You are on page 1of 1

Water Vol.

of water Total Water Supply per Cumulative Surplus


Time Consumption demand consumption hour supply /Deficit
Liters per
hr second Liters liters liters liters liters
2 23.8 171360 171360 414120 414120 242760
4 15.6 112320 283680 414120 828240 544560
6 33.9 244080 527760 414120 1242360 714600
8 68.3 491760 1019520 414120 1656480 636960
10 72.4 521280 1540800 414120 2070600 529800
12 65.9 474480 2015280 414120 2484720 469440
14 66.7 480240 2495520 414120 2898840 403320
16 72.1 519120 3014640 414120 3312960 298320
18 95.9 690480 3705120 414120 3727080 21960
20 95 684000 4389120 414120 4141200 -247920
22 50.5 363600 4752720 414120 4555320 -197400
24 30.1 216720 4969440 414120 4969440 0
Total 4969440

Total water requirement for 24 hours =4969440 liters

The constant pumping rate = (4969440/ 24*3600) = 57.516 lit/sec

Pumping rate for 2 hours = 57.516 lit/sec* (2*3600) = 414120 liters

Fire water requirement =216*2 m3 =648 m3 = 648000 lit

Distribution storage required = Maximum surplus +Minimum deficit + Fire water requirement

= 714600 + 247920 + 648000

=1610520 liters

Approaches for water disinfection

Disinfection of water is done to ensure that water is microbiologically safe( free from bacteria, viruses )

1. Chlorination
2. Ozonasation
3. Ultraviolet light disinfection