Professional Documents
Culture Documents
AND TROUBLESHOOTING
Data subject to change without notice. We decline all responsibility for the use of non-original components or accessories wich
have not been tested and submitted for approval.
ZF reserves all rights regarding the shown technical information including the right to file industrial property right applica-
tions and the industrial property rights resulting from these in Germany and abroad.
© ZF Friedrichshafen AG, 2014.
2 EN 3340.758.001a - 2014-10
TABLE OF CONTENT
MMSC5000 SmartCommand User Manual
Table of Contents
Table of Contents
MMSC5000
SW70327.0I
2 Operation ........................................................................................... 19
2.1 DC Power On ...................................................................................................................................19
2.2 Take Control ....................................................................................................................................19
2.3 Basic Operation ...............................................................................................................................20
2.4 Engine Start Interlock ......................................................................................................................21
2.5 Proportional Pause ..........................................................................................................................21
2.6 Station Transfer at Neutral ..............................................................................................................22
2.7 Station Transfer on the Fly ..............................................................................................................22
2.8 Warm Up Mode (Throttle Only) .......................................................................................................23
2.9 High / Low Idle ................................................................................................................................24
2.10 Twin Screw Synchronization ...........................................................................................................24
2.11 One Lever Operation Mode .............................................................................................................25
2.12 Cruise Mode (Default) ....................................................................................................................29
2.13 Proportional Pause ..........................................................................................................................29
2.14 Dimming Control Head LEDs ...........................................................................................................30
2.15 AutoTroll Mode (Optional) ...............................................................................................................30
2.16 EasiDock Mode (Optional)...............................................................................................................32
2.17 Two Speed Operation (Optional).....................................................................................................35
2.18 Mode Stacking.................................................................................................................................36
3 Installation: Planning.......................................................................... 39
3.1 Processor.........................................................................................................................................39
3.2 Tools For Installation .......................................................................................................................40
3.3 Control Heads..................................................................................................................................40
MMSC5000 Rev B 01/13 Page 3
EN 3340.758.001a - 2014-10 3
TABLE OF CONTENT
MMSC5000 SmartCommand User Manual
Table of Contents
4 Installation ......................................................................................... 49
4.1 Processor.........................................................................................................................................49
4.2 Power, Start Interlock, Clutch Pressure, and Alarm Circuit Harness ..............................................50
4.3 Control Heads..................................................................................................................................54
4.4 Synchronization ...............................................................................................................................57
4.5 Main Engine Speed Control - Throttle Harness ...............................................................................58
4.6 Clutch and Troll Control...................................................................................................................58
4.7 Engine Stop Switch .........................................................................................................................59
4 EN 3340.758.001a - 2014-10
TABLE OF CONTENT
MMSC5000 SmartCommand User Manual
Table of Contents
EN 3340.758.001a - 2014-10 5
TABLE OF CONTENT
MMSC5000 SmartCommand User Manual
Table of Contents
6 EN 3340.758.001a - 2014-10
LIST OF FIGURES
MMSC5000 SmartCommand User Manual
List of Figures
List of Figures
Figure 2-1: Take Control at a Station................................................................................................................. 20
Figure 2-2: Control Head Detents ..................................................................................................................... 21
Figure 2-3: Warm Up LED ................................................................................................................................ 23
Figure 2-4: One Lever LED................................................................................................................................ 25
Figure 2-5: One Lever Mode: Inactive Lever Ahead ........................................................................................... 26
Figure 2-6: One Lever Operation: Inactive Lever in Neutral ............................................................................... 27
Figure 2-7: Cruise Mode Response Function..................................................................................................... 29
Figure 2-8: AutoTroll Lever Response Function ................................................................................................. 32
Figure 2-9: EasiDock Response Function .......................................................................................................... 33
Figure 3-1: Processor ....................................................................................................................................... 39
Figure 3-2: System Configuration Showing CAN bus and Control Heads for Six Station Installation .................. 41
Figure 3-3: Processor Harness Connector Locations ......................................................................................... 43
Figure 3-4: Wire Harness Deutsch Pluggable Connectors ................................................................................. 44
Figure 3-5: System Installation Diagram............................................................................................................ 45
Figure 4-1: Processor Dimensions for Installation.............................................................................................. 49
Figure 4-2: Wiring DC Power Using the APS..................................................................................................... 50
Figure 4-3: Alternative Wiring for APS Power ................................................................................................... 51
Figure 4-4: Connections for Start Interlock Circuit............................................................................................. 53
Figure 4-5: Control Head Assembly .................................................................................................................. 54
Figure 4-6: Deutsch Connector on 70269 Wire Harness ................................................................................... 55
Figure 4-7: Turck Connector on 70269 Wire Harness........................................................................................ 55
Figure 4-8: Daisy Chaining Control Heads......................................................................................................... 56
Figure 5-1: Processor Display and Arrow Push Buttons ..................................................................................... 61
Figure 5-2: Processor Display and Push Buttons ............................................................................................... 62
Figure 5-3: Control Head ID’s Not Set............................................................................................................... 63
Figure 5-4: Display Normal Operating Condition ............................................................................................... 63
Figure 5-5: Display Set Up Activated ................................................................................................................ 64
Figure 5-6: Enter PIN ........................................................................................................................................ 64
Figure 5-7: Change the Value of the Function Code.......................................................................................... 65
Figure 6-1: Service Field Test Unit and Multimeter............................................................................................ 93
Figure 6-2: E1, E2, E3, E4, E6, L3, and d3 Processor, Test Unit, and Multimeter Connections........................... 94
Figure 6-3: L1, L2, d1, and d2 Processor, Test Unit, and Multimeter Connections............................................. 94
Figure 7-1: Multimeter and Test Unit Connections ......................................................................................... 106
Figure 8-1: Alarm Circuit Requirements .......................................................................................................... 119
Figure 8-2: Alarm Circuit Example .................................................................................................................. 120
Figure 8-3: Clutch Pressure Switch Showing Processor Wire Harness and Shuttle Valve................................. 121
Figure 10-1: Basic Control System .................................................................................................................. 125
Figure 10-2: System Diagram ......................................................................................................................... 126
Figure 10-3: Three Power Sources.................................................................................................................. 128
Figure 10-4: Control Head LEDs ..................................................................................................................... 133
EN 3340.758.001a - 2014-10 7
LIST OF FIGURES
MMSC5000 SmartCommand User Manual
List of Figures
8 EN 3340.758.001a - 2014-10
LIST OF TABLES
MMSC5000 SmartCommand User Manual
List of Tables
List of Tables
Table 2-1: Steps to Take Control....................................................................................................................... 20
Table 2-2: Warm Up Mode LED ........................................................................................................................ 23
Table 2-3: L0 Function Code Values.................................................................................................................. 30
Table 2-4: d0 Function Code Values ................................................................................................................. 33
Table 3-1: Maximum Cable Lengths for Control Heads ..................................................................................... 41
Table 3-2: Key to Wire Harness Connections .................................................................................................... 44
Table 3-3: Key for Figure 5: System Installation Diagram .................................................................................. 46
Table 3-4: Control Stations ............................................................................................................................... 46
Table 3-5: Control Head to Control Head Cables............................................................................................... 46
Table 3-6: Control Head to Processor Cables .................................................................................................... 46
Table 3-7: Wire Harnesses and Other Parts ...................................................................................................... 47
Table 4-1: Wire Gauges for Cables at Flag 1 ..................................................................................................... 51
Table 4-2: Wire Gauges for Cables at Flag 2 ..................................................................................................... 51
Table 4-3: Identifiers for Figure 4-2: Wiring DC Power Using the APS............................................................... 51
Table 4-4: Alternative Wiring for APS Power..................................................................................................... 52
Table 4-5: Connections for Start Interlock Circuit .............................................................................................. 53
Table 4-6: Connections Between Control Heads ............................................................................................... 56
Table 5-1: Push Button Keys in Normal Operating Mode................................................................................... 62
Table 5-2: Push Buttons in Function Menu (Function Code LED’s are illuminated steadily)................................ 62
Table 5-3: Push Buttons in Set Up Mode (Function Code LED’s are blinking) .................................................... 62
Table 5-4: Push Buttons at Password Prompt (PIn? Appears on display) ........................................................... 63
Table 5-5: Push Buttons for PIN Entry ............................................................................................................... 63
Table 5-6: Push Buttons In Error Code Display (’Er’ shows in Function Code).................................................... 63
Table 5-7: Engine Throttle Profile Definitions .................................................................................................... 68
Table 5-8: L0 Function Code Values.................................................................................................................. 74
Table 5-9: Trolling Valve Type Selection............................................................................................................ 75
Table 5-10: J6 and J7 Values as Related to J0.................................................................................................. 78
Table 5-11: d0 Function Code Values ............................................................................................................... 79
Table ENG-289-1: Revision List......................................................................................................................... 81
Table ENG-289-2: System Definition Functions (SmartCommand) .................................................................... 82
Table ENG-289-3: Engine Functions and Values (SmartCommand)................................................................... 83
Table ENG-289-4: Dual Throttle Engine Functions and Values (SmartCommand) .............................................. 84
Table ENG-289-5: Clutch Functions and Values (SmartCommand) ................................................................... 84
Table ENG-289-6: Troll Functions and Values (SmartCommand)....................................................................... 85
Table ENG-289-7: Docking Functions and Values (SmartCommand)................................................................. 85
Table ENG-289-8: Governed Electric Troll Functions and Values (SmartCommand)........................................... 86
Table ENG-289-9: Troubleshooting Functions (SmartCommand) ...................................................................... 87
Table ENG-289-10: Steering and Helm Functions (POD)................................................................................... 87
Table ENG-289-11: Low Speed Configuration Functions (POD) ........................................................................ 87
Table ENG-289-12: High Speed Configuration Functions (POD) ....................................................................... 88
EN 3340.758.001a - 2014-10 9
LIST OF TABLES
MMSC5000 SmartCommand User Manual
List of Tables
10 EN 3340.758.001a - 2014-10
LIST OF TABLES
MMSC5000 SmartCommand User Manual
List of Tables
Table 10-25: Wire Harness - Clutch/Shaft Tach, SmartCommand (p/n 70259-XX) .......................................... 171
Table 10-26: Power, Start Interlock Harness Pin-Out (p/n 13756-XX) ............................................................. 172
Table 10-27: Wire Harness - Power, SI & Clutch Pressure Switch (p/n 13552-XX) .......................................... 172
Table 10-28: Wire Harness - Power, SI, Clutch Pressure Switch & Alarm (p/n 13631-XX) ............................... 173
Table 10-29: Wire Harness- Power Use w/ existing Start Interlock Only (p/n 15023-XX)................................. 173
Table 10-30: Wire Harness- Power/Backup Input For MTU Start Interlock w/ SC (p/n 71021-XX) .................. 174
Table 10-31: Wire Harness - Power, Start Interlock, Pressure SW, Alarm & Backup (p/n 71476-XX) ............... 175
Table 10-32: Wire Harness- Control Head To OBOF Panel, Port and Stbd (p/n 71495-XX).............................. 176
Table 10-33: Wire Harness - Control Head to Control Head (p/n 70268-XX) ................................................... 177
Table 10-34: Wire Harness - Control Head to Processor (p/n 70269-XX) ........................................................ 177
Table 10-35: Wire Harness - Iso CAN (p/n 70559-XX) .................................................................................... 178
Table 10-36: CANtrak termination resistor (p/n 70540-XX) ............................................................................. 178
EN 3340.758.001a - 2014-10 11
12 EN 3340.758.001a - 2014-10
REVISIONS LIST
MMSC5000 SmartCommand User Manual
Revision List
Revision List
Rev Date Description
Cross Reference in Copyright Notices corrected
Fuse Value in Figure 14 in Section 3 corrected
- 12/05 Error codes included in Troubleshooting Section
System drawing in Appendix C updated to Rev. A
Password instructions changed in Section 5
Some changes made in all Sections.
Extensive changes and/or rewrites made to Section 2 - Operations; Section 5 - Set Up; Section 7 - Sea
- 11/06
Trials; Appendix A (Section 11) and Appendix C (Section 13).
Contact information updated for international sales and service centers in Appendix B (Section 12).
Text of Section 10, “Troubleshooting,” has been substantially updated and enhanced. Illustrations of
- 1/07
pinouts for all major SmartCommand wiring situations were added.
Added Start Interlock to Section 2, Operation.
Added Engine Stop Switch warning to Section 2, Operation.
- 9/07 Added Mode Stacking to Section 2, Operation
Added E7 Values to Table 8, Section 5, Set Up Procedures
A 4/08 Replaced MMC-165 - Electronic Propulsion Limited Warranty
Replaced MMC-165 - Electronic Propulsion Limited Warranty
A.1 1/09
Replaced MMC-123, MMC-151, MMC-172 - Factory Authorized Sales & Service Centers Lists
Reformatted to FrameMaker, Restructured manual contents, Updated SW number, Various revisions
A.2 11/11
per ELR00055, ELR00113, ELR00118 and ELR00130, updated all external documents
Revised per ELR00084, ELR00104, ELR00105, ELR00113, ELR00150, ELR00158, ELR00159,
B 01/13
ELR00186 and ELR00202.
EN 3340.758.001a - 2014-10 13
14 EN 3340.758.001a - 2014-10
PREFACE
MMSC5000 SmartCommand User Manual
Preface
Preface
IMPORTANT: Keep this manual in a safe place for future reference. It contains essential information about the
installation and operation of the ZF Marine Propulsion Systems Miramar control system for your vessel.
Important Information
WARNING: Personal Injury could occur if the following steps are not followed exactly.
CAUTION: On Control Systems with more than one Processor, ZF Marine Propulsion Systems Miramar highly
recommends that ALL UNITS utilize the same software revision for each Processor.
CAUTION: Electro-static discharge can damage this equipment. Personnel working on this equipment must be
grounded to the chassis with an anti-static wrist strap.
EN 3340.758.001a - 2014-10 15
PREFACE
MMSC5000 SmartCommand User Manual
Preface
CAUTION: Disconnect the power from the processor whenever welding is being done on the vessel. Failure to
do so can cause permanent damage to the processor.
CAUTION: This equipment is designed to work with other ZF Marine Propulsion Systems Miramar designed
equipment. DO NOT operate this equipment with any other manufacturer's equipment unless approved so in
writing by ZF Marine Propulsion Systems Miramar Engineering Department.
NOTE: ZF Marine Propulsion Systems Miramar is not liable for any damage incurred if these notices are not
followed exactly.
16 EN 3340.758.001a - 2014-10
INTRODUCTION
MMSC5000 SmartCommand User Manual
Introduction
1 Introduction
Important: This manual contains information about all of the options available with the SmartCommand
system. Your application might not use all of the options, so you can disregard those sections of the manual
that do not apply to your configuration.
1.1.1 Features
SmartCommand has the following performance features:
a Clutch and Engine Speed Sequencing
b Start Interlock
c High/Low Idle
d Multi Screw Engine Synchronization
e Electric Trolling Valve Control
f Emergency Reversal Protection
g Clutch Oil Pressure Interlock (optional)
Features that make the control head easy to use are:
a Indicator for Station-in-Command
b Six bi-color LEDs for indicating control system mode and status
c One to six Remote Stations, and up to three control heads on each of two independent CAN
bus lines, for commanding and controlling the vessel.
d Sound transducer for system status indication.
The processor includes the following features:
a Four digit LED and key pad at main processor to simplify set up, configuration, and
troubleshooting.
b Plug-in cable connections
c SmartCommand failure alarm contact (optional)
d Built-in diagnostics
Vessels that have more than one power source, which is recommended, should use an automatic power
selector (APS). The APS (part number 13505, available from ZF Marine), compatible with 12 VDC or 24
VDC systems, increases the reliability of power delivery.
Cruise mode is the default mode of SmartCommand. This mode uses a single lever for clutch and throttle
control, with one control lever for each screw. Automatic engine synchronization is enabled in Cruise
mode.
EN 3340.758.001a - 2014-10 17
INTRODUCTION
MMSC5000 SmartCommand User Manual
Introduction
mode gives you positive clutch response while ensuring easy and precise
maneuvering ability in tight docking situations
18 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
2 Operation
This Section is intended for vessel operators. Generally speaking, most other Sections of this manual, while
informative for users, contain information that is primarily useful for installers.
Warning: An Engine Stop Switch MUST be installed at every remote operating station. Refer to the Code of
Federal Regulations (CFR) 46, 62.35-5 and the American Boat and Yacht Council (ABYC) standards on electric
and electronic propulsion control systems (P-24.5.8). Personal Injury may result if this message is disregarded.
2.1 DC Power On
When DC power is turned ON, the SmartCommand control system:
• Commands neutral and idle from the processor.
• Sounds an intermittent tone pattern at all stations indicating that no station has control. (Refer to
explanations of audible tones in section 10: Troubleshooting.)
• Starts the transmission in the low speed gear. (If the vessel uses the Two Speed feature, the two
speed solenoid is de-energized.)
Important: The next control head lever movement shifts the transmission.
• Start the engine while commanding Neutral. If the control head levers are out of Neutral, the
start interlock switch prevents the engines from starting.
• Move levers into the Ahead or Astern detent. The transmission shifts into gear and the Control
LEDs light steady red, indicating the station is in control and the operator is commanding
ahead or astern.
EN 3340.758.001a - 2014-10 19
OPERATION
MMSC5000 SmartCommand User Manual
Operation
2 B Press Control/Set until CONTROL LEDs light Neutral Station takes control
Vessel moves in response to
3 C Move levers to ahead detent Ahead detent
lever position
Note: The Engine Start Interlock feature prevents the engines from starting if the DC power is not on, if a
station is not in command, and if the control head levers are not in neutral. An exception to this rule is when
the system is in Warm Up mode, when Start Interlock allows the engines to start with the levers in the throttle
range.
Warning: An Engine Stop Switch MUST be installed at every remote operating station. Refer to the Code of
Federal Regulations (CFR) 46, 62.35-5 and the American Boat and Yacht Council (ABYC) standards on electric
and electronic propulsion control systems (P-24.5.8). Personal Injury may result if this message is disregarded.
20 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
Note: The neutral detent (the center of control head movement) is 10 degrees in the ahead direction. The
degrees of lever movement are measured from this point, not from the vertical.
EN 3340.758.001a - 2014-10 21
OPERATION
MMSC5000 SmartCommand User Manual
Operation
Warning: Follow the steps in this section exactly. Personal Injury may result if this message is disregarded.
To transfer control from one station to another with the levers in neutral:
1. Verify that both control head levers at the station in command are in the neutral detent.
2. Verify that both control head levers at the station taking control are in the neutral detent.
3. At the station taking control, press Control/Set.
4. The Control LEDs on both sides illuminate steady green, indicating that this station has control.
5. AutoTroll, EasiDock, and Warm Up modes, as well as the high idle function (see explanation of Function Code
E6 in section 5: Set Up Procedures), transfer to this station, and LEDs illuminate appropriately.
6. The Control LEDs on the original station go out.
7. Move the control levers into gear. The Control LEDs on both sides illuminate steady red. The LEDs stay red as
long as the vessel is in gear.
Important: The next control head lever movement shifts the transmission.
