Professional Documents
Culture Documents
MAINTENANCE MANUAL
FOR SCREW COMPRESSORS
Models:
NEWTON 4075/4090
EDISON 4075/4090DV
Address________________________________________
Telephone______________________________________
Fax___________________________________________
OQ7_5ARG021EN
INSPECTION REPORT
POWER SYSTEM s.r.l., Via Dell’Emigrante, 11/13 - 36040 Brendola, Vicenza, ITALY
declares that the screw compressor package:
− All electrical tests on safety have been carried out and found within set limits.
− There are no leakages in the oil circuit and the air circuit.
− Capacity, absorbed power and various operating temperature have been checked and
found satisfactory.
Attention!
Failure to observe and apply the rules and recommendations listed in this manual
invalidates all types of guarantee on the compressor.
POWER SYSTEM s.r.l. declines all responsibility with regard to damage caused to persons and/or things as a
result of incorrect use of the compressor and its accessories, lack of maintenance or neglect and, in general, the
failure to observe the warnings given in this manual, which are to be considered as complementary to the
general safety standards in force.
Before using the machine, please fill in the document and return it to us, following the indications given below.
AUTHORISED DEALER
Company
…………………………………………………………………………………………………………………………………………………………………………
Street No.
………………………………………………………………………………………………………………… …………………………………
Town
…………………………………………………………………………………………………………………………………………………………………………
Province
…………………………………………………………………………………………………………………………………………………………………………
Postcode Stamp
……………………………………………………………
Country
……………………………………………………………
Telephone
……………………………………………………………
Fax
……………………………………………………………
VAT No.
……………………………………………………………
Internet
www. …………………………………………...…………………………………………...…………………………………………...……………………….
E-mail
…………………………………………………………………………………………………………………………………………………………………………
GUARANTEE
1) Within the limits established in this guarantee, the undersigned manufacturer undertakes to repair all
construction defects that may arise during the guarantee period, set at 12 (twelve) months from the date of start-
up or 15 (fifteen) months from the date of delivery.
The obligations deriving from the guarantee cease in the event of suspension or variation of the agreed terms of
payment.
2) The guarantee ceases if the buyer does not correctly follow the rules described in the “Instructions for use and
maintenance” of the compressor.
3) The guarantee does not cover: faults and defects due to normal wear of those parts which are by nature subject
to rapid and continuous wear and faults resulting from the use of tools and accessories not supplied directly by the
manufacturer.
4) In order to benefit from the right to the guarantee, when the defect arises the purchase must promptly notify the
manufacturer, at any rate no later than 8 (eight) days after the date of discovering the fault, and must allow
the manufacturer, if necessary, to carry out the required inspections and repairs.
5) The buyer must send the faulty part, covered by the guarantee, at his own expense to the manufacturer for
repair or replacement. As contemplated in this clause, the guarantee obligation is considered fulfilled with the
delivery to the buyer of the adequately repaired or replaced part.
6) During the guarantee period contemplated in clause 1) the labour costs, for the duration of the work alone, will
be at the manufacturer’s expense.
If the repairs or replacements have to be carried out on the place of installation of the compressor, the travel and
lodging expenses of the personnel will be borne by the buyer.
7) All breakages resulting from incorrect manoeuvres, lack of skill, fortuitous events or for which the user can be
held responsible, are excluded from the guarantee, whether the user is directly responsible or through a third
party, or when the buyer has made modifications or carried out repairs without the manufacturer’s consent in
writing, irrespective of whether or not there is a connection between said modifications or repairs and the defects
found.
8) It is expressly agreed that the manufacturer shall be relieved of all responsibility for any damage of lost or
decreased production suffered by the buyer, resulting from faults or defects in construction for which this
guarantee is applicable.
1 GUARANTEE CONDITIONS................................................................................................................................. 4
7 INTENDED USE................................................................................................................................................................... 19
7.1 ENERGY SUPPLY SOURCES ...................................................................................................................................... 19
7.2 STAGES OF USE ........................................................................................................................................................... 19
7.3 LIMITS OF USE ............................................................................................................................................................. 19
7.4 OPTIONAL ACCESSORIES.......................................................................................................................................... 20
10 INSTALLATION..................................................................................................................................................... 22
10.1 GENERAL WARNINGS ................................................................................................................................................ 23
10.2 POSITIONING ............................................................................................................................................................... 23
10.3 SECURING THE COMPRESSOR AND CONNECTING THE AIR PIPE .................................................................... 23
10.4 TEMPERATURE BELOW 0° C..................................................................................................................................... 23
10.5 AIR TANK...................................................................................................................................................................... 24
10.6 DISTRIBUTION LINE................................................................................................................................................... 24
10.7 WARM AIR OUTLET CONVEYING............................................................................................................................ 24
11 ELECTRICAL CONNECTION................................................................................................................................ 25
11.1 ELECTRICAL DATA TABLE ................................................................................................................................................ 25
13 FIRST START-UP...................................................................................................................................................... 26
13.1 AUXILIARY PROTECTION FUSES ........................................................................................................................................ 27
14 STORAGE ............................................................................................................................................................................. 27
16 SAFETY ....................................................................................................................................................................... 28
16.1 SAFETY SIGNALS ........................................................................................................................................................ 28
16.2 RESIDUAL RISKS ......................................................................................................................................................... 31
16.3 AUTHORISED OPERATORS: PLACES OCCUPIED .................................................................................................. 31
17 CONTROL PANEL DNAIR MAXI .................................................................................................................................... 33
17.1 GENERAL DESCRIPTION ....................................................................................................................................... 33
17.2 MENU STRUCTURE ................................................................................................................................................. 33
17.3 DNAIRMAXI CONTROL PANEL ................................................................................................................................. 34
17.4 KEYPAD ........................................................................................................................................................................ 34
17.5 SIGNALS – SETTINGS LEDS....................................................................................................................................... 35
17.6 ALPHANUMERIC DISPLAY........................................................................................................................................ 35
17.7 RAPID LANGUAGE SELECTION................................................................................................................................ 35
18 COMPRESSOR CONTROL ............................................................................................................................................... 36
18.1 START COMPRESSOR................................................................................................................................................. 36
18.2 STOP COMPRESSOR.................................................................................................................................................... 37
18.3 EMERGENCY STOP ..................................................................................................................................................... 37
19 CONFIGURATION – MENU TREE .................................................................................................................................. 38
19.1 ADDITIONAL INFORMATION MENU....................................................................................................................... 39
19.1.1 SUBMENU A........................................................................................................................................................... 39
19.2 MENU TREE (CONTROL AND PROGRAMMING).................................................................................................... 40
19.2.1 SUBMENU B........................................................................................................................................................... 40
19.3 MAINTENANCE MENU ............................................................................................................................................... 41
6.3.1 TIME TO SERVICE................................................................................................................................................. 42
6.3.2 COMPONENTS LIFE ............................................................................................................................................. 42
6.3.3 REPLACE AND RESET COMPONENTS ............................................................................................................... 42
6.3.4 MIN MAX COMPONENTS LIFE............................................................................................................................ 42
6.3.5 MODIFY COMPONENTS LIFE ............................................................................................................................. 43
19.4 ACCESS: STOP RI-AS................................................................................................................................................... 43
6.3.6 BLOCK NO-MAINTENANCE ................................................................................................................................. 43
19.5 ACCESS: STOP RI-AS................................................................................................................................................... 43
6.3.7 RUNNING HOURS ................................................................................................................................................. 44
6.3.9 RESET CPU ............................................................................................................................................................ 44
6.3.10 COMPRESSOR TYPE MENU................................................................................................................................. 44
19.6 GENERAL SETTINGS MENU ...................................................................................................................................... 45
6.4.1 LANGUAGE............................................................................................................................................................ 47
6.4.2 MEASURING UNIT ................................................................................................................................................ 47
6.4.3 DATE AND TIME ................................................................................................................................................... 47
6.4.4 DISPLAY SETTINGS .............................................................................................................................................. 47
6.4.5 OPERATING MODE .............................................................................................................................................. 47
6.4.6 COMPRESSOR CONTROL .................................................................................................................................... 47
6.4.7 DRYER CONTROL ................................................................................................................................................. 48
6.4.8 TYPE OF REMOTE CONTROL.............................................................................................................................. 48
6.4.9 AUTORESTART FUNCTION.................................................................................................................................. 49
6.4.10 INPUT CONFIGURATION..................................................................................................................................... 49
6.4.11 MAXIMUM SPEED CALIBRATION....................................................................................................................... 49
