Status Text
The lower layer of the PROFIBUS has detected a synchronization error. During a
baudrate change this error may occur for a short time. If it remains, check the PROFIBUS
hardware (cables, connectors, slaves).
The hardware watchdog on the backup CI854/CI854A/CI854B was not triggered by the
CI854/CI854A/CI854B firmware within the timeout.
A general error has been detected on the backup unit and the CI854/CI854A/CI854B
stops the normal operation. This error prohibits a redundancy switchover.
-
-
-
-
Bit Code (Hex) Code (Dec)
22 16#00400000 4194304
23 16#00800000 8388608
24 16#01000000 16777216
25 16#02000000 33554432
26 16#04000000 67108864
27 16#08000000 134217728
28 16#10000000 268435456
29 16#20000000 536870912
30 16#40000000 1073741824
31 16#80000000 2147483648
4 16#00000010 16
5 16#00000020 32
6 16#00000040 64
7 16#00000080 128
8 16#00000100 256
17 16#00020000 131072
18 16#00040000 262144
Status Text
Channel Error
I/O Warning
Underflow
Overflow
Forced
General Warning
Warning Primary
Description
In CI854B Redundant configuration, if one of the CI854B module is hot swapped with CI854A,
Device Specific Error 10 ('Wrong pairs of CIs used for redundancy') message in unit status appears and
remains until it is replaced back with CI854B module.
The hardware watchdog on the primary CI854/CI854A/CI854B was not triggered by the
CI854/CI854A/CI854B firmware within the timeout.
A configuration error has been detected on the Primary unit.
The PROFIBUS connection between primary and backup unit failed.
Overload of the communication memory access. There is too much access from the application tasks to the
PROFIBUS I/O-data in the shared memory on the CI854/CI854A/CI854B so that the CI854/CI854A/CI854B
cannot update the memory in time.
Two or more PROFIBUS slaves have the same address.
If line redundancy is enabled, this warning reflects the state of the RxA LED of the primary
unit.
If line redundancy is enabled, this warning reflects the state of the RxB LED of the primary
unit.
A hardware failure has been detected on the primary unit, for example RAM failure
The primary unit does not contain a valid firmware.
32
31 30
0 0
00000000000000000000000100000000
29 28 27 26 25 24 23 22 21 20
0 0 0 0 0 0 0 0 0 0
19 18 17 16 15 14 13 12 11 10
0 0 0 0 0 0 0 0 0 0
1
9 8 7 6 5 4 3 2 1 0
0 1 0 0 0 0 0 0 0 0