Warning: Follow the steps in this section exactly. Personal Injury may result if this message is disregarded.
22 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
EN 3340.758.001a - 2014-10 23
OPERATION
MMSC5000 SmartCommand User Manual
Operation
4. At the station in control, position the control head levers in the ahead range. The percentage of throttle
increases, while the transmission remains in Neutral. The Control LEDs blink green. If you move the
levers into the astern range, the engine speed returns to idle and the clutch remains in neutral.
5. Warm Up mode is active (signified by the lighted Warm Up LED) until you deselect it by going to
neutral as described below.
Important: The next control head lever movement shifts the transmission.
4. Move the control head levers into the position you want to command in Cruise mode (Control LEDs
illuminate steady red) or select another mode.
Caution: Do not shift in High Idle, if the engine RPM at High Idle is higher than the maximum RPM
recommended for your gears. For gear specifications and other information, refer to documentation provided
with your transmission.
To switch from low to high idle, move the control head levers to any of the detents. Press Control/Set on the
control head and hold it down for one-half second. To switch back to low idle, move the control head levers
to any of the detents and press and hold Control/Set for one-half second.
24 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
• Active Synchronization — requires a tachometer signal representing the RPM of each engine,
in addition to the throttle command signal. The function provides for the tachometer frequency
to be measured and the throttle command signal outputs to be changed until both engines are
running at the same RPM, as measured by the tachometer signals.
Warning: Whichever way you choose to use it, follow the steps to enable and disable One Lever Mode exactly.
Personal Injury may result if this message is disregarded.
Note: One Lever mode can only be employed when you are in Cruise mode. The One Lever LED is always lit
while in One Lever mode. The position of the active control head lever does not affect this LED.
EN 3340.758.001a - 2014-10 25
OPERATION
MMSC5000 SmartCommand User Manual
Operation
Note: Keep the inactive lever at the Ahead detent or further forward. If the inactive lever is moved to neutral
(or through neutral to astern) One Lever mode is deactivated.
Note: Processor IDs determine which lever is considered port or starboard. The colors stated assume that the
port processor has Processor ID 1 and the starboard processor has Processor ID 2.
5. You can leave the inactive lever in the Ahead detent or move it further forward.
• Disable One Lever Operation: (Inactive Lever Ahead)
The easiest way to break out of One Lever mode is to move both levers to the neutral detent
for at least a half second. Alternatively, you can move the inactive lever to the neutral detent.
Or you can put both levers at the Ahead detent, and press the mode button until the One
MMSC5000 Rev B 01/13 Page 26
26 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
Lever LED goes out. You know you are out of One Lever mode, and that both levers are
active again, when the One Lever LED is off. Both levers are now active.
Important: If you are in One Lever mode at one station and you transfer vessel command to another station,
One Lever mode does not transfer. To use One Lever mode at the new station in command, set it at that
station.
2.11.2 One Lever Operation: Option Two (Inactive Lever in Neutral): Default Mode
In the default mode of operation, the inactive lever remains in the neutral detent when it is unused.
Function Code A2 is set to a value of 02 at the processors for this mode of operation.
EN 3340.758.001a - 2014-10 27
OPERATION
MMSC5000 SmartCommand User Manual
Operation
The processor ID’s control which lever is considered port or starboard: the colors stated assuming the
Port Control Processor has Processor ID 1 and the Starboard Control Processor has Processor ID 2.
Move the active lever to the throttle position you want to command. Do not move the inactive lever.
Note: Best Practice: To break out of One Lever mode, move both levers to neutral and press the Mode button
until the One Lever LED extinguishes.
Warning: If you attempt to disable One Lever mode with one lever in Neutral and the other lever in ahead
results in different engine speeds on the port and starboard sides. The vessel turns until the levers are brought
closer together. Personal Injury may result if this message is disregarded.
Important: One Lever mode does not transfer when SmartCommand transfers stations. To use One Lever
mode at the new station, set it at that station.
28 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
Note: If your vessel uses ZF Friedrichshafen gears with an MTCU, there is a short pause at clutch engagement,
and the throttle increases slowly for the first two seconds the clutch is engaged.
The example shown in Figure 2-7: Cruise Mode Response Function assumes a 2:1 gear ratio, and an engine
with an idle speed of 600 RPM and full throttle at 2300 RPM. In this situation, shaft RPM increases from 300
to 1150 RPM. (In real life situations, values may be different.)
EN 3340.758.001a - 2014-10 29
OPERATION
MMSC5000 SmartCommand User Manual
Operation
The default pause from Astern to Ahead is one half the Reversal Pause value, since most vessels do not reach
the same throttle in Astern as they do in Ahead. Use the C4 Function Code to change the Astern to Ahead
relationship.
AutoTroll mode controls electric Trolling Valves using single solenoids or dual solenoids for Troll On/Off and
Proportional. Set up AutoTroll and its Function Codes at the processor. After Function Codes have been set
up, AutoTroll is enabled and disabled from the control heads. AutoTroll gives your vessel specific, repeatable
shaft RPM for trolling. The gears installed in the vessel determine whether troll can operate with or without
feedback. Gears with feedback have additional wire harness connections, either a tachometer signal or an
MTCU. AutoTroll with feedback requires an output shaft sender to close the loop.
This system has three modes of operation when a troll valve is present and has been configured: AutoTroll,
Cruise mode, and EasiDock. When the control system initially powers up, Cruise mode is selected by default.
If the vessel uses the tachometer signal to provide shaft RPM feedback, and the tachometer signal is lost,
AutoTroll operates in open loop troll. Slip is commanded without feedback and can vary.
In Cruise mode, the trolling valve is at the maximum gear oil pressure position (locked up). The trolling valve
is not used in Cruise mode.
AutoTroll must be selected and deselected at the control head.
30 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
1. Place both control head levers in the Neutral, Ahead, or Astern Detent. Both levers must be in the same
detent. The EasiDock, One Lever, and Warm Up LEDs cannot be illuminated.
2. Press Mode until the AutoTroll LED blinks. If no button is pressed in ten seconds, the LED stops blinking
and the mode does not change.
3. Press Control/Set once to illuminate the AutoTroll LED. AutoTroll mode is enabled.
Note: If your vessel uses ZF Friedrichshafen gears with an MTCU, the throttle increases slowly for the first two
seconds the clutch is fully engaged.
EN 3340.758.001a - 2014-10 31
OPERATION
MMSC5000 SmartCommand User Manual
Operation
The upper limit for the troll throttle percentage is 20% of full throttle. The default value for maximum
troll throttle percentage is 0%: the engine always remains at idle. Only change the default value after
completing the checks and calculations in section 7.6.2: Set the Troll Throttle Limit, and Throttle in
Docking Range.
Caution: If the vessel is underway in AutoTroll with the control head levers in the Ahead or Astern detent and
AutoTroll is disabled, the vessel enters Cruise mode. The vessel accelerates to normal idle in gear speed.
EasiDock mode gives you positive clutch response and appropriate thrust allowing you to modulate the
clutches and control the engine speed for easy maneuverability in confined waters. It provides a rapid,
smooth change from ahead to astern while docking the vessel.
SmartCommand commands a higher clutch pressure when SmartCommand enters EasiDock mode. The
propeller shaft starts to move; the thrust is noticeable. After a short time, the pressure drops to a lower lockup
percentage. Clutch pressures in EasiDock can be optionally configured at setup, either at a specific value or
through a range. If the tachometer feedback used by EasiDock is lost, the vessel drops out of EasiDock mode.
EasiDock mode commands decreased clutch pressure at the Ahead or Astern detents, and in the EasiDock
range. The clutch engages fully if the levers move past the EasiDock range; there is no slip.
32 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
In the example graph, docking mode is active the first 40 degrees from the detent position and allows a
smooth but quick prop response (from 150 to 330 RPM) due to the combined action of clutch slip and engine
speed increasing from 600 to 940 RPM. For the remaining 20 degrees, the clutch is fully engaged and engine
speed increases to 75% of the full engine speed, to 1875 RPM.
Caution: The maximum throttle percentage in EasiDock mode is limited to prevent damage to the clutch pack.
Most transmissions require that the throttle is limited to less than 1000 RPM. Detailed information about
choosing the upper limit is found in section 7.6.1: Calculating the highest throttle percentage allowed.
The upper limit for the EasiDock throttle percentage is 20% of full throttle. The default value for the EasiDock
throttle percentage is 0%: the engine always remains at idle. Only change the default value after completing
the checks and calculations in section 7.6.1: Calculating the highest throttle percentage allowed.
EN 3340.758.001a - 2014-10 33
OPERATION
MMSC5000 SmartCommand User Manual
Operation
* If the d0 Function Code is set to 05, you can exit EasiDock while the levers are in the ahead range.
Warning: Follow the steps in this section exactly. Personal Injury may result if this message is disregarded.
1. Place both control head levers in the Neutral, Ahead, or Astern Detent. Both levers must be in the same
detent. The AutoTroll, Warm Up, and One Lever LEDs cannot be illuminated.
2. Press Mode until the EasiDock LED blinks. If no button is pressed in ten seconds, the LED stops
blinking and the mode does not change.
3. Press Control/Set once to light the EasiDock LED. The Control LEDs blink green. EasiDock mode is
enabled.
The output shaft tachometer signal must be present for the vessel to enter EasiDock mode. If
EasiDock is set up, and no tachometer signal can be detected, the system delays two to three
seconds. If no tachometer signal is detected after the delay:
• The station in command generates an error tone.
• A fault code appears on the processor:
- fault code 92 if the input shaft sensor faults,
or
- fault code 93 if the output shaft sensor faults.
• The EasiDock LED blinks rapidly.
• The clutch remains fully engaged.
EasiDock mode does not enable until the processor receives the tachometer signal.
34 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
approximately one second until the EasiDock LED extinguishes and the clutch is locked up; the clutch
does not slip as it does in EasiDock.
Caution: Disabling Easidock if the vessel is underway with the control levers in the Ahead or Astern detent
causes SmartCommand to enter Cruise mode. The vessel accelerates to normal idle in gear speed.
There is no additional acceleration if you disable EasiDock in the ahead range when d0 is set to 05.
The clutch is already fully engaged and you are traveling at the normal in-gear speed.
EN 3340.758.001a - 2014-10 35
OPERATION
MMSC5000 SmartCommand User Manual
Operation
36 EN 3340.758.001a - 2014-10
OPERATION
MMSC5000 SmartCommand User Manual
Operation
EN 3340.758.001a - 2014-10 37
38 EN 3340.758.001a - 2014-10
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
3 Installation: Planning
Note: ZF Marine Propulsion Systems Miramar recommends installing the system in accordance with current
ABYC E-11 and P-24 standards.
3.1 Processor
3.1.1 Requirements
3.1.2 Location
Note: Read MMC-287 Grounding (Bonding) and MMC-165 Warranty at the end of this manual. Improper
mounting location may cancel warranty.
The preferred location for the processor is the engine room. If the engine room is too small, locate the
processor in any area where it is accessible for electrical connections. Bulkhead mounting is
preferred for easy access to the processor for wiring and adjustments.
Processors are spray proof, but must not be immersed.
The processor can be mounted in any attitude as long as the LEDs on the front cover are readable. Do
not mount the processor on the engine, on the transmission, or in any location that will subject it to
excessive vibration.
Locate processors away from heat sources, such as engine exhaust manifolds or turbochargers. Allow
four feet (1.2m) or more clearance between processors and heat sources.
EN 3340.758.001a - 2014-10 39
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
Do not mount close to gas engine ignition systems, alternators, or electric motors. Allow four feet
(1.2m) clearance between the processor and alternators or electric motors.
Caution: Electromagnetic fields can influence SmartCommand’s electronic circuits and cause erratic
operation. Heat can damage the SmartCommand system. Compasses should not be located near the
processors.
A threaded hole and screw are provided to connect to the vessel’s grounding (bonding) system. See
section 4: Installation for processor dimensions and MMC-287 Grounding (Bonding) for details on
grounding electronics.
3.2.2 Optional
• Wire cutter, stripper, and crimper (ZF Marine Propulsion Systems Miramar recommends
Thomas & Betts WT-2000 if using single terminated harnesses)
• Service Field Test Unit (Break-out Box)
• Calibrated Digital Multimeter (for CAT engines, the Multimeter must read PWM: ZF Marine
Propulsion Systems Miramar recommends Fluke 87 III or equivalent)
Warning: Mount SmartCommand control heads at least 250 mm (9.84 in.) from compasses. If a safe mounting
distance is not maintained, electromagnetic fields could influence SmartCommand Control Head electronic
circuits, cause erratic operation, and possibly impair compass directions. Personal injury could result if this
message is disregarded.
Each control head is shipped with mounting hardware and the necessary gasket attached. One or two
control heads must be directly connected to the processor or processors. If the system has more than two
control heads, at least two are daisy-chained. Each chain has a maximum of three control heads.
40 EN 3340.758.001a - 2014-10
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
Figure 3-2: System Configuration Showing CAN bus and Control Heads for Six Station Installation
Warning: An Engine Stop Switch MUST be installed at every remote operating station. Refer to the Code of
Federal Regulations (CFR) 46, 62.35-5 and the American Boat and Yacht Council (ABYC) standards on electric
and electronic propulsion control systems (P-24.5.8). Personal Injury may result if this message is disregarded.
EN 3340.758.001a - 2014-10 41
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
Caution: Voltage differences between the processors on power or ground can damage the processors.
42 EN 3340.758.001a - 2014-10
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
3.6.2 Propeller Shaft Speed Sensor Requirements — Active Sensor with Open Collector Input
The sensor must have:
• A source current capability not less than 2 mA.
• A minimum frequency of 5 Hz at idle.
• A maximum frequency of 8 kHz at full throttle.
• An operational voltage of 9 - 10 VDC.
Note: Every connector should be plugged into either a wire harness or a plug. Do not leave a connector empty
or with pins dangling.
EN 3340.758.001a - 2014-10 43
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
Connector Keying
Large Plug side view
Processor Key
Depress & Hold Small Plug end view Connector
Keying
1
Depress
2
Cable &
Hold
3
5
4
11232_ART
Depress & Hold
11230_ART Connector
Keying 15138_ART
15137_ART
44 EN 3340.758.001a - 2014-10
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
EN 3340.758.001a - 2014-10 45
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
Warning: ZF Marine Propulsion Systems Miramar strongly recommends that the first control station be located
on the Station A bus, and the second control station be located on the Station B bus, to provide for
redundancy in case of failure. Personal Injury may result if this message is disregarded.
46 EN 3340.758.001a - 2014-10
INSTALLATION: PLANNING
MMSC5000 SmartCommand User Manual
Installation: Planning
EN 3340.758.001a - 2014-10 47
48 EN 3340.758.001a - 2014-10
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
4 Installation
As directed in section 3: Installation: Planning, collect all parts and tools before starting the actual system
installation of SmartCommand. Determine locations and cable lengths for the processors, the APS, and the
control heads. Read the instructions for each separate part before installing it.
Note: When installing or removing a plug, always press release buttons down and continue to hold until the
plug is fully connected or disconnected, to avoid damage.
Note: Place clamps or straps at least every 18 inches (~0.5 m) to support wire harnesses, unless the harness is
contained in a conduit, and ensure that each cable is protected from physical damage. Refer to ABYC Standard
E-11.16.4.1.10.
4.1 Processor
Warning: Do not open the processor enclosure -- this will void the warranty. The enclosure contains no user-
serviceable parts and ZF Marine Propulsion Systems Miramar cannot guarantee that the unit will operate as
designed if it is opened. Personal Injury may result if this message is disregarded.
EN 3340.758.001a - 2014-10 49
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
4.2 Power, Start Interlock, Clutch Pressure, and Alarm Circuit Harness
Several different harnesses can be used for the four functions in the title. The exact harness will depend on
the application. Refer to section 10: Troubleshooting for harness information. The Power and Start Interlock
connections are required. Clutch Pressure and Alarm Circuit connections are optional.
The harness has one plug on the processor end of the cable, and is supplied with two to four cables
extending from the plug, depending on the requirement.)
Caution: Turn Power OFF before connecting the Power Harness to the processor.
Insert the Wire Harness plug in the POWER connector on the processor.
Continue with the sections that apply to the application. In all cases, make the Power and Start Interlock
connections. Your application may have neither Alarm or Clutch Pressure, or it may have one or both.
50 EN 3340.758.001a - 2014-10
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
Table 4-3: Identifiers for Figure 4-2: Wiring DC Power Using the APS
ID Description ID Description
A “OFF” position for Circuit Breaker G DC Common Return
B ’ON” Position for Circuit Breaker H PN 13505 Automatic Power Selector
PN: HFB Fuse Holder
C RED wire J
PN: AGC-30 Fuse
D Connection to processor K 30 Amp Fuse
E Black or Yellow Wire L Power Source 2
F PN 810: 10 Amp Circuit Breaker M Power Source 1
EN 3340.758.001a - 2014-10 51
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
Review section 13: Appendix C - System Drawings to confirm termination points for power
connection. The power for the control system should come from the same power distribution panel as
the other engine functions. The return conductor of the processor must be connected to the common
ground. Connect the processor’s return conductors together.
Caution: Voltage differences between the processors on power or ground can damage the processors.
Caution: The processor is designed for a start signal current with a maximum of 5 Amperes and 50 Volts.
Current greater than 5 Amperes can damage the interlock circuit.
52 EN 3340.758.001a - 2014-10
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
Caution: SmartCommand control heads should be mounted only in forward-facing stations, with the operating
buttons facing aft. Mounting a control head in a manner other than this can result in reversed operational
effects.
EN 3340.758.001a - 2014-10 53
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
Caution: The most common source of trouble is loose wiring connections. Verify that wiring connectors are
properly crimped and cannot be pulled out. Crimps and connections must be made to the wire, not to the wire
insulation. Verify that all screwed wire connections are secure. Damage to equipment may occur if this
message is disregarded.
Important: Before drilling or cutting, make sure there is a clearance space of at least 3.5 inches (88.9 mm)
below the mounting surface (for control head cables and connections).
Warning: Mount SmartCommand control heads at least 250 mm (9.84 in.) from compasses. If a safe mounting
distance is not maintained, electromagnetic fields could influence SmartCommand electronic circuits, cause
erratic operation, and possibly impair compass directions. Personal injury could result if this message is
disregarded.
54 EN 3340.758.001a - 2014-10
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
• Tighten washers and nuts enough that they will not come loose during normal vibration. Since
mounting surfaces vary, the exact torque depends on the application. When tightening, be
careful not to damage the mounting surface or control head.
• See the following sections for connecting the cables and terminating resistors at the control
head.
Warning: Do not open the control head. If you do, the warranty is voided. Control heads contain no user
serviceable parts, and ZF Marine Propulsion Systems Miramar cannot guarantee the operation of a unit once
it has been opened. Damage to the equipment may occur if this message is disregarded.
EN 3340.758.001a - 2014-10 55
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
See section 4.3.3: Cable Connection for cable connection at the control head.
56 EN 3340.758.001a - 2014-10
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
Use Control Head-to-Control Head wire harnesses (PN 70268-XX) for a system with more than two
control heads. Install termination resistors at the last station in the daisy chain.
