You are on page 1of 8

PARALLEL PROCESSING UPS

E33A
Low energy, high quality, high reliability parallel processing type UPS

PARALLEL PROCESSING UPS

Parallel operation
E33A Supporting
network

Battery backup time


Input Output Output capacity
8 min
AC380, 400, 415, 420V AC380, 400, 415, 420V 100kVA 200kVA 300kVA 5min min
3 phase 3 wires / 3 phase 4 wires 3 phase 3 wires / 3 phase 4 wires (90kW) (180kW) (270kW) Standard Standard

Internal Battery
Parallel redundant operation
Input Output Output capacity min min min min
AC380, 400, 415, 420V AC380, 400, 415, 420V 100kVA 200kVA
Extended battery
3 phase 3 wires / 3 phase 4 wires 3 phase 3 wires / 3 phase 4 wires (90kW) (180kW)

1 High efficiency
■ Achieves 98 % efficiency. Running costs can be drastically reduced.
■ Contribute on protecting the environment.

■ Power consumption comparison for one year


Conversion
Double conversion UPS Difference in efficiency

98%
(kWh)
1,768,926kWh 1,621,945kWh yearly power
2,000,000 consumption
146,981kWh
1,500,000

1,000,000
Commercial
power

500,000
Facility equipment
・Data center equipment
・Factory equipment
0 ・Power plant, etc.
*When power is supplied based on rated power.
*Includes power consumption of facility equipment and
air conditioning system used for UPS cooling.

2 High quality
■ No interruption of output power
Supplies power in sine wave and completely without interruption of output even when there is a power outage,
such as black out instantaneous power break or voltage dip.
When a surge generates by injection of a static capacitor, etc., the power feeding is switched to temporally
mode which supplies power from the inverter.
This power supply is not from battery, so stress is not placed on the battery.
Waveform during power outage Waveform during surge addition
Commercial Normal Power outage Commercial Normal
During
surge addition Normal
power power
Operational Commercial and Inverter power Commercial and Inverter Commercial and
inverter parallel supply Operational power supply
status status inverter parallel (capacitor inverter parallel
operation (battery power supply) operation power supply) operation

Input Input
voltage Completely voltage
without Removes
interruption of surge and
output
power. noise.
Output Output
voltage voltage

2
■ Active filter function
A bi-directional inverter makes the UPS input current into a sine wave. It removes harmonic current from
commercial power supply and other equipment. At the same time, power factor is improved and becomes
approximately 1.0.

UPS
Commercial
power AC switch
Cancel
harmonic

Bi-directional inverter Facility equipment


・Data center equipment
Input current ・Factory equipment
The commercial power ・Power plant, etc.
Compensation current Output current
side is a sine wave with no Battery
Reverse current for Currents that include
harmonic components
harmonic current harmonics generated
from equipment and
devices

3 High reliability
■ Parallel redundant operation
E33A is the industry's first parallel processing UPS, that can perform parallel redundant operation. In addition,
it is a completely individual control system by setting control units to each UPS for parallel operation.
The parallel redundant operation with the independent control units makes it highly reliable.

During parallel redundant operation

When it is common control system When it is completely individual control system


Control unit

Commercial Commercial
power power UPS No.1
UPS No.1
Control unit

UPS No.2
UPS No.2
Control unit

Facility equipment Facility equipment


・Data center equipment UPS No.3 ・Data center equipment
UPS No.3 ・Factory equipment ・Factory equipment
・Power plant, etc. Control unit ・Power plant, etc.

■ Automatic battery operation test


The UPS runs periodic battery operation tests on its own to maintain the battery in a reliable operating condition
in the event of an actual power outage. During testing, power is supplied from the commercial power supply
ensuring that power supply can be maintained even if the battery is worn out.
Start of operation check

Normal operation Battery power supply check

Commercial Filter Periodic Commercial Filter


AC switch AC switch
power
Device
check power
Device

Battery Inverter Battery Inverter

The battery test is performed while power is supplied from the commercial power supply.
When the battery is worn out, a battery replacement alarm sounds.
The automatic battery operation test cycle can be changed.