6.4.12 OUTPUT CONFIGURATION................................................................................................................................. 50
6.4.13 TYPE OF START..................................................................................................................................................... 50
6.4.14 DRAIN VALVE ACTIVATION ................................................................................................................................ 50
6.4.15 OIL PRE-HEATING................................................................................................................................................ 50
6.4.16 MAINTENANCE TIMES BASE ............................................................................................................................... 50
6.4.17 NET SETTINGS....................................................................................................................................................... 50
19.7 OPERATING PARAMETERS ....................................................................................................................................... 51
6.4.18 PRESSURES ........................................................................................................................................................... 51
6.4.19 TEMPERATURES ................................................................................................................................................... 52
6.4.20 TIMINGS................................................................................................................................................................. 53
6.4.21 SPEED CONTROL.................................................................................................................................................. 54
19.8 PROGRAMMING MENU.............................................................................................................................................. 55
POWER SYSTEM s.r.l. Operating instructions (translation from original IT)
6 Via Dell’Emigrante, 11/13 Cod. OQ7_5ARG021EN
36040 Brendola, Vicenza, ITALY Emiss. 28/01/2004 Rev. 8 - Agg. 23/01/2013
6.6.1 RESET PROGRAMMING ....................................................................................................................................... 56
6.6.2 PROGRAMMING MODE ....................................................................................................................................... 56
6.6.3 DAILY PROGRAMMING........................................................................................................................................ 56
6.6.4 WEEKLY PROGRAMMING.................................................................................................................................... 56
19.9 DIAGNOSTICS MENU.................................................................................................................................................. 57
6.6.5 ERROR MESSAGES MENU ................................................................................................................................... 58
6.6.6 PASSWORD MENU ................................................................................................................................................ 58
6.6.7 INFORMATION MENU.......................................................................................................................................... 59
20 COMMUNICATION BETWEEN COMPRESSORS........................................................................................................ 60
20.1 INSTALLATION............................................................................................................................................................ 60
20.2 ASSEMBLY OF THE CAN-BUS MODULE ................................................................................................................. 61
20.3 CONNECTIONS FOR COMMUNICATION................................................................................................................. 61
20.3.1 CONNECTION OF 4 COMPRESSORS .................................................................................................................. 61
20.3.2 CONNECTION OF 3 COMPRESSORS .................................................................................................................. 62
20.3.3 CONNECTION OF 2 COMPRESSORS .................................................................................................................. 62
21 CONFIGURATION AND OPERATION ........................................................................................................................... 63
21.1 MASTER-SLAVE SYSTEM .......................................................................................................................................... 63
21.2 SYNCHRONY AND SEQUENCE MODES .................................................................................................................. 63
21.2.1 SYNCHRONY MODE.............................................................................................................................................. 63
21.2.2 SEQUENCE MODE................................................................................................................................................ 63
21.2.3 NETWORK PARAMETERS CONFIGURATION .................................................................................................... 64
21.2.4 COMPRESSOR ID .................................................................................................................................................. 65
21.2.5 Number compressors in prefill / prefill time ........................................................................................................... 65
21.2.6 Max number of compressors ON............................................................................................................................. 65
21.2.7 Sequence rotation time............................................................................................................................................ 65
21.2.8 Reaction times delay ON and delay OFF................................................................................................................ 65
22 DRYER - DISPLAY.............................................................................................................................................................. 66
28 OPERATING PRINCIPLE.................................................................................................................................................. 71
31 SPECIAL MAINTENANCE..................................................................................................................................... 75
31.1 CHANGING THE OIL AND THE OIL FILTER............................................................................................................ 75
32 TROUBLESHOOTING ............................................................................................................................................ 80
33 ELECTRIC DIAGRAM............................................................................................................................................. 81
33.1 REMOTE CONTROL..................................................................................................................................................... 81
33.2 AUTOMATIC RESTART .............................................................................................................................................. 81
34 GENERAL WARNINGS...................................................................................................................................................... 81
34.1 ORDERING PROCEDURE............................................................................................................................................ 81
34.2 DEMOLITION................................................................................................................................................................ 81
35 REGISTRATION AND COMMISSIONING REPORT ................................................................................................... 82
37 84
Models: NEWTON 75 90
EDISON DV 75 90
EN 1012-1 : 1997
(Compressors and vacuum pumps. Safety requirements. compressors)
EN 60204-1 : 2006
(Fundamental safety standards on the Electrical equipment of machines)
Left side
Fig.1 (Marcatura CE)
This technical manual of “Instructions for use and maintenance” has been drawn up according to the indications given by the European
Directives, in order to ensure easy and correct understanding of the topics dealt with by the operators authorised to perform the use
and maintenance of the compressor concerned. If, despite the care taken by the manufacturer when drawing up the manual, these
operators find any problem in understanding it, in order to avoid incorrect personal interpretations that might endanger safety, they are
requested to apply promptly to the manufacturer for the correct explanations and any further information.
Before using the compressor, the authorised operators must read and understand all parts of this technical manual of “Instructions for
use and maintenance” and strictly follow all the rules in it, in order to ensure their own safety and that of other people, obtain the best
compressor performance, and ensure the maximum efficiency and long life of all its components. This manual must be at the disposal
of the authorised operators at all times and must always be kept safely, near the compressor.
THIS MANUAL MUST ALWAYS BE AT THE DISPOSAL OF THE AUTHORISED OPERATORS AND
MUST BE KEPT SAFELY, NEAR THE COMPRESSOR.
THIS MANUAL REFLECTS THE STATE OF THE ART AT THE TIME THE COMPRESSOR WAS SOLD
AND CANNOT BE CONSIDERED INADEQUATE ONLY BECAUSE IT MAY BE UPDATED LATER IN
THE LIGHT OF NEW EXPERIENCE.
IF THE MANUAL IS LOST OR SPOILT, ASK THE MANUFACTURER FOR A NEW COPY, SPECIFYING
THE COMPRESSOR IDENTIFICATION DATA (SEE CE MARKING) AND THE REVISION.
THE GENERAL DANGER SIGNAL AND THE FRAMED TEXT IN CAPITAL LETTERS DRAW THE
OPERATOR’S ATTENTION TO THE WARNINGS GIVEN IN THIS MANUAL.
This technical manual is intended exclusively for the operators authorised to carry out use and maintenance of the compressor,
according to the specific technical and professional skills required for the type of activity. The symbols shown below placed at the
beginning of a chapter and/or of a paragraph indicate which operator is involved in the subject dealt with.
THE AUTHORISED OPERATORS MUST PERFORM ON THE COMPRESSOR ONLY THE ACTIVITIES
FOR WHICH THEY ARE SPECIFICALLY COMPETENT.
BEFORE CARRYING OUT ANY ACTIVITY ON THE COMPRESSOR, THE AUTHORISED OPERATORS
MUST ENSURE THAT THEY ARE IN FULL POSSESSION OF THEIR PHYSICAL AND MENTAL
FACULTIES IN ORDER TO ENSURE THAT THE SAFETY CONDITIONS ARE ALWAYS RESPECTED.
GENERAL OPERATOR
This is a professionally trained operator, over 18 years of age, in compliance with the laws in force in the country of use,
authorised only to switch on, use, fine-tune (obligatorily with the guards enabled and the machine switched off) and
switch off the compressor, absolutely respecting the instructions given in this manual, provided with the personal
protective equipment (PPE) contemplated in table 7 and occupying the positions described in fig. 9.
HANDLING OPERATOR
This is a professionally trained operator, over 18 years of age, in compliance with the laws in force in the country of use,
authorised to use fork-lift trucks, bridge cranes or cranes, to transport and handle the compressor and/or its parts safely,
provided with the personal protective equipment (PPE) contemplated in table 7 and occupying the positions described in
fig. 9.
ELECTRICAL OPERATOR
This is a qualified technician (electrician in possession of the technical and professional skills required by the
regulations in force), approved to perform only operations on electric devices to carry out adjustments, maintenance
and/or repairs even with the system live and with the guards disabled (with the consent of the safety manager),
absolutely respecting the instructions given in this manual or any other specific document supplied exclusively by the
manufacturer, provided with the personal protective equipment (PPE) contemplated in table 7 and occupying the
positions described in fig. 9.
In the manual you can also find, next to a table, a figure, or a text, a double line “║“; this indicates the parts of the manual that have
been varied with respect to the previous revision.
It is obligatory to disconnect the supply of electric power before carrying out any kind of maintenance work and/or
adjustment on the compressor.
1) Main electric switch turned “OFF” and padlocked;
2) Electric power supply switch (Customer) turned “OFF”;
3) Pressurised air discharged from the compressor (see pressure gauge on compressor).
4) Reservoir air outlet valve closed.
3.4 ABBREVIATIONS
TAB. 1 lists some abbreviations used in the text of the “instructions for use and maintenance”.
appro
Approximately min Minutes
x.
All information (text, drawings, diagrams, etc.) given here is reserved. No part of this manual may be reproduced and made known
(completely or in part) with any means of reproduction (photocopies, microfilm or other) without the Manufacturer’s authorisation in
writing.
All the trade marks mentioned belong to their respective owners.
NEWTON 4075 – 10
Pressure (7,5 – 10 – 13 )
Power (Hp)
Series:
NEWTON= fixed speed
EDISON= variable speeD
FIG. 2 and 3 show and name the main components of the compressors listed above.
2 1 10 7 8 3
Pianta view
Overhead
9
Fig.2
11 12
Fig.3
Key:
1) Air output
2) Right side intake prefilter
3) Left side intake prefilter
4) Emergency button (not present on inverter series)
5) Control board
6) Connections for electric fan
7) Left front panel handle
8) Right front panel handle
9) Electric fans
10) Top cable entry
11) Left rear panel handle
12) Right rear panel handle
Lato sx
Left side LatoFront
anteriore
Fig.4
NEWTON/
MOD.
EDISON DV
4075/4090
A 2380
B 1220
C 1130
D 156
E 826
F 1780
G 1300
* : without packaging
8 bar
Mod. NEWTON NEWTON EDISON EDISON
4075 4090 4075 DV 4090 DV
Type of drive Direct Direct Direct Direct
400V/50 Hz (230V/60 Hz) transmission transmission transmission transmission
min. 4 - min. 4 - min. 4 - min. 4 -
Delivery pressure bar
max. 11 max. 11 max. 11 max. 11
10 bar
Mod. NEWTON NEWTON EDISON EDISON
4075 4090 4075 DV 4090 DV
Type of drive Direct Direct Direct Direct
400V/50 Hz (230V/60 Hz) transmission transmission transmission transmission
min. 4 - min. 4 - min. 4 - min. 4 -
Delivery pressure bar
max. 11 max. 11 max. 11 max. 11
13 bar
TAB.2
IT IS ABSOLUTELY FORBIDDEN TO USE AIR PIPES AND COUPLINGS THAT ARE NOT SUITABLE
AND/OR THAT DO NOT COMPLY WITH THE REGULATIONS IN FORCE.