4.4 Synchronization
SmartCommand uses Equal Throttle Synchronization by default. The processors send equal throttle
command signals to both governors when the levers are in the synchronization range. (See section 2.10: Twin
Screw Synchronization) In most cases, Equal Throttle Synchronization is very effective. For engine RPM
synchronization, select Active Synchronization at processor at set-up time (refer to the E7 Function Code in
section 5: Set Up Procedures). Active Synchronization requires a tachometer signal representing the RPM of
each engine, in addition to the throttle command signal. The function provides for the tachometer frequency
to be measured and the throttle command signal outputs to be changed until both engines are running at the
same RPM, as measured by the tachometer signals.
Run the harness cable to the next processor and plug into the SERIAL connector there.
EN 3340.758.001a - 2014-10 57
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
NOTE: Set up all processors with the same Wire Harness and Engine Set Up selections
The processors connect directly to the engine interface using a Throttle Wire Harness. Refer to section 10:
Troubleshooting to select the correct Throttle Wire Harness for the engine signal required.
Connect the plug end of the Throttle Wire Harness into the THROTTLE connector at the processor.
Run the cable to the engine interface.
Refer to the engine documentation for termination points at the engine interface.
CAUTION: For ZF Hurth Gears with Two Proportional Solenoids Only: The maximum current to ZF Hurth
solenoids must be limited by the control system. Set up the processor values before connecting the cable from
the processor to the gear box. If the processor is connected to the gear box before values are assigned, the
solenoids can be permanently damaged.
Refer to the transmission documentation for termination points at the clutch solenoids.
4.6.2 Tachometer Sensor Wire Harness (Required for AutoTroll and EasiDock)
This harness has plugs on both ends of the cable. The plug on the sensor side is designed to mate
with tachometer assemblies supplied by ZF Marine Propulsion Systems Miramar.
Remove the TACH connector cap from the processor and discard.
Insert the Tachometer Sensor Wire Harness plug in the TACH connector on the processor.
Run the Port Tachometer Sensor Cable to the Port engine tachometer source.
Run the Starboard Tachometer Sensor Cable to the Starboard engine tachometer source.
Make tachometer cable connections as instructed by the engine manufacturer’s documentation.
58 EN 3340.758.001a - 2014-10
INSTALLATION
MMSC5000 SmartCommand User Manual
Installation
WARNING: It is important that each control station have a method, independent of SmartCommand, for
stopping the engines. Refer to the Code of Federal Regulations (CFR) 46, 62.35-5 and the American Boat and
Yacht Council (ABYC) standards on electric and electronic propulsion control systems (P-24.5.8). Personal
Injury may result if this message is disregarded.
EN 3340.758.001a - 2014-10 59
60 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
5 Set Up Procedures
Set up procedures apply to all combinations of required and optional features. The vessel may have all,
some, or none of the optional features. For each vessel, refer to sections that apply to options installed.
Each SmartCommand processor has several functions that must be prepared for an application. Assign
Function Code values only after reading each function set up thoroughly.
EN 3340.758.001a - 2014-10 61
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
Table 5-2: Push Buttons in Function Menu (Function Code LED’s are illuminated steadily)
Key Action Result
UP ARROW or
DOWN ARROW Press UP ARROW or DOWN ARROW. Scroll the Function displayed.
For H0, first two pads blink. Use DOWN ARROW to view
diagnostic values.
LEFT ARROW and Press LEFT ARROW and RIGHT ARROW All functions except H0: Function Code LEDs blink if the PIN
RIGHT ARROW simultaneously and hold for two seconds.
was entered earlier. Enter Set Up mode.
PIn? prompt appears if PIN not entered yet.
Left Arrow Press LEFT ARROW and hold for one second. Stored Error Codes Display.
For Function Codes with values to the right of the decimal
Right Arrow Press and hold. point, displays the complete Function Code value so you can
see all the digits.
Table 5-3: Push Buttons in Set Up Mode (Function Code LED’s are blinking)
Key Action Result
UP ARROW or
Press UP ARROW or DOWN ARROW. Scroll through Function Codes.
DOWN ARROW
LEFT ARROW and Press LEFT ARROW and RIGHT ARROW Save Value: Function Code LEDs stop blinking. Exit Set Up
RIGHT ARROW simultaneously and hold for two seconds. mode.
Escape: Exit set up mode without changes. Function Code
Left Arrow Press LEFT ARROW and hold for one second.
LEDs stop blinking.
For Function Codes with values to the right of the decimal
Right Arrow Press and hold. point, displays the complete Function Code value so you can
see all the digits.
62 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
Table 5-6: Push Buttons In Error Code Display (’Er’ shows in Function Code)
Key Action Result
UP ARROW or
DOWN ARROW Press either UP ARROW or DOWN ARROW. Scroll through the error messages.
NOTE: To exit set-up mode, press and hold the right and left arrows simultaneously for one second, always
making sure to press the right arrow first. If you press the left arrow first, it is possible that the newly-entered
values will not be saved.
The part number (the digits 5000, flashing sequentially) does not appear immediately after set up exits. It
reappears five minutes after the last key press. The part number also appears when power is cycled.
At first power up, the processor displays four dashes, blinking concurrently:
EN 3340.758.001a - 2014-10 63
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
This is the PIN for all processors at the first release. After you enter the last digit, press the right arrow.
64 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
1. The Function Code appears. The left two pads blink. Setup mode is activated
SmartCommand must identify which processor controls which screw, so processors must have a
unique identifying number. Two processors can never have the same Processor Identification Number.
The values of this Function are 01 (Default Value), and 02. Set this Function Code value and the value
of A1 before any other Function Code values are set. Set the values to 01 for Port and 02 for
Starboard. To change the value of the function, press LEFT ARROW and RIGHT ARROW simultaneously
and hold for two seconds to enter set up mode. The PIn? prompt appears: enter the PIN as shown in
section 5.2: Activating Set Up Mode. Set the value of the function depending on the processor you
are programming.
The total number of screws must be entered into the memory of every processor. The same value
must be entered in every processor on a vessel. The default value for this function is 02 Twin Screw
(Default Value). Confirm that this value is correct.
To change the value of the function the processor, press Left Arrow and Right Arrow simultaneously
and hold for two seconds to enter set up mode. Press Up Arrow or Down Arrow to increment or
EN 3340.758.001a - 2014-10 65
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
decrement the value as required. Press Right Arrow and Left Arrow simultaneously and hold for two
seconds to save the new value.
IMPORTANT: The A0 and A1 values must be set before any other Function Code values are set.
WARNING: Follow the complete procedure in this section if you replace or add processors or control heads.
One or both control head levers on some or all stations could become nonresponsive.
At the first power up, all control heads sound a one-second tone and all six LED’s flash. After you set the
values for the A0 and A1 Function Codes, confirm that A3 shows that zero stations are assigned. Go to any
station. Press Control/Set until the Control LEDs are the only LEDs illuminated. Station One is assigned. Go to
each of the other control heads in the order you want to assign the station IDs. (See your notes from Figure 3-
5: System Installation Diagram and Table 3-4: Control Stations. Press Control/Set at each station until the
AutoTroll, EasiDock, Warm Up, and One Lever LEDs extinguish. At both processors, the value of A3
increments when each station ID is defined.
After all station IDs are assigned, the display at power up changes to the digits shown below, flashing
sequentially from left to right.
When you are in the Function Menu (Function Code illuminated steadily), the A3 (Number of Control
Stations) Function Code displays the number of stations that are set up.
66 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
Press the left and right arrows and hold until the station ID disappears and you exit set up mode for
the A3 function. This deletes the station ID and the number of stations decrements automatically.
Release the buttons. Repeat for each station ID. The PIn? prompt stops appearing after the first time.
IMPORTANT: Verify that you have deleted all the station IDs on both processors. If a control head is assigned
two different station IDs, it will not operate correctly.
Once all the station IDs are removed, take control at each control head in the order you want to
renumber the stations.
IMPORTANT: Make certain that you delete all the station IDs on both processors. If a control head is assigned
two different station IDs, it will not operate correctly.
After you have removed all the station IDs, take control at each control head in the order you want.
One Lever Mode allows a single control head lever to command all engines and gears at the same speed and
direction. The values of this function are 00 Disable and 01 Option 1, and 02 Option 2 (Default Value). After
one lever mode is set at the processor, you can select it at the active control head. Option 1 and Option 2
enter and exit One Lever Mode in different ways; vessel operation is the same in both modes. See section
2.11: One Lever Operation Mode for operations information.
JMS Station Pairing, A7, serves two purposes. The first is to enable communication between the JMS
Maneuvering Control Unit (MCU) and the SmartCommand system. The second is to establish the pairing
method that will be used between the JMS operation and the SmartCommand control head. The values of
MMSC5000 Rev B 01/13 Page 67
EN 3340.758.001a - 2014-10 67
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
this function are: 00 - No JMS (Default Value), 01 – JMS Split Pairing, and 02 - JMS Full Pairing. See
MMMCU5000 Joystick Maneuvering System Installation, Operation & Troubleshooting Manual for further
information regarding the JMS control system.
IMPORTANT: For JMS MCU software versions 71333.0E and earlier, A7 should be set to the type of pairing that
is desired to be used when the JMS system is operational.
For JMS MCU software versions 71333.1A and later the type of pairing is set by the JMS AutoCommissioning
tool; therefore, A0 must always be set to 02 – JMS Full Pairing.
Engine manufacturers use different electronic interfaces to command engine speed. Enter the engine
type so the correct signals are sent to the specific type of engine in the vessel. The Engine Throttle
Profile, in combination with the Throttle Harness type, configures the throttle output profile to meet
the specifications of engines from different manufacturers in specific configurations. The values of this
function are:
Table 5-7: Engine Throttle Profile Definitions
E0 Value Engine Type
01 Caterpillar (PWM) (8 to 92%)
02 Cummins Centry (Voltage) (0.9 to 4.5VDC)
03 Cummins Quantum (Voltage) (0.9 to 1.2- 4.0VDC)
04 Detroit Diesel (Voltage) (0.64 to 4.65 VDC)
05 MTU or MAN (Current) (4.0 to 20 mA)
06 Scania (Voltage) (0.4 to 2.95 VDC)
07 John Deere (Voltage) (0.5 to 4.5 VDC) EDC Only
Volvo EDC Engines (Voltage) (0.6 to 3.6 VDC)
08
Volvo EVC Engines use a different voltage.
09 Detroit Diesel (Frequency) (120.64 to 360.9 Hz)
68 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
SmartCommand uses Active Synchronization by default. If the tachometer signal is not available, the
system automatically uses Equal Throttle Synchronization.
Equal Throttle Synchronization is very effective in most cases. The processors send equal throttle
command signals to both governors when synchronization criteria are met but the RPM rates of the
engines do not necessarily match. For additional information about synchronization, see section 2.10:
Twin Screw Synchronization.
If you want the RPM of the engines to match, select Active Synchronization at the processor. In
addition to the throttle command signal, Active Synchronization requires a tachometer signal
representing the RPM of each engine. The tachometer frequency is measured and the throttle
command signal outputs are changed until the frequencies of the tachometer signals are the same (in
other words, both engines are running at the same RPM). The values of this function are 00 (equal
throttle synchronization enabled - this is the default), 01 (Active Synchronization enabled with equal
throttle if tach signal fails), 02 (disabled), and 03 (Active Synchronization enabled with no
synchronization if the tach signal fails).
The Function Code E8 allows the SmartCommand control system to be automatically activated in the
“Warm Up” mode upon initially energizing and taking command at a control station. The values of this
Function Code are: 00 – Cruise Mode at power up (Default) and 01 – Warm up mode at power up.
EN 3340.758.001a - 2014-10 69
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
IMPORTANT: Set the value of this function to 01 (INSTALLED) only if the optional clutch oil pressure switch is
used with this application.
The C0 Function Code indicates to the processor whether or not a clutch oil pressure switch is in use
and how it is being used. The primary function of a clutch oil pressure switch is to protect the clutch
pack (damage to which could be very costly). The clutch oil pressure switch commands the throttle to
idle if full pressure is not reached, or pressure is lost, when ahead or astern clutch engagement is
commanded. The values of this function are:
• 00 -- Not Installed (Default)
• 01 -- Installed
• 02 -- Throttle Clutch Pressure Interlock Mode
When this Function Code is set, the value most likely to be used is 02. When C0 is set to 02, the
throttle will remain in idle until it recognizes that the oil pressure switch has been closed.
IMPORTANT: The clutch oil pressure interlock delay C1 Function Code is operable only if the optional clutch oil
pressure switch, Function Code C0, is set to 01 or 02, as explained below. If C0 is set to the default of 00, a C1
Function Code setting will have no effect.
The clutch oil interlock delay prevents drops in throttle when gear oil pressure fluctuates. The system
responds to the low pressure by reducing the throttle command signal to idle. Used in conjunction
with the clutch oil interlock function (Function Code C0), the value entered for the C1 function
determines how quickly the system responds to low gear oil pressure.
If the C0 value is 01, the C1 Function Code setting indicates the period of time the system will wait
until it actually looks at the status of the clutch oil pressure switch. (For example, if the value of C1 is
3.0 the system will wait 3 seconds before dropping the throttle command signal to idle.)
If the value of C0 is 02, the C1 Function Code setting indicates the amount of time that must pass
with the switch open before the throttle will be pulled back to idle.
The C1 Function Code can be set from 0.5 to 10 seconds, in increments of 0.1 (one tenth) second.
The default Value is set to 01.0 second delay.
70 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
If you reverse the direction of the vessel, there is a pause before the opposite clutch command signal
takes effect. This pause allows time for the engine RPM to drop to idle and for the vessel to slow
through the water. The C2 function determines when this pause occurs -- either while the clutch is
engaged or in neutral. In general, you would use in-gear delay to allow the propeller to slow vessel
progress through the water, but neutral delay if the vessel has shaft brakes. The three values the C2
Function Code can be set to are 00 (in gear -- this is the default), 01 (neutral), and 02 (fixed neutral).
The sequence of events depends on the value set, as described below.
In-Gear Delay (00):
• Throttle drops to idle.
• Transmission remains engaged in ahead or astern.
• Control system pauses for the duration of the pause.
• Transmission shifts into the opposite gear.
• Throttle changes to match the control head lever position.
.
IMPORTANT: If J0 is set to 08 (ZF Friedrichshafen gears with MTCU), full throttle is limited for the first two
seconds the opposite gear is engaged.
CAUTION: Fixed Neutral Delay is used for Thruster Control installations. The drive train can be damaged if it is
used in reverse reduction gear applications, or reversal time can be reduced unduly.
IMPORTANT: If J0 is set to 08 (ZF Friedrichshafen gears with MTCU), full throttle is limited for the first two
seconds the opposite gear is engaged.
EN 3340.758.001a - 2014-10 71
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
After you command a Full Speed Reversal, the Reversal Pause Time feature decelerates the engine
and pauses before throttling to the commanded speed in the opposite direction when C2 is set to 00
or 01. The pause time is proportional to the percent throttle commanded and the length of time it has
been commanded.
For the system to pause for the full duration specified in the C3 Function Code, the vessel must be at
full throttle and ahead, and have remained at this setting for at least six times the duration of the
pause value. If the vessel is at a lower throttle setting or has been at speed for less than six times the
duration of the pause value, the pause is shorter. The pause may be shorter for astern to ahead
maneuvers, depending on the value of C4.
The throttle position drops to Idle and the transmission remains engaged or shifts to neutral,
depending on the value of the C2 function.
The limits for this function are 00.0 to 16.0 seconds. Adjust this function during sea trials. You must
have instruction to determine the correct setting.
Default Value is set to 03.0 second pause.
00 - 2:1 Ratio
This is the default setting and determines how the value set in the Reversal Pause Time (C3) Function is
applied for astern to ahead maneuvers. If the C4 Function Code is set to the 00 value, an astern to
ahead maneuver is one half of the Reversal Pause Time. This is the typical selection, since most vessels
do not reach the same throttle in astern as they do in ahead. The duration to slow to a sufficient water
speed for a safe reversal is significantly faster.
01- 1:1 Ratio
A 01 value for the C4 function sets the same pause time for ahead to astern maneuvers and astern to
ahead maneuvers. Choose this value for vessels that reach the same water speed in both directions, for
example, a Double Ended Ferry or Bow or Stern Thruster control.
The values of this Function are 00 2:1 (Default Value) and 01 1:1.
72 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
This Function Code must be set to 00, unless a ZF Hurth gear with proportional ahead and astern
solenoids is installed. The current is limited to the solenoids when the 01 or 02 values are selected.
00 - All shift solenoids except ZF Hurth (Default)
01 - ZF Hurth Gears with two proportional solenoids using 12 VDC power
02 - ZF Hurth Gears with two proportional solenoids using 24 VDC power
CAUTION: For ZF Hurth Gears with Two Proportional Solenoids Only: The maximum current to ZF Hurth
proportional solenoids must be limited by the control system. Set up the processor values before connecting
the cable from the processor to the gear box. If this value is not correct or the processor is connected to the
gear box before the value is set up, the solenoids can be permanently damaged.
This Function Code adjusts the maximum current available to the ahead proportional solenoid. Failure
to limit the current may result in permanent damage to the solenoid. The values available are 0% to
100.0% duty cycle. The default value is 100%. Do not change the value of this function unless
directed to do so by ZF Marine Propulsion Systems Miramar.
This Function Code adjusts the maximum current available to the Astern proportional solenoid. Failure
to limit the current may result in permanent damage to the solenoid. The values available are 0% to
100.0% duty cycle. The default value is 100%. Do not change the value of this function unless
directed to do so by ZF Marine Propulsion Systems Miramar.
Only use C8 when C2 is set to 00 or 01, that is, when the vessel uses a proportional delay. C8
programs in a delay time in addition to the proportional delay.
EN 3340.758.001a - 2014-10 73
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
IMPORTANT: To configure a ZFF Transmission with MTCU, set J0 to a value of 08 first, then set L0 to the
desired troll lever range. J1 through J7 are not accessible with this configuration.
The troll lever range can be adjusted to one of five values at processor set up, through the L0 Function
Code. The values for L0 are as shown below in Table 5-8: L0 Function Code Values
Table 5-8: L0 Function Code Values
Troll Range (in Movement between Ahead Movement through Troll
L0 Value Movement Beyond Troll Range
Degrees) and Astern Detents Range
Clutch Fully Engaged, throttle NA Clutch Fully Engaged, Neutral
00 No Troll
at idle to Full Throttle
Minimum Troll Clutch Minimum to Maximum troll Clutch fully engaged, throttle
01 15 degrees
pressure, throttle at idle Clutch pressure, throttle at idle from minimum to full
Minimum Troll Clutch Minimum to Maximum troll Clutch fully engaged, throttle
02 30 degrees pressure, throttle at idle Clutch pressure, throttle at idle from minimum to full
Minimum Troll Clutch Minimum to Maximum troll Clutch fully engaged, throttle
03 40 degrees
pressure, throttle at idle Clutch pressure, throttle at idle limited to 75% of full
Minimum Troll Clutch Minimum to Maximum troll Clutch fully engaged, throttle
04 50 degrees
pressure, throttle at idle Clutch pressure, throttle at idle limited to 10% of full
Minimum Troll Clutch No Movement: Troll at Detents Clutch fully engaged, throttle
05 Detents Only
pressure, throttle at idle only. from minimum to full
NOTE: The default value for Function Code L0 is 00 (No Troll). If this function is set to 00, the other L Function
Codes (meaning Troll) do not appear in the function menu.