4 Designed for factory equipment


Designed with a high overload capacity of 800% (0.5 seconds) and can withstand rush currents of transformer, etc.

3
Expanding the capacity with unit extensions
The capacity can be expanded by adding a 100kVA unit when required. Up to 300kVA of expansion is possible.
*Consider the I/O power cabinet that match the maximum capacity of the expected UPS, from the beginning of the installation.

UPS unit I/O power UPS unit I/O power UPS unit
cabinet cabinet

Parallel operation Output capacity


100kVA 200kVA 300kVA
Parallel redundant operation Output capacity (N+1 units)
ー 100kVA 200kVA

Parallel processing type


The conventional On-line UPS is a double conversion UPS, however this product, SANUPS E33A, using parallel
processing type always operates a utility power source and the inverter in parallel redundant at normal mode.
It supplies superior quality power to information communications devices and so on.
Since this operation, power feeding of SANUPS E33A is highly efficient and reliable.

Specifications
Item                   Model E33A104 E33A204 E33A304 E33AR104 E33AR204 Remarks
System Parallel operation Parallel redundant operation
Apparent power 100 kVA 200 kVA 300 kVA 100 kVA 200 kVA
Rated output capacity
Effective power 90 kW 180 kW 270 kW 90 kW 180 kW
Operation system Parallel processing type
Number of phases / wires 3 phase 3 wires / 3 phase 4 wires
Rated voltage 415 V (380, 400, 420 V)
Rate frequency 50 / 60Hz
AC Required capacity 120 kVA 240 kVA 360 kVA 120 kVA 240 kVA
input Distorted Compensation capacity Within rated capacity
current Compensation order 2 to 20 order harmonic
compensation Compensation rate 75% In case of 3 phase 3 wires
Input power factor 0.97 or higher At rated operations
Number of phases / wires Same as AC input
Rated voltage 415 V (380, 400, 420 V) Same as AC input
At commercial parallel
Within +10% and -8%
Voltage precision operation
At battery operation Within ± 2%
Rate frequency 50 / 60 Hz Same as AC input
At commercial parallel
Rated Within ± 5%
operation
frequency precision
At battery operation Within ± 0.5%
AC
output Load power factor Rating 0.9 (lagging)
Variation range 1.0 to 0.7 (lagging)
Voltage wave form At linear load 2% or less
At battery operation
distortion factor At rectifier load 5% or less
Instantaneous
Variation rate Within ± 5% At battery operation
voltage variation
At commercial parallel
200% (30 seconds), 800% (0.5 seconds)
Overload capacity operation
At battery operation 150% (1 minute), 125% (10 minutes)
Switching to battery operation Without momentary power break
Efficiency Single UPS unit characteristics, load
98% or higher
(commercial parallel operation) power factor 1.0
Acoustic noise 70 dB 73 dB 76 dB 73 dB 76 dB 1 m from front, height 1 m
Installation Indoor
Ambient temperature 0°C to 40 °
C
Environment
Relative humidity 20% to 90% (no condensation)
Altitude 1000 m or below
* Contact us about the changes on voltage precision and frequency precision.

Options

■ Networks
 ・LAN interface card *A card that connects to LAN (100Base-T).
 ・UPS management software (SANUPS SOFTWARE)

4
Heating value and cooling flow rate
*The calculated values for this chart are 0.9
Items E33A104 E33A204 E33A304 E33AR104 E33AR204
load power factor, 40˚C room temperature
Input capacity 120kVA 240kVA 360kVA 120kVA 240kVA and 30˚C outside air temperature. The
Heating value 2.5kW 5.0kW 7.5kW 3.4kW 5.9kW heating value and cooling flow rate are
Cooling flow rate 12.8m3/min 25.6m3min 38.4m3/min 17.2m3/min 30.0m3/min the values of the rated output after the
battery completes charging.