The following accessories are available on request for models NEWTON 4075/4090:
- electric motor with high efficiency (IE3);
- heating resistance for the oil reservoir;
- intake valve with proportional regulation;
- heat recovery kit with oil/water heat exchanger;
- three-stage air filter for dusty environments;
- tropicalized version.
The following accessories are available on request for models EDISON 4075/4090 DV:
- electric motor with high efficiency (IE3);
- heating resistance for the oil reservoir;
- heat recovery kit with oil/water heat exchanger;
- three-stage air filter for dusty environments;
- dV/dt filter for electric motor (only 75kW);
- tropicalized version.
Contact POWER SYSTEM s.r.l.if you require further information.
8.1 PACKAGING
The compressor may be supplied alone, with a dryer, with a reservoir, or complete with dryer and reservoir.
The packaging may therefore be of different sizes. The cardboard packaging that covers the compressor and any accessories is marked
on the outside with one or more adhesive labels with the respective information.
ENSURE THAT THE PACKAGING HAS NOT BEEN DAMAGED DURING TRANSPORT.
MAKE A NOTE OF ANY DAMAGE FOUND ON THE DELIVERY NOTE AND SIGN IT STATING
“ACCEPTED WITH RESERVE”.
IF ANY FAULTS ARE FOUND IT IS FORBIDDEN TO USE THE COMPRESSOR. YOU MUST APPLY TO
YOUR DEALER OR TO THE MANUFACTURER FOR TECHNICAL ASSISTANCE.
THE MACHINE PACKAGING MUST BE LIFTED WITH A FORK-LIFT TRUCK (SUITABLE FOR THE
USE), RESPECTING THE INSTRUCTIONS APPLIED ON THE OUTSIDE OF THE PACKAGING.
Proceed as follows:
1) Open and remove the cardboard using a suitable tool
2) Remove any screws securing the compressor to the pallet
3) Get into position on the longest side and insert the forks of the suitable fork-lift truck under the compressor or the reservoir,
until they come out on the opposite side.
4) Carefully lift the load and carry it to the place of use.
5) Lower the load very carefully until it is completely resting on the ground.
6) Extract the forks of the fork-lift truck from under the compressor or reservoir.
Fig.5
LIFT THE COMPRESSOR ONLY BY THE BASE; DO NOT TRY TO LIFT IT BY OTHER PARTS SUCH
AS THE CANOPY, MOTOR, PIPES AND SO ON.
PROTECT THE COMPRESSOR CANOPY WITH A CARDBOARD BOX
2 4
min.3000
3 6
Vista A - A
1
1500
1500
9000
A A
Vista in pianta
Fig.6
Key fig. 6:
1) Auxiliary reservoir condensate drain
2) Auxiliary reservoir (customer)
3) Compressor
4) Air expulsion
5) Main electric switch
6) Air intake
7) Electric power supply duct
8) Pneumatic system connecting pipe
IT IS ABSOLUTELY FORBIDDEN TO USE AIR PIPES AND COUPLINGS THAT ARE NOT
SUITABLE AND/OR DO NOT COMPLY WITH THE REGULATIONS IN FORCE.
THE AIR SENT INTO THE PLACE WHERE THE COMPRESSOR IS INSTALLED MUST BE
CLEAN AND FREE FROM DUST, FUMES AND INFLAMMABLE VAPOURS.
10.2 POSITIONING
The compressor must be positioned in the place of installation and use in conformity with the provisions in the table of
“Technical data”.
TO ENSURE THAT THE AUTHORISED OPERATORS ARE ABLE TO OCCUPY THE WORK PLACES
CONTEMPLATED IN FIG. 11, IT IS OBLIGATORY TO RESPECT THE MINIMUM POSITIONING
MEASUREMENTS GIVEN IN FIG. 6.
After having respected the minimum positioning measurements given in FIG. 6 it is necessary to anchor
the feet to the floor with screws suitable for the purpose.
After having positioned and secured the compressor correctly, proceed as follows:
1) Connect the pipe to the air output fitting on the compressor (FIG. 6 - Ref. 8);
2) Connect the pipe to the air input fitting of the pneumatic system (FIG. 6 - Ref. 8).
IF AN AIR STORAGE TANK OUTSIDE THE COMPRESSOR IS USED, DO NOT FIT CHECK VALVES
BETWEEN THE COMPRESSOR AND THE TANK.
Once the compressor has been positioned, the air outlet conveyors must be raised to improve the ejection of warm air.
• If the ventilation of the premises is insufficient it will be indispensable to install a duct with a section the same size as the radiator
surface.
Fig.7
TO ENSURE AN EFFICIENT EXPULSION OF WARM AIR FROM THE MACHINE THESE CHANNELS
MUST NOT BE MORE THAN 3 METRES LONG; OTHERWISE IT IS NECESSARY TO INSTALL AN
AUXILIARY FAN ON THE OUTLET SIDE (FIG.7).
WARNING: SMOOTH DC RESIDUAL CURRENTS OR CURRENTS WITH LOW RESIDUAL RIPPLE MAY
OCCUR IN THE EVENT OF FAULTS ON FREQUENCY CONVERTERS. TYPE A RESIDUAL CURRENT
PROTECTIVE DEVICES ARE UNABLE TO DETECT THESE SMOOTH DC RESIDUAL CURRENTS.
FURTHERMORE, SUCH SMOOTH DC RESIDUAL CURRENTS MAKE TYPE A DEVICES INCREASINGLY
INSENSITIVE TO AC RESIDUAL CURRENTS AND PULSATING DC RESIDUAL CURRENTS. IF A FAULT
OCCURS, THERE IS THEREFORE NO TRIPPING AND THE DESIRED PROTECTIVE FUNCTION IS NO
LONGER ASSURED.
THE ELECTRIC POWER MAINS TO WHICH THE COMPRESSOR IS CONNECTED MUST SATISFY
THE TECHNICAL CHARACTERISTICS GIVEN IN THE PREVIOUS TABLES AND COMPLY WITH THE
REQUIREMENTS CONTEMPLATED BY THE REGULATIONS IN FORCE IN THE COUNTRY OF USE.
Operating instructions (translation from original IT) POWER SYSTEM s.r.l.
Cod. OQ7_5ARG021EN Via Dell’Emigrante, 11/13 25
Emiss. 28/01/2004 Rev. 8 - Agg. 23/01/2013 36040 Brendola, Vicenza, ITALY
THE ELECTRICAL CONNECTION OF THE COMPRESSOR TO THE ELECTRIC POWER LINE
MUST BE CARRIED OUT BY A QUALIFIED ELECTRICIAN, IN POSSESSION OF THE TECHNICAL
AND PROFESSIONAL SKILLS REQUIRED BY THE REGULATIONS IN FORCE.
FAILURE TO RESPECT THE ABOVE WARNINGS MAY CAUSE IRREPARABLE DAMAGE TO THE
ELECTRICAL EQUIPMENT OF THE COMPRESSOR AND THE CONSEQUENT VOIDING
OF THE GUARANTEE.
13 FIRST START-UP
NEWTON 4075/4090
The first compressor start-up (testing operation) must obligatorily be performed by a specialized technician.*
These compressors are equipped with a safety device as regards the direction of rotation. Running the compressor with the wrong
direction of rotation may damage it seriously and may cause the leakage of oil from the suction valve.
To perform the first start-up, after installation, proceed as follows:
1. Start the compressor by pressing the START button on the control panel.
2. If in this phase the compressor turn in the direction contrary to the arrows, it will stop immediately and the following message will
appear on the display of the card EPS3: “INVERSE ROTATION”.
Then:
a) switch off the power,
b) exchange the connections of two phases of the power supply line,
c) Restore the power.
3. Reset the machine by pressing the “RESET” button and restart the machine.
EDISON 4075/4090 DV
BEFORE THE FIRST STARTING, PLEASE CONSULT THE SPECIFIC INVERTER MANUAL SUPPLIED WITH THE
MACHINE DOCUMENTATION.
1. The first start-up of the screw compressor package (commissioning) must be carried out compulsorily by our authorized service
technician.*
2. The compressor with speed variator are provided with an electronic system for controlling the power absorbed and the
temperature of the motor. However, it is always important to take the greatest care during the first starting in order to avoid
very serious damage to the compressor.
3. It's recommended to start the compressor and stop it in one second. During that time check if the fan motor is rotating in the right
way, otherwise see the following procedures:
a. take off power,
b. exchange two phases in the power line.
c. Take on power and restart the compressor. Visual checking on the right rotation of the fan motor.
ATTENTION:
POWER SYSTEM s.r.l. Operating instructions (translation from original IT)
26 Via Dell’Emigrante, 11/13 Cod. OQ7_5ARG021EN
36040 Brendola, Vicenza, ITALY Emiss. 28/01/2004 Rev. 8 - Agg. 23/01/2013
IN THE EVENT OF MAINTENANCE TO THE ELECTRIC PANEL OR REPLACEMENT OF THE ELECTRIC MOTOR OR OF
THE FAN, AT THE TIME OF RESTARTING IT IS ADVISABLE TO CHECK VISUALLY THE DIRECTION OF ROTATION OF
THE INDIVIDUAL MOTORSI.
Already during this phase it is absolutely indispensable to follow very carefully the SAFETY INFORMATION on the use of
the compressor..
* = If the technician fills up the R.C.R. the possibility of a safer and more efficient operation of compressor unit are increased and
eventual warranty communications and decision will be more prompt.
13.1 Auxiliary protection fuses
EDISON 4075/4090
MODE
DV
Auxiliary fuses F1, F2, F3 (10x38) N° x A Refer to electrical diagram
14 STORAGE
If for various reasons the compressor cannot be installed at the time of delivery and has to remain some time in storage, it must be
placed in a safe environment, with an adequate temperature and degree of humidity, and protected against dust.