74 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
NOTE: Set the J2 through J7 Function Codes only if you are instructed to do so by ZF Marine Propulsion
Systems Miramar. If J0 is set to 08 (ZF Friedrichshafen gears with MTCU), the J1 through J7 functions are not
displayed.
This function determines the behavior of the current signal to the proportional valve. The default value
is 00.
When the value of J0 is set to 08, no other J Function Codes can be displayed.
Using definitions from Table 5-9: Trolling Valve Type Selection determine what value to choose for a
particular application. After selecting the appropriate value, enter your selection for Function Code J0
on the processor.
Table 5-9: Trolling Valve Type Selection
Value Selection and Definition
Normal - no current when off. The current to the proportional valve increases as clutch pressure increases. When full
00 pressure (lockup) is reached, the current to the valve drops to zero. This is the default value.
Preset for generic 10 - 25% duty cycle.
Inverse - no current when off. The current to the proportional valve decreases as clutch pressure rises. When full
01 pressure (lockup) is reached, the current increases to maximum.
Preset for generic 10 - 25% duty cycle.
Normal - no current when off. The current to the proportional valve increases as clutch pressure rises. When full
pressure (lockup) is reached, the current to the valve drops to zero.
02
Preset for ZF Padova 220 - 665 12 VDC Systems. All values assume 12V/10 Ohm proportional solenoid. New or
upgraded transmissions only.
Normal - no current when off. The current to the proportional valve increases as clutch pressure rises. When full
pressure (lockup) is reached, the current to the valve drops to zero.
03
Preset for ZF Padova 220 - 665 24 VDC Systems. All values assume 12V/10 Ohm proportional solenoid. New or
upgraded transmissions only.
Normal - no current when off. The current to the proportional valve increases as clutch pressure rises. When full
04 pressure (lockup) is reached, the current to the valve drops to zero.
Preset for ZF 2000, 24 VDC systems
Inverse - no current when off. The current to the proportional valve decreases as clutch pressure rises. When full
05 pressure (lockup) is reached, the current increases to maximum.
Preset for ZF 1900 and 2500 24 VDC systems.
Preset for 12 VDC ZF Hurth transmissions with two (2) proportional solenoids only. ZF Hurth with one (1) proportional
06 solenoid, use 00.
07 Preset for 24 VDC ZF Hurth transmissions with two (2) proportional solenoids only. ZF Hurth with one (1) proportional
solenoid, use 00.
08 Preset for ZF Friedrichshafen transmissions with MTCU (Marine Transmission Control Unit).
EN 3340.758.001a - 2014-10 75
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
IMPORTANT: If J0 is set to 08 (ZF Friedrichshafen gears with MTCU), throttle is limited for the first two seconds
after clutch engagement is commanded, to prevent clutch damage. In Cruise mode, the throttle pause
following a shift (E5 Function Code value) is increased to 0.9 seconds and throttle in the subsequent 1.1
seconds is limited to a 15% increase. In AutoTroll or EasiDock, when lever command leaves the troll range, in
the subsequent two seconds throttle is limited to a 15% increase.
The value for J1 is actually the frequency of the signal being generated by the output shaft sensor
(Tach 2), when the engine is running at idle and the ahead clutch is engaged. Determine the value for
J1 by using the H0 diagnostics function (refer to section 10: Troubleshooting for detailed diagnostic
information), during a sea trial, or calculate the value using the following information:
1. Engine RPM @ idle = ________________________
2. Reduction ratio = _______________________
3. Number of pulses per revolution (PPR) = ________________________
Following is an example of the way to calculate the frequency of the Tach 2 signal:
1. Engines RPM @ idle = 600
2. Reduction ratio = 2:1
3. PPR = 60
4. Multiply engine RPM by the reduction ratio times the PPR:600 x .50 x 60 = 18000 pulses per minute
(PPM)
5. To convert the PPM to pulses per second (Hz), divide by 60:18000 / 60 = 300 Hz.
Enter 300 as the value for the J1 Function Code. (Remember that you can see values greater than
two digits by pressing and holding the right arrow key down, which dedicates all four LEDs to the
value.)
If the J0 Function Code has been set to 08, no entry for the value of the J1 Function Code is required.
The default value for the J2 Function Code is 30. This value should not be changed, except at the
direction of ZF Marine Propulsion Systems Miramar.
The value entered for J2 determines the frequency of the output shaft when it is at minimum pressure
during trolling. At the default 30 setting, the output shaft will rotate at 30% the value of the J1
Function Code setting.
If J1 is set to 300 and J2 is set to 30, the processor will maintain an output frequency of 90 Hz
(300 x .30) while at minimum pressure. This frequency represents a speed that is 30% of full clutch
engagement.
76 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
The default value for the J3 Function Code is 70. This value should not be changed, except at the
direction of ZF Marine Propulsion Systems Miramar.
The value entered for J3 determines the frequency of the output shaft when it is at maximum pressure
during trolling. At the default 70 setting, the output shaft will rotate at 70% the value of the J1
Function Code setting.
If J1 is set to 300 and J3 is set to 70, the processor will maintain an output frequency of 210 Hz
(300 x .70) while at maximum pressure. This frequency represents a speed that is 70% of full clutch
engagement.
The default value for the J4 Function Code is 00.0. This value should not be changed, except at the
direction of ZF Marine Propulsion Systems Miramar.
The value entered for J4 determines how closely the processor should attempt to reach the
frequencies set by the J2 and J3 Function Codes (tolerances). When J4 remains at the default value
of 00.0, the processor will constantly adjust the output signal to the proportional valve until the
frequency determined by J2 or J3 is matched.
The default value for the J5 Function Code is 00.3. This value should not be changed, except at the
direction of ZF Marine Propulsion Systems Miramar.
The value entered for J5 determines how often the processor measures the speed of the output shaft
to compare the actual speed to the expected speed (refresh rate). If the expected and actual speeds
don’t match, the signal to the proportional solenoid is increased or decreased as necessary.
The default value of the J6 Function Code varies, depending on the value set for the J0 Function
Code. The J6 Function Code value should not be changed, except at the direction of ZF Marine
Propulsion Systems Miramar.
The J6 and J7 functions set the limitations for controlling a specific trolling valve, allowing the control
system to lock quickly onto the required RPM. Table 5-10: J6 and J7 Values as Related to J0 below,
lists the expected values for the J6 Function Code, as determined by the J0 setting.
EN 3340.758.001a - 2014-10 77
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
The default value of the J7 Function Code varies, depending on the value set for the J0 Function
Code. The J7 Function Code value should not be changed, except at the direction of ZF Marine
Propulsion Systems Miramar.
Along with the J6 Function Code, J7 sets the limitations for controlling a specific trolling valve,
allowing the control system to lock quickly onto the required RPM. The expected values for the J7
Function Code, as determined by the values set for J0, are shown in Table 5-10: J6 and J7 Values as
Related to J0.
J0 Value 00 01 02 03 04 05 06 07 08
J6 Value 10.0 30.0 17.0 08.0 10.0 30.0 05.0 10.0 --.--
J7 Value 25.0 10.0 24.0 11.5 30.0 10.0 10.0 20.0 --.--
The J8 Function Code initiates the process of the automated troll setup which will find the best
minimum and maximum trolling settings (J6 & J7) by cycling the trolling valve throughout its range.
During setup, the Function Code will sequence through several steps (00-07) while the automated
troll process is occurring.
Time for each step and sample to complete. This value is in seconds. The default value is set to 60
seconds, minimum 20 and Max 250 seconds.
Number of samples per step. The default value is 3 samples per step, minimum 1 and Max 5 samples
per step.
78 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
Automatic Troll Setup Deadband Window, This parameter is used to increase or decrease the amount
of deadband needed for the Automatic Troll Setup function to determine the correct Troll Frequency.
The default is 2%, minimum 1% and maximum is 100%.
CAUTION: Although the EASIDOCK Function Codes provide similar versatility to the AUTOTROLL Function Codes,
experience has shown that, in general, the EASIDOCK default values provide the best response. Use extreme
caution when making any adjustments to the “d” Function Codes.
EN 3340.758.001a - 2014-10 79
SETUP PROCEDURES
MMSC5000 SmartCommand User Manual
Set Up Procedures
IMPORTANT: Factory default Function Code settings are different from those supplied with customized kits.
This means that if you reset Function Codes to their defaults, the kit presets will be overridden.
80 EN 3340.758.001a - 2014-10
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
ZF Marine Propulsion Systems Miramar, LLC
12125 Harbour Reach Dr Ste B
SETUP PROCEDURES
Mukilteo, WA 98275
P - 425-583-1900
F - 425-493-1569
www.zf.com
Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
Confidentiality Protection Classification: Public
Integrity Protection Classification: Normal
Availability Protection Classification: Normal
NOTE: The information contained within this document is ZF Proprietary and must NOT be duplicated and/or
distributed, electronically or otherwise to any person or organization outside of ZF Marine without explicit
permission from the ZF Marine Business Unit Manager or responsible department Manager.
Table of Contents
SmartCommand Function Codes .............................................................. page 82
POD Function Codes ................................................................................................. page 87
Sport Fish Function Codes........................................................................................ page 89
SteerCommand Function Codes ............................................................................... page 89
Two Speed Function Codes ...................................................................................... page 91
Speed Boost Function Codes.................................................................................... page 91
MCU Function Codes ................................................................................ page 91
Below is a list of Function Codes, each defined by application, function name, default value, and range. There is a
place to enter data for Sea Trials, if you are not performing a Sea Trial please disregard these columns.
IMPORTANT: Factory default Function Code settings are different from settings supplied with customized kits.
This means that if you reset Function Codes to their defaults, the kit presets will be overridden.
EN 3340.758.001a - 2014-10 81
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
CAUTION: If the vessel has ZF Hurth gears with two proportional solenoids installed, set the J0 Function Code
immediately after setting the A0 Function Code. J0 sets Function Codes to limit current to a Hurth gear box:
the solenoids can be permanently damaged if other Function Codes are set first.
82 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
EN 3340.758.001a - 2014-10 83
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
84 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
EN 3340.758.001a - 2014-10 85
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
86 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
EN 3340.758.001a - 2014-10 87
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
88 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
nA Enable bits for Pod warnings FF Are for use by certified ZF technicians only.
nb Enable bits for Pod faults FF Are for use by certified ZF technicians only.
nc Pod Faults Enabled. 00 Are for use by certified ZF technicians only.
EN 3340.758.001a - 2014-10 89
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
90 EN 3340.758.001a - 2014-10
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
EN 3340.758.001a - 2014-10 91
SETUP PROCEDURES
ENG-289 Function Codes for SmartCommand, JMS, SBW, MCU and POD Systems
CAUTION: If the vessel has ZF Hurth gears with two proportional solenoids installed, set the J0 Function Code
immediately after setting the A0 Function Code. J0 sets Function Codes to limit current to a Hurth gear box:
the solenoids can be permanently damaged if other Function Codes are set first.
92 EN 3340.758.001a - 2014-10
DOCK TRIALS: ADJUSTMENTS AND TESTS SECURED TO DOCK
MMSC5000 SmartCommand User Manual
Dock Trials
NOTE: If any of the tests in this section fail, verify Start Interlock Installation and Start Interlock Connections.
6.3 Service Field Test Unit (Break-out Box) and Multimeter Use
ZF Marine Propulsion Systems Miramar recommends the use of ZF Marine Service Field Test Unit (P/N
13927) (Break-out Box) and a calibrated Multimeter to adjust the functions listed in Table 6-1: Functions
Requiring Service Field Test Unit and Multimeter.
EN 3340.758.001a - 2014-10 93
DOCK TRIALS: ADJUSTMENTS AND TESTS SECURED TO DOCK
MMSC5000 SmartCommand User Manual
Dock Trials
Table 6-1: Functions Requiring Service Field Test Unit and Multimeter
Function Section Showing Adjustments
E1 Section 6.8: E1 - Throttle in Neutral
E2 and E3 Section 6.4: E-2 Throttle Minimum and E-3 Throttle Maximum Signal (Engines Stopped)
E4 Section 6.9: E4 - Throttle Maximum Astern
E6 Section 6.10: E6 - High Idle
Section 7.5: L1 and L2 AutoTroll Minimum and Maximum Adjustments Do not use this setup procedure for L1
L1 and L2
or L2 if MTCU-equipped ZF Friedrichshafen gears are installed.
L3 Section 7.6: L3 - Troll Throttle Limit
Section 7.6: L3 - Troll Throttle Limit. Do not use this setup procedure for d1 or d2 if MTCU-equipped ZF
d1 and d2
Friedrichshafen gears are installed.
d3 Section 7.6: L3 - Troll Throttle Limit
For Functions E1, E2, E3, E4, E6, L3, and d3 connect the eight pin connector of the Service Field Test Unit
into the Processor Throttle connector and to the Throttle Wire Harness on the ECM (Reference “1” in Figure 6-
2: E1, E2, E3, E4, E6, L3, and d3 Processor, Test Unit, and Multimeter Connections)
Figure 6-2: E1, E2, E3, E4, E6, L3, and d3 Processor, Test Unit, and Multimeter Connections
For Functions L1, L2, d1, and d2 connect the twelve pin connector of the Service Field Test Unit to the
Processor Clutch connector and to the Clutch Wire Harness on the gear box (Reference “1” in Figure 6-3: L1,
L2, d1, and d2 Processor, Test Unit, and Multimeter Connections).
Figure 6-3: L1, L2, d1, and d2 Processor, Test Unit, and Multimeter Connections
94 EN 3340.758.001a - 2014-10
DOCK TRIALS: ADJUSTMENTS AND TESTS SECURED TO DOCK
MMSC5000 SmartCommand User Manual
Dock Trials
6.4 E-2 Throttle Minimum and E-3 Throttle Maximum Signal (Engines Stopped)
Adjustments may not be required. Verify the existing Throttle Minimum and Maximum values before adjusting
them.
NOTE: For Equal Throttle Synchronization, the setting for throttle minimum must be the same on both
processors and the setting for throttle maximum must be also be the same on both processors. Otherwise, the
engines will synchronize at different RPM.
NOTE: Before beginning any adjustments, select the correct Engine Profile (described in Section 5.8.1: E0 —
Select Engine Throttle Profile).
EN 3340.758.001a - 2014-10 95
DOCK TRIALS: ADJUSTMENTS AND TESTS SECURED TO DOCK
MMSC5000 SmartCommand User Manual
Dock Trials
2. In the diagram,
a Shows the ECM with the throttle cable connected to the eight pin connector.
b Shows the unused twelve pin connectors.
c Identifies the break out box
d Is a reminder to press the MA button on the breakout box to take the
measurement.
3. Turn ON power to the engine’s throttle interface. Verify processor power is ON.
a At the processor, press UP ARROW or DOWN ARROW once to enter the Function
Menu.
96 EN 3340.758.001a - 2014-10
DOCK TRIALS: ADJUSTMENTS AND TESTS SECURED TO DOCK
MMSC5000 SmartCommand User Manual
Dock Trials
WARNING: Never adjust Throttle Maximum while at dock. Personal Injury may result if this message is
disregarded.
NOTE: To read current on the Service Field Test Unit, press the mA push button on the box.
e On the processor, press LEFT ARROW and RIGHT ARROW simultaneously and
hold for two seconds to enter set up mode. The Function Code blinks or the
PIn? prompt appears if PIN not entered yet.
f Change the value of the function, or enter the PIN and change the value of the
function.
NOTE:
• To show values that have more than two digits (for example, 010.5), press the RIGHT ARROW key and hold
it until the Function Code disappears and the display shows three or four digits: this is the full three- or
four-digit value. The decimal indicator lights if the number has a decimal value.
• To make small adjustments to the signal, press RIGHT ARROW simultaneously with UP ARROW or DOWN
ARROW.
• Release the RIGHT ARROW key to return to Set Up mode: the Function Code blinks in the two left pads and
the first two digits of the value display in the two right pads.
g When the value you want displays or you reach the RPM that you want, store
the value and exit Set Up mode.
h Shut down power to the engine and processor.
i Remove the Service Field Test Unit. Reconnect the Throttle Wire Harness to
the processor.
EN 3340.758.001a - 2014-10 97
DOCK TRIALS: ADJUSTMENTS AND TESTS SECURED TO DOCK
MMSC5000 SmartCommand User Manual
Dock Trials
Warning: An Engine Stop Switch MUST be installed at every remote operating station. Refer to the Code of
Federal Regulations (CFR) 46, 62.35-5 and the American Boat and Yacht Council (ABYC) standards on electric
and electronic propulsion control systems (P-24.5.8). Personal Injury may result if this message is disregarded.
WARNING: Do not attempt to continue tests until the Engine Stop Switches function correctly. Personal Injury
may result if this message is disregarded.
CAUTION: Verify the vessel is secured to the dock. Step B engages the transmission briefly.
NOTE: Lever movement tests whether the control head is operating. Verify the Port Control Head lever
operates the Port Processor and the Starboard Control Head lever operates the Starboard Processor.
4. Place the control head levers in the neutral detent position to prepare for the next test.
NOTE: To confirm Speed Command operation, use Warm-Up mode on each engine from each station, one
engine at a time.
1. At the station in command, put the control head lever in the neutral detent position.
2. Press the MODE button until the WARM UP LED blinks. If no button is pressed in ten seconds, the LED stops
blinking and the mode does not change.
3. Press CONTROL/SET once. The WARM UP LED illuminates steady red and the CONTROL LEDs blink green.
4. Move the control head lever into the ahead range. The throttle increases and the transmission remains in
Neutral. Moving the lever in the astern direction does not increase throttle.
5. If the WARM UP LED is illuminated steady red and the CONTROL LEDs blink green, Warm Up mode has been
activated. Continue with adjustments and tests.
6. If the WARM UP LED is not lit, blinking, or anything other than steady red, verify all connections are correct. Make
any necessary changes. Repeat the Warm Up mode Test.
7. Move each control head lever to full throttle. Verify the engine reaches full throttle
98 EN 3340.758.001a - 2014-10
DOCK TRIALS: ADJUSTMENTS AND TESTS SECURED TO DOCK
MMSC5000 SmartCommand User Manual
Dock Trials
CAUTION: If any tests in Section 6.6: Lever Movement at Control Heads or Section 6.7: Warm-Up Mode Test
(Engines Running) fail, correct the problem before taking the vessel out for sea trials.
NOTE: Only use this function when the E0 SELECT ENGINE THROTTLE PROFILE is set to: 03 - CUMMINS QUANTUM.
The Cummins-Quantum Engine requires different throttle command signals in Neutral than when In-Gear.
These engines require a voltage throttle signal of 0.9 VDC when unloaded at Neutral. When a load is placed
on the engine by engaging the clutch, the throttle command signal increases to 1.2 VDC.
