Professional Documents
Culture Documents
Sepam Range Self-Powering Protection
Sepam Range Self-Powering Protection
and control
Sepam range
Sepam 100 LA
Self-powering protection
contents page
presentation 2
protection 4
functional and connection 6
schemes
other connection schemes 7
connection 8
characteristics 9
installation 10
commissioning 11
ordering information 12
advantages
■ protection against low-value phase and
earth faults,
■ self-powering: Sepam 100 LA is powered
by the current sensors,
■ may be put in disabled status (inactive
output) via an external inhibition contact,
■ tripping by a low power-consuming
«MITOP» trip unit (1).
■ high level of immunity to electromagnetic
disturbances.
Sepam 100 LA.
(1)
MITOP: Merlin Gerin circuit breakers may be
equipped with this type of trip unit upon request.
2
description
The front face of Sepam 100 LA contains
the instruments needed for the phase and CT 1A
earth protection settings.
CT 5A
Each set of microswitches, marked K1, K2, K1
K3 and K4 and associated potentiometer CT5A CT1A 1 0
12 60
P1, P2, P3, P4 should be positioned
10,8 54
according to the desired setting. 9,6 48
8,4 42
7,2 36
6 30
K P1
x1 x1,3
1 0 I> I> = K1 x P1
K2 In N
t (ms) 1 0
1350
1100
N
850
Setting example:
600 CT = 100/5, K1 = 12, P1 = 1.2 and N = 3.
350 1
microswitch set to 0. 100 using the formula: I> = 12 x 1.2
2
In 3
3 I>
P2 = 4.8, I> = 480A primary
0 +250 ms 6 In
K 8
1 0
K3 10
CT5A CT1A 1 0 12
- -
- - The microswitch is fitted with a
0,4 0,8 potentiometer that the user turns to adjust
0,2 0,4 the setting.
0,1 0,2
microswitch set to 1. 0,06 0,12
setting increases as
P3
x1 x2 potentiometer is turned
Io>
)
) Io>= K3 x P3 to right
K4 In
t (ms) 1 0 Potentiometer turned fully
1350
1100
to left = minimum setting,
850 to right = maximum setting.
600
350
100
P4
0 +250 ms
sepam 100
S01 LA
3
protection
earth protection
setting range set point time delay
0.12 to 1.6 In on 1A CT 100 to 1600 ms
0.06 to 0.8 In on 5A CT 100 to 1600 ms
accuracy ± 5% ± 10%
Setting includes:
(1)
■ positioning microswitch K3 ,
■ fine tuning using the potentiometer:
min to max.
4
time delays
100 to 1600 ms with definite time.
Setting includes:
■ positioning microswitch K2 (phase protection),
K4 (earth protection) (1),
■ fine tuning using the potentiometer:
0 to + 250 ms.
current sensors
The current transformers should be sized
so as not to saturate at the setting, taking
into consideration Sepam 100 LA's input
impedances:
■ phase input: 0.02 Ω,
■ earth input: 0.08 Ω,
(i.e. 0.1 Ω for phase + earth protection).
In practice, a 2.5 VA, 10P15, 5A secondary
type transformer is appropriate.
The current transformer windings should be
coiled round a separate magnetic coil and
must not supply power to any circuits other
than the Sepam 100 LA's circuit.
(1)
If all the microswitches are set to 0,
the protection will be inhibited.
Only one microswitch in the group should be
set to 1.
The potentiometer associated to the microswitch
allows a tunning of the setting value:
minimum setting (+0ms): turned fully to left,
maximum setting (+250ms): turned fully to right.
5
functional and connection scheme
ACE 955
P1 S1 3 21
1A ECM 50
4 20
51
P2 S2 5 18 50N
6 17 51N
7 15
8 14
2A
DPC
2 9 12
30 A
1 10 11 2A
blue (-) 8
circuit breaker (1)
MITOP trip unit 7
red (+)
Sepam 1000 or 5
Sepam 2000
watchdog contact 4
(1)
the linking between Sepam 100 LA
and the MITOP mustn’t be bigger than 5 Ω.
6
other connection schemes
2A
DPC
3 phase CT arrangement. 30 A
2A
9 12 2A
10 11 DPC
30 A
2A
P1 S1 2
1
P2 S2
7
connection
Sepam 100 LA 1A
A 21
1 A 21-pin CCA 621 connector, screw
terminal cabling with cables 0.6 to 2.5 mm2 A 20 phase 1 current
max., each terminal capable of receiving 21 19
two 1.5 mm2 cables. 20 18
19 17 phase 2 current
18
16
17
15
14 phase 3 current
16
13
15
12
14
11 residual current
13
10
12
9
11
8
10
7 MITOP
9
6
8
5
7 4 inhibition
6 3
5 2
4 1
3
earthing terminal
on right side face. Rear view.
Terminal identification 1 A 4
Each terminal is identified by 3 characters.
board slot number
connector identification
letter
connector terminal number
(1 to 21)
interposing ring CT
phase 1 current (1)
N.B.
The ACE 953 interposing ring CT does not have
a residual current circuit. ACE 955/ACE 951 interposing ring CT connection scheme.
8
characteristics
environmental characteristics
climatic
operation IEC 68-2 -5°C to 55°C
storage IEC 68-2 -25°C to 70°C
damp heat IEC 68-2 95% to 40°C
mechanical
degree of protection IEC 529 IP 51 front face
vibrations IEC 255-21-1 class I
shocks IEC 255-21-2 class I
fire NFC 20455 glow wire
electromagnetic
radiation IEC 255-22-3 class x 30 V/m
electrostatic discharge IEC 255-22-2 class III
electrical
1.2/50 µs impulse wave withstand IEC 255-4 (1) 5 kV
damped 1 MHz wave IEC 255-22-1 class III
5 ns fast transients IEC 255-22-4 class IV
energetic transients IEC 801-5 (2)
(1)
printed in 1976 and amended in 1979.
(2)
pending.
“ ” marking on our product guarantees their conformity to European directives.
9
installation
86 max.
20 175
88 84 max.
e = 3 mm max
80 100
115
240 240
weight 1 Kg weight 1.5 Kg
Connection
By 6.35 mm2 clip, max. wire cross-section
2.5 mm2.
10
commissioning
11
Ordering information
(1)
Sepam 100 LA does not include supply of the MITOP trip unit which should be provided with
the circuit breaker.
(2)
With Sepam 100 LA, it is mandatory to choose the type of protection
and the type of current transformer secondary.
Schneider Electric SA postal address As standards, specifications and designs change This document has been
F - 38050 Grenoble cedex 9 from time to time, please ask for confirmation printed on ecological paper.
tel : 33 4 76 57 60 60 of the information given in this publication.
telex : merge 320 842 F