The medical air compressors are of the oil-less reciprocat- Local audible and visual alarms are provided per NFPA 99
ing air-cooled design. The air compressors feature a cast for compressor thermal malfunction and "Backup in use".
iron crankcase, teflon-composite compression and rider The alarms include indicating lights as well as the horn. In
rings, lubricated and totally sealed bearings, stainless steel addition, the thermal malfunction shut-down is provided
reed valves, non-asbestos gaskets. No oil is used in with a manual reset. The audible alarm can be acknowl-
operation of the compressors, so the discharge air is edged with the "Silence" button. The visual alarm will
100% oil-free. Cooling is provided by a fan type compres- remain energized until the problem has been corrected.
sor pulley with air shroud. Each alarm function includes a set of dry contacts for
Compressors are V-belt driven by 3 phase, 60 cycle, 1750 connection to the master alarm. All control and alarm
RPM, NEMA design B motors. functions will remain energized while any compressor in the
system remains electrically on-line.
The system includes a pressure storage tank of ASME
construction rated for 200 PSI MWP service. The tank is Field adjustable control switches are pre-set to operate the
equipped with a pressure gauge, safety relief valve, 3 way lead compressor between 100 PSIG and 125 PSIG. The lag
by-pass, gauge glass and automatic tank drain with manual 1 compressor between 95 PSIG and 125 PSIG, the lag 2
override. compressor between 90 PSIG and 125 PSIG. The stand-by
Also included as standard equipment are compressor compressor will automatically start at 85 PSIG if the lead
discharge check valves of bronze construction, safety compressor fails to operate.
relief valves, bronze intake and discharge flexible connec-
tors, solenoid unloaders for reliable no-load starting, iso- The Medical Air system is guaranteed by the manufacturer
lation valves, high discharge temperature shut-down for a period of 12 months from the date of start-up or 18
switches, pressure control switches as well as copper months from the date of shipment (whichever comes first)
tubing with shut-off cock for gauge and switches. against defects in design, materials, or construction.
The system includes a UL labeled control panel in a NEMA Optional System Accessories
12 enclosure. The panel includes the following standard (only checked options will be supplied)
accessories for each pump: externally operable circuit "Dura-coat" rust protection receiver lining
breaker with a door interlock, control circuit transformer Galvanized receiver
with fused primary and secondary coils, H-O-A switch, run Air-cooled aftercoolers
light, hour meter and magnetic starter with 3 leg overload Dual medical air treatment system
protection and reset switch. The panel is equipped with a with refrigerated air dryers
multiple position selector switch for selection of normal Dual medical air treatment system
operation (automatic alternation) or manual selection of with desiccant air dryers
lead and lag pumps if one of the pumps is taken out of Interface to AIMS (AMICO Information
service due to scheduled maintenance. Management System)
QUADRUPLEX BASE MOUNTED
"Q" SERIES MEDICAL AIR SYSTEMS
20 THROUGH 30 HP (2-STAGE)
LAYOUT AND PERFORMANCE TABLE
AIR COMPRESSOR
DISCHARGE
RECEIVER
CONTROL
PANEL
INTAKE 2"
(TYP.)
L W
System Horsepower Capacity SCFM (Each Pump) Disch. Tank Dimensions, In. Weight
Model Number Each Total 100 PSIG 125 PSIG Conn. (Gal.) L W H Lbs.
Power Requirements:
(Four) _____ HP Motors, 3 Phase 60 Hertz 208 v 230 v 460 v