The Throttle in Neutral Function adjusts the throttle signal level at Neutral/Idle. The Neutral value may be
adjusted between 1% to 25% of the maximum throttle output capability of the voltage circuit. Throttle at Idle
Ahead and Astern is adjusted with the E2 - Throttle Minimum Function Code.
For example, if the circuit has the ability to drive 0 to 5.00 VDC and the value entered is 10, the output at
Neutral would be 0.50 VDC.
The limits for this function are 01.0% to 25.0%. Throttle defaults are based on the Throttle Profile selected.
• Disconnect the Throttle Wire Harness from the SmartCommand Processor.
• Connect both eight pin connectors from the Service Field Test Unit to the Processor Throttle
connector and to the Throttle Wire Harness. See Figure 6-2: E1, E2, E3, E4, E6, L3, and d3 Processor,
Test Unit, and Multimeter Connections for details.
• Power up the engine’s throttle interface. Verify processor power is ON.
• Press UP ARROW or DOWN ARROW to activate the Function Menu.
• Use UP ARROW or DOWN ARROW to scroll to the E1 Function Code
EN 3340.758.001a - 2014-10 99
DOCK TRIALS: ADJUSTMENTS AND TESTS SECURED TO DOCK
MMSC5000 SmartCommand User Manual
Dock Trials
For example, if Throttle Minimum (E2) is 10 and Throttle Maximum (E3) is 80, and E4 is 50%,
Throttle Percentage Astern 80 10 – ( ) 0.5 × ( ) 10
the final throttle percentage astern is 45% of full throttle.
The breakout box may not be necessary to adjust this function. In some cases, you may know the percentage
of Throttle Ahead you want to use. In those cases, set the parameter without the breakout box.
To use the breakout box:
WARNING: Verify that Warm Up mode is active before adjusting this function. Personal Injury may result if this
message is disregarded.
NOTE: To read current on the Service Field Test Unit, press the mA Push Button on the box.
• Activate Set Up mode: press LEFT ARROW and RIGHT ARROW and hold for two seconds, until the
Function Code blinks or the PIn? prompt appears if PIN not entered yet.
• Change the value of the function, or enter the PIN and change the value of the function using UP
ARROW or DOWN ARROW.
• When the value you want displays, store it. Press RIGHT ARROW and LEFT ARROW simultaneously and
hold for one second.
• Exit Set Up mode.
• Shut down power to the engine and processor.
• Remove the Service Field Test Unit and reconnect the Throttle Wire Harness to the processor.
CAUTION: High Idle can be set higher than the safe shift RPM for the gear.
• Connect both eight pin connectors from the Service Field Test Unit to the Processor Throttle
connector and to the Throttle Wire Harness. See Figure 6-2: E1, E2, E3, E4, E6, L3, and d3 Processor,
Test Unit, and Multimeter Connections for details.
• Power up the engine’s throttle interface. Verify processor power is ON.
• Press UP ARROW or DOWN ARROW to activate the Function Menu.
Use UP ARROW or DOWN ARROW to scroll to the E6 Function Code. The Multimeter reads the output signal for
High Idle.
NOTE: To read current on the Service Field Test Unit, press the mA Push Button on the box.
NOTE: To make small current adjustments, press RIGHT ARROW and hold while pressing UP ARROW or DOWN
ARROW.
• Activate Set Up mode: press LEFT ARROW and RIGHT ARROW and hold for two seconds, until the
Function Code blinks or the PIn? prompt appears if PIN not entered yet.
• Change the value of the function, or enter the PIN and change the value of the function using UP
ARROW or DOWN ARROW.
• When the value you want displays, store it. Press RIGHT ARROW and LEFT ARROW simultaneously and
hold for one second.
• Shut down power to the engine and processor.
• Remove the Service Field Test Unit and reconnect the Throttle Wire Harness to the processor.
To select High Idle at the control head: When power is first applied to the system, idle speed is set to low
idle. Move the levers to any detent and press CONTROL/SET on the control head for one half second and
release it to set the idle speed to high idle. Release the button and press and hold again for one half second
to switch from High Idle back to Low Idle.
NOTE: Set Port and Starboard High Idle to the same value. Both processors output high idle or low idle at the
same time.
This value defines the pause time from the time the clutch engagement signal is given to the time throttle is
allowed to increase above Idle. The pause value can be set from 00.0 to 02.5 seconds. The default value is
00.5 second pause. This is a good starting point for most hydraulic clutches.
NOTE: ZF Marine Propulsion Systems Miramar recommends you use a stopwatch and a test control head to
set this parameter. If a test control head is not available, two people may be required to run this test.
Set the value for the E5 Function Code to 0.0 if the vessel has a mechanical clutch, such as a dog or cone
clutch. There is no delay built in to these systems.
NOTE: If the time recorded is greater than 5.0 seconds, install a clutch oil pressure interlock. See Section 8.2:
Clutch Oil Pressure Interlock
G Activate Set Up mode: press LEFT ARROW and RIGHT ARROW and hold for two seconds, until the
Function Code blinks or the PIn? prompt appears if PIN not entered yet.
H Change the value of the function, or enter the PIN and change the value of the function using UP
ARROW or DOWN ARROW.
I When the value you want displays, store it. Press RIGHT ARROW and LEFT ARROW simultaneously and
hold for one second.
CAUTION: Start slowly and learn to appreciate that the SmartCommand System provides a light touch that is
fast and accurate. Damage to the vessel may occur if this message is disregarded.
CAUTION: Test proportional pause as outlined below to ensure it was properly programmed. Failure to do so
could cause transmission damage.
A Position the boat in open water and slowly increase the throttle to 25% of the speed range.
B Leave the control head levers at this position for at least 60 seconds.
C Quickly move the control head levers to Idle Astern.
• The engine RPM should drop to idle.
• The clutch should stay engaged or shift to Neutral for 25% of the time selected with
Function Code C3 proportional pause time.
• After the time has expired, the clutch shifts to Astern.
• The engine RPM drops slightly when the Astern load is placed on the engine, but not to the
point where it comes close to stalling.
D Increase the throttle slightly until the vessel starts moving in the opposite direction.
E If the engine stalled or came very close to stalling, increase the value of Function Code C3 by
one second. Repeat steps A through C.
F Repeat steps A through D with the throttle at 50%, 75%, and 100% of the speed range.
G If the engine stalls at any time, increase the value of Function Code C3 by one second and
repeat the steps A through D again.
The engine is properly adjusted after you complete a full speed reversal without the engine
approaching a stall. The throttle setting drops to Idle and the transmission shifts to Neutral or remains
in gear during the pause, depending on the value of the C3 Function Code.
If reversal stalls occur and maximum proportional delay is programmed, speed boost or shaft brakes
may be required; contact a ZF representative. Have the following information ready:
• Vessel Length
• Hull Type, Planing, Displacement, etc.
• Engine Type and horsepower rating
• Gear type and reduction ratio
See section 5.9.3: C2 — Reversal Pause, section 5.9.4: C3 — Reversal Pause Time, and section 5.9.5:
C4 — Reversal Pause Ratio, for settings related to Reversal Pause.
1% different at any throttle setting, or if the engines appear to be continually “hunting” for the matching RPM,
refer to section 10: Troubleshooting.
IMPORTANT: Measure the Propeller Shaft RPM when the transmission oil has reached operating temperature.
Do not make adjustments before oil has reached temperature.
This Function Code is not displayed if J0 is set to 08 - ZF Friedrichshafen gears with MTCU. Measure the
propeller shaft frequency using the tachometer value in the SmartCommand processor diagnostic menu.
A On the processor, press UP ARROW or DOWN ARROW on the processor to activate the function menu.
B Press UP ARROW or DOWN ARROW to scroll to H0 Diagnostics.
C Press DOWN ARROW once to see the battery voltage.
D Press DOWN ARROW once to see the Output Shaft frequency reading. The Output shaft frequency
reading has two decimal points, as in this example:
E Start the engine and command Idle Ahead without AUTOTROLL or EASIDOCK enabled.
F Record the value shown on the processor display in Table 7-1: Output Shaft Idle Lockup RPM. If the
vessel has a troll valve and AutoTroll is set up, record this value in Table 7-2: Troll Minimum and
Maximum Values. If the vessel has a troll valve and EASIDOCK is set up, also record the value in F-259
SmartCommand Sea Trial Report.
Port
Starboard
G Exit the H0 Function Code. Press LEFT ARROW and hold until the H0 LED pads stop blinking.
H Return the control head to the Neutral/Idle position and shut down the engine.
I Repeat steps A - G for each engine.
J Set the J1 value:
K Use UP ARROW to scroll to J1 - Idle Lockup RPM.
L Press LEFT ARROW and RIGHT ARROW simultaneously and hold for two seconds until the J1 Function
Code blinks or the PIn? prompt appears if PIN not entered yet.
M Change the value of the J1 function, or enter the PIN and change the value of the function using UP
ARROW or DOWN ARROW to match the value recorded for the propeller shaft RPM.
The Troll Maximum Pressure (L2) function sets the amount of current delivered to the Proportional
Valve at Maximum Pressure. The range for this value is between 2.0% and 100.0% of the total current
output capability of the circuit. The value set must be at least 1% more than Troll Minimum if non-
inverted is selected or 1% less than Troll Minimum if inverted is selected. The Default Value depends
on the gear type installed. Typically, it is about 70%.
7.5.2 AutoTroll Maximum Pressure (L2)
The amount of current required to reach minimum and maximum rotation varies from gear to gear. It
is not uncommon for two trolling valves on the same vessel to have different settings for Troll
Minimum and Maximum.
If J1 is not defined (value is 00), L1 and L2 are percentages of the full range of the open loop troll
current.
7.5.3 Adjust Minimum AutoTroll Pressure
Measure and adjust the current at the minimum troll pressure. Use the Service Field Test Unit and a
Multimeter:
A Disconnect the Clutch Wire Harness from the SmartCommand Processor.
B Connect the twelve pin connectors from the Service Field Test Unit to the Processor Clutch
connector and to the Clutch Wire Harness. Refer to Figure 6-3: L1, L2, d1, and d2 Processor,
Test Unit, and Multimeter Connections.
C Set Multimeter to read Current (mA).
D Attach the black lead to COM and the red lead to mA on the Multimeter.
E Attach the black lead to the COM connector and the red lead to the mA connector on the
breakout box as shown in Figure 7-1: Multimeter and Test Unit Connections. Move the Troll
Command toggle switch towards TROLL COMMAND to read the current signal (Reference A).
WARNING: If either meter lead is disconnected while testing AutoTroll current, the transmission locks up (fully
engages). Personal Injury may result if this message is disregarded.
I Press UP ARROW or DOWN ARROW on the processor to activate the function menu.
J Press UP or DOWN ARROW to scroll to the L1 AutoTroll Minimum Pressure Function Code.
K Activate Set Up mode: press LEFT ARROW and RIGHT ARROW and hold for two seconds, until the
Function Code blinks or the PIn? prompt appears if PIN not entered yet.
L Change the value of the function, or enter the PIN and change the value of the function using
UP ARROW or DOWN ARROW.
M When the value you want displays, store it: press RIGHT ARROW and LEFT ARROW
simultaneously and hold for one second.
N If you are using closed-loop troll, measure propeller shaft RPM using the Tachometer Sensor
Input 2 value in the H0 diagnostics menu (the third H0 value) and record Propeller Shaft RPM
in Table 7-2: Troll Minimum and Maximum Values
Table 7-2: Troll Minimum and Maximum Values
Lock-Up (100%)
L1-Minimum
L2-Maximum
NOTE: It is difficult to use a slipping clutch to control shaft RPM between 70 percent and 100 percent of
normal shaft RPM. Adjusting Troll Maximum above 75% typically results in full lock-up.
B Use the UP ARROW or DOWN ARROW to scroll to the L2 Troll Maximum Pressure Function Code.
C The Multimeter reads the output signal for Troll Maximum when the Troll Command toggle
switch on the test unit is flipped towards TROLL COMMAND. See Figure 7-1: Multimeter and
Test Unit Connections for details on connections and switch.
D Activate Set Up mode: press LEFT ARROW and RIGHT ARROW and hold for two seconds, until the
Function Code blinks or the PIn? prompt appears if PIN not entered yet.
E Change the value of the function, or enter the PIN and change the value of the function using
UP ARROW or DOWN ARROW.
F When the value you want displays, store it: press RIGHT ARROW and LEFT ARROW
simultaneously and hold for one second.
G If you are using closed-loop troll, measure propeller shaft RPM using the Tachometer Sensor
Input 2 value in the H0 diagnostics menu and record Propeller Shaft RPM in Table 7-2: Troll
Minimum and Maximum Values.
H Position the control head lever into the Neutral/Idle position.
I Shut down power to the engine and the processor.
J Remove the Service Field Test Unit and reconnect the Clutch Wire Harness to the processor.
The values of this Function are 00% to 20% of Throttle Maximum. The default value is 00.
CAUTION: The maximum throttle percentage in AutoTroll mode should not cause the engines to exceed the
maximum RPM for Troll. The throttle in troll is limited to prevent overheating damage to the clutch packs, and
the maximum value RPM allowed can be found in the transmission manufacturer’s literature. Carefully read
section 7.6.1: Calculating the highest throttle percentage allowed carefully before setting the L3 Function
Code.
The upper limit for the troll throttle percentage is 20% of full throttle. The default value for the L3 and d3
Function Codes is 0%. The engine always remains at idle.
7.6.1 Calculating the highest throttle percentage allowed
The maximum RPM allowed in docking and troll is limited by the gear and engine type. Check the
transmission’s accompanying literature before setting any throttle above idle. Typically, the limit is
1000 RPM for engines, but can be lower in many circumstances.
After finding the Maximum Throttle RPM at Troll, calculate the highest troll throttle percentage
allowed. Verify the L3 Function Code is set below that value. Two examples are shown below:
Example 1: if Maximum Rated RPM are 2300 and Idle RPM are 600, and ZF Type 0 gears are installed
(J0 is set to 0):
Get two values from the engine manufacturer’s specifications: Idle RPM and Maximum Rated Engine
RPM, and read the Maximum Troll RPM from the transmission manufacturer’s literature.
Maximum Throttle Percentage = 100 x MaximumTrollRPM - Idle RPM
MaximumRatedRPM - Idle RPM
In this example,
Maximum Throttle Percentage = 100 x 1000-60
2300-60
or 23.5%. Set L3 to any value less than or equal to 20, the maximum value allowed for L3.
Example 2: Maximum Rated RPM are 2300, Idle RPM are 600, and the maximum engine rotation in
troll is 700 RPM:
Get two values from the engine manufacturer’s specifications: Idle RPM and Maximum Rated Engine
RPM.
Maximum Throttle Percentage = 100 x MaximumTrollRPM - Idle RPM
MaximumRatedRPM - Idle RPM
For example, if Maximum Rated RPM are 2300 and Idle RPM are 600, and the Maximum Troll RPM is
700 RPM.
Maximum Throttle Percentage = 100 x 700-600
2300-600
or 5.88%. Set L3 to less than or equal to 5 to avoid damaging the clutch packs.
7.6.2 Set the Troll Throttle Limit, and Throttle in Docking Range
A Disconnect the throttle wire harness from the SmartCommand processor.
B Connect both 8-Pin connectors from the Service Field Test Unit to the processor throttle
connector and to the Throttle Wire Harness. See Figure 31: E1, E2, E3, E4, E6, L3 and D3
Processor, Test Unit, and Multimeter Connections for details.
C Power on the Engine’s ECM.
D Verify processor power is ON.
E Use the UP ARROW or DOWN ARROW to scroll to the L3 Troll Throttle Limit Function Code.
F The Multimeter reads the output signal for the Troll Throttle Limit output signal.
G Activate Set Up mode: press LEFT ARROW and RIGHT ARROW and hold for two seconds, until the
Function Code blinks or the PIn? prompt appears if PIN not entered yet.
H Change the value of the function, or enter the PIN and change the value of the function using
UP ARROW or DOWN ARROW.
I When the value you want displays, store it: press RIGHT ARROW and LEFT ARROW
simultaneously and hold for one second.
J Exit Set Up mode.
K Shut down power to the engine and the processor.
L Remove the Service Field Test Unit and reconnect the Throttle Wire Harness to the processor.
NOTE: Do not change this function unless directed to do so by ZF Marine Propulsion Systems Miramar, LLC.
The values of this function are 0.0 to 9.9 Seconds. The default value is 0.6 seconds.
To change the value:
A Press UP ARROW or DOWN ARROW on the processor to activate the Function Menu.
B Press UP ARROW or DOWN ARROW to scroll to the L4 Troll Pulse Duration Function Code.
C Activate Set Up mode: press LEFT ARROW and RIGHT ARROW and hold for two seconds, until the
Function Code blinks or the PIn? prompt appears if PIN not entered yet.
D Change the value of the function, or enter the PIN and change the value of the function using UP
ARROW or DOWN ARROW.
E When the value you want displays, store it: press RIGHT ARROW and LEFT ARROW simultaneously and
hold for one to two seconds.
NOTE: Do not change this function unless directed to do so by ZF Marine Propulsion Systems Miramar, LLC.
IMPORTANT: The adjustments described below for minimum and maximum docking pressure functions must
be made with the engines running and the transmission(s) at normal operating temperature.
When adjusting the Docking Minimum Pressure function, consider the following:
• The value selected for the d1 function determines the RPM of the propeller, and the thrust that
will result, when EASIDOCK mode is commanded and the control head lever is in the ahead
detent. Adjust the Function Code according to the amount of thrust that will be needed in
docking situations.
• When d1 is set to the default value of 50%, the propeller rotates at 50% of the normal idle
speed. If this setting causes too much thrust to be produced, decrease the value. Conversely,
if not enough thrust is produced, increase the value.
When adjusting the Docking Maximum Pressure function (if the d0 Function Code is not set to the
value of 05 Detent Only), the value can be increased or decreased depending on the amount of thrust
desired when the control head lever is at the limit of the docking range. Make Maximum Docking
Pressure adjustments as follows:
1. At the station in command, select EASIDOCK mode.
2. Move the control head lever to the ahead detent.
3. On the processor, scroll to Function Code d2.
4. Enter setup mode by holding the right and left arrow buttons down simultaneously until “d2” begins to
blink on the left.
CAUTION: Be aware that an increase in vessel thrust will occur immediately when d2 is reached in setup
mode, typically causing a noticeable lurch.
5. To increase the amount of thrust, set the d2 value higher; to decrease the thrust, set the value lower.
6. Store the new value in the processor memory by depressing the right and left arrow buttons
simultaneously until the value stops blinking.
NOTE: Adjust the d3 Function Code after the d1 and d2 Function Codes have been set. When the d0 (Docking
Lever Range) Function Code is set to a value of 05, it is not necessary to set the d3 Function Code.
CAUTION: During clutch slippage, the maximum throttle percentage in EASIDOCK mode should not cause the
engines to exceed the maximum engine RPM allowed by the transmission manufacturer. When EASIDOCK is
commanded, the throttle is limited to prevent overheating damage to the clutch pack. Therefore, pay
particularly close attention to information in the following, section 7.11.1: Calculating the Highest Throttle
Percentage Allowed before setting the D3 Function Code.
