You are on page 1of 8

SURUHANJAYA KOMUNIKASI DAN MULTIMEDIA MALAYSIA

(MALAYSIAN COMMUNICATIONS AND MULTIMEDIA COMMISSION)

TIME 3 PHASE 3 PROGRAM


PART 2 SITE ACCEPTANCE TEST CHECKLIST

REGION: NORTHERN
DATE :

CLUSTER NO. 20 SITE ID T3_0385

SITE NAME MN_SGDENDANG

USP TARGET BATU KURAU STATE PERAK

LATITUDE 5.16564 LONGITUDE 100.71672

TOWER TYPE Three Legged Tower 76m

SITE
Existing Outdoor
CATEGORY

PART 1

PART 2

INVITATION TO REGISTER INTEREST AS UNIVERSAL SERVICE PROVIDER


Ref: MCMC/USPD/PMO(1)/T3_RT/TCA/11/11(08)
Revision Date: 14 November 2016
NO. WORK DESCRIPTION REMARKS

N/A OK Need Work

1.0 BASE TRANSCEIVER STATION (BTS) EQUIPMENT

Equipment Type & Make: __________________________________

Number of Cabinet: _______________________________________

Number of Physical Radio Unit (Transceiver): ___________________

Number of Activated Radio Unit (Transceiver): _________________

Type of Service :_________________________________________

Site Configuration : _______________________________________

Freq (MHz):

*1.1 APPARATUS ASSIGNMENT

Radio Base Station (Y/N)

Backhaul - Microwave/VSAT (Y/N)

*1.2 2G FREQUENCY

TRX Sector Tx Rx ARFCN Cell ID

0.2 1 1783.6 1878.6 879 20126

0.2 2 1 1783.2 1878.2 877 13616

0.2 3 1782.0 1877.0 871 3851

0.2 4 1737.8 1832.8 650 20127

0.2 5 2 1738.2 1833.2 652 13617

0.2 6 1738.6 1833.6 654 3852

0.2 7 1714.2 1809.2 532 20128

0.2 8 3 1711.4 1806.4 518 13618

0.2 9 1712.8 1807.8 525 3853

(If TRX is more than 6 channels, please provide attachment)

*1.3 3G FREQUENCY
Primary Scrambling
Cell ID
Carrier Sector Code

5 1 342 51961
10662 2 350 51962

3 358 51963

5 1 129 45531
10812 2 137 45532

3 145 45533

5 1 202 13931
10762 2 210 13932

3 218 13933
*2.0 BACKHAUL EQUIPMENT N/A OK Need Work

Tx Via : Microwave VSAT Fibre

For MW Link 1 Link 2 Link 3

Antenna Type & Make

Diameter (m)

Height (m AGL)

Azimuth (deg)

TX / RX Freq (GHz)

Weight (kg)

*3.0 BTS ANTENNA SYSTEM N/A OK Need Work

SECTOR 1 2 3

Total no. of antennas

Antenna height (meter)

Antenna direction

Height (m AGL)

Type of antennas

Antenna Band

Antenna Lobe
E: M: E: M: E: M:
Antenna tilt

Antenna Gain

Ant. Dimensions(mm)
(HxWxD)

Weight of antennas (Kg)

Max. wind velocity


NO. WORK DESCRIPTION REMARKS

N/A OK Need Work

BTS FEEDER DETAILS

SECTOR 1 2 3

Total no. of feeders

Type of feeders

Feeders and DC cable


length

*4.0 DC POWER SUPPLY

Equipment Type & Make: ______________________________

No of active power modules: __________________________

Back-up Batteries: ___________________hrs

*5.0 ALARM MONITORING SYSTEM

Alarm Monitoring System Functioning well: YES / NO

System Type & Make: ______________________________

*6.0 SERVICES VERIFICATION

Result
Service Service Provider Test
Sector 1 Sector 2 Sector 3

Voice MOC OK OK OK
SP1:
Voice MTC OK OK OK

Voice MOC OK OK OK
2G SP2:
Voice MTC OK OK OK

Voice MOC OK OK OK
SP3:
Voice MTC OK OK OK

Result
Service Service Provider Test
Sector 1 Sector 2 Sector 3

Voice MOC OK OK OK
SP1:
Voice MTC OK OK OK

Throughput 11.40 Mbps 9.62 Mbps 9.08 Mbps

Voice MOC OK OK OK
3G SP2:
Voice MTC OK OK OK

Throughput 10.28 Mbps 9.50 Mbps 9.88 Mbps

Voice MOC OK OK OK
SP3:
Voice MTC OK OK OK

Throughput 11.53 Mbps 4.13 Mbps 9.16 Mbps


NO. WORK DESCRIPTION SPECIFICATION ACTUAL REMARKS

7.0 ANTENNA LOADING (LIGHT DUTY 76M) N/A OK Need Work

- Panel/Omni antenna Max 9 Nos.


