Professional Documents
Culture Documents
Distance Protection Basic Principles PDF
Distance Protection Basic Principles PDF
APPAZENT IMPEDANCE
Sage Undeneach = fastr x100%.
ez
whee Ze = REACH SETTING
Zp + EFFEMVE LEACH
UNCOMPENSATED GARTH FAULT RELAY.
Zu
Rear. 7
Impepance SEEN = [1+ 2ro- Bede]
amu
RELAY.
IMPEDANCE SEEN > xZu ali
Limit of Operetion is when Tepedance Seen> Zy
This cecvrs when =x
TE
-. EFFECTIVE REACH = = Zo
pee] Kw
Boge Vrdeweah > 21> BE. es KE
aUNDERREACHING DUE To BUSBAR INFEED setweEn
ET EEO BUSBAR INFEED BETWEEN
RELAY AND FaAUCT
Ta Za Ta+Ig Ze
‘al
RELAY LOCATION
Nea * TaZa + (La+Tg)Zg
Iq + Ia
Ze * In+2Zg + Te 2g xs
Zh Ta
um
RELAY WITH SETING Za+Zg wir UNOERREACH WITH
INFEED.
RELAY WITH SETTING ZaeZg eZ .Zg war MEASURE ConescTY
ta
WITH INFEED PRESENT BUT IF INFEED 1S REMOVED THE
RELAY WILL OVERSEACH .
MAnMuM ALLOWABLE SETTING DICTATED BY :-
1. LOAD IMPEDANCE
2. NON OPERATION FoR REVERSE EARTH FAULTS.WHAT RELAY REACH SETTING
To ENSURE FAULT AT F
OF OPELATION 7
1S REQUIRED
\S AT BouNDAgY
IMPEDANCE SEEN Fok FACT ATF
= Zg+ Oqele. Ze
a
Limih of Operothon is when Impedarce Seen = Reach Sethag
~.REaCH SETING CEQuiked
> Zg+ Leelp. 2.
ae~
~
OVER -REACH
IMPEDANCE SEEN < APPARENT IMPEDANCE
age Overteach = Ze- Fe ~r100F
Fe
whee Ze = REACH SETTING
Ze > EFFECTIVE REACH.
OVER-REACHING DUE To PAAALLEL LINE OUT OF SERVICE
teay.
| Zu, tun, to
x (Zu1,a, Be),
> Deo . Zon Also Tei Zer> Teo
Zoo
Relay Voltage = Cl+x) (2 2c 21j +Teo%ie) - To tom
=I « + - Det
cof \+x) (22+ 20) By
Relay Cunet = Ig+ Too { #5 = 3Te0+ Teof HEE]
> Toof aoe ey
2
Impedance Measued = zat Cas) - Fetch
React, Setting = Bry = Impedance Measuied at selon valance -
Bont
1 Dota hey
EFretrive Pee = (lex) Zy
PELCENTAGE oveldeteh > Zr-tg - (H2)21-hiooZ: x-l60h
zh Ze —For TWprcal 4ookeV Line
Zoom + O-& Afiem.
Zep = O-UAN/ tm
Bo + O-bR/km.
2. ome Zou > _O4™
Zeof{2rtheoy orb fo.su+ oney
= O-l6d.
Fage Ovenench > lo-4f.
ZONE | REACH SOMETIMES EDUCED Flom
O82, + 065 2%, To PREVENT ovediFichyG
n.6.
Mutua) Compersathen cannot help.
Probability of fault with lie our is Small.Close-up Ground Faults Can Operate
Phase Elements
Zone -1
4 |
A-E fault
Note : Source impedance is zero
PH - G Elements not Ideal for
PH - PH - G Fault
B-C-E resistive fault
Note : Source impedance is zeroBiased Neutral Current Level
Detectors
Ground fault High set neutral
40 comparators enabled current detector
!
my (Slope = 0,76)
Ty (Amps)
N Low set neutral
1 current detector
Phase fault
(Slope = 0,1) comparators enabled
041 1 10 34 100
Greatest | Phase difference current | +1, (Amps)FAULT RESISTANCE
m™ Main causes :- ARC RESISTANCE.
TOWER FOOTING RESISTANCE.