The upper limit for the troll throttle percentage is 20% of full throttle. The default value for the d3 Function
Code is 0%; the engine always remains at idle.
The available values are from 0.0 to 9.9 seconds in 0.1 (one tenth) of a second increments. The
default value is 3.0 seconds.
NOTE: Do not change this function unless directed to do so by ZF Marine Propulsion Systems Miramar.
NOTE: Do not change this function unless directed to do so by ZF Marine Propulsion Systems Miramar.
Date: __________________
Transmission _______________________________________________________________________________________
Mfg:
Model: __________________________________ Ratio: ___________________________________
#. of Stations
(max 6) _______________________________________________________________________________________
Are the electrical cable connections tight at the Processors and Control Heads? Yes No
Is the Processor’s Start Interlock Circuit being used? If not, what type of start interlock is
Yes No
being used?
What is the length of the Control Head Harness? Sta. 3_______ Sta. 4_______
What is the source of Processor power and how is it charged? ___________ ___________
What is the Battery Voltage when not being charged? ___________ ___________
What is the Processor Voltage when not being charged? ___________ ___________
What is the Battery Voltage when connected to Shore Power? ___________ ___________
What is the Processor Voltage when connected to Shore Power? ___________ ___________
What is the Battery Voltage when the engines are running? ___________ ___________
What is the Processor Voltage when the engines are running? ___________ ___________
Does the engine start remotely when the Control System is turned OFF? Yes No
Does the Engine Stop Switch function at all Stations, regardless of RPM? Yes No
While in Warm-up, does Engine RPM increase when in the ahead direction? Yes No
Does the vessel surge forward with Control Head lever in the Ahead Detent? Yes No
Throttle in Neutral (Cummins Quantum only) VDC, mA., Hz. or % ___________ ___________
Do the Dual Control Head levers match position and RPM throughout the speed range? Yes No
Shaft Idle RPM (Calculate the Shaft Idle RPM as follows: Engine Idle RPM/Gear Ratio) ___________ ___________
Any Irregularities:
Is a copy of this completed Report faxed to ZF Marine Propulsion Systems Miramar? Yes No
8 Control Options
8.1 Alarm Capability
SmartCommand’s alarm is a single, normally closed alarm connection that opens when there is a system
power failure or circuit malfunction.
The alarm circuit in the processor operates an alarm system supplied by others. You can order the
SmartCommand Power Wire Harness with a cable for the alarm connection.
The shipyard is responsible for using the alarm connection in an appropriate alarm circuit. The alarm circuit
must have the same common mode voltage (common ground) as the power supply for the SmartCommand
processor.
NOTE: The Clutch Oil Pressure Interlock must be set to INSTALLED to be used. See Section 5.9: Clutch Function
Codes for the process to set Clutch Oil Pressure Interlock to INSTALLED or NOT INSTALLED.
The Clutch Oil Pressure Interlock prevents high engine RPM when the clutch is not fully engaged and is
typically used when the clutch takes longer than five seconds to engage. The interlock blocks a speed signal
to the engine until the hydraulic clutch pressure has reached a value recommended by the transmission
manufacturer that ensures clutch engagement.
The power harness 13552-XX has a cable to be used for the clutch oil pressure switch connection.
NOTE:
• The installer must supply the pressure switch.
• The switch must be a Normally Open (N.O.) pressure switch with a trip point that will adjust to match the
transmission manufacturer’s recommended setting.
• The closing of contacts indicates to the processor that the clutch is sufficiently engaged to allow a speed
command above idle speed. This is a safety feature for protection of the clutch.
If the clutch pressure falls below the pressure switch setting, the engine speed drops to Idle RPM. A shuttle
valve is required.
Figure 8-3: Clutch Pressure Switch Showing Processor Wire Harness and Shuttle Valve
If an external alarm circuit is being used in addition to the clutch pressure switch, substitute the
13631-XX power wire harness for the 13552-XX harness, because the 13631-XX harness has the extra
connection necessary for the alarm.
9.3 Battery
Specific instruction about battery maintenance is beyond the scope of this manual. However, it is important
to remember that batteries must be maintained in good working condition. Be sure to operate and service
batteries according to the manufacturers’ specifications and guidelines.
WARNING: Batteries contain sulfuric acid and emit hydrogen gas while charging. Therefore, specific safety
precautions must be adhered to while handling and servicing. Specific information on handling and servicing
batteries can be obtained from the Battery Council International, Battery Service Manual. Personal Injury may
result if this message is disregarded.
CAUTION: In many newer batteries, the vent cap is permanently attached, preventing access to the electrolyte
for water level and specific gravity tests. Attempting to pry off these caps could result in premature battery
failure. Damage to equipment may occur if this message is disregarded.
10 Troubleshooting
10.1 General
The SmartCommand control system consists of one processor per engine, typically mounted in the engine
room, and one to six control heads located at remote vessel stations. The processors are designed to
precisely control electronic throttles and transmissions equipped with solenoid-activated clutches.
If there is a system malfunction, first determine whether other vessels are around, check whether the vessel is
pulling to port or to starboard, and figure out how to get the vessel out of harm’s way. After handling the
immediate situation, the operator usually turns to the control head, which has six red/green light-emitting
diodes (LED) and two sound transducers (one port and one starboard). These features provide for the
emission of visual and audible cues to problems with the control system.
This section contains guidelines for dealing with problems that occur, beginning with general questions and
issues and progressing to detailed information.
1 Processor SC5000 1 or 2
7C Wire Harness, Power, Start Interlock, Clutch Pressure, Alarm Circuit 13631-XX 2
10.1.2 Processor
The processor receives CAN messages from other processors, from control heads, and from other
devices. The processor also receives input and output shaft RPM information. Using the information
received, the processor supplies appropriate electronic or electric outputs to the engine governor and
to the gear box at the correct time and in the correct sequence. Information about throttle and gear
type, throttle/gear sequencing, and performance characteristics is stored in the memory of the
processor.
NOTE: Brief information about tones is provided here to aid in initial troubleshooting of problems. In-depth
details about the tones can be found later in this section, in section 10.6: Audible Tones Detailed Information
• Slow, repetitious tone -- also referred to as the “initialization tone” because this is the tone
you hear when the SmartCommand system is first powered up. This tone means:
• Power has just been applied to the control system.
• The software is operating normally.
• The processor is commanding the throttle to idle and the clutch to neutral.
• The start interlock relay is open.
• If this tone sounds when a remote station is already in control, it means that power has been
lost to the system (perhaps only momentarily) and there is a possible problem.
• One long note, three short notes
Indicates that an invalid command signal has been given at the control head in command. When this
tone sounds, an error code (or codes) will be displayed on the processor to aid in the diagnostic
process.
• Steady tone
Indicates that a significant processor failure has occurred. This tone also will be accompanied by error
codes to help with diagnosis of the problem. If the processor LED display is not functioning, measure
the DC battery voltage at the processor. If the VDC is less than 8.0, correct the power supply issue. If
the VDC is 8.0 or greater, replace the processor.
• Five second steady tone (one time)
Indicates that processor to processor serial communication has been lost. When this tone sounds, an
error code (or codes) will be displayed on the processor to aid in the diagnostic process. (See section
10.9: Problem Scenarios for a list of error codes and their meanings.) As long as the processors have
power, the tone occurs just one time. When serial communication is lost, modes which require serial
communication, such as EASIDOCK, AUTOTROLL, ONE LEVER, WARM UP, and Synchronization, will not
function.
NOTE: This error message will be displayed when engines are not powered up at the same time. Once both
engines have been powered up, the error message can be cleared from the display.
NOTE: Brief information about LED illumination is provided here to aid in initial troubleshooting of problems.
In-depth details about the LED status can be found later in this section in section 10.4: LED Detailed
Information
NOTE: Do not attempt to troubleshoot the system any further than one of the main components listed here. If
a control system component is faulty, replace that component. If an engine appears to be causing the
problem, contact the service representative for that engine.
A DC Power Source
1. Verify that the processor power is connected to a properly charged 12 VDC or 24 VDC battery through a
10 ampere circuit breaker. An adequate battery charging system should maintain the battery charge
when the vessel is both docked and underway, regardless of engine RPM.
2. The use of an APS (automatic power selector) with each processor is highly recommended, because it
provides that processor with at least two alternative power sources. Then, when power is needed in
one place (for example, to start the engine) and there is a big power draw from somewhere else, the
APS will select power from the battery with the most voltage available.
NOTE: When you are testing the DC distribution system, keep in mind that a 0.7 volt drop across the diodes of
the APS is normal.
B Component Locations
• Control Heads
1. May be situated almost anywhere on the vessel where they are useful, taking the following
conditions into consideration:
• A minimum distance of 9.8 inches (249 mm) from a compass must always be
maintained.
• The ambient temperature must be at least -13 degrees Fahrenheit (-25
degrees centigrade).
• The ambient temperature must never be higher than 158 degrees Fahrenheit
(70 degrees centigrade).
2. The control head design meets the IP56 rating. This rating ensures that the control head is
protected against:
• Damage caused by a one mm or greater item (such as a wire)
• Dust damage
• Damage from powerful jets of water coming from any direction
WARNING: Do not attempt to open a control head or a processor. If you do, the warranty is voided. These
components contain no serviceable parts, and ZF Marine Propulsion Systems Miramar cannot guarantee the
operation of a unit once it has been opened. Damage to the equipment may occur if this message is
disregarded.
• Processors
1. Usually located in the engine room, although this is not a requirement. Be sure to take the
following conditions into consideration, wherever the processors are situated:
MMSC5000 Rev B 01/13 Page 132
• A minimum distance of 7.9 inches (200.66 mm) from a compass must always
be maintained.
• A minimum distance of four feet (1.22 m) from sources of high heat, electro-
magnetic interference (EMI) and radio frequency interference (RFI) must
always be maintained.
• The ambient temperature must be at least -13 degrees Fahrenheit (-25
degrees centigrade).
• The ambient temperature must never be higher than 158 degrees Fahrenheit
(70 degrees centigrade).
2. The processor design meets the IP56 rating, which specifies protection against:
• A one mm or greater wire
• Dust
• Powerful jets of water coming from any direction
C Component Condition
• Control heads
1. Inspect for any signs of physical damage.
2. Check for loose connectors or termination resistors.
• Processors
1. Inspect for any signs of physical damage.
2. Make certain that all harness plugs are fully seated in the processor sockets.
D Interconnecting Wire Harnesses
• Check all the interconnecting system harnesses for bent pins or signs of corrosion.
WARNING: Do not open a control head. If you do, the warranty is voided. Control heads contain no
serviceable parts, and ZF Marine Propulsion Systems Miramar cannot guarantee the operation of a unit once
it has been opened. Damage to the equipment may occur if this message is disregarded.
Port and/or
In Control- Commanding Neutral
Stbd. Steady Not Lit Not Lit Not Lit Not Lit
Green (Cruise Mode)
Port and/or
In Command- Clutch Engaged-
Stbd. Rapidly Not Lit Steady Red Not Lit Not Lit AutoTroll Mode Selected
Blinking Red
Port and/or
Stbd. Slowly Not Lit Not Lit Steady Red Not Lit In Control- Warm-Up Mode Selected
Blinking Green
Port Side Slowly Slowly Slowly Port side of Control Head not
Blinking Red Blinking Red Blinking Red Not Lit Not Lit communicating with CAN Bus or not
assigned.
• If none of the control heads has had an ID assigned (mapped), the display shows four dashes
blinking simultaneously.
NOTE: If the control head IDs have not been set, follow the instructions in section 5.5: Assigning Station IDs to
gain access to the function menu.
B Press the UP arrow or the DOWN arrow. The characters A0, then 00, 01, or 02 will be displayed.
E Press the DOWN arrow to scroll through the diagnostic values, which are displayed (beginning with
battery voltage) in the order shown in Table 10-3: Diagnostic Values.
To obtain the value necessary to program Function Code J1 (IDLE LOCKUP HZ), command ahead/idle
from a control station and note the displayed value. If this signal is lost, a one-time three second
steady tone will sound from all control stations and error code Er93 will be displayed at the associated
processor. EASIDOCK mode will also be disabled and AUTOTROLL will no longer be automatic, but will
perform in open-loop fashion only.
G Input Shaft (Engine) Frequency
Press the DOWN arrow to display the input shaft frequency. This signal is used for engine
synchronization and, where applicable, two-speed operation. The value shown on the display is a
product of the engine RPM times the number of pulses per revolution (PPR), divided by 60.
For example:
Engine RPM = 600
Sensor PPR = 25
600 * 25 = 1500/60 = 250 Hz
NOTE: Generally speaking, on vessels with multiple engines, the RPM is identical among them. However,
there may be certain cases where there are slight differences in RPM from one engine to the next.
• If the second from the right and the left most decimal points are absent, station No. 6 is
displayed.
Station No. 1 CONTROL / SET Button (Closed) Station No. 4 CONTROL / SET Button (Closed)
Station No. 2 CONTROL / SET Button (Closed) Station No. 5 CONTROL / SET Button (Closed)
Station No. 3 CONTROL / SET Button (Closed) Station No. 6 CONTROL / SET Button (Closed)
NOTE: If the processor power supply has an automatic power selector (APS), take into account the 0.7 VDC
forward voltage drop of the diodes. This increases the permissible voltage drop from the power source to the
processor to 1.1 VDC in 12 VDC systems and 1.5 VDC in 24 VDC systems.
E If the source voltage measured in step C above is within specifications, and you have ruled
out a voltage drop between the source and the processor, check to make certain that the
power source is not loaded down by another piece of equipment. When you monitor the
power source in the investigation of a problem, turn on all other equipment which requires
substantial amounts of current, such as heaters, starters, thrusters, large DC motors, etc.
F If you find that the voltage drops significantly at the power source, the processor needs to be
provided with an alternate source of power, either through an APS or some other way.
NOTE: This fault will only occur in applications where Function Code J0 is set to 08.
• EASIDOCK and AUTOTROLL modes become inoperative, but associated control head LEDs would
incorrectly indicate that these modes are operational.
• Clutch and throttle functions operate normally.
• Error code 88 or 89 displays at the appropriate processor.
• The CONTROL, ONE LEVER and WARM UP LEDS blink red if the fault is on the starboard side.
• An error code from the range 68 through 73 will be displayed on the associated processor.
• Control cannot be transferred to this station.
• Fault at station in command
• In addition to the five-second tone sounded at the faulty station, a tone of one long and
three short notes will sound at other control stations.
• The CONTROL, EASIDOCK and AUTOTROLL LEDS blink red if the fault is on the port side.
• The CONTROL, ONE LEVER and WARM UP LEDS blink red if the fault is on the starboard side.
• The processor on the side without the fault will remain in command.
• If EASIDOCK, AUTOTROLL, ONE LEVER and/or synchronization are selected, they will be
disabled.
• An error code from the range 68 through 73 will be displayed on the associated processor.
• An error code from the range 23 through 28 will be displayed on the associated processor.
• Control can be transferred to another station, which will silence the one long-three short
audible indication tone
• The five seconds per minute tone continues until the problem is corrected.
13 Station #1 control head is defective (A to D too low). Replace station #1 control head. Reassign station ID
(A3).
Replace station #2 control head. Reassign station ID
14 Station #2 control head is defective (A to D too low).
(A3).
Replace station #3 control head. Reassign station ID
15 Station #3 control head is defective (A to D too low).
(A3).
Replace station #4 control head. Reassign station ID
16 Station #4 control head is defective (A to D too low).
(A3).
Replace station #5 control head. Reassign station ID
17 Station #5 control head is defective (A to D too low).
(A3).
Replace station #6 control head. Reassign station ID
18 Station #6 control head is defective (A to D too low).
(A3).
Replace station #1 control head. Reassign station ID
23 Station #1 control head is defective (A to D too high).
(A3).
Replace station #2 control head. Reassign station ID
24 Station #2 control head is defective (A to D too high). (A3).
Replace station #3 control head. Reassign station ID
25 Station #3 control head is defective (A to D too high).
(A3).
Replace station #4 control head. Reassign station ID
26 Station #4 control head is defective (A to D too high).
(A3).
Replace station #5 control head. Reassign station ID
27 Station #5 control head is defective (A to D too high).
(A3).
Replace station #6 control head. Reassign station ID
28 Station #6 control head is defective (A to D too high).
(A3).
a) The CONTROL/SET button on the station No. 1 control
a) Clear the error code from the processor memory.
head was held down for 12 seconds or longer.
33
b) Station No. 1 control head CONTROL/SET button is
defective. b) Replace the station No. 1 control head.
Table 10-5: Problem Scenarios with Error Codes and Possible Solutions
Error # Cause Solution
a) The CONTROL/SET button on the station No. 4 control
a) Clear the error code from the processor memory.
head was held down for 12 seconds or longer.
36
b) Station No. 4 control head CONTROL/SET button is
b) Replace the station No. 4 control head.
defective.
a) The CONTROL/SET button on the station No. 5 control
a) Clear the error code from the processor memory.
head was held down for 12 seconds or longer.
37
b) Station No. 5 control head CONTROL/SET button is
b) Replace the station No. 5 control head.
defective.
a) The CONTROL/SET button on the station No. 6 control
a) Clear the error code from the processor memory.
head was held down for 12 seconds or longer.
38
b) Station No. 6 control head CONTROL/SET button is
b) Replace the station No. 6 control head.
defective.
43 A termination resistor is missing from a processor. Replace the processor.
44 A termination resistor is missing from a processor. Replace the processor.
45 A processor is faulty. Replace the processor.
a) Relocate the processors so that the length of the
a) The serial harness is longer than 120 ft. (37m). serial harness is less than 120 ft. (37m). Install the
46 shorter serial harness.
b) Install a serial harness with the shields terminated at
b) The serial harness is not properly shielded.
pin 8 on both sides.
a) Relocate the processors so that the length of the
a) The serial harness is longer than 120 ft. (37m). serial harness is less than 120 ft. (37m). Install the
47 shorter serial harness.
b) Install a serial harness with the shields terminated at
b) The serial harness is not properly shielded.
pin 8 on both sides.
a) Relocate the processors so that the length of the
a) The serial harness is longer than 120 ft. (37m). serial harness is less than 120 ft. (37m). Install the
48 shorter serial harness.
b) Install a serial harness with the shields terminated at
b) The serial harness is not properly shielded.
pin 8 on both sides.
a) Relocate the processors so that the length of the
a) The serial harness is longer than 120 ft. (37m). serial harness is less than 120 ft. (37m). Install the
49 shorter serial harness.
b) The serial harness is not properly shielded. b) Install a serial harness with the shields terminated at
pin 8 on both sides.
a) Power was applied to the starboard processor a) Turn off power to both processors and reapply
before it was applied to the port processor. Typically,
the port processor is set to ID 1 (A001). power to the processors simultaneously.
b) Power was lost to processor ID 1 (A001). b) Determine and correct the cause of power loss, and
50 repower the processors.
c) The A0 Function Code of both processors is set to c) Set Function Code A0 to 01 on the port processor.
02. Cycle power.
d) The port processor is faulty. d) Replace the port processor.
