com/us/products/2835626
Signal isolator - PI-EX-AIS-I/I - 2835626
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Ex i analog input: Input isolating amplifier, HART. Sends 4-20 mA signals from externally supplied measuring
transducers installed in Ex areas to a load in safe areas. Galvanic 3-way isolation (input / output / supply).
Technical data
Dimensions
Width 12.4 mm
Depth 147 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 55 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Input data
Signal input Current input, intrinsically safe
Current input signal 4 mA ... 20 mA
0 mA ... 20 mA
Output data
Signal output Current output
Current output signal 4 mA ... 20 mA
0 mA ... 20 mA
03/11/2020 Page 1 / 5
https://www.phoenixcontact.com/us/products/2835626
Signal isolator - PI-EX-AIS-I/I - 2835626
Technical data
Output data
Output current with short-circuit 0 mA
Output current with wire break 0 mA
Load/output load current output ≤ 600 Ω
Output ripple (current) < 65 µAPP (For 600 Ω)
Power supply
Supply voltage range 20 V DC ... 35 V DC
Max. current consumption < 36 mA (at 24 V)
Power consumption < 0.9 W (at 24 V)
General
No. of channels 1
Maximum transmission error ≤ 0.1 % (Of end value (at 20°C))
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) < 100 µs
Status display Green LED (supply voltage)
Standards/regulations NAMUR recommendation NE 21
Housing material PBT and polyamide PA non-reinforced
Color green
Designation Input/output
Electrical isolation 375 V (Peak value as per EN 50020 / EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value as per EN 50020 / EN 60079-11)
Designation Output/supply
Electrical isolation 1.5 kV (50 Hz, 1 min., test voltage)
Conformance CE-compliant
ATEX II (1) GD [EEx ia] IIC
II 3 G Ex nA II T4 X
UL, USA/Canada UL applied for
Safety data
Max. output voltage Uo 2.4 V
Max. output current Io 13 mA
Max. output power Po 8 mW
Safety-related maximum voltage Um 250 V AC
03/11/2020 Page 2 / 5
https://www.phoenixcontact.com/us/products/2835626
Signal isolator - PI-EX-AIS-I/I - 2835626
Technical data
Standards and Regulations
Standards/regulations NAMUR recommendation NE 21
Conformance CE-compliant
ATEX II (1) GD [EEx ia] IIC
II 3 G Ex nA II T4 X
UL, USA/Canada UL applied for
Drawings
Block diagram
03/11/2020 Page 3 / 5
https://www.phoenixcontact.com/us/products/2835626
Signal isolator - PI-EX-AIS-I/I - 2835626
Dimensional drawing
Classifications
eCl@ss
ETIM
UNSPSC
03/11/2020 Page 4 / 5
https://www.phoenixcontact.com/us/products/2835626
Signal isolator - PI-EX-AIS-I/I - 2835626
Classifications
UNSPSC
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
Accessories
Additional products
Ex base terminal block for intrinsically safe signals with knife disconnection and test connections
Intrinsically safe basic terminal block with isolating connector, test connections and surge protection, for mounting on NS
35/7.5
Ex basic terminal block, with three terminal points to the field level (Ex area)
03/11/2020 Page 5 / 5