
•System upgrade
•Commissioning
•Training
Optimisation
•Monitoring Operation
•System audit •Genuine spare parts
•Repair services
Contact us:
Americas: +1 (507) 625 4011
Europe & Rest of the world: +33 238 609 908
Asia Pacific: +65 6250 8488
China: +86 591 88373036
India: +91 806 726 4867
Middle East: +971 4 5687431 Scan the code or go to:
service.epg@leroy-somer.com www.lrsm.co/support
www.leroy-somer.com/epg
Linkedin.com/company/leroy-somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
4342 en - 2020.05 / l