- 2.4m diameter MW dish Max 2 Nos.
- 1.8m diameter MW dish Max 2 Nos.
- 1.2m diameter MW dish Max 2 Nos.

8 ELECTRICAL WORKS & POWER SUPPLY


8.1 Source of Power Supply (To fill one item only)

*a Dedicated supply fromTNB/SESB/SESCO Completely Connected & Commissioned 3 Phase 60 amps

b Permanent Generator Set Completely Connected & Commissioned


c Hybrid Power System Solution

8.2 Weatherproof KwH Meter Panel in accordance with specification of TNB

a Pole mounted with HDG mounting brackets


b Floor standing
Incoming power cable from Utility is neatly laced to the pole and enter from the bottom of the
c
KwH meterboard
Output power cable from KwH meter board is protected and concealed in GI conduit and
d
secured with flexiband strapping
e Cut-out fuses and neutral link are secured and correctly rated 60 amps

8.3 Power Distribution Board

*a Type : ACPDB Indoor / PDU Outdoor

*b Incoming power cables are housed directly from KWH metering board to distribution board

*c Laminated circuit diagram with chargeman endorsement is attached inside of the panel door

All wires are of the right size, colour-code and are properly labelled with approved labels
*d
including correspond to single line diagram

*e 5 pin flange inlet plug (male) for mobile genset power connection

*f All indoor electrical wiring are concealed in PVC trunking / conduits

g Junction box is link to all external alarm signal and to ATF/DDF

Wall mounted distribution board is securely bolted but not punched through the cabin walls
h
(applicable for ACPDB only)

9.0 GENSET (if applicable)


a Permanent Genset Capacity 2 Nos
- Light Duty 76m - 20kVA Genset c/w 2,000L skid tank 2 Nos
b Auto Switch-Over in accordance to specification
c All equipment properly secured to prevent theft

10.0 HYBRID POWER SYSTEM (if applicable)


10.1 Hybrid type: _______________________________________
10.2 Usable load
- Light Duty 76m site 6kW
NO. WORK DESCRIPTION

*11.0 COVERAGE OBJECTIVE


No. Azimuth Distance Coverage Objective Est. Population
(Km) (Name of Kampung, Highway etc) (# of Houses)

1 20 1.50 Residential Area 20

2 130 1.50 Kp baharu Dendang, Jalan Kubu Gajah, Kp Sungai lempong 100

3 300 1.00 Jalan Kubu Gajah 70

12.0 COVERAGE OBJECTIVE PLOT

315° 45°

1km 2km 3km


270° 90°

225° 135°

180°
Note: Results of Drive Test which cover all areas listed under the coverage objective are to be attached with this checklist
and shall comply with Determination No. 2 of 2002 - Mandatory Standard for QoS (Public Cellular Service).
The test results shall indicate below items :
1. Coverage and quality plot together with RxLev, RxQual, RSCP and Ec/No legend
2. Drop call rate (DCR) and Call Setup Success Rate (CSSR)
3. Service Functionality
3.1 Mobile originated and terminated call
3.2 SMS and MMS
4. Handover Functionality:
4.1 Intra-site
4.2 Inter-site (if applicable)
4.3 Inter Radio Access Technology (IRAT)
4.4 Reselection
5. Average DL and UL Throughput (EDGE and WCDMA)
PART 2 SITE COMPLETION DEFECT LIST

LIST OF DEFECTS:
ITEM DEFECTS DETECTED *MAJOR DEFECT PHOTO DATE
DEFECT RECTIFIED
(Photo
Attachment
Compulsory)

Items marked '*' are mandatory requirement for Completion.


PART 2 SITE ACCEPTANCE TEST RESULT

CLUSTER NO. 20 SITE ID T3_0385

SITE NAME MN_SGDENDANG CATEGORY Collector / Spur

USP TARGET BATU KURAU STATE PERAK

LATITUDE 5.16564 LONGITUDE 100.71672

COMPLETION DATE TIME

TEST RESULT
DRIVE TEST DATE &
COMPLIANCE
TIME
(Y/N)

PART 1
PART 2

Site is COMPLETED
Site is COMPLETED WITH MINOR DEFECTS

Site is NOT COMPLETED *


* Major defects detected and Part 2 to rectify defects as listed in page 6

REMARKS:

Part 2 / SKMM Representatives

Part 2 MCMC

Signature & company's stamp Signature & company's stamp


Name: Name:

Date: Date:

MCMC Others

Signature & company's stamp Signature & company's stamp


Name: Name:

Date: Date: