You are on page 1of 2

SPC HPDS SELECTION/RATING SUMMARY

Version Number: Version 4.3


Mode: Selection
Licence Ref: Standard

(1) Air On Heatpipe Precool


(2) Air Off Heatpipe Precool
(3) Air Off Cooling Coil
(4) Air Off Heatpipe Reheat
(1) (2) (3) (4)
Dry Bulb Temp (°C): 35.0 28.5 13.5 20.0
Wet Bulb Temp (°C): 27.6 26.0 13.1 15.6
Relative Humidity (%): 57 82 95 63
Humidity Ratio (kg/kg): 0.0203 0.0203 0.0092 0.0092
Enthalpy (kJ/kg): 87.35 80.58 36.71 43.41
----------------------------------------------------------------------------------------------------
Pre Cool Saving: 16.3 kW
Cooling Coil Duty 105.3 kW
Reheat Saving: 16.3 kW
----------------------------------------------------------------------------------------------------
GENERAL
Air Flow Rate: 2.00 m³/s
Coil Height: 1200
mm
Coil Width 1800 mm
Air Velocity 0.94 m/s
Barometric Pressure: 101.33 kPa
Fin Material: Aluminium
----------------------------------------------------------------------------------------------------
HEAT PIPE
Fin Type: Louvre
Rows: 1
FPI: 12
Effectiveness: 30 %
Pressure Drop: 16 Pa
----------------------------------------------------------------------------------------------------
COOLING COIL
Heat Pipe Only: No
Chilled Water: Yes
Refrigerant: No
Inlet Water Temp: 5.5 °C
Outlet Water Temp: 14.4 °C
Air Pressure Drop: 27 Pa
Fluid Pressure Drop: 21.1 kPa
Fin Type: Louvre
FPI: 10
Rows: 3
----------------------------------------------------------------------------------------------------
OPTIONS
Casing Material: N/A
Drain Pan: N/A
Heatpipe: N/A
Eliminators: N/A
----------------------------------------------------------------------------------------------------
Size: N/A N/A
Weight: N/A N/A
----------------------------------------------------------------------------------------------------

21-May-17 10:13:28 AM

S & P Coil Products Limited


SPC House,
Evington Valley Road,
Leicester, LE5 5LU,
England
Tel: +44 (0)116 2490044
Fax: +44 (0)116 2490033
e-mail: spc@spcoils.co.uk
Web: www.spcoils.co.uk

You might also like