Ventilation rate
■ Individual battery ■ Common battery
Combination UPS unit Backup time Ventilation rate Remarks Combination UPS unit Backup time Ventilation rate Remarks
E33A104 5 minutes 2.6m3/min E33A104 5 minutes 2.6m3/min
10 minutes 4.1m3/min 10 minutes 4.1m3/min
E33A204 5 minutes 2.6m3/min × 2 sets E33A204 5 minutes 5.4m3min
10 minutes 4.1m3/min 10 minutes 8.2m3/min
E33A304 5 minutes 2.6m3/min × 3 sets E33A304 5 minutes 8.0m3/min
10 minutes 4.1m3/min 8 minutes 10.8m3/min
E33AR104 5 minutes 2.6m3/min × 2 sets E33AR104 5 minutes 5.4m3/min
10 minutes 4.1m3/min 10 minutes 8.2m3/min
E33AR204 5 minutes 2.6m3/min × 3 sets E33AR204 5 minutes 8.0m3/min
10 minutes 4.1m3/min 10 minutes 10.8m3/min

External dimensions
■ UPS unit ■ I/O Power cabinet
Dimension (mm) Combination Dimension (mm)
W D H UPS unit W D H
700 800 1900 Individual battery Common battery (built-in DC branching circuit)
Standard type External maintenance bypass type Standard type External maintenance bypass type
E33A104 − (500) − −
E33A204 800 800 1300 1300
E33A304 1000 1000 1500 1500 800 1900
E33AR104 800 800 1300 1300
E33AR204 1000 1000 1500 1500

■ Battery cabinet individual battery (for a 0.8 load power factor) ■ Battery cabinet common battery (for a 0.8 load power factor)
Combination Backup time Dimension (mm) Combination Backup time Dimension (mm)
UPS unit W D H UPS unit W D H
E33A104 5 minutes 700 E33A104 5 minutes 700
10 minutes 1100 10 minutes 1100
E33A204 5 minutes 700x2 E33A204 5 minutes 1400
10 minutes 1100x2 10 minutes 2200
E33A304 5 minutes 700x3 E33A304 5 minutes 2200
800 1900 800 1900
10 minutes 1100x3 8 minutes 2700
E33AR104 5 minutes 700x2 E33AR104 5 minutes 700
10 minutes 1100x2 10 minutes 1100
E33AR204 5 minutes 700x3 E33AR204 5 minutes 1400
10 minutes 1100x3 10 minutes 2200
*The backup time for 25˚C ambient temperature and the initial value.
*Contact us about the 30, 60, 120, 180 minute backup times and the 0.9 load power factor.

UPS unit I/O power cabinet


(Parallel redundant
operation)
1900

700 800 W D
50
50

Battery cabinet I/O power cabinet


(Parallel operation)
H

W D W D
50

50

5
System Configuration Diagram

■ Single Operation

Without external
maintenance bypass

UPS unit

Battery

With external
maintenance bypass I/O power board
Circuit breaker

Switch Switch
UPS unit

Battery

■ Parallel Operation (200kVA) / Parallel Redundant Operation (100kVA)

Each UPS unit shares a battery (common battery) Each UPS unit is connected to a separate battery
(individual battery)

Without external
maintenance bypass
*For parallel operation if I/O power board I/O power board
the output is 200kVA or
less, the UPS unit can be
separated into a single Circuit Circuit
breaker
unit. Switch Switch Switch Switch breaker
UPS unit UPS unit

Switch
Battery Battery

Switch Switch Switch Switch


UPS unit UPS unit

Switch
Battery

With external
maintenance bypass
I/O power board I/O power board
Circuit breaker Circuit breaker

Circuit Circuit
Switch Switch breaker Switch Switch breaker
UPS unit UPS unit

Switch
Battery Battery

Switch Switch Switch Switch


UPS unit UPS unit

Switch
Battery

6
■ Parallel Operation (300kVA) / Parallel Redundant Operation (200kVA)

Each UPS unit shares a battery (common battery) Each UPS unit is connected to a separate battery
(individual battery)

Without external
maintenance bypass

I/O power board I/O power board

Circuit Circuit
Switch Switch breaker Switch Switch breaker
UPS unit UPS unit

Switch
Battery Battery

Switch Switch Switch Switch


UPS unit UPS unit

Switch
Battery

Switch Switch Switch Switch


UPS unit UPS unit

Switch
Battery

With external
maintenance bypass

I/O power board


I/O power board
Circuit breaker
Circuit breaker

Circuit
breaker Circuit
Switch Switch breaker
UPS unit Switch Switch
UPS unit

Switch
Battery Battery
Switch Switch
UPS unit Switch Switch
UPS unit
Switch

Battery
Switch Switch
UPS unit Switch Switch
UPS unit
Switch

Battery

*Contact us about the 2-system input, the output branching, and other system configurations.