Table 10-5: Problem Scenarios with Error Codes and Possible Solutions
Error # Cause Solution
a) Power was applied to the port processor before it
a) Turn off power to both processors and reapply
was applied to the starboard processor. Typically, the
power to the processors simultaneously.
starboard processor is set to ID 2 (A0-02).
b) Determine and correct the cause of power loss, and
51 b) Power was lost to processor ID 2 (A0-02)
repower the processors.
c) The A0 Function Code of both processors is set to c) Set Function Code A0 to 02 on the starboard
01. processor. Cycle power.
d) The starboard processor is faulty. d) Replace the starboard processor.
a) The battery is being over-charged. a) Correct the charging system as necessary.
56 b) Loose battery connections while the engine/ b) Making certain that the battery switches are turned
alternator is running. off, clean and tighten all battery connections.
a) The battery is not being charged. a) Correct the charging system as necessary.
b) Defective battery. b) Replace the battery.
57 c) Measure the voltage at the battery and at the
processor. The difference should not be greater than
c) Excessive resistance in the power circuit.
3% (taking into consideration the normal 0.7 V drop
across the APS).
a) Station No. 1 control head cable is not connected. a) Connect the harness to station No. 1 control head.
b) Station No. 1 control head harness is defective. b) Replace the station No. 1 control head harness.
68 c) Station No. 1 control head ID does not match the
c) Re-assign station IDs using the A3 Function Code.
programmed processor ID.
d) Defective station No. 1 control head. d) Replace the station No. 1 control head.
a) Station No. 2 control head cable is not connected. a) Connect the harness to station No. 2 control head.
b) Station No. 2 control head harness is defective. b) Replace the station No. 2 control head harness.
69 c) Station No. 2 control head ID does not match the
c) Re-assign station IDs using the A3 Function Code.
programmed processor ID.
d) Defective station No. 2 control head. d) Replace the station No. 2 control head.
a) Station No. 3 control head cable is not connected. a) Connect the harness to station No. 3 control head.
b) Station No. 3 control head harness is defective. b) Replace the station No. 3 control head harness.
70 c) Station No. 3 control head ID does not match the
c) Re-assign station IDs using the A3 Function Code.
programmed processor ID.
d) Defective station No. 3 control head. d) Replace the station No. 3 control head.
a) Station No. 4 control head cable is not connected. a) Connect the harness to station No. 4 control head.
b) Station No. 4 control head harness is defective. b) Replace the station No. 4 control head harness.
71 c) Station No. 4 control head ID does not match the
c) Re-assign station IDs using the A3 Function Code.
programmed processor ID.
d) Defective station No. 4 control head. d) Replace the station No. 4 control head.
Table 10-5: Problem Scenarios with Error Codes and Possible Solutions
Error # Cause Solution
a) Station No. 5 control head cable is not connected. a) Connect the harness to station No. 5 control head.
b) Station No. 5 control head harness is defective. b) Replace the station No. 5 control head harness.
72 c) Station No. 5 control head ID does not match the
c) Re-assign station IDs using the A3 Function Code.
programmed processor ID.
d) Defective station No. 5 control head. d) Replace the station No. 5 control head.
a) Station No. 6 control head cable is not connected. a) Connect the harness to station No. 6 control head.
b) Station No. 6 control head harness is defective. b) Replace the station No. 6 control head harness.
73 c) Station No. 6 control head ID does not match the
c) Re-assign station IDs using the A3 Function Code.
programmed processor ID.
d) Defective station No. 6 control head. d) Replace the station No. 6 control head.
a) The control head is installed backwards (the button
a) Remount the control head so the button labels and
labels and LEDs face away, rather than toward, the
LEDs face toward the operator.
78 operator).
b) Reverse the port and starboard control head
b) Port and starboard control head cables are reversed.
harnesses.
a) The plugs of the clutch harness are not properly a) Reconnect the clutch harness plugs at the processor
seated. and the MTCU.
b) The tachometer wire harness is not properly seated. b) Re-seat the plugs at the processor and the
92 transmission.
c) The tachometer wire harness is defective. c) Replace the tach wire harness.
d) The input shaft sensor is defective. d) Replace the input shaft sensor.
a) The sensor is too far from the rotating surface. a) Readjust the air gap.
b) AUTOTROLL or EASIDOCK modes have been selected b) Before selecting the AUTOTROLL or EASIDOCK modes,
without the engines running. start the engines.
c) Re-seat the plugs at the processor and the
93 c) The tachometer wire harness is not properly seated.
transmission.
d) The 9 VDC power supply is lost. d) Check pin 1 at the processor tach plug for 9 VDC.
e) The tachometer wire harness is defective. e) Replace the tach wire harness.
f) The output shaft sensor is defective. f) Replace the output shaft sensor.
• If additional control heads are connected down the line, there are four (4) harness
connections. Refer to Figure 10-18: Connections between control heads.
5. Insert the Port harness plug into either of the Port sockets and the Starboard harness plug into either
of the Starboard sockets. Make sure to align the plug and socket keys. See Figure 10-20: Socket key.
6. Remove termination resistors from all control heads except the last one in the chain.
IMPORTANT: It is essential that wire harnesses connected to the port side of the processor be connected to
the port side of the control head, and that wire harnesses connected to the starboard side of the processor be
connected to the starboard side of the control head. If any wires are crossed, some or all of the system
components associated with the incorrect control bus will be inoperable.
NOTE: If a station has more than one control head and the control heads are “daisy-chained” together, remove
termination resistors and attach control head to control head wire harnesses in place of the resistors.
NOTE: If an error code appears on the display of either processor, ignore it at this time; press the left arrow to
exit the error menu and enter the function menu.
10. At the port processor, press the “Down” arrow until A3xx is displayed.
11. Press and hold the “Left” and “Right” arrows simultaneously until you are prompted for the pin number
(PIn?), and then release. A second or two later, four dashes will be displayed.
12. Press the “Up” arrow once. The number “1” will appear on the first LED.
13. Press the “Right” arrow once. A dash will appear at the second LED.
14. Press the “Down” arrow once. The number “9” will appear on the second LED
15. Press the “Right” arrow once. A dash will appear on the third LED.
16. Press the “Down” arrow twice. The number “8” will appear on the third LED.
17. Press the “Right” arrow once. A dash will appear on the fourth LED.
18. Press the “Down” arrow three times. The number “7” will appear on the fourth LED.
19. Press the “Right” arrow once. “A301” will appear with the “A3” blinking.
20. Press the “Left” and “Right” arrows simultaneously for approximately two seconds. Release. Repeat this
step until “A300” is displayed.
21. Go to the starboard processor and press the “Down” arrow until “A3xx” is displayed.
22. Repeat steps 10 through 19.
23. At the primary control station (Station No. 1) make sure that the levers are at the neutral/idle detent. All
six LEDs should be blinking red and you should hear a tone.
24. Press the CONTROL/SET button. At this point, the blinking red LEDs should go out, the tone should stop,
and the CONTROL LEDs should light green.
25. Go to the next control station (if installed) and make sure that the levers are at the neutral/idle detent.
Once again, all six LEDs should be blinking red and you should hear a tone.
26. Press the CONTROL/SET button. Again, the blinking red LEDs should go out, the tone should stop, and
the CONTROL LEDs should light green.
27. Repeat steps 24 and 25 at all remaining stations.
28. The new Control Head is ready for operation.
10. Repeat the previous two steps until you have recorded the values for all Function Codes in Table 10-6:
Function Code Values.
Table 10-6: Function Code Values
Function Code Value Function Code Value Function Code Value Function Code Value Function Code Value
A0 E5 C7 d2 J3
A1 E6 C8 d3 J4
A2 E7 L0 d4 J5
A3 C0 L1 d5 J6
A4 C1 L2 d6 J7
E0 C2 L3 d7 U0 *
E1 C3 L4 d8 U1 *
E2 C4 L5 J0 U2 *
E3 C5 d0 J1 U3 *
E4 C6 d1 J2 U4 *
* The U Function Codes are used only with two-speed applications and, therefore, may not be displayed.
11. Turn DC power to the processors off.
12. Unplug the connectors for the clutch, power, throttle, station A, station B, serial, tach, and -- if used --
the ZF CAN 1 and CAN 2 from the defective processor.
13. Disconnect the bonding (grounding) connection from the processor frame.
14. Remove the processor’s mounting hardware and set it aside.
15. Remove the processor.
NOTE: If an error code appears on the display of either processor, ignore it at this time; press the left arrow to
exit the error menu and enter the function menu.
5. Press and hold the “Left” and “Right” arrows simultaneously until you are prompted for the pin number
(PIn?), and then release. A second or two later, four dashes will be displayed.
6. Press the “Up” arrow once. The number “1” will appear on the first LED.
7. Press the “Right” arrow once. A dash will appear at the second LED.
8. Press the “Down” arrow once. The number “9” will appear on the second LED
9. Press the “Right” arrow once. A dash will appear on the third LED.
10. Press the “Down” arrow twice. The number “8” will appear on the third LED.
11. Press the “Right” arrow once. A dash will appear on the fourth LED.
12. Press the “Down” arrow three times. The number “7” will appear on the fourth LED.
13. Press the “Right” arrow once. “A301” will appear with the “A3” blinking.
14. Press the “Left” and “Right” arrows simultaneously for approximately two seconds. Release. Repeat this
step until “A300” is displayed.
15. Go to the new Processor and press the “Down” arrow until “A3xx” is displayed.
16. Repeat steps 5 through 14.
17. At the primary control station (Station No. 1) make sure that the levers are at the neutral/idle detent. All
six LEDs should be blinking red and you should hear a tone.
MMSC5000 Rev B 01/13 Page 157
18. Press the CONTROL/SET button. At this point, the blinking red LEDs should go out, the tone should stop,
and the CONTROL LEDs should light green.
19. Go to the next control station (if installed) and make sure that the levers are at the neutral/idle detent.
Once again, all six LEDs should be blinking red and you should hear a tone.
20. Press the CONTROL/SET button. Again, the blinking red LEDs should go out, the tone should stop, and
the CONTROL LEDs should light green.
21. Repeat steps 19 and 20 at all remaining stations.
22. The control heads are now ready for operation.
23. At the new Processor and press the “Up” arrow until “A3xx” is displayed.
24. Check the value you see against the value noted in Table 10-6: Function Code Values. Remember that
the Port value should be 01 and Starboard should be 02.
25. If the value is incorrect and needs to be changed, enter set-up mode by pressing the “left” and “Right”
arrows until A0 starts to blink and then release.
26. Press the “Up” or “Down” arrow until you see the appropriate value, and then press and hold the “Left”
and “Right” arrows simultaneously to enter the new value into memory.
27. Press the “Down” arrow to display the next Function Code.
28. Press and hold the “Right” arrow down until the full four digit value is displayed (on all four LEDs).
29. If the value is incorrect and needs to be changed, enter set-up mode by pressing the “left” and “Right”
arrows until the Function Code starts to blink and then release.
30. Press the “Up” or “Down” arrow until you see the value you want and then press and hold the “Left” and
“Right” arrows simultaneously to enter the new value into memory. (In some cases, it may be necessary
to press and hold the “Right” arrow while you are pressing the “Up” or “Down” arrow.
31. Repeat steps 26 through 30 to set the values for the remaining Function Codes.
32. Press the “Left” arrow on both processors to display the error menu. At this point, there should be no
blinking error code values (signifying active errors). Clear inactive errors -- i.e., those which appear, but
are not blinking -- by pressing and releasing the “Right” arrow one error code at a time.
NOTE: If there are no errors, either active or inactive, pressing the left arrow (as directed at the beginning of
the last step) will have no effect.
Termination A Termination B
Termination A Termination B
Termination A Termination B
Table 10-10: Wire Harness - Throttle (Pulse Width Modulation [PWM]), (p/n 13533-XX)
Termination A Termination B
Table 10-11: Wire Harness - Cable, Throttle, MAN EDC (p/n 14421-XX)
Termination A Termination B
Table 10-12: Wire Harness- Throttle & Clutch Ahead/Astern w/Neutral Interlock, MAN- Sc (p/n 70588-XX)
Termination A Termination B
Table 10-13: Wire Harness- Throttle, Yanmar CAN Interface, SC (p/n 70766-XX)
Termination A Termination B
Table 10-14: Wire Harness- Throttle, MTU Smartline- SmartCommand (p/n 70747-XX)
Termination A Termination B
Termination A Termination B
Termination A Termination B
Table 10-17: Wire Harness- Throttle, Dual Voltage- SmartCommand And MiniCommand (p/n 71589-XX)
Termination A Termination B
Termination A Termination B
Termination A Termination B
Table 10-20: Subassembly, Wire Harness Clutches with Troll (p/n 15725-XX)
Termination A Termination B
Termination A Termination B
Termination A Termination B
Termination A Termination B
Table 10-24: Wire Harness - Clutch ZF Gear, MTU Smartline- SmartCommand (p/n 70901-XX)
Termination A Termination B
Termination A Termination B
Termination A Termination B
Table 10-27: Wire Harness - Power, SI & Clutch Pressure Switch (p/n 13552-XX)
Termination A Termination B
Table 10-28: Wire Harness - Power, SI, Clutch Pressure Switch & Alarm (p/n 13631-XX)
Termination A Termination B
Table 10-29: Wire Harness- Power Use w/ existing Start Interlock Only (p/n 15023-XX)
Termination A Termination B
Table 10-30: Wire Harness- Power/Backup Input For MTU Start Interlock w/ SC (p/n 71021-XX)
Termination A Termination B
Table 10-31: Wire Harness - Power, Start Interlock, Pressure SW, Alarm & Backup (p/n 71476-XX)
Termination A Termination B
Termination A Termination B
Table 10-33: Wire Harness - Control Head to Control Head (p/n 70268-XX)
Termination A Termination B
Termination A Termination B
Termination A Termination B
Termination A Termination B
IMPORTANT: Every effort has been made to ensure that this drawing is to scale. However, there can be no
absolute guarantee that the drawing size is exact. Therefore, it is important that you verify all
measurements before cutting.
WARNING: Mount SmartCommand control heads at least 250 mm (9.84 in.) from compasses. If a safe
mounting distance is not maintained, electromagnetic fields could influence SmartCommand control head
electronic circuits, cause erratic operation, and possibly impair compass directions. Personal injury could
result if this message is disregarded.
This Service Sheet reflects all current variations of the standard 3-detent (Neutral, Forward, Reverse) ZF
Marine Propulsion Systems Miramar 4000 Series Control Heads.
Requirements:
Control System Wire Harness Description
(1) Control Head wire harness per lever.
MicroCommander/
ClearCommand (non- See Figure MMC-337-2: 9000 Hard Wired Drawing 14119-2, Figure MMC-337-3: Port Processor -
Hard wiring Drawing 13932A - 15B and Figure MMC-337-4: Starboard Processor - Hard wiring
pluggable)
Drawing 13932A - 15A
Pluggable Micro
(1) Control Head wire harness per lever.
Commander/Clear See Figure MMC-337-1: Cable / Harness Connections - Pluggable Drawing 14119-1
Command
(1) Control Head wire harness per lever.
CruiseCommand
See Figure MMC-337-1: Cable / Harness Connections - Pluggable Drawing 14119-1
(1) Control Head wire harness per Control Head.
MiniCommand
See Figure MMC-337-1: Cable / Harness Connections - Pluggable Drawing 14119-1
CONNECTIONS
The 4000 series Control Heads are only available with pluggable connections and must not be modified in
any way. However, there are two types of Wire Harnesses available for connecting the Control Head to the
Processor (CruiseCommand, ClearCommand, etc.):
• Pluggable on both ends.
• Pluggable on one end and hard wired on the other.
The Wire Harnesses for CruiseCommand and the MiniCommand Processors are always pluggable at both
ends. The Wire Harnesses for the 9000 Processors (MicroCommander and ClearCommand) can be pluggable
at both ends or pluggable at the Control Head end and hard wired at the Processor end.
PLUGGABLE
1. Plug Control Head wire harness into the corresponding connector/pigtail coming from the Processor. Ensure the
correct Processor Cable is being plugged into the correct Control Head pigtail. (Example: Port to Port, Starboard
to Starboard.)
When making the connection, ensure that the mating connectors (plug and receptacle) are fully inserted
such that the connector latches are locked in place. (Note: To disconnect the connectors, the release
button or buttons must be depressed and held until the plug and receptacle are fully disconnected.)
CAUTION: Disconnecting plugs without depressing and holding the release button or buttons will damage the
plug.
PLUGGABLE CONNECTIONS
WARNING: Pluggable Control Heads are supplied with a harness pigtail for each lever. When disconnecting
the plugs, ensure that the release button or buttons are depressed and held until the plug is fully
disconnected.
Disconnecting the plugs without depressing and holding the release button or buttons WILL damage the plug.
Figure MMC-337-9: Control Head Mounting Holes and Cutout – Dwg #13293
SEE FOLLOWING PAGE FOR TEMPLATE
Figure MMC-337-10: Control Head Mounting Holes and Cutout – Dwg #14649
WARNING: Note that the dimensions are out of scale, pay attention to properly size the cut out before use !
This Service Sheet reflects all current variations of the standard 3-detent ZF MC2000 Series Control Heads.
REQUIREMENTS:
MicroCommander/ClearCommand: one (1) 8-Conductor Cable per Control Head lever.
Pluggable MicroCommander/ClearCommand: one (1) Control Head Harness per Control Head lever.
CruiseCommand: one (1) Control Head Harness per Control Head lever.
Included with the Control Head:
• Mounting screws
• Terminals (For 8-Conductor or 1-Connector Harnesses)
• Watertight cable grip for the cable entrance on the Processor (For 8-Conductor)
When the Control Head is properly mounted on a console, it is spray proof from the top only. An adhesive
gasket is mounted on the bottom of the Control Head to seal it to the mounting surface. However, below the
mounting surface it needs protection from water or spray. Consider using a Weather Mount Enclosure, which
is available from ZF.
WARNING: Do not mount control head less than 250mm from Compass.
Mounting a control head too close to compass can cause the compass to malfunction.
Dimensions
Standard Cable
A Strip back the PVC cover on the shielded cable approximately 2-1/2” (63,5mm) at the Control Head.
B At the Control Head end of the cable strip and cut off the shielding and drain wire flush with the end
of the PVC cover (the drain wire at the Control Head is not connected to ground).
C Strip 3/8” (9,5mm) insulation off each wire.
D Twist the individual strands of the wires to minimize fraying.
E Crimp a locking fork terminal (included with each Control Head) to each of the conductors.
F Make connections to the Control Head as indicated in the following TERMINAL CONNECTIONS
diagrams.
ALWAYS REFER TO THE MANUAL THAT IS SUPPLIED WITH THE CONTROL SYSTEM FOR ANY UNIQUE
CONTROL HEAD CONNECTIONS FOR YOUR SYSTEM.
When cable connections are complete, MOUNT Control Head to the console using the two (2) mounting
screws and washers supplied with the Control Head.
CABLE/HARNESS CONNECTIONS:
Dual Control Head Connections
WARNING: Do not mount control head less than 250mm from Compass.
Mounting a control head too close to compass can cause the compass to malfunction.
