Calcul reactante trafo cu 3 infasurari !!!

uk_HV_MV := uk_HV_LV := uk_MV_LV :=


uk0_HV_MV := uk0_HV_LV := uk0_MV_LV :=
S_HV_MV := S_HV_LV := S_MV_LV :=

XT_HV := 0.5  
uk_HV_MV uk_HV_LV uk_MV_LV 
+ - =
 S_HV_MV S_HV_LV S_MV_LV 

XT_MV := 0.5  
uk_MV_LV uk_HV_MV uk_HV_LV 
+ - =
 S_MV_LV S_HV_MV S_HV_LV 

XT_LV := 0.5  
uk_HV_LV uk_MV_LV uk_HV_MV 
+ - =
 S_HV_LV S_MV_LV S_HV_MV 

XT0_HV := 0.5  
uk0_HV_MV uk0_HV_LV uk0_MV_LV 
+ - =
 S_HV_MV S_HV_LV S_MV_LV 

XT0_MV := 0.5  
uk0_MV_LV uk0_HV_MV uk0_HV_LV 
+ - =
 S_MV_LV S_HV_MV S_HV_LV 

XT0_LV := 0.5  
uk0_HV_LV uk0_MV_LV uk0_HV_MV 
+ - =
 S_HV_LV S_MV_LV S_HV_MV 