7
Notes when investigating use of this product in your applications
●Before starting installation, assembling and use, read the “Operation  (d) And other equipment that are related to safety of human life and that
 Manual” carefully and use the product correctly in your applications.    can affect severe effects on maintenance of public functions.
●When you are going to use this product in the following application, the ●For the applications that undergo vibration such as vehicles, ships and
 special considerations are required for operation, running, maintenance  transportation facilities, please consult with our company.
 and control. Be sure to consult with our company as a part of your ●Never modify this product or give additional processing to this product.
 investigations. ●For the installation andmaintenance work, please consult with our
 (a) Medical equipment and other equipment that are related directly to  company or with specialized company.
   human life.
 (b) Train or elevator that can give injury to human body.
 (c) Socially and publicly important computer systems. ※For any inquiry or consultation, please contact our sales representative.

http://www.sanyodenki.com

TEL: +81 3 5927 1020


3-33-1, Minami-Otsuka, Toshima-ku, Tokyo, 170-8451, Japan

TEL: +33 1 48 63 26 61
P.A. Paris Nord Ⅱ, 48 Allée des Erables-VILLEPINTE, BP.57286, F-95958 ROISSY CDG Cedex, France

TEL: +1 310 783 5400


468 Amapola Avenue Torrance, CA 90501, U.S.A.

TEL: +86 21 6235 1107


Room 2106-2109, Bldg A, Far East International Plaza, No.319, Xianxia Road, Shanghai, 200051, China
Beijing Branch
TEL: +86 10 6522 2160
Room1222, Tower B, Beijing COFCO Plaza, No.8 Jianguomennei Dajie, Dong Cheng District, Beijing 100005 China

TEL: +852 2312 6250


Room 2305, 23/F, South Tower, Concordia Plaza, 1 Science Museum Road, TST East, Kowloon, Hong Kong
Tianjin Representative Office
TEL: +86 22 2320 1186
Room AB 16th Floor TEDA Building, No. 256 Jie Fang Nan Road, Hexi District, Tianjin 300042 China
Chengdu Representative Office
TEL: +86 28 8661 6901
Room2105B, Block A, Times Plaza, 2 Zongfu Road, Jinjiang District, Chengdu, 610016 China

TEL: +886 2 2511 3938


N-711, 7F, Chia Hsin 2nd Bldg., No.96, Sec.2, Zhongshan N. Rd., Taipei 10449, Taiwan (R.O.C.)

TEL: +65 6223 1071


988 Toa Payoh North, #04-05/06/07/08, Singapore 319002
Indonesia Representative Office
TEL: + 62 21 252 3202
Summitmas II 4th Floor, Jl. Jend. Sudirman Kav.61-62, Jakarta 12190, Indonesia

TEL: +49 6196 76113 0


Frankfurter Strasse 92, 65760 Eschborn, Germany

TEL: +82 2 773 5623


9F, Sunhwa B/D 89, Seosomun-ro, Jung-gu, Seoul, 100-731, Korea
Busan Branch
TEL: +82 51 796 5151
8F, CJ Korea Express Bldg., 119, Daegyo-ro, Jung-gu, Busan, 600-016, Korea

TEL: +86 755 3337 3868


2F 02-11, Shenzhen International Chamber of Commerce Tower, No.168 Fuhua 3 Road, Futian District, Shenzhen, 518048 China

TEL: +66 2261 8670


388 Exchange Tower, 25th Floor, Unit 2501-1, Sukhumvit Road, Klongtoey, Klongtoey, Bangkok 10110 Thailand
The names of companies and/or their products specified in this catalogue are the trade names, and/or trademarks and/or registered trademarks of such respective companies.
*Remarks : Specifications Are SubjectTo Change Without Notice. CATALOG No. P0947B003 ’14.10.IT

You might also like