VLT® AutomationDrive
Selection Guide
The modular VLT® AutomationDrive FC 300
VLT® AutomationDrive allows for mass production of highly customised drives
2
7
8 3
7 5
3
5 10
8
9
10 11
2
9 Display options 10 24 V Built-in Smart Logic Controller
Danfoss Drives’ removable Local The 24 V supply keeps the VLT® The Smart Logic Controller is a
Control Panel is now available AutomationDrive logic “alive” simple but clever way to keep your
in 28 languages. Six of these are when the AC mains is removed. drive, motor and application
built-in (including Chinese), two working together.
of the languages can be changed Safety
by the user. The info button makes The VLT® AutomationDrive FC The controller monitors a specified
the printed manual virtually re- 302 comes standard with safe event. When an event occurs, the
dundant. stop functionality. The solution is controller triggers a specified act
approved by authorities for cate- and starts monitoring the next
Alternatively the drive can be gory 3 installations in accordance event continuing for up to 20
commissioned via the built-in with EN 954-1 and SIL2/IEC 61508. steps before returning to step one.
USB/RS485 connection or a field-
bus from the VLT® set-up software This feature prevents the drive
MCT 10. from starting unintendly.
Enhanced safety features are
The Automatic Motor Adaptation, available as options.
Quick Set-Up menu and large
graphic display make commis- 11 Mains switch option
sioning and operation a breeze. This switch interrupts the mains
Your choice of numerical display, supply and has a free useable
Danfoss Drives received the Frost & Sullivan
graphical display or blind cover. auxiliary contact. Award for Product Innovation 2006 for the unique
VLT® AutomationDrive series.
Total separation between cooling air Forced convection cooling Cold plate cooling
and electronics allows for solutions A fan blows cold air through the cool- External cooling is possible through
where heat is removed from outside ing ribs of the aluminium base. the back side of the aluminium base.
of the cabinets. The channel is easily cleaned without
touching the electronics.
With VLT® AutomationDrive, a flanged
heat sink kit is available for mounting
the drive in the backplate of a cabinet.
3
Just one drive series to run an entire production line
VLT® AutomationDrive
FC 302 runs permanent
magnet motors
The standard version covers a wide You will find a comparison between
range of functions such as PLC the versions on page 13 in this book- All supply voltages
functionality, automatic fine-tuning let. Both versions are equipped with The VLT® AutomationDrive series
of motor control and self-analysis of user friendly control panels, spring covers the power range from 0.25 to
performance. loaded cage clamps and housing 1200 kW. It supports supply voltages
designs. in the ranges 200, 380 – 480/500 V,
The VLT® AutomationDrive FC 301 525 – 600 V and 690 V. Also, operation
holds many excellent features like Nearly all options are available for in special network grids such as IT Net
VVC+ vector control, Automatic Motor both performance levels. is possible.
Adaptation, PID controller and/or
RS485-/USB connection.
The fieldbus option ready to plug in beneath the The VLT® AutomationDrive is controlled locally Large selection of encoder interfaces:
front panel. It can be turned upside down if you via a control panel. This is plugged in directly or HTL/TTL incremental, with Resolver or SinCos
prefer to have the cable on top. connected via a cable. HIPERFACE, SSI or EnDat absolute encoders.
4
One wire safety
Hazardous situations are avoided without Terminal 37 can be used as “safe coast” for safe stop Security-related elements can be switched
interrupting the mains supply. – the stop function satisfies stop category 0 EN 60204-1. directly to the FC 300.
5
Perfect for all conditions
6
High reliability even in harsh environments
FC 300 devices in IP55/IP66 enclosure. Also here, all components such as EMC
filter and DC-DC chokes are integrated. The cables enter drop-safe from the
bottom side.
The VLT®
AutomationDrive is
also available with
a mains switch
All VLT® AutomationDrive versions withstand the harsh cleaning agents option. This switch
have manganese phosphor rear in the food & beverage industry. interrupts the
mains supply and
bodies. The back of IP 66 versions is has a free useable
dip-coated with epoxy or polyester Cooling air is kept outside the device auxiliary contact.“
spray finish (60-100 μm). The cover is to prevent any pollution of the
powder coated (80-100 μm). electronics. The surfaces are smooth
and can easily be cleaned.