MIB-SPAN FAULTS - VEGETATION
ARE RESISTANCE
Various formulae :-
Van Warsingten S250
Reve * re M/Hot ane
Arrabelou Rane + 352 A/H. ot are
_ T
Ackermann
Race + 3000 BiH. ore
zr
At lew current values ot Rage ftom formulae abe different
At cusents > 3000A the values ate similar
Pr Ios 4000R , Rage tanges from 0-062 R+e 0-092
Fee this case Remar is Small compated with line
wmpedance
TowER FooTING RESISTANCE
Any value from fractions +e hundteds of ohms
Reduced by counterpeises under towers and earth wiies,
MIS SPAN FAULTS
Caused by vegetation growth en line breaking and telling
Any value up +o loo's of ohms.
Distance protection cannet be selad on to operate. 0g. Zpaucrriss
on IA selays with Zisman t 63-Sohms.
~
Directional Garth fault compariion oF phase Compemion sheld be used.DEF Features (Options)
™@ Time delayed tripping
® Instantaneous high set tripping if no zone 1
ground distance
@ Aided tripping
™ Choice of directignal measurement by
comparison of:
@ V, against |,
@ |, against |,
@ V, against |,
© Vy +I, against |,
™ Magnetising inrush detector
Transmission models only
Directional Earth Fault Protection
si
™ Covers high resistance faults which are undetectable with
distance protection alone
= Time delayed back up and/or signal-aided fast DEF tripping
is possible
™ To cover all applications a choice of directional element
polarizing quantity is idealZero Sequence Voltage
Polarising of DEF
Optional Ig Polarising of DEF
Vo = small since
Zgo totalDiagoresy
ourfer
FIG.L- Bleck DAG@Am ee A TYPICAL Dunc Peareed$ DEF
DIRETIANAL ELEMENTLFZP 11x SERIES R-S9LIC
SERVICE MANUAL CHAPTER 2
Page 313
Operating
time (s)
Current (Multiples of Is)
Figure 7-17 IEC Characteristics (Time Multiplier = 1)LFZP 11x SERIES R-S9LIC
SERVICE MANUAL CHAPTER 2
Page 314
100
10
Operating
time (s)
05
1 5 10 50 100
Current (Multiples of Is)
Figure 7-18 American Characteristics (Time Mulitplier = 1)LFZP 11x R-S911C
SERVICE MANUAL CHAPTER 1
Page 93,
~
MAIN BUS
~
%
‘oPTIMHO
@ STANDBY RELAY
~
FEEDER 1 FEEDER 2
~
Figure 28 Typical Double Bus Installation with By-pass FacilitiesPOWER SWING BLOCKING
1.0 INTRODUCTION
Power swings are variations in power flow which can be caused by sudden
removal of faults, loss of synchronism between the ends of the power system,
or changes in direction of power flow. Such disturbances can cause
generators on the system to accelerate or decelerate which in turn leads to
Power swinging.
The result of a power swing may cause the impedance presented to a distance
relay to move away from the normal load area and into the relay character-
istic. In the case of a transient power swing it 1s obviously important
that the distance relay should not trip.
In the case of a loss of synchronism it will be necessary to split the
‘system at the mst convenient point. Most of the distance relays affected
should not trip except those at the required disconnection point. Therefore,
some method is required to prevent a distance relay from tripping during
power swings. This is achteved by means of a power swing blocking relay
which inhibits distance relay operation in pre-selected zones.
2.0 IMPEDANCE CHARACTERISTIC OF A POWER SWING
A power swing will normally start from a load condition. If we consider the
emf's at each end of the system as E, and E, (see fig 1), then a power swing
can be simulated by considering the fotation of one voltage with respect to
‘the other.
The impedance measured at one end of the line will be given by the ratio of
V,/I. The locus of this impedance as E, rotates relative to E, represents
the ratio of source emf's at each end of the system and may be represented
by a series of circular loci{ with centres on the extension of the total
system impedance. The position of the centre of the circle and radius will
depend on the ratio of E, to Ey.
Typical power swing loci{ are shown in fig 2.
The angle @ subtended on the locus from the outer points of the total system
impedance A' and 8! represents the angle between source emf's E, and £3. The
general expression for Z = Y,/I is given by
(n= cos @) = § sin ®
Zo= Ugg + 2, + Legit ~
SATU TTS (n= cos 0)? + sin? @
SA
(n = cos 8) - j sin @
z,
a -
Mr" Tees aimeePage 2
where :
2. eA
&
and Z; = total system impedance = Ze, + Z + Zoq
When E, = Eg, the locus of the pover swing becomes 2 straight Tine bisecting
the total s¥stem impedance.
when E, > Ege n> le
Distance fron B' to centre of circle = _“T
Radius of cirele = 2
nee]
When E, < Eg, n