c/L OF POLE ——~]
FINISHED SIDEWALK, MEDIAN
OR PLANTING STRIP
BONDING BUSHING.
INSPECTION PLATE
FULL POLE FLANGE COVER
FACE OF CURB
jong Fo a
[== 1/2" RIGID GALVANIZED STEEL CONDUIT
(LONG RADIUS BEND) IN CONCRETE
RIGIO GALVANIZED STEEL CONDUIT SHALL
EXTEND TO THE NEAREST PULL BOX.
19)
SEE NOTE 5
See NOTE 4 See Nore 2
ale te
7 ay =
No.4 BARE COPPER WIRE FOR
GROUNDING 22° TO 25° AEQ'D. BOND
TO LIGHT POLE GROUNDING LUG.
MIN. 127 Om)
SPIRAL COIL
NOTES:
t CONSTRUCTION SHALL CONFORM TO THESE:
BY THE COUNTY ENGINEER.
J2.IN AREAS WHERE CONCRETE SIDEWALKS WILL
BE POURED AFTER THE POLE FOUNDATION TS
INSTALLED, POUR FOUNDATION TO BOTTOM
ELEVATION’ OF SIDEWALK. IN AREAS WITHOUT
CONCRETE AROUND FOOTING, CONSTRUCT A
2° XB" CONCRETE PAD (4" THICK}
Is. FOUNDATION BOLTS SHALL NOT BE CUT OFF
FOR ANY REASON. EXTENSION COUPLERS SHALL.
NOT BE PERMITTED.
Jd. LEVELING OF GASE SHALL CONFORM TO THE
REQUIREMENTS OF STANDARD DRAWING NO. 620.
IS. ANCHOR BOLT OIMENSTONS PER MANUFACTURERS
SPECIFICATION. ANCHOR BOLTS SHALL BE
GALVANIZED STEEL.
FEGUIRENENTS EXCEPT AS OTHERWISE DIRECTED
SAND CUSHION
‘COUNTY OF SONOMA
DEPARTMENT OF TRANSPORTATION
‘AND PUBLIC WORKS.
CONCRETE FOOTING DETAIL
‘STANDARD STREET LIGHT POLE
DATE: may 2004 [REVISED
IS. CONCRETE SHALL BE CLASS 2 P.C.C. POURED APPROVED BY: SCALE: ]ORAWING NO
AGRINST UNDISTURBED SOIL. SEE DRAWING NO. 618 NONE | g46
FOR FOOTING DETAILS