IP 66 enclosed drives are suitable for An external
watertight USB
installation outdoor and in washdown Furthermore, all components such as plug connected to
areas. EMC filters for Class A1/B1 according the control card
inside IP 55/66
to EN 55011, as well as the DC coils, enclosures makes
The silicone gasket is tested with are protected inside the drive. USB access easy.
different detergents so the drives
Special mounting accessories are available to reduce Spring-loaded connectors save considerable time and Built-in circuit chokes reduce the impact on the supply
costs and time for retrofitting. costs, both in reinstallation and service. network and increase the lifetime of the drive.
7
Built-in Smart Logic Controller
Smart Logic
The Smart Logic Controller is a simple flow, time, load, frequency, voltage
but clever way to keep your drive, and other parameters combined with
motor and application working the operators “>”, “<”, “=”, “and” and
together. “or” forms logical statements.
You can analyse and operate the Smart Logic Controller To disconnect wires, simply unplug The VLT® AutomationDrive is controlled locally via a
with the graphical LCP. the terminal blocks. control panel. This is plugged in directly or connected via
a cable to the robust Sub-D terminal – also while the
drive is running.
8
Easy retrofit with VLT® AutomationDrive
Fast conversion
Sophisticated conversion kits reduce
downtime, modernising existing
installations.
The fan speed is regulated according to the temperature To disconnect wires, simply unplug the terminal blocks. With the terminal adapter it is possible to re-use existing
of the drive and can easily be removed and remounted wiring from VLT® 3000 or VLT® 5000.
for cleaning.
9
User friendly control panel
Three panel options: graphical, numerical, blind cover. The VLT® AutomationDrive is controlled locally via a The VLT® AutomationDrive can be remote commissioned
control panel. This is plugged in directly or connected and monitored via a USB cable or fieldbus communica-
via a cable. tion. Special software is available: Wizards, Data transfer
tool, VLT® Set-up Software MCT 10, and Language
changer.
10
VLT® Motion Control Tool MCT 10
Explorer-like interface
The MCT 10 software features an
explorer-like interface design and
functionality to ease both use and
learning of the facilities.
Basic
• Scope & Graph
• Alarm history in saved projects
• MCO 305 support
• Graphical Smart Logic Controller
• Graphical Timebased Actions,
Preventive Maintenance and
Basic Cascade Controller
(FC 102/FC 202 only)
• Multiple fieldbus support MCT 10 has a Windows-like design,
• VLT® 5000 to FC 302 Drive Conver- leading to intuitive operation.
sion Wizard
11
Energy saving products
12
One drive – two performance levels
Special needs require special features and performance
13
Specifications
(Basic unit without extensions)
Main supply (L1, L2, L3) FC 301 FC 302 Analogue output FC 301 FC 302
Supply voltage 200 – 240 V ±10% Programmable
1
Supply voltage 380 – 480 V ±10% 380 – 500 V ±10% analogue outputs
Output data (U, V, W) FC 301 FC 302 USB interface 1.1 (Full Speed)
Digital output FC 301 FC 302 • The FC 300 is protected against short-circuits on motor terminals
U, V, W
Programmable
1 2 • The FC 300 is protected against earth fault on motor terminals U, V, W
digital/pulse outputs
Voltage level at • Protection against mains phase loss
0 – 24 V DC
digital/frequency output
Max. output current
40 mA
(sink or source)
Maximum output frequency
0 to 32 kHz
at frequency output
Accuracy on frequency
Max. error: 0.1% of full scale Global Marine
output
14
Connection examples
The numbers represent the terminals on the drive.
(1)
(1)
(2)
The diagram shows the port terminals (terminals 88 and 89) must be drive (S801). The drive can be
of the FC 301 and FC 302. Additional specified when configuring/ordering. equipped with a fieldbus option if
options will expand the number of Users can set the mode of the necessary.
terminals. analogue inputs 53 and 54 using the
S201 and S202 switches. To switch from NPN to PNP logic for
The numbers indicated refer to the the digital signals, use parameter
terminal numbers of the drives. All FC 301/302 have an RS485 and a 5-00.