This Service Sheet reflects all current variations of the standard 3-detent ZF 400 Series Control Heads.
WARNING: Do not mount control head less than 100mm from Compass.
Mounting control head too close to compass can cause the compass to malfunction.
3. Type 1 - Pluggable
Plug Control Head cable into the pigtail at the Control Head. (Ensure the correct Processor Cable is being
plugged into the corresponding Control Head lever pigtail).
When connecting the plugs, ensure that the release button or buttons are depressed and held until plug is
fully connected or disconnected. Connecting or disconnecting plugs without depressing and holding the
release button or buttons will damage the plug.
4. Type 2 - Hard-wired
A Strip back the PVC cover on the shielded cable approximately 2-1/2” (63,5mm) at the Control Head.
B At the Control Head end of the cable strip and cut off the shielding and drain wire flush with the end
of the PVC cover (the drain wire at the Control Head is not connected to ground).
C Strip 3/8” (9,5mm) insulation off each wire.
D Twist the individual strands of the wires to minimize fraying.
E Crimp a locking fork terminal (included with each Control Head) to each of the conductors.
F Make connections to the Control Head as indicated in the following TERMINAL CONNECTIONS
diagrams.
5. CABLE/HARNESS CONNECTIONS:
Terminal 3 Red Terminal 3 Red Terminal 3 Red & JUMPER Terminal 3 Red & JUMPER
6. Pluggable Connections
Pluggable Control Heads are supplied with a harness pigtail for each lever. When disconnecting/
connecting the plugs, ensure that the release button or buttons are depressed and held until plug is
fully disconnected or connected. Disconnecting/connecting plugs without depressing and holding
the release button or buttons WILL damage the plug.
7. AFT FACING CONTROL HEADS
WARNING: Do not mount control head less than 100mm from Compass.
Mounting control head too close to compass can cause the compass to malfunction.
WARNING:
MMC-280 Rev N.2 02/12 Note that the dimensions are out ofPage
scale,
205 pay attention to properly size the cut out before use !
A GENERAL INFORMATION
The APS, Model 13505, provides a simple, solid state solution to the need for routing redundant DC power
sources for vital electronic equipment while maintaining isolation of the DC power sources.
Two independent batteries rated at the same nominal voltage are wired to separate terminals on the APS and
internal diodes maintain total isolation between them. A single output terminal is wired to the ZF Marine
Propulsion Control System.
The APS is rated for loads of up to 70 Amps on 12-24VDC systems. The unit is ruggedly constructed with
heavy-duty wiring studs and epoxy-potted components in an anodized aluminum case.
B APS SPECIFICATIONS
Model: 13505
Maximum Load Current: 70 amps
Operating Temperature: - 40 degrees C to +80 degrees C; derate linearly from 100% @ 50 degrees C to 70%
@ 80 degrees C
Voltage Drop: 0.7 VDC @ 50% load; 0.9 VDC @ full load
Dimensions: 3.25" x 4.5" x 3.1" (8,3 x 11,4 x 7,9 cm)
C MATERIALS PROVIDED
The single APS is supplied with a hardware packet containing (6) hex nuts, (3) lock washers, (4) self-tapping
mounting screws, (1) instructions diagram.
NOTE: Not all of the hardware will be used in the installation; some spares are provided. Nut size is M-6.
The twin APS is supplied with (2) single APS hardware packets.
D INSTALLATION
Refer to Drawing 11488 DC Power Source Kit.
1. Shut off all charging sources and disconnect the negative (ground) side of each battery which will be wired to
the APS.
2. Mount the APS(s) in a suitable location which will keep wire runs to a minimum length, and is preferably
ventilated, for cooler operation. The case of the APS is electrically isolated from the internal diodes, so
mounting on either a metal or non-metal surface is acceptable.
3. Complete the wiring as indicated.
4. Reconnect the negative battery posts.
E IMPORTANT NOTE ABOUT BATTERY SOURCES
Whenever the load is turned on, it can be drawing power from the batteries. Therefore, if the batteries are
not simultaneously being recharged, or if charging will not be available for an extended period, it is
recommended that the load be shut off to prevent complete discharge of batteries.
Page 209
Page 211
Page 213
Page 215
Page 217
Grounding (Bonding)
Grounding (Bonding) - 46 CFR 111.05 and ABYC Section E-11: July 2012
Grounding (Bonding) should be done according to ABYC Section E-11 and Code of Federal Regulations 46
CFR 111.05.
Each grounded system must have only one point of connection to ground regardless of the number of
power sources operating in parallel in the system.
A vessel's hull must not carry current as a conductor. A metallic hull, or the bonding and DC
grounding systems, shall not be used as a return conductor.
There are some limited exceptions: (1) Impressed current cathodic protection systems. (2) Limited
and locally grounded systems, such as a battery system for engine starting that has a one-wire system
and the ground lead connected to the engine. (3) Insulation level monitoring devices if the circulation
current does not exceed 30 milliamperes under the most unfavorable conditions. (4) Welding systems
with hull return except vessels subject to 46 CFR Subchapter D.
Grounding conductors should be identified via a green or green with a yellow stripe jacket, and shall not be
used as a return. Where grounding conductors are attached to Processors or other CE marked devices – a
tinned copper braid is the preferred grounding method - per References: CFR Sec. 111.05-11, Sec. 111.05-13
and ABYC E-11 sect. 11.4.
a
Grounding diagram is used courtesy of American Boat and Yacht Council.
All parts of figure except processors and processor connection ©
2003 American Boat and Yacht Council
Metal - Hull Vessels
The hull of a metal hull vessel may serve as the common grounding conductor. If it is desirable for the item
being installed to be bonded to the vessel grounding system, and the installation or mounting method does
not provide the desired path, a separate grounding conductor may be required.
References
A American Boat & Yacht Council (ABYC)
3069 Solomons Island Road
Edgewater, MD 21037-1416
E-3 Wiring Identification on Boats
E-11 AC and DC Electrical Systems on Boats
H-2.4e or 32.4g Ambient Temp. 50 degrees C
P-24 Electric/Electronic Propulsion Controls
B Code of Federal Regulations
33 CFR 183 Subpart I - Electrical Systems
33 CFR 183.410 Ignition protection
33 CFR 183.415 Grounding
33 CFR 183.425 Conductors: General
33 CFR 183.430 Conductors in circuit of less than 50 Volts
33 CFR 183.445 Conductors: Protection
33 CFR 183.455 Over-current and Protection: General
46 CFR 111.01 - 15(b) Ambient Temp. Machinery Spaces 50 degrees C
46 CFR 111.05- System Grounds
C Society of Automotive Engineers
400 Commonwealth Drive
Warrendale, PA 15096
J1171 External Ignition Protection
J1428 Marine Circuit Breakers
J378 Marine Engine Wiring
D National Marine Manufacturers Association
401 North Michigan Avenue
Chicago, IL 60611
E Underwriters Laboratories
Parts Source
Anti-Static Wrist Strap - - - - - - - - - P/N 517 [Thomas & Betts (P/N AWCC)]
Automatic Power Selector - - - - - - - P/N 13505
Circuit Breaker- UL Approved - - - - - - P/N 810 [E-T-A (P/N 41-2-514-LN2-10)]
Fuse- - - - - - - - - - - - - - - - - - P/N 1030 [Bussman (P/N. GDC-1A)]
Relay 12 VDC - - - - - - - - - - - - - P/N 1114 [Potter-Brumfield (P/N KRPA5D6-12)]
Relay 24 VDC - - - - - - - - - - - - - P/N 1122 [Potter-Brumfield (P/N KRPA5D6-24)]
Service Field Test Unit (Break-out Box) - P/N 13927
WAGO Tool - - - - - - - - - - - - - - P/N 397 [WAGO (P/N 236-332)]
Field Test Control Head - Dual - - - - - P/N 14000
Chili
Company: Equipamiento Marino Ltda
Contact: Christian Rogers Nickelmann
Address: Rafael Correa 1268 Vitacura
Santiago, Chili
Phone: (56-2) 4158737
Fax: (56-2) 9-9975059
Email: info@equipamientomarino.cl
China Denmark
Company: Foilborne Engineering, Ltd. Company: ZF Danmark APS
Contact: Paul Chow Contact: Michael Johansson, Frank Kiessling
Address: Unit A 7-9, 13/F Veristrong Address: Taastrupgaardsvej 8-10
34-36 Au Pui Wan Street / FO-Tan Taastrup, DK-2630, Denmark
Shatin, N.T. Phone: 45-7022-6243
Hong Kong, China Fax: 45-7022-2643
Phone: 852-2687-2988 frank.kiessling@zf.com;
Email: michael.johansson@zf.com
Fax: 852-2687-1996 Website: www.zf-marine.com
Email: paulchow@foilborne.biz.com.hk
Ecuador
Company: Renford Marine Equipment (China) Ltd. Company: ZF Marine’s Consulting
Contact: Anthony Yuen Contact: Pedro Aspiazu
Address: 501 Laws Commercial Plaza Address: Urdesa Central 1A #13184 Costanera
788 Cheung Sha Wan Road Guaaquil – Guayas, Ecuador
Hong Kong, China Phone: (593-4) 238-9306
Phone: 852-27427111 Fax: (593-4) 238-4010
Fax: 852-27427171 Email: zfmarineconsulting@yahoo.com
Email: anthony.yuen@renford.com
Finland
Company: Renford Marine Equipment (Shanghai) Ltd.
Company: Atoy Oy
Contact: Anthony Yuen
Contact: Antti Hiidenheim
Address: 811 Jiaxing Building
Address: PO Box 137
877 Dong Fang Road, Pudong
FIN-00101, Helsinki
Shanghai, China 200122
Finland
Phone: 8621-50589000
Phone: 35-8968271
Fax: 8621-505880007
Fax: 35-896827305
Email: anthony.yuen@renford.com
Email: anttihiidenheimo@atoy.fi
Ireland
Germany
Company: ZF Services Great Britain, Ltd
Company: Otto Piening Propeller GMBH
Contact: Adi License
Contact: Mathias Pien
Address: Abbeyfield Road, Lenton
Address: AM Altendeich 83
Nottingham, United Kingdom
D25348 Glückstadt
NG7 2SX, England
Germany
Phone: 44-115-986-9211
Phone: 49-4124-916812
Fax: 44-115-986-9261
Fax: 49-171-4853376
Email: adi.license@zf.com
Email: pein@piening-propeller.de
Website: www.zf-marine.com
Website: www.piening-propeller.de
Italy
Greece
Company: Saim SPA
Company: Amaltheia Marine, Ltd
Contact: Antonio Renzetti, Alessandro Busetto
Contact: Demetris Kyriazis
Address: Via Donizetti, 9/11
Address: 13 Papaflessa Str.
20090 Assago (MI)
143 43 N. Halkidona
Italy
Athens, Greece
Phone: 39-02-488-521
Phone: 30210-25-88-985
Fax: 39-02-45703070
Fax: 30210-25-89-986 alessandro.busetto@saim-group.com;
Email:
Email: amalmar@otenet.gr antonio.renzetti@saim-group.com
Website: www.saim-group.com
Iceland
Japan
Company: Maras ehf
Company: ZF Marine Japan Co. Ltd
Address: Gudmundur Bragasson
Contact: Y. Ikeda, Nobora Kasajima
Akralind 2
Address: Fujikoshi Bldg. 1-10-11 Iriya taito-ku
201 Kopavogur
Tokyo, 110-0013
Iceland
Japan
Phone: 354-555-6444
Phone: 81-03-5808-4521
Fax: 354-565-7230
Fax: 81-03-5808-4531
Email: Gummi@maras.is
Email: mikio.sato@zf.com
Website: www.zf-marine.com
Russia
Company: ZF South East Asia
Company: ZF Russia
Contact: Sharon Ho
Contact: Anastassia Selverstova
Address: 11, Tuas Drive 1
Address: 71, Marata Street Ste 313
Singapore
St Petersburg
Phone: 6861-0177
Russia 191119
Fax: 6861-9173
Phone: 7-812-324-54-72
Email: sharon.ho@zf-seasia
Fax: 7-812-140-18-15
Email: anastassia.selverstova@zf.sp.ru
South Africa
Company: ZF South Africa Pty, Ltd
Scotland
Contact: Heather Hermann
Company: ZF Services Great Britain, Ltd
Address: PO Box 2098
Contact: Adi License
Kempton Park, 1620 South
Address: Abbeyfield Road, Lenton
Africa
Nottingham, United Kingdom
Shipping: C/O Barlows Power Systems
NG7 2SX England
Cnr Peter Barlow and Kasselss Vlei Rd
Phone: 44-115-986-9211
Phone: 27-11-453-1818
Fax: 44-115-986-9261
Fax: 27-11-453-7506
Email: adi.license@zf.com
Email: heather@zfsa.za
Website: www.zf-marine.com
Spain
Singapore
Company: ZF Espana S.A.
Company: Mammoth Enterprises Pte, Ltd
Contact: Maria Valladolid
Contact: Steven Wee
Address: Avda. Fuentemar, 11
Address: PO Box 283
Coslada (Madrid) 28820
Siglap Post Office
Spain
Singapore 914503
Phone: 34 (0) 91485-2695
Shipping: 6-A Waringin Park
Fax: 34 (0) 91485-0036
Singapore 416320
Email: maria.valladolid@zf.com
Phone: 65-6-44-88266
Website: www.zf-marine.com
Fax: 65-6-44-89800
Email: mament@singnet.com.sg
Sweden Thailand
Company: KG Knutsson AB Company: ZF Thailand Co. Ltd
Contact: Karl-Henry Pragsten Contact: Reungpoj V
Address: Tansmissions Divisionen Address: 159/33 Soi Vipawasee 64
Hammarbracken 8 Vipawasee-Rangsit Road
S-191 81 Sollentuna Laksi, Bangkok 10210 Thailand
Sweden Phone: 66-2-521-6520
Phone: 46-08-923-312 Fax: 66-2-521-6523
Fax: 46-08-929-599 Email: tanapath@bkk.loxinfo.th
Email: zf-marine@kgk.se
Website: www.kgk.se The Netherlands (Holland)
Company: ADS/van Stigt
Switzerland Contact: Ton Hekman, Rob van der Linde
Company: Marine Parts Technic Address: Avelingen – West 30
Contact: Fabian Kraemer NL-4202 MS Gorinchem
Address: Pfaffikerstrasse 6 The Netherlands
CH-8604 Volketswil Phone: 31-0-183-650000
Zurich, Switzerland Fax: 31-0—183-650001
Phone: 41-1997-4090 Email: Ton.Hekman@vanstigt.com
Fax: 41-1997-4094 Website: info@vanstigt.com
info@marineparts.ch;
Email:
fabian.kraemer@marineparts.ch
Website: www.marineparts.ch U.A.E.
Company: ZF Middle East, LLC
Taiwan Contact: M. Narasimhan (Narsi), A.T. Moorthy
Address: 8F-1, No. 34, Min Chuan 1s. Road Shipping: #502 Golden Tower Building
United Kingdom
Company: ZF Marine Propulsion Systems Miramar –West
Company: Atlantis Marine Power, Ltd Coast
Contact: Peter Middleton, Paul Lakey Contact: Kevin Zwicker
Address: Western wood Way Address: 12125 Harbour Reach Drive Ste B
A Limited Warranty: Your ZF product was designed and manufactured by experienced engineers and
craftsmen. ZF Marine Propulsion Systems Miramar, LLC warrants for the period indicated below,
each product manufactured by ZF Marine Propulsion Systems Miramar, LLC to be free from defects
in materials and workmanship. If during the applicable warranty period a product is determined by
ZF Marine Propulsion Systems Miramar, LLC to be in breach of this limited warranty, ZF Marine
Propulsion Systems Miramar, LLC, at its option, will repair or replace the defective product.
B Warranty Exclusions: This warranty covers only failures due to defects in materials or workmanship
that occurs during normal use. This warranty does not cover damage that occurs in shipment,
failures that are caused by products not supplied by ZF Marine Propulsion Systems Miramar, LLC,
failures that result from installation that is not in compliance with ZF specifications, accident,
misuse, abuse, neglect, water damage, mishandling, misapplication, setup adjustments, improper
maintenance, alterations, modification or service by anyone other than a ZF Authorized Service
Center, damage that is attributable to acts of God or other causes unrelated to defects in materials
and workmanship.
C Warranty Period: The length of the applicable warranty period will depend on the use of your vessel.
For Commercial Craft the standard warranty period is for 24 months from the date of original
shipment by ZF or 12 months after commissioning of the craft, whichever occurs first. A commercial
craft is defined as any vessel used for any commercial purpose including but not limited to any use
as a workboat, passenger vessel, charter or rental fleet.
D For Pleasure Craft the warranty period is 36 months from the date of original shipment by ZFME or
24 months after commissioning of the craft, whichever occurs first. A Pleasure Craft is any vessel
that is or has not been used for any commercial purpose including but not limited to any use as a
workboat, passenger vessel, charter or rental fleet.
E Repair or replacement parts provided under this Warranty will not be covered by the remainder of
the unexpired warranty in effect on the complete unit.
F No Coverage Under Warranty: The exclusive remedy under this warranty is the repair or replacement
of the defective component and this warranty specifically does not provide coverage for:
1. Towing or transportation of the vessel, or travel to and from the job site or vessel.
2. Original installation charges or start-up costs.
3. Loss of use or income from the vessel and/or rental of equipment during the performance of warranty repairs.
G To Obtain Warranty Service: Please go to www.zf.com or call 1-425-583-1900 or (U.S. only) 1-800-
546-5455 for the nearest ZF Factory or Authorized Service Center.
1. The Service Center will contact ZF Service Department for a Service Return Authorization (SRA) number. Return
the product freight prepaid, marked clearly with the SRA number, and with a description of the malfunction
included.
2. If there are defects covered by this warranty, ZF will, at its option, either repair or replace the defective part or
product. If after inspection, ZF determines that the product is not defective, ZF will charge a testing fee and
return the product to the sender, freight collect.
3. Repair or replacement during the warranty period will not extend the warranty period.
4. All SRA claims must be requested and submitted within 30 days from the date of repair service.
5. Claims for over 3 hours labor must be pre-approved by the ZF Service Department.
This warranty is expressly in lieu of all other warranties, express or implied. Except to the extent prohibited by applicable law, ZF hereby disclaims all other implied or express warranties
of any kind, including warranties of merchantability and fitness for a particular purpose. Under no circumstances shall ZF be liable for any incidental or consequential damages
sustained in connection with the product or its use, including any costs or damages that result from loss of use of the product or any engine or boat with which it is used. ZF does not
authorize any representative or agent to assume for it any obligation or liability other than those expressly set forth above. Some States and other jurisdictions do not allow limitations on
how long an implied warranty lasts or the exclusion or limitation of consequential damages, so above limitations may not apply to you. All implied warranties, if any, are limited to the
duration of this express warranty. This warranty gives you legal rights, and you may have other rights that may vary from State to State.
Warranty Registration
Purchase Date
Dealer's Name
Installer's Name
Purchaser's Name
Street Address
Phone
YOUR VESSEL:
Length
Manufacturer
EN 3340.758.001a - 2014-10