THE CUSTOMER (EMPLOYER) MUST TAKE ALL NECESSARY STEPS TO ENSURE THAT HIS
EMPLOYEES CANNOT ACCESS THE PLACE OF INSTALLATION OF THE COMPRESSOR FOR ANY
REASON UNTIL IT HAS BEEN TESTED.
N.B.: A COPY OF THE INSPECTION CERTIFICATE, FULLY COMPILED AND SIGNED, MUST BE
GIVEN TO THE MANUFACTURER’S INSPECTION TECHNICIAN.
REFERENCE DESCRIPTION
“Of the European Parliament and of the Council, of 17 May 2006, concerning
2006/42/EC
machinery and amending directive 95/16CE”.
“Low Voltage Directive - Of the European Parliament and of the Council of 12
2006/95/EC December 2006 on the harmonisation of the laws of Member States relating to
Electrical Equipment designed for use within certain voltage limits”.
“Electromagnetic Compatibility Directive - Of the Council, of 15 December 2004,
2004/108/EC on the approximation of the laws of the Member States relating to Electromagnetic
Compatibility and repealing Directive 89/336/EC”.
“Pressure Equipment Directive” 2009/105/EC - Of the European Parliament and of
2009/105/EC
the Council of 16 September 2009 relating to simple pressure vessels”.
EN 1012-1 : 1997 “Compressors and vacuum pumps. Safety requirements. Compressors”.
EN 60204-1 : 2006 “Fundamental safety standards on the Electrical equipment of machines”.
TAB.5
16 SAFETY
IT IS FORBIDDEN TO TAMPER WITH, EXCLUDE, REMOVE AND/OR REPLACE ANY
SAFETY DEVICE PRESENT IN THE COMPRESSOR.
GENERAL RISK
The compressor must work with the doors closed (five languages).
RISK OF NOISE
During compressor operation the noise may reach dangerous levels for
your hearing.
TAB.6
We inform the authorised operators that, although the manufacturer has taken all the technical and constructive precautions possible to
make the compressor safe, there remain some potential residual risks described in TAB. 7.
RESIDUAL RISK
RISK OF BEING STRUCK BY PRESSURISED AIR AND/OR PIPES
No.1
FREQUENCY OF Low and accidental. There may be exposure if the operator decides of his own accord to perform an
EXPOSURE action that is incorrect, forbidden and not reasonably foreseeable.
EXTENT OF
Slight injuries (normally reversible).
DAMAGE
Respect of the correct procedure for connecting/disconnecting air pipes (see par. 10.3).
STEPS TAKEN
Safety signals (tab. 6).
TAB.7
Depending on the type of manual intervention required, the authorised operators must occupy exclusively the positions indicated in
fig. 9.
Main electric
Interruttore
switchelettrico
C Rear
LATO
generale
(installato a parete)
POSTERIORE
D
Left side
LATO SX
Right side
LATO DX
Front
LATO
ANTERIORE
Overhead view
A
Vista in pianta
Fig.9
ALL To perform all the operations of transporting and handling the machine (see chap. 8 - 9)
To carry out installation and the necessary maintenance operations, after consent from the
ALL
safety manager.
TAB.8
The menus for configuring the unit DNAirMaxi are structured hierarchy level : depending on the
PASSWORD LEVEL attached may be granted access to different functions.
Password entry is made in a special menu, refer to section menu.
The hierarchy of access level is structured as follows:
3.1 User Level: the level of basic access, for the end user, allowing normal operation on the
compressor and a basic customization of the operation thereof; do not need a PASSWORD 3.1.a User Level Encrypted with PASSWORD :is
the level that provides access to the configuration of Autorestart (automatic restart after black-out and restore power) and the PASSWORD
is provided by the manufacturer, after written declaration of the Customer
Indication shortened for access UT
3.2 Customer Center Level : is the level of access for those who must carry out the ordinary and extraordinary maintenance of the compressor,
the functions available, if badly used, may cause malfunction and / or damage to the compressor
3.2.a Customer Center Level with Encrypted PASSWORD : is the level of access that allows you to perform special functions, for which you
need the consent of Manufacturer: functions in changing the counters of the hours of the compressor and RESET the controller unit
Indication shortened for access CA
3.3 Factory Level : is the level of access for the manufacturer of the compressor : the functions available, if badly used can cause a
malfunction and / or damage to the compressor
Menu levels are structured so that the level “ Factory” includes both levels and the level UT CA contains only the level of UT and not inverse.
K7
DY K8
K9
L4 K6
L5 K3 L3 L1 K1 K2
L2
17.4 KEYPAD
K3 – RESET KEY
Allows resetting of the compressor malfunction signals after having eliminated the cause or causes that produced
them. It is effective only on the main screen. On the change parameters menu it allows resetting of the factory
values.
K4 –ESC KEY
Allows you to return to the previous menu or to cancel the modifications in progress
If the display is in stand-by, pressing the key the first time does not produce any function except maximum
lighting of the display light.
K5 – ARROW UP KEY
Allows you to scroll up the menu items and to choose from the options available.
If the display is in stand-by, pressing the key the first time does not produce any function except maximum
lighting of the display light.
K7 – PLUS KEY
Allows you to increase the parameter value when changing it. Also allows you to view and scroll through the
additional information
If the display is in stand-by, pressing the key the first time does not produce any function except maximum
lighting of the display light.
K8 – MINUS KEY
Allows you to decrease the parameter value when changing it.
Also allows you to view and scroll through the additional information
If the display is in stand-by, pressing the key the first time does not produce any function except maximum
lighting of the display light.
POWER SYSTEM s.r.l. Operating instructions (translation from original IT)
34 Via Dell’Emigrante, 11/13 Cod. OQ7_5ARG021EN
36040 Brendola, Vicenza, ITALY Emiss. 28/01/2004 Rev. 8 - Agg. 23/01/2013
K9 – ENTER KEY
Allows you to access the menu displayed and the menu tree. Allows you to confirm the value or the multiple
choice when modifying the parameters.
If the display is in stand-by, pressing the key the first time does not produce any function except maximum
lighting of the display light.
DY – MULTIFUNCTION DISPLAY
Backlit LCD display with 4 lines of twenty characters each. Displays all the
operative conditions of the compressor and allows programming and control
operations.
When the keys K5 or K6 are pressed from the main screen, you can select the desired language immediately
without entering the submenus. The chosen language will become the one used also for all the setting
functions and messages of the controller.
If the compressor is running, Lines 1 and 2 always show the information described above.
Special signals (error messages), additional information or information about the management menu are displayed on LINES 3 and 4.
If LINE 3 shows “ready for start”, the compressor is ready to start.
If the compressor does not start and none of the cases listed above appears, see chapter 9.
When the machine starts the following contactors will be switched on in sequence
LINE > STAR > DELTA
When the display indicates “Load run” the intake valve is open and the machine is running at full load (rated production of
compressed air).
The delivery pressure increases during operation and, once it reaches the predetermined threshold value of the maximum line pressure,
the control system switches the compressor to unload run by closing the intake valve (Unload run). When the pressure falls below the
predetermined minimum threshold value, the intake valve opens again and the machine resumes running at full load.
The compressor indicates “unload run”, the machine never Unload run
stops, remaining always ready to resume air production Time – date
immediately if requested
the compressor does not stop immediately, but begins a series of operations to stop the machine, depending on the operative conditions
at the time of the STOP command.
If at the time of STOP the compressor is running at full load, the control unit switches the machine to “unload run”.
The display DY shows a countdown; at the end of the countdown the motor is Stop in xxx sec.
stopped. Time – date
When the red emergency button PE is pressed, the compressor operation is blocked instantaneously, preventing a condition considered
dangerous.
The emergency button is also intercepted by the controller, which will show the
following message with LED L3 lit EMERGENCY STOP
Compressor block
To reset, release the EMERGENCY button PE and press the RESET key K3
60 seconds after the last key was pressed, the display DY passes to a low level of brightness.
When a key is first pressed (except K1, K2 and K3), the display returns to normal brightness, while pressing the key again produces
the associated function.
ESC BUTTON TO RETURN TO THE MAIN SCREEN FROM ANY SUBMENU Pressure XX,X bar (psi)
Temperature XXX °C(°F)
Ready for start
BUTTONS FOR MOVING IN THE MENU ITEMS: + KEY AND - KEY
10:40 MON 25/05/2011
19.1.1 SUBMENU A
If enabled, indicates the state of the AUTORESTART function (automatic restart after power cut) Autorestart Function
State : OFF
Compressor ID
Station No: 1
Information visible only if the CAN-BUS communication module is installed
the next screen allows you to see the order in which the machines are started
Net sequence
ID 4-3-1-2
Indicates the operating hours of the compressor running at full load Operating time
On load : XXXX hours
Indicates the time remaining till the first service; any other jobs to be performed are also displayed Time to service
cyclically Oil : XXXX hours
ESC BUTTON TO RETURN TO THE MAIN SCREEN FROM ANY SUBMENU Pressure XX,X bar (psi)
Temperature XXX °C(°F)
Ready for start
BUTTONS FOR MOVING IN THE MENU ITEMS: + KEY AND - KEY
10:40 MON 25/05/2011
19.2.1 SUBMENU B
>MAINTENANCE <
…..
Visible only if the CAN-BUS communication module is installed >NETWORK SETTINGS <
….
>PROGRAMMING <
…..
>DIAGNOSTICS <
…..
>PASSWORD <
…..
>INFORMATION <
…..
The choices and settings made in the various menus may be:
CONFIRMED
by pressing key K9 - ENTER
OPERATION
COMPLETED
ABORTED
OPERATION
by pressing key K4 - ESC
ABORTED
Whenever a parameter is modified it is possible to return to the default value set in the factory for the chosen type of compressor by
pressing key K3 - RESET
>MAINTENANCE <
ESC BUTTON TO RETURN TO THE MAIN SCREEN FROM ANY SUBMENU
…..
>Time to service
…..
>Time to service
xxx hours
Operating time.
Total xxx hours
Operating time.
On load xxx hours
ENABLED: with this setting the menu item “Replace components” is visible at all levels the User is therefore authorised to replace the
components and to reset the respective hour counters
The factory setting is “ENABLED”, that is the end User is allowed to perform maintenance.
ATTENTION! When the function is DISABLED the menu item “Replace components” is not longer visible at any level; so, when performing
service it is necessary to:
3. RESET the replaced components with the “Component replacement” menu, made visible by the setting in point 2.
At the end of the described operations the control unit is again protected against the unauthorised RESET of components.
This menu is used for modifying the minimum and maximum service life of the components, so that customisation – which may be performed during
installation – remains within the defined range.
Example:
setting the following parameters:
Minimum service life air filter = 800 hours
Maximum service life air filter = 1200 hours
will mean that customisation of the “air filter service life” can be made only within the defined limits.
Remember that, for alphanumeric values, it is always possible to return to the factory values during the editing phase by pressing the
"RESET" key.
NOTE: the first oil change should be made after the first 100 working hours: this is the only exception to the values in the table supplied.
The time for the first change of the oil filter cannot be modified.
This menu is for modifying the service life of the individual components, used for the counters that manage programmed maintenance.
Customisation is useful in the case of special applications or in particular working conditions.
Examples:
use of synthetic instead of mineral oil: the service life of the “oil” component can be increased
compressor installation in places with a high amount of dust in the environment: the service life of the various filters can be reduced for
more frequent servicing
“Replace component”
XXX excess hours
where XXX represents the number of excess running hours with respect to the programmed service life of the component.
The following situations may occur, corresponding to the possible settings of the Block NO-maintenance function:
DISABLED: the count of the excess hours proceeds indefinitely, always accompanied by the message inviting the user to replace the
component, without ever blocking the machine
ENABLED: when the hour count reaches 30% of excess hours with respect to the service life of the component, it causes blocking of the
compressor; the respective error message is stored in the malfunctions log. Example: service life of the oil filter = 1000 hours; the compressor is
blocked when the counter arrives at 1300 running hours.
Once this function is ENABLED and combined with the “Enable component RESET” function (setting = DISABLED), it allows total
control of the compressor maintenance programme, denying the Customer the possibility to do the maintenance work himself, in the certainty that
they will be performed at the programmed intervals, otherwise the machine will be blocked.
When the compressor is blocked due to exceeding 30% of the service life of a component, it is possible, in cases of extreme necessity, to
perform the “forced start" procedure described in paragraph 9.
Operating instructions (translation from original IT) POWER SYSTEM s.r.l.
Cod. OQ7_5ARG021EN Via Dell’Emigrante, 11/13 43
Emiss. 28/01/2004 Rev. 8 - Agg. 23/01/2013 36040 Brendola, Vicenza, ITALY
6.3.7 RUNNING HOURS
ACCESS: ALWAYS CF
This indicates the compressor running time (total running hours, running hours at full load).
The same information can also be obtained, more rapidly, from the “Additional information menu”
FAMILY APPLICABLE TO
Customised Prototype, modified or customised compressors
The choice entails the automatic configuration of all the parameters at factory values. The following parameters are excluded from auto-
configuration and maintain the values set previously by the User:
Choosing the “Customised” type of compressor allows creation of the parameter configuration of a new machine, inheriting the settings from another
“type of compressor”. It is then possible to customise the desired parameters by entering the setting/configuration menus.
>LANGUAGE
…..
>Select Language:
v ITALIAN
Select Language:
Other languages…
Temperature unit
Unit Cels.
Contrast
Intensity xxx%
Lighting ON
Brightness xxx%
Lighting OFF
Brightness xxx%
>Operating mode
Operating mode
AUTOMATIC
Operating mode
CONTINUOUS
COMPRESS. CONTROL
v LOCAL
COMPRESS. CONTROL
REMOTE
COMPRESS. CONTROL
PROGRAM
COMPRESS. CONTROL
V CONTINUOUS Only if the CAN-BUS
module is installed
COMPRESS. CONTROL
NET PROGRAM
DRYER
disabled
AUTORESTART
ENABLED
Once they have been typed in you can confirm the password with the Enter key K9 or cancel it with the ESC key K4
NOTE: remember that control from the control unit keypad always has priority over any remote and/or program control: this means that, to allow the
remote control and/or program control to be effective, the START button must be pressed, putting the compressor into “Stand-by rem. comm.”
(“Stand-by progr.comm.”). Likewise it is possible to stop the compressor, without any fear of its being restarted remotely and/or by the preset
program, by pressing the STOP key K2.
For example, to enable the operation with remote control (without program) of a single compressor you must:
1) Make modifications to the wiring with the connection of one/two switches
2) Select REMOTE control
3) Select the control mode (ON/OFF, LOAD/UNLOAD, ON/OFF – LOAD/UNLOAD)
4) Make the compressor ready for remote control by pressing the START key K1 on the control unit.
Again for example, to enable the operation by program (without remote control) of a single compressor you must:
1) Select PROGRAM control
2) Select the programming mode to be followed (DAILY / WEEKLY)
3) Program the chosen daily or weekly calendar, first performing RESET if necessary
4) Enable program control by pressing the START key K1 on the control unit.
This menu allows you to configure the state of the digital INPUTS of the electronic control unit. The main usefulness of this menu consists of the
following possibilities:
1. configuration of the REMOTE CONTROL inputs (INPUT 5 = ON/OFF control ;
INPUT 6 – LOAD / UNLOAD control)
2. temporary exclusion of an alarm device for malfunctions of the same (e.g. phase sequence relay): this allows you to avoid
making jumpers on the wiring
Remember that, for alphanumeric values, it is always possible to return to the factory values during the editing phase by pressing the
"RESET" key.
This menu allows you to configure the state of the “free” digital OUTPUTS (not intended to activate machine appliances) of the electronic control
unit. The main usefulness of this menu consists of the possibility of configuring the ALARM output as preferred, according to plant requirements.
The Motor ON output is available only for compressors that do not have a dryer controlled by the control unit; otherwise this output is intended to
control the dryer, so its configuration is not accessible.
Remember that, for alphanumeric values, it is always possible to return to the factory values during the editing phase by pressing the
"RESET" key.
>Pressures
…..
>Operating press.
Max : XXX bar
>Operating press.
Min XXX bar
>Timings
…..
Unload run time
val: XXX min
6.4.18 PRESSURES
ACCESS: STOP CF/RI/AS
Max. operating pressure: this is the network pressure value beyond which the compressor changes to unload; the parameter is accessible also
at User level. The maximum settable value is represented by the “Max rated pressure” parameter. In variable speed compressors, reaching the
maximum pressure is also accompanied by slowing to the minimum allowed speed.
The factory setting coincides with the “Max rated pressure” contemplated for the type of compressor.
Min. operating pressure: this is the network pressure value on reaching which the compressor resumes operation on load or restarts after an
automatic stop; the parameter is accessible also at User level. The maximum settable value is limited by the “Max rated pressure” parameter
and by the “Min difference” value. In variable speed compressors, reaching the minimum pressure is also accompanied by acceleration to the
maximum speed allowed at that pressure.
The factory setting coincides with the “Max rated pressure” contemplated for the type of compressor, decreased by 1 bar (“Min
difference” value).
Max rated pressure: this is the pressure value that limits the “Max operating pressure” at the top; this value is set in the factory, based on the
machine configuration (type of compressor, transmission ratio, safety valves, tank approval pressure, etc.). There are no particular
contraindications in the reduction of the parameter value; however, since the increase of the value causes the compressor to run at higher
operating pressures than it was designed for, a series of modifications must be made to the machine.
Max overpressure: this is the network pressure value on reaching which the compressor is blocked for “Net pressure too high”. This alarm
threshold allows the compressor to be protected against external overpressure, caused by some compressors (the network pressure is measured
downstream from the machine's minimum pressure and check valve). The factory setting contemplates an overpressure of 1.5 bar with
respect to the programmed “Max operating pressure”; this does not apply to compressors with a rated pressure of 15 bar, for which the
"Max overpressure" value is limited to 1 bar. The overpressure alarm does not supply any indication on the state of clogging of the oil
separator filter.
Min difference: this is the minimum difference between the “Max. operating pressure” and the “Min. operating pressure”. When the “Max.
operating pressure” is reduced, also the “Min. operating pressure" is reduced accordingly, respecting the set “Min difference". The factory
setting contemplates a difference of 1 bar. It is recommended not to program lower values, to avoid too frequent changing over between load
and unload operation or, in the case of a variable speed compressor, too narrow a field of adjustment, with consequent operating instability.
Operating instructions (translation from original IT) POWER SYSTEM s.r.l.
Cod. OQ7_5ARG021EN Via Dell’Emigrante, 11/13 51
Emiss. 28/01/2004 Rev. 8 - Agg. 23/01/2013 36040 Brendola, Vicenza, ITALY
6.4.19 TEMPERATURES
ACCESS: STOP RI/AS
Temper. fan ON: in compressors with a thermostat-controlled fan it supplies the temperature value at which the fan is activated. The factory
setting contemplates a value of 80°C for compressors at 8 and 10 bar and 90 °C for compressors at 13 and 15 bar. When the “Temper.
fan ON" is reduced, also the "Temper. fan OFF" is reduced accordingly, respecting a minimum difference of 5°C, useful to preserve the fan
against frequent starts. The modification of the “Temp. fan ON” and that of the “Temp. fan OFF” may be useful for adapting the thermal
conditions of the machine to the environmental conditions in which it has to operate. Hot and very humid climates (e.g. tropical climates)
generally require a rise in the operating pressure, so as to avoid the formation of condensate inside the separator tank; on the other hand this has
a negative effect on the machine performance (more viscous oils must be used) and on the lifetime of the oil (rapid deterioration). For
temperature climates with relatively low humidity it is possible to use a thermostat-controlled regime focussed on lower temperature values, all
to the advantage of the lasting integrity of the components (e.g. hoses, gaskets, etc.).