Brake resistance (terminals 81 and 82) USB interface as standard. The RS485
and intermediate circuit connection terminations are integrated in the
15
Power, currents and enclosures
T2 T4/T5 T4/T5 T6 T7
200 – 240 V 380 – 440 V 441 – 480 V (FC 301) 525 – 600 V (FC 302 only) 690 V (FC 302 only)
441 – 500 V (FC 302)
(@ 200/240 V) (@ 400V) (@ 480/500V) (@ 575 V) (@ 690 V)
IP 55/IP 66
IP 55/IP 66
IP 55/IP 66
IP 21/IP 5x
[kW] [A] [kW] [A] [kW] [A] [kW] [A] [kW] [A]
IP 00
IP 20
IP 20
IP 20
IP 21
IP 21
IP 21
IP00
IP54
FC 300 HO NO HO NO HO NO HO NO HO NO HO NO HO NO HO NO HO NO HO NO
A1*/A2
PK75 0.75 4.6 0.75 2.4 0.75 2.1 0.75 1.7
A2
P1K1 1.1 6.6 A5 1.1 3 1.1 2.7 A2 A5 1.1 2.4
P1K5 1.5 7.5 1.5 4.1 1.5 3.4 1.5 2.7 A3 A3 A5
P2K2 2.2 10.6 A2 2.2 5.6 2.2 4.8 2.2 3.9
A2
P3K0 3 12.5 3 7.2 3 6.3 3 4.9
A3 A3
P3K7 3.7 16.7
P4K0 4 10 4 8.2 A2 A2 4 6.1
P5K5 5.5 7.5 24.2 30.8 5.5 13 5.5 11 A5 5.5 9 A3 A3 A5
B3 B1 B1 A3 A3
P7K5 7.5 11 30.8 46.2 7.5 16 7.5 14.5 7.5 11
P11K 11 15 46.2 59.4 B2 B2 11 15 24 32 11 15 21 27 11 15 18 22 11 15 13 18
B4 B3 B1 B1 B3 B1 B1
P15K 15 18.5 59.4 74.8 15 18.5 32 37.5 15 18.5 27 34 15 18.5 22 27 15 18.5 18 22
B2
P18K 18.5 22 74.8 88 C1 C1 18.5 22 37.5 44 18.5 22 34 40 18.5 22 27 34 18.5 22 22 27
C3 B2 B2 B2 B2
P22K 22 30 88 115 22 30 44 61 22 30 40 52 B4 22 30 34 41 B4 22 30 27 34
P30K 30 37 115 143 30 37 61 73 30 45 52 65 30 37 41 52 30 37 34 41
C4 C2 C2
P37K 37 45 143 170 37 45 73 90 45 55 65 80 C1 C1 37 45 52 62 C1 C1 37 45 41 52
C3 C3
P45K 45 55 90 106 55 75 80 105 45 55 62 83 45 55 52 62 C2
P55K 55 75 106 147 75 90 105 130 55 75 83 100 55 75 62 83
C4 C2 C2 C4 C2 C2
P75K 75 90 147 177 90 110 130 160 75 90 100 131 75 90 83 100
P90K 90 110 177 212 110 132 160 190 90 110 108 131
D3 D1 D1
P110 110 132 212 260 132 160 190 240 110 132 131 155 D3 D1
P132 132 160 260 315 160 200 240 302 132 160 155 192
P160 160 200 315 395 200 250 302 361 D4 D2 D2 160 200 192 242
D4 D2
P200 200 250 395 480 250 315 361 443 200 250 242 290
IP 00/Chassis IP 20/Chassis IP 21/NEMA Type 1 With upgrade kit** IP 54/NEMA Type 12 IP 55/NEMA Type 12 IP 21, IP 54 or IP 55
** MCF 101 – IP 21 Kit (upgrades from IP 20 to IP 21). See page 34
16
Ordering type code for VLT® AutomationDrive
[1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18]
FC – – – – – – – – – X – X – SXX X – – – – – – –
[1] Application [5] RFI Filter (EN 55011) [14] B Option (Application)
301 VLT® AutomationDrive FC 301 H1 RFI-Filter Class A1/B BX No application option
302 VLT® AutomationDrive FC 302 H2 No RFI-Filter, Class A2 BK MCB 101 – general purpose I/O
H3 RFI -Filter Class A1/B 1) BR MCB 102 – encoder input
[2] Power Size
H4 RFI -Filter, Class A1 2) BU MCB 103 – resolver input
PK25
H6 RFI -Fillter für Marine 2) BP MCB 105 – relay expansion
PK37
HX No RFI-Filter (only 600 V) BZ MCB 108 – safety PLC interface
PK55
B2 MCB 112 – ATEX-PTC thermistor
PK75 [6] Braking & Safety
P1K1 X No brake IGBT [15] C0 Option (Motion Control Option)
P1K5 B Brake IGBT mounted CX No motion control option
P2K2 Safe stop without brake 1) MCO 305/350/351 motion control,
T
P3K0 (FC 301 – only in A1 enclosure) C4 synchronising and/or positioning
P3K7 With brake and Safe Stop 1) (see [17])
U
P4K0 (FC 301 – only in A1 enclosure)
See ratings data on page 16 [16] C1 Option (Extended Relay)
P5K5
for power ratings [7] Display (Local Control Panel) X No option
P7K5
X Blank faceplate, no LCP installed R MCB 113 – extended relay (FC 302 only)
P11K
G LCP 102 – Numeric LCP installed
P15K [17] Software for Motion Control Option
N LCP 101 – Graphic LCP installed
P18K No motion software
P22K [8] Conformal Coating (IEC 721-3-3) Note: C4 option in [15] selected with no
XX
P30K X No conformal coating (Class 3C3) motion software in [17] will require program-
ming by a qualified individual
P37K C Conformal coating on all PCBs (Class 3C2)
MCO 350 synchronising control software
P45K 10
[9] Mains Input (must select C4 in position [15])
Pxxx
X No option MCO 351 positioning control software
P200 11
1 Mains disconnect (must select C4 in position [15])
[3] AC Line Voltage 3 Mains disconnect and fuses 2) MCO 352 – Center winder
12
T2 3 x 200/240 V AC 5 Mains disconnect, fuses and load sharing 2) (Choose C4 under field [15])
T4 3 x 380/480 V AC (FC 301) 7 Fuses 2)
[18] D Option (Control Power Backup Input)
T5 3 x 380/500 V AC (FC 302) 8 Mains disconnect and load sharing 3)
DX No DC input installed
T6 3 x 525/600 V AC (FC 302) A Fuses & load sharing terminals 2)
D0 MCB 107 24 VDC backup input
T7 3 x 525/690 V AC (FC 302) D Load sharing terminals 3)
1) FC 301/A1 enclosures only
[4] Enclosure [12] LCP Language 2) D1, D2, D3, D4 enclosures only
For cabinet mounting: 3) B1, B2, C1, C2 enclosures only
Standard language package including
E00 IP 00 (enclosure D3, D4) X English, German, French, Spanish, Danish,
Italian and Finnish Please beware that not all combinations
Z20 IP 20 (enclosure A1, FC 301 only) are possible. Find help configuring your drive
E20 IP 20 (enclosure A2, A3, B3, B4, C3, C4) Consult factory for other language options with the online configurator found under:
Standalone: driveconfig.danfoss.com
[13] A Option (Fieldbus)
E21 IP 21 (enclosure B1, B2, C1, C2, D1, D2)
AX No fieldbus option
E54 IP 54 (enclosure D1, D2)
A0 MCA 101 – Profibus DPV1
E55 IP 55 (enclosure A5, B1, B2, C1, C2)
A4 MCA 104 – DeviceNet
E66 IP 66 (enclosure A5, B1, B2, C1, C2)
A6 MCA 105 – CANopenp
Special designs:
AN CA 121 – Ethernet/IP
MCA
IP 00 (enclosure E00 – air duct in stainless
C00
steel)
P20 IP 20 (enclosure B4, C3, C4 – rear heat sink)
E2M IP 21 (enclosure D1, D2 – protective cover)
P21 IP 21 (Enclosure as E21 – rear heat sink)
E5M IP 54 (enclosure D1, D2 – protective cover)
P55 IP 55 (enclosure as E55 – rear heat sink)
17
200 – 240 VAC
IP 20 A1
Enclosure IP20 (IP21) A2 A3
PK25 PK37 PK55 PK75 P1K1 P1K5 P2K2 P3K0 P3K7
Typical Shaft Output [kW] 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 3.7
Continuous IVLT, N [A] 1.8 2.4 3.5 4.6 6.6 7.5 10.6 12.5 16.7
Output Current
Intermittent/60 s IVLT, MAX [A] 2.9 3.8 5.6 7.4 10.6 12.0 17.0 20.0 26.7
Output Power
Continuous (208 V) SVLT, N [KVA] 0.65 0.86 1.26 1.66 2.38 2.70 3.82 4.50 6.00
Continuous IL, N [A] 1.6 2.2 3.2 4.1 5.9 6.8 9.5 11.3 15.0
Rated Input Current
Intermittent/60 s IL, MAX [A] 2.6 3.5 5.1 6.6 9.4 10.9 15.2 18.1 24.0
Estimated power loss at rated maximum load [W] 21 29 42 54 63 82 116 155 185
Efficiency 0.94 0.95 0.96
Max. cable cross-section [mm2]
(input mains terminals, motor output terminals, ([AWG2]) 0.2 – 4 (24 – 10)
brake resistor terminals)
Max. external input (mains) fuses [A] 10 20 32
Weight
IP 20 (A1) [kg] 2.7 –
IP 20 (A2/A3) [kg] 4.7 4.8 4.9 6.6
IP 55, IP 66 (A5) [kg] 13.5
IP20 B3 B4
Enclosure IP21, IP55, IP66 B1 B2
P5K5 P7K5 P11K
Intermittent HO NO HO NO HO NO
Typical Shaft Output [kW] 5.5 7.5 11 15
Continuous IVLT,N [A] 24.2 30.8 46.2 59.4
Output Current
Intermittent/60 s IVLT,max [A] 38.7 33.9 49.3 50.8 73.9 65.3
Output Power
Continuous (208 V) SVLT,N [KVA] 8.7 11.1 16.6 21.4
Continuous IL,N [A] 22 28 42 54
Rated Input Current
Intermittent/60 s IL,MAX [A] 35.2 30.8 44.8 46.2 67.2 59.4
Estimated power loss at rated maximum load [W] 239 310 371 514 463 602
Efficiency 0.96 0.96 0.96
Max. cable cross-section 2
[mm ]
(input mains terminals, motor output terminals, ([AWG2]) 16 (6) 35 (2)
brake resistor terminals)
Max. external input (mains) fuses [A] 63 80
Weight
IP 20 [kg] 12 23.5
IP 21, IP 55, IP 66 [kg] 23 27
IP 20 B4 C3 C4
Enclosure IP21, IP55, IP66 C1 C2
P15K P18K5 P22K P30K P37K
Intermittent HO NO HO NO HO NO HO NO HO NO
Typical Shaft Output [kW] 15 18.5 22 30 37 45
Continuous IVLT,N [A] 59.4 74.8 88 115 143 170
Output Current
Intermittent/60 s IVLT,max [A] 89.1 82.3 112 96.8 132 127 173 157 215 187
Continuous
Output Power SVLT,N [KVA] 21.4 26.9 26.9 31.7 31.7 41.4 41.4 51.5 51.5 61.2
(208 V)
Continuous IL,N [A] 54 68 80 104 130 154
Rated Input Current
Intermittent/60 s IL,MAX [A] 81 74.8 102 88 120 114 156 143 195 169
Estimated power loss at rated maximum load [W] 624 737 740 845 874 1140 1143 1353 1400 1636
Efficiency 0.96 0.97
[mm2]
Max. cable cross-section (IP20) ([AWG2]) 35 (2) 90 (3/0) 120 (4/0)
[mm2]
Max. cable cross-section (IP21, IP55, IP66) ([AWG2]) 90 (3/0) 120 (4/0)
Max. external input (mains) fuses [A] 125 160 200 250
Weight
IP 20 [kg] 23.5 35 50
IP 21, IP 55, IP 66 [kg] 45 65
HO (High overload) = 160%/60 s, NO (Normal overload) = 110%/60 s
18
380 – 480/500 VAC
IP20 A1
IP20 (IP21) A2 A3
Enclosure
IP55, IP66 A5
PK37 PK55 PK75 P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5
Typical Shaft Output [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5
Output Current Continuous IVLT,N [A] 1.3 1.8 2.4 3 4.1 5.6 7.2 10 13 16
380 – 440 V Intermittent 160%/60 s IVLT,max [A] 2.1 2.9 3.8 4.8 6.6 9.0 11.5 16 20.8 25.6
Output Current Continuous IVLT,N [A] 1.2 1.6 2.1 2.7 3.4 4.8 6.3 8.2 11 14.5
441 – 480/500 V Intermittent 160%/60 s IVLT,max [A] 1.9 2.6 3.4 4.3 5.4 7.7 10.1 13.1 17.6 23.2
400 V 0.9 1.3 1.7 2.1 2.8 3.9 5.0 6.9 9.0 11.0
Output Power SVLT,N [KVA]
460 V 0.9 1.3 1.7 2.4 2.7 3.8 5.0 6.5 8.8 11.6
Rated Input Current Continuous IL,N [A] 1.2 1.6 2.2 2.7 3.7 5.0 6.5 9.0 11.7 14.4
380 – 440 V Intermittent 160%/60 s IL,MAX [A] 1.9 2.6 3.5 4.3 5.9 8.0 10.4 14.4 18.7 23.0
Rated Input Current Continuous IL,N [A] 1.0 1.4 1.9 2.7 3.1 4.3 5.7 7.4 9.9 13.0
441 – 480/500 V Intermittent 160%/60 s IL,MAX [A] 1.6 2.2 3.0 4.3 5.0 6.9 9.1 11.8 15.8 20.8
Estimated power loss at rated maximum load [W] 35 42 46 58 62 88 116 124 187 255
Efficiency 0.93 0.95 0.96 0.97
Max. cable cross-section [mm2]
(input mains terminals, motor output terminals, ([AWG2]) 0.2 – 4 (24 – 10)
brake resistor terminals)
Max. external input (mains) fuses [A] 10 20 32
Weight
IP20 [kg] 4.7 4.8 6.6
IP55, IP66 [kg] 13.5 14.2
IP 20 B3 B4
Enclosure IP21, IP55, IP66 B1 B2
P11K P15K P18K P22K
Intermittent HO NO HO NO HO NO HO NO
Typical Shaft Output [kW] 11 15 18.5 22.0 30.0
Output Current Continuous IVLT,N [A] 24 32 37.5 44 61
380 – 440 V Intermittent 160%/60 s IVLT,max [A] 38.4 35.2 51.2 41.3 60 48.4 70.4 67.1
Output Current Continuous IVLT,N [A] 21 27 34 40 52
441 – 480/500 V Intermittent 160%/60 s IVLT,max [A] 33.6 29.7 43.2 37.4 54.4 44 64 57.2
400 V 16.6 22.2 26 30.5 42.3
Output Power SVLT,N [KVA]
460 V 21.5 27.1 31.9 41.4
Rated Input Current Continuous IL,N [A] 22 29 34 40 55
380 – 440 V Intermittent 160%/60 s IL,MAX [A] 35.2 31.9 46.4 37.4 54.4 44 64 60.5
Rated Input Current Continuous IL,N [A] 19 25 31 36 47
441 – 480/500 V Intermittent 160%/60 s IL,MAX [A] 30.4 27.5 40 34.1 49.6 39.6 57.6 51.7
Estimated power loss at rated maximum load [W] 291 392 379 465 444 525 547 739
Efficiency 0.98
[mm2]
Max. cable cross-section ([AWG2])
16 (6) 35 (2)
Max. external input (mains) fuses [A] 63 80
Weight
IP20 [kg] 12 23.5
IP21, IP55, IP66 [kg] 23 27
19
380 – 480/500 VAC
IP 20 B4 C3 C4
Enclosure IP21, IP55, IP66 C1 C2
P30K P37K P45K P55K P75K
Intermittent HO NO HO NO HO NO HO NO HO NO
Typical Shaft Output [kW] 30 37 45 55 75 90
Output Current Continuous IVLT,N [A] 61 73 90 106 147 177
(380 – 440 V) Intermittent/60 s IVLT,max [A] 91.5 80.3 110 99 135 117 159 162 221 195
Output Current Continuous IVLT,N [A] 52 65 80 105 130 160
(441 – 480/500 V) Intermittent/60 s IVLT,max [A] 78 71.5 97.5 88 120 116 158 143 195 176
400 V SVLT,N [KVA] 42.3 50.6 62.4 73.4 102 123
Output Power
460 V SVLT,N [KVA] 51.8 63.7 83.7 104 128
Rated Input Current Continuous IL,N [A] 55 66 82 96 133 161
(380 – 440V) Intermittent/60 s IL,MAX [A] 82.5 72.6 99 90.2 123 106 144 146 200 177
Rated Input Current Continuous IL,N [A] 47 59 73 95 118 145
(441 – 480/500 V) Intermittent/60 s IL,MAX [A] 70.5 64.9 88.5 80.3 110 105 143 130 177 160
Estimated power loss at rated maximum load [W] 570 698 697 843 891 1083 1022 1384 1232 1474
Efficiency 0.98 0.99
Max. cable cross-section [mm2] 35 (2) 50 (1) 95 (4/0) 150
(IP20, input mains terminals, motor output terminals) ([AWG2]) (300mcm)
Max. cable cross-section [mm2] 35 (2) 50 (1) 95 (4/0)
(IP20, DC Link, brake resistor terminals) ([AWG2])
Max. cable cross-section [mm2] 90 (3/0) 120 (4/0)
(IP21, IP55, IP66) ([AWG2])
Max. external input (mains) fuses [A] 100 125 160 250
Weight
IP20 [kg] 23.5 35 50
IP21, IP55, IP66 [kg] 45 65
IP21, IP54 D1 D2
Enclosure IP00 D3 D4
P90K P110 P132 P160 P200
Intermittent HO NO HO NO HO NO HO NO HO NO
Typical Shaft Output (400 V) 90 110 132 160 200 250
[kW]
(500 V) 110 132 160 200 250 315
Output Current Continuous IVLT,N [A] 177 212 260 315 395 480
(400 V) Intermittent/60 s IVLT,max [A] 266 233 318 286 390 347 473 435 593 528
Output Current Continuous IVLT,N [A] 160 190 240 302 361 443
(460/500 V) Intermittent/60 s IVLT,max [A] 240 209 285 264 360 332 453 397 542 487
400 V SVLT,N [KVA] 123 147 180 218 274 333
Output Power 460 V SVLT,N [KVA] 127 151 191 241 288 353
500 V SVLT,N [KVA] 139 165 208 262 313 384
Rated Input Current (400 V) Continuous IL,N [A] 171 204 251 304 381 463
Rated Input Current Continuous IL,N [A] 154 183 231 291 348 427
(460/500 V)
Estimated power loss at rated maximum load [W] 2641 3234 2995 3782 3425 4213 3910 5119 4625 5893
Efficiency 0.98
Max. cable cross-section [mm2] 2 x 70 2 x 185
(input mains terminals, motor output terminals,
brake resistor terminals, DC Link) ([AWG2]) (2 x 2/0) (2 x 350 mcm)
Max. external input (mains) fuses [A] 300 350 400 500 600
Weight
IP00 [kg] 82 91 112 123 138
IP21, IP54 [kg] 96 104 125 136 151
20
525 – 600 VAC
(FC 302 only)
IP20 (IP21) A3
Enclosure IP55, IP66 A5
PK75 P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5
Typical Shaft Output (575 V) [kW] 0.75 1.1 1.5 2.2 3 4 5.5 7.5
Output Current
Continuous (525 – 550 V) [A] 1.8 2.6 2.9 4.1 5.2 6.4 9.5 11.5