Temper. fan OFF: in compressors with a thermostat-controlled fan it supplies the temperature value at which the fan is deactivated. The
factory setting contemplates a value of 70°C for compressors at 8 and 10 bar and 80 °C for compressors at 13 and 15 bar. For
suggestions on how to set this parameter, refer to the description of the previous parameter.
Max Temper. alarm: represents the temperature at which the compressor indicates critical working conditions, without the machine being
blocked. The factory setting contemplates a value of 100°C. It is recommended not to modify this parameter.
Max Temper. block: represents the temperature at which the compressor is blocked for too high compression temperature. The factory
setting contemplates a value of 110 °C. It is recommended not to modify this parameter.
Min Temper. alarm: represents the temperature at which the compressor indicates critical working conditions (typically during starting),
without the machine being blocked. The factory setting contemplates a value of 5°C. It is recommended not to modify this parameter.
Min Temper. block: represents the temperature at which the compressor is blocked for low ambient temperature. The factory setting
contemplates a value of 0°C. It is recommended not to modify this parameter. Low ambient temperature is a critical condition for starting
the compressor; in fact, the high viscosity of the oil may cause a low oil flow rate (poor or insufficient lubrication) and high starting torques.
Temperatures below 0°C are absolutely to be avoided as the following events may occur: the oil is separated from the water (condensate) that it
contains, creating a stratification of liquids inside the separator tank; the water, which lies at the bottom of the tank, freezes, forming a plug of
ice in the oil drawing pipe; when the compressor starts the oil is unable to circulate and the air end may seize in just a few seconds’ operation.
When the compressor is blocked for low ambient temperature you can, in a case of extreme necessity, perform the "forced start" procedure
described in paragraph 9. In compressors with a system for preheating the oil, blocking of the machine for low temperature is inhibited, as the
oil in the tank is kept at the required temperature with the electric resistance.
Temperature DRYER OFF: this parameter is present only when the compressor is fitted with a built-in dryer controlled by the electronic
control unit. It represents the temperature value at which the refrigerating compressor of the dryer is deactivated. The factory setting
contemplates a value of 0°C. It is recommended not to modify this parameter.
Temp. diff. DRYER: this parameter is present only when the compressor is fitted with a built-in dryer controlled by the electronic control unit.
It represents the (positive) difference between the refrigerating compressor deactivation temperature (“Temperature DRYER OFF”) and the
activation temperature. The factory setting contemplates a value of 6°C. It is recommended not to modify this parameter. If the setting of
the two parameters for control of the dryer is the factory setting, the refrigerating compressor is activated when the dewpoint temperature
reaches 6°C and is deactivated when it reaches 0°C.
Dewpoint OFFSET: represents the difference between the temperature measured by the sensor and that shown on the display. The factory
setting contemplates a value of 0°C. It is recommended not to modify this parameter.
Bottom speed: represents the speed of the electric motor corresponding to the minimum signal (4 mA) supplied by the control unit to the
analog INPUT of the INVERTER. In correspondence to this signal the INVERTER provides the minimum programmed frequency feeding the
motor. The factory setting is variable according to the type of compressor. It is recommended not to modify this parameter.
Top speed: represents the speed of the electric motor corresponding to the maximum signal (20 mA) supplied by the control unit to the analog
INPUT of the INVERTER. In correspondence to this signal the INVERTER provides the maximum programmed frequency feeding the motor.
The factory setting is variable according to the type of compressor. It is recommended not to modify this parameter.
Min speed: represents the minimum allowed speed of the electric motor in running conditions. Typically this speed is reached when the
pressure approaches “Max operating pressure”, when the compressor works for a certain time above the target pressure (mean between “Max
operating pressure” and “Min operating pressure”, or when the compressor is on unload run or is stopping. The factory setting is variable
according to the type of compressor. It is recommended not to modify this parameter.
Max speed: represents the maximum allowed speed of the electric motor in running conditions. Typically this speed is reached when the
pressure is low, during the first filling of the system. The factory setting is variable according to the type of compressor. It is
recommended not to modify this parameter.
Max speed 13bar: represents the maximum allowed speed of the electric motor in a hypothetical point of operation at 13 bar; this parameter
allows you to define the slope of adjustment of the maximum admissible speed at each operating pressure, in compatibility with the power
available. The factory setting is variable according to the type of compressor. It is recommended not to modify this parameter.
Fan ON speed: this parameter allows you to define at what speed of the main motor the compressor fan should start, in the motor acceleration
phase. The factory setting is variable according to the type of compressor. It is recommended not to modify this parameter.
Suction start speed: this parameter allows you to define at what speed of the main motor the suction regulator should open, in the motor
acceleration phase. The factory setting is variable according to the type of compressor. It is recommended not to modify this parameter.
PWM integration time: this parameter allows you to manage the voltage variation of the inverter command
PRS integration time: this parameter determines the “window” value of the network pressure to be monitored
SPD integration time: this parameter defines the interval of time between two consecutive speed corrections
based on the evaluation of the network pressure. If the pressure is below the target value the speed
correction is positive (the motor is accelerated); instead, if the pressure is above the target value the speed
correction is negative (the motor is decelerated).
The factory setting is 200 msec.
It is recommended not to modify these parameters.
The extent of the speed correction is defined by the following parameter.
SPD integration RPM: this parameter defines the maximum correction (positive or negative) to be made at each “SPD integration time”. Bear
in mind that, for greater fluidity and stability of regulation, the correction is maximum when the pressure is at the extremes of the range of
adjustment (“Max operating pressure” and “Min operating pressure”), while it is nil at the target value (mean between “Max operating pressure”
and “Min operating pressure”). The factory setting is 10 RPM. Usually this parameter is suitable for most applications; in cases where the
compressor appears to be particularly slow in restoring the target pressure it is possible to increase the parameter value; on the contrary, if the
network pressure is unstable and continuously swinging around the target value, it is better to decrease the parameter value. When the
parameter is set at zero the system will no longer be able to make speed corrections in steady operating conditions, and so it will not guarantee a
constant network pressure.
Pressure for max speed: represents the maximum pressure that the compressor can “reach” (during the first filling of the system) with the
motor at "Max speed". The factory setting is 5.5 bar. It is recommended not to modify this parameter.
>Reset programm.
Confirm RESET
programming OK?
>Programming mode
…..
Programming mode
v Daily
Weekly programming
>Daily programming
…..
Every day
Start 1: --
Every day
Stop 1 - -
other days
other cycles
Mon
Start 1: --
Mon
Stop 1 --
other days
other cycles
1) Select the PROGRAM control or, in the case of communicating compressors, NET-PROGRAM
2) Select the programming mode to be followed (DAILY / WEEKLY)
3) Program the chosen daily or weekly calendar, first performing RESET if necessary
4) Enable program control by pressing the START key K1 on the control unit.
5) If there is a remote control device, enable it, to supply consent to the compressor and follow the set program
This menu indicates to the control unit whether, once the PROGRAM control is activated, the machine must follow daily or weekly
programming. The two types of programming are independent.
>DIAGNOSTICS
…..
>Diagnostic test
DIAGNOSTIC TEST
TEST digital INPUT
INPUT 1: state
Emergency OK
Other inputs…
DIAGNOSTIC TEST
TEST OUTPUT
OUTPUT 1 active
Line
Other outputs…..
DIAGNOSTIC TEST
Rot. direction test
Press if OK
Press ESC if WRONG
CAUTION!
When running the test, parts of the machine are live and moving parts are activated (compressor
motor and fan). It is therefore indispensable for operators to take all the necessary precautions when
checking.
> PASSWORD
ENTER PASSWORD
ENTER PASSWORD
0000
Once they have been typed in you can confirm the password with the Enter key K9 or cancel it with the ESC key K4
The access passwords are supplied by the Manufacturer, according to the qualifications of the applicant.
The access password, for Service Centre level or for Authorised Dealer level, is typed in on the menu:
>PASSWORD>Enter password<
The coded password based on the serial number of the electronic control unit, must be typed in on the menu:
>PASSWORD>Enter password>Enter password: 0000
where, in place of the zeroes, you must type in the four alphanumeric characters that make up the password.
Remember that the password “expires”, returning the system to “User level”:
after five minutes without pressing any keys on the control unit
when the power supply to control unit is interrupted
> INFORMATION
Software version
Software version
<<DNAIR MAXI>>
The advantages offered by coordinated management with communication between compressors are:
1. equal sharing of the compressor work load, with consequent synchronisation of maintenance work
2. energy saving, thanks to the “splitting up” of the air flow to be produced and the automatic reduction of the work pressure difference
3. “intelligent” management of the redundant compressors
The control algorithm of compressor rotation (SEQUENCE) offers the best performances when the connected compressors have the same or
comparable performances (comparable compressed air flow rates), while it cannot provide the described advantages if the connected machines
supply very different flows. This does not apply to the combination of fixed speed and variable speed compressors (generally only one unit), where
the variable speed compressor can have substantially different performances from the fixed speed ones. Instead, the control algorithm in
SYNCHRONY allows the connection of compressors of different sizes, albeit with limitations on the network control functions.
20.1 INSTALLATION
This paragraph provides indications for the installation and connection of the network communication boards. At origin, variable speed
compressors are already equipped with the network communication module. It is presumed that all the compressors have been correctly installed
(pneumatic and electrical connection) according to the instructions in the User manual of each machine.
Note: this paragraph IS NOT INTENDED AS A REPLACEMENT of the manual supplied in the pack of CAN-BUS communication
modules, but merely as an extension.
To make the CAN-BUS communication you must have a module for each compressor to be connected in the network.
For network operation it is indispensable for the communicating compressors to be connected with the same storage capacity; if there
is a manifold for the flows of the individual compressors, it must have suitable dimensions so that, in operating conditions, the individual
machines “read” the same system pressure.
CAUTION! Check that the software version installed on the control units is 2.0.1.0 or later. If the software version is prior to the one
indicated, it must be updated: contact the Manufacturer’s Customer Service. To check the software version, look at the screen that appears
as soon as the electric power of the compressor is switched on, or consult the INFORMATION menu.
CAUTION! Switch off the electric power supply to the compressors before installing the CAN-BUS communication modules.
3. tighten the screw 3 x 10 supplied in hole B (figure COM1), inserting the faston as in figure COM3.
The MASTER is defined by the attribution of the network identification number ID #1, the SLAVES by the other numbers ID #2, #3, #4.
The parameters must always be configured on the MASTER, the only machine able to "impose" its configuration on the others.
The MASTER is always recognisable by the blinking L4 Remote / Program LED. Moreover, from the main screen, by pressing +/- it is
possible to view various parameters, including the network identification number ID.
The system developed is of the REAL MULTI-MASTER type and is based on CAN-BUS communication technology. With this technology the
network is not “rigidly” configured but, when necessary (e.g. black-out of the MASTER compressor), the role of MASTER is automatically
transferred from one machine to another, in which case the last one inherits all the parameters for network management. This makes the system very
flexible and reliable.
The pON and pOFF values are calculated by the control system based on the limits pmax e pmin , on the number of compressors available to run on
load, and on the number of compressors already running on load. The higher the number of compressors available, the narrower the “band”
determined by pON and pOFF , achieving “fine” pressure control, to the advantage of energy saving. Within the “band” determined by pmax and
pmin , the “band” determined by pON and pOFF , moves upwards or downwards in order to make the network stable, activate the minimum number
of compressors necessary and minimise the number of compressors running at unload.
ATTENTION! For good operation of the set of compressors it is important for the “Max. operating pressure” and “Min. operating
pressure” values to be set in the same way as on a single compressor; in fact the control system automatically decreases the difference in
operating pressures, based on a set of network parameters.
EXAMPLE:
a network of three compressors has been sized so that only two machines can cope with the need of compressed air; the third machine is a “spare”.
By setting the maximum number of compressors ON at two, you will obtain, at the most, the simultaneous operation of two machines; the third one
is activated only if one of the first two stops. The two active machines are “chosen” in rotation among the ones available, respecting the sequence
rotation time (SEQUENCE mode).
CAUTION! Do not use this setting for normal network operation, but only for the test during installation! In fact, such a short sequence
rotation time entails frequent and harmful starts of the compressors, without allowing them to reach stabilised operating conditions.
The “Sequence rotation time = OFF” mode allows the deactivation of the rotation function; the starting priorities of the compressors present
when the sequence rotation was switched OFF remain valid. This function is particularly useful when you intend to even up the number of working
hours of compressors installed at different times.
EXAMPLE:
a network of two compressors has been created by adding, to a pre-existing compressor (assigned ID #1), another new compressor (assigned ID #2).
It is possible to balance the working times of the two compressors by means of the following procedure:
1. Activate SEQUENCE mode, setting, only for the configuration time, the TEST sequence rotation time of five minutes
2. activate network operation, starting both compressors, until the starting sequence goes to “2-1” (compressor ID #2 = compressor with
starting priority). Stop the compressors.
3. set the sequence rotation time OFF, so as to “freeze” the situation in which ID #2 is started with priority over ID #1
The network must operate with this setting until the working hours of the two compressors are balanced; checking whether balance has been
accomplished must be done manually, periodically consulting the hour counters of the two machines. Once the working hours are the same, return
the sequence rotation time to a definite value (e.g. 24 hours), to reactivate the effective rotation of the starting priorities.
Unlike the t OFF parameter, the t ON value must never be brought close to zero, as the compressor has its own starting inertia (star-delta
switching, delay in opening of the suction regulator) which delays the supply of compressed air with respect to the moment in which the
“pump” command is given. The time t ON must never be lower than the starting delay time (e.g. star-delta time = 4 sec; acceleration time =
2sec do not set a time t ON lower than 6 sec)
If the network has a large storage capacity and is characterised by almost constant consumption, you may consider lengthening the t OFF and t
ON times, thus obtaining a smaller frequency of compressor start and stop cycles. Reaction times that are too long result in network instability.
In the event of problems in configuring and optimising the network, contact the Customer Service.
22 DRYER - DISPLAY
Not available for these compressor size
a) Compressor block due to prolonged failure to carry out one or more maintenance jobs
b) Compressor block due to too low ambient temperature
c) Compressor block due to exceeding the maximum allowed number of starts/hour
There is an emergency procedure that allows the compressor to be started anyway, ignoring the fault, to be performed only in cases of extreme
necessity.
This procedure is called “forced start” and is performed as follows:
holding down the RESET key (K3) and pressing the START key (K1)
The message “FORCED START procedure” appears on the third and fourth line of the display and the L3 led blinks; the compressor starts regularly
and the operation is stored in the fault log; when the RESET key is pressed again, the display returns to showing the normal operation messages.
In any case, the next time the motor stops (either by command or automatic), the compressor will again go into block conditions, requiring a
new forced start procedure, if necessary.
The “forced start” procedure does not work if faults other than the ones mentioned above occur.
MESSAGE COMMENT
High Compressor temp. set temperature parameters exceeded
see table of parameter values
Low Ambient temperature the oil temperature is too low
see table of parameter values
Replace air filter excess hours=hours beyond the predetermined component life;
XXX excess hours see table of parameter values
Replace oil filter excess hours=hours beyond the predetermined component life;
XXX excess hours see table of parameter values
Replace oil excess hours=hours beyond the predetermined component life;
XXX excess hours see table of parameter values
Replace oil separator filter excess hours=hours beyond the predetermined component life;
XXX excess hours see table of parameter values
Replace dryer filter excess hours=hours beyond the predetermined component life;
XXX excess hours see table of parameter values
Replace air filter excess hours=hours beyond the predetermined component life;
Excess clogging X01-8 = closed
The machine status function is accomplished by means of a dry contact relay located on the power board.
To use this switching contact you must operate directly on the terminal board in the electric panel on the terminals C (common) and
NC (normally closed); see fig.A ref.1.
The activation of this relay may influence running status, alarm status or motor rotation.
2 2 1 1
EBDV
EFM
EFV
W1
U1
V1
SC
NA
NC
RA
CD
N
C
T
Fig.A
If present, the heating element (max. 150W) is positioned in the separator tank ( fig.C ref.A) and, when the temperature is below 10°C,
it starts up to heat the oil. The temperature is detected by the oil probe NTC.
The heating element is connected to the “T” and “N” terminals of the electric panel (fig.A ref.2).
SEPARATOR TANK A
Fig.C
ENSURE THAT THE DESIRED “USER PROGRAM” HAS BEEN SET IN THE WORK PARAMETERS
3
(WHICH CAN BE SEEN ON THE DISPLAY).
ENSURE THAT THE AIR PIPES ARE CONNECTED TO THE SYSTEM (CUSTOMER) AND THAT
4
THE AIR OUTLET VALVE IS OPEN.
ENSURE THAT ROUTINE MAINTENANCE WAS REGULARLY CARRIED OUT THE LAST TIME
5
THE COMPRESSOR WAS SWITCHED OFF (SEE CHAP. 25).
6 ENSURE THAT YOU HAVE READ AND UNDERSTOOD ALL PARTS OF THIS MANUAL.
TAB.9
THE AUTHORISED OPERATORS MAY SWITCH ON THE COMPRESSOR ONLY AFTER THEY HAVE
OBLIGATORILY CARRIED OUT THE CHECKS LISTED IN CHAP. 14 – 15 – 16.
25 SWITCHING OFF
BEFORE DISCONNECTING THE AIR PIPES, ENSURE THAT THE AUTOMATIC DISCHARGE PHASE
HAS TAKEN PLACE AND THAT THERE IS NO PRESSURE IN THE PIPES. THERE IS A RESIDUAL
RISK (TAB.7).
Fig. 10
• When the motor has reached steady operating speed: in this phase the air passes through the intake valve (2) and arrives at the
compressor (3).
• In this phase the compressor operates at full speed, compressing the air inside the separator tank (4).
• The compressed air does not come out of the minimum valve (6) until a pressure of 3÷4 bar has been reached (minimum valve
calibration pressure).
• The compressed air compresses the oil inside the separator tank and forces it to flow through the pipes towards the thermostatic
valve (9) and towards the oil radiator (10).
• If the oil temperature is lower than 71°C, the oil coming from the pipe flows directly to the compressor through the thermostatic
valve (9) passing through the filter (11).
• If the oil temperature is higher than 71°C the thermostatic valve (9) closes the pipe duct, making the oil arrive at the compressor
through the radiator (10), passing through the filter (11).
• The oil arrives at the compressor and mixes with the air taken in, creating an air/oil mixture which guarantees the seal and
lubrication of the moving parts of the compressor.
• The air/oil mixture into the separator tank (4) undergoes a centrifugal and then a final separation of the oil by means of the
separator filter (5).
• Then only water comes out of the tank, arrives at the final air cooler (7), passes through the condensate separator (8) and then
goes to the network.
• The light oil residue deposited at the bottom of the separator filter (5) is sent back into the compressor through the oil recovery
pipe.
• When the maximum working pressure set on the electronic board is reached the compressor works without load until the system
pressure reaches the reset value. If this no-load operating time is long, due to low or ceased consumption, the compressor stops in
stand-by mode.
N.B. In particularly harsh environmental conditions, the maintenance intervals must be halved. After 8000 working hours it is
necessary to contact the POWER SYSTEM s.r.l. technical service
A mineral oil for hydraulic purposes must be used, or for screw compressors with oil injection, with the addition of oxidation
inhibitors, and having anti-foam and anti-wear properties.
The degree of viscosity must comply with the following table:
Use only non toxic oils when there is the risk of inhaling the air distributed.
When supplied by Power System, the compressor is filled with POWERFLUID 2000 oil.
This lubricant is formulated to the highest quality standards and is factory authorized, tested and approved for use in rotary screw
compressors.
POWER SYSTEM s.r.l. lubricants are available through your authorized compressor distributor.
THE IMPROPER USE OF LUBRICANT MAY CAUSE DAMAGE TO THE SYSTEM. IT IS ABSOLUTELY
FORBIDDEN TO MIX LUBRICANTS OF A DIFFERENT TYPE AND BRAND TOGETHER.
INADEQUATE MAINTENANCE WITH THE USE OF SYNTHETIC LUBRICANTS MAY DAMAGE THE
SYSTEM. THE OIL FILTER AND THE CARTRIDGE OF THE SEPARATOR MUST BE CHANGED
REGULARLY TO GUARANTEE MAXIMUM PROTECTION AND EFFICIENCY OF THE
COMPRESSOR.
CHECK THE PRESENCE OF CONDENSATE IN THE SEPARATOR TANK EVERY 500 WORKING
HOURS.
By special maintenance we mean all the activities aimed at maintaining the conditions of use and operation of the
equipment with various types of intervention performed exclusively by the manufacturer’s technician.
ALWAYS CHECK THE OIL LEVEL WITH THE MACHINE SWITCHED OFF.
Procedure to be followed for changing the oil and the oil filter:
1. Stop the machine with the stop pushbutton on the electronic board.
2. Switch off the power: turn the isolating switch to “0” position and block it with the padlock.
3. Ensure that there is no pressurized air or oil in the oil reservoir.
AIR AND OIL UNDER HIGH PRESSURE CAN CAUSE SERIOUS INJURY. SHUT DOWN THE
COMPRESSOR AND RELIEVE THE SYSTEM OF ALL PRESSURE BEFORE REMOVING VALVES,
CAPS, PLUGS, FITTINGS, BOLTS AND FILTERS.
4. Always completely empty the circuit. (It is best to do this operation when the oil is still hot since it is more fluid and will drain
better).
5. To drain the circuit just unscrew the cap and turn on the tap
6. To drain the circuit use one of the following methods:
a) If the unit is not sitting at a sufficient height to use the oil drainage line, a manual, electric or pneumatic pump must be used to
drain the oil from the tank through the drainage valve.
b) If the unit is sitting at a height where it is possible to use the drainage pipe, empty the tank through the drainage valve using a
suitable container or pit.
c) If the drained oil and/or the oil filter cartridges are contaminated with dirt, clean the whole circuit: tank, oil cooler, thermostatic
valve and pipes. Check whether there is a build-up of dirt or presence of scale in the filter cartridge of the separator.
7. Clean off any dirt before removing the oil cap.
USED OIL MUST BE DISPOSED OF IN CONFORMITY WITH THE LOCAL REGULATIONS IN FORCE.
8. Fill the tank to the required level (fig. 11 green zone). When the compressor starts the level will fall because the oil will fill the
parts of the circuit; keep the oil level above the minimum mark.
9. During idling or after stopping, some oil will return to the tank and the oil level may increase as a result.
DO NOT DRAIN ANY OIL TO ADJUST THE LEVEL. The next time it starts, the oil will fill the system again and the level will
indicate the using conditions.
DO NOT OVERFILL OR THERE WILL BE OIL LEAKS (in the event of excess oil, the indicator in fig. 11 will be in the yellow
zone).
10. Use only CLEAN containers and funnels so that no dirt gets into the tank. Store the oil in a clean place. Changing the oil
incorrectly does not offer any advantage.
11. Start the machine, let it run under load for about 5 minutes, check the oil level and ensure that there are no leaks.
Fig.11
BEFORE REMOVING THE OIL CAP AND/OR THE OIL FILTER, STOP THE COMPRESSOR AND
ENSURE THAT IT IS COMPLETELY DEPRESSURIZED. IF IT IS NOT COMPLETELY
DEPRESSURIZED IT MAY BE VERY DANGEROUS AS IT CAN CAUSE EVEN MORTAL INJURY..
This must be done when the oil level visible in the plastic pipe is below the recommended oil level.
N.B. The value must be read with the unit is stop.
BE SURE THE UNIT IS COMPLETELY OFF AND THAT NO AIR PRESSURE IS IN THE OIL
RESERVOIR. ADD OIL AS REQUIRED TO RETURN THE OIL LEVEL TO THE CORRECT POSITION.
TOP UP TO THE REQUIRED LEVEL. DO NOT OVERFILL.
Repeated topping up with oil between one change and the next indicates excessive oil consumption; it is recommended to have the
compressor checked by a skilled technician to remove the cause.
AIR AND OIL UNDER HIGH PRESSURE CAN CAUSE SERIOUS INJURY. SHUT DOWN THE
COMPRESSOR AND RELIEVE THE SYSTEM OF ALL PRESSURE BEFORE REMOVING VALVES,
CAPS, PLUGS, FITTINGS, BOLTS AND FILTERS.
The oil filter fitted on the compressors contains a bypass valve. If the cartridge is particularly clogged, the valve prevents oil
circulation being blocked, that is it still guarantees the circulation of oil on the screw.
4) Remove the retaining screws of the separator tank cover. Lift the separator tank cover
5) Change the cartridge. When changing the cartridge, the gasket is also changed. Remove any materials adhering to the cover or to
the tank.
6) Lower the new cartridge into the tank and put the gasket in position.
7) Set top plate on separator housing flange; install and tighten all cap screws.
8) Start the machine, let it run under load for at least 10 minutes and check that there are no oil leaks.
9) Dispose of the old filter in conformity with the regulations in force.
G
3. Unscrew the special nut of the filter hose and unscrew the
retaining nut of the air filter cartridge (G). Fig.13
4. Remove the air filter cartridge
5. Clean the filter with a jet of air, working from inside to outside; do not use water or solvents. Alternatively, fit a new
filter
6. Fit the filter and close the nut (ref. G).
7. If the cartridge has to be changed, dispose of the old filter in conformity with the local regulations in force.
IF THE ELECTRIC MOTOR HAS BEEN CHANGED, WHEN STARTING PRESS “START” FOR A FEW
MOMENTS (JUST ENOUGH TO SEE THE COOLING FAN TURNING) AND CHECK THAT IT TURNS IN
THE DIRECTION INDICATED BY THE STICKER APPLIED ON THE MOTOR. IF IT IS TURNING IN
THE WRONG DIRECTION, SWITCH OFF THE POWER AND INVERT THE CONNECTIONS OF TWO
PHASES OF THE MOTOR POWER SUPPLY.
IF THE ELECTRIC FAN HAS BEEN CHANGED, WHEN STARTING PRESS “START” FOR A FEW
MOMENTS (JUST ENOUGH TO SEE IT TURNING) AND CHECK THAT IT TURNS IN THE DIRECTION
INDICATED BY THE STICKER APPLIED ON THE STRUCTURE. IF IT IS TURNING IN THE WRONG
DIRECTION, SWITCH OFF THE POWER AND INVERT THE CONNECTIONS OF TWO PHASES OF
THE FAN POWER SUPPLY.
DURING ROTATION THE MACHINES CAN CAUSE SEVERE DAMAGE OR DEATH OF PERSONNEL.
DO NOT ACTIVATE THE MACHINE WITHOUT THE GUARD. ALL THE SCREWS AND NUTS MUST
BE ADEQUATELY SECURED.
Alignment -The coupling is permanently aligned by the flanges on the compressor and motor.
Grani di bloccaggio
Set screws
Fig. 15
Fig.15A
34 GENERAL WARNINGS
34.1 ORDERING PROCEDURE
34.2 DEMOLITION
When demolishing the compressor, abide scrupulously by the regulations in force in the country concerned regarding the protection of
the environment.
Distributor Customer
INSTALLATION
1 Location (compressors room, department, outside, etc.. ..)
2 Atmosphere (dirty, dusty, humid, closed, etc. ..)
3 Ambient temperature with unit working (°C)
4 Kind of installation (compressor, receiver, dryer, filters, etc…)
SETTING
5 Check oil level OK NO OK
6 Check tightening of all electric components OK NO OK
7 Check power feed:
a) check voltage ± 10% (Volt) instrument
b) check voltage auxiliary circuit ± 10% (Volt) instrument
8 Check correct direction of rotation: OK NO OK
a) check load current (Amp)
(verify with test certificate)
b) check overloads protection adjustment (motor – fan)
9 Check right operation of electronic panel OK NO OK
10 Operate the compressor at max temperature and check after 30 seconds:
a) Check air leaks YES NO
b) Check oil leaks YES NO
c) Check regular return on oil recovery of separator YES NO
d) Check load and no load pressure (bar Load) (bar no-Load)
e) Check oil temperature (°C) At ambient temperature (°C)
f) Check oil level YES NO
Customer
Technician Signature
Signature
Working Air Filter Oil Filter Separator Oil filling Couplings Check electrical absorption Date Signature
hours cartridge Cartridge Cartridge Belts
load un-load Measure
C R R Check R C T R C T R instrument
l e e e h o e h e e
e p p Press. p e p p e n p
a l l l c p l c s l
n a a Diff. a k i a k i a
i c c c n c o c
n e e e g e n e
g m m m m i m
e e e u e n e
n n n p n g n
t t t t t
OK KO OK KO
value value
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO
OK KO OK KO