Intermittent (525 – 550 V) [A] 2.9 4.2 4.6 6.6 8.3 10.2 15.2 18.4
Continuous (551 – 600 V) [A] 1.7 2.4 2.7 3.9 4.9 6.1 9.0 11.0
Intermittent (551 – 600 V) [A] 2.7 3.8 4.3 6.2 7.8 9.8 14.4 17.6
Output Power
Continuous (525 V) [KVA] 1.7 2.5 2.8 3.9 5.0 6.1 9.0 11.0
Continuous (575 V) [KVA] 1.7 2.4 2.7 3.9 4.9 6.1 9.0 11.0
Estimated power loss at rated maximum load [W] 35 50 65 92 122 145 195 261
Rated Input Current
Continuous (525 – 600 V) [A] 1.7 2.4 2.7 4.1 5.2 5.8 8.6 10.4
Intermittent (525 – 600 V) [A] 2.7 3.8 4.3 6.6 8.3 9.3 13.8 16.6
Efficiency 0.97
Max. cable cross-section [mm2] 0.2 – 4 mm2 (24 – 10) 0.2 – 4 mm2 (24 – 10 )
(input mains terminals, motor output terminals, ([AWG2])
brake resistor terminals)
Max. external input (mains) fuses [A] 10 20 32
Weight
IP20 [kg] 6.5 6.6
IP55, IP66 [kg] 13.5 14.2
IP20 B3 B4
Enclosure IP21, IP55, IP66 B1 C1 B2
P11K P15K P18K5 P22K P30K
Intermittent HO NO HO NO HO NO HO NO HO NO
Typical Shaft Output (575 V) [kW] 11 15 18.5 22 30 37
Output Current
Continuous (525-550 V) [A] 19 23 28 36 43 54
Intermittent (525-550 V) [A] 30 25 37 31 45 40 58 47 65 59
Continuous (525-600 V) [A] 18 22 27 34 41 52
Intermittent (525-600 V) [A] 29 24 35 30 43 37 54 45 62 57
Output Power
Continuous (500 V) [KVA] 18.1 21.9 26.7 34.3 41.0 51.4
Continuous (575 V) [KVA] 17.9 21.9 26.9 33.9 40.8 51.8
Rated Input Current
Continuous 550 V [A] 17.2 20.9 25.4 32.7 39 49
Intermittent (550 V) [A] 28 23 33 28 41 36 52 43 59 54
Continuous (575 V) [A] 16 20 24 31 37 47
Intermittent (575 V) [A] 26 22 32 27 39 34 50 41 56 52
Estimated power loss at rated maximum load [W] 225 285 329 700 700
Efficiency 0.98
Max. cable cross-section IP20 2
[mm ]
(input mains terminals, motor output terminals, ([AWG2]) 35 (2)
brake resistor terminals, DC Link)
16 (6)
Max. cable cross-section IP21, 55, 66 [mm2]
(input mains terminals, motor output terminals, 90 (3/0)
brake resistor terminals, DC Link) ([AWG2])
Max. external input (mains) fuses [A] 63 63 63 80 100
Weight
IP20 [kg] 12 23.5
IP21, IP55, IP66 [kg] 23 27
21
525 – 600 VAC
(FC 302 only)
22
690 VAC
(FC 302 only)
IP21/IP55 B2 C2
Enclosure
P11K P15K P18K5 P22K P30K P37K P45K P55K P75K
Intermittent HO NO HO NO HO NO HO NO HO NO HO NO HO NO HO NO HO NO
Typical Shaft Output (690 V) [kW] 11 15 18.5 22 30 37 45 55 75 90
Output Current
Continuous (525 – 550 V) [A] 14 19 23 28 36 43 54 65 87 105
Intermittent (525 – 550 V) [A] 22.4 20.9 30.4 25.3 36.8 30.8 44.8 39.6 54 47.3 64.5 59.4 81 71.5 97.5 95.7 130.5 115.5
Continuous (551 – 690 V) [A] 13 18 22 27 34 41 52 62 83 100
Intermittent (551 – 690 V) [A] 20.8 19.8 28.8 24.2 35.2 29.7 43.2 37.4 51 45.1 61.5 57.2 78 68.2 93 91.3 124.5 110
Output Power
Continuous (550 V) [KVA] 13.3 18.1 21.9 26.7 34.3 41.0 51.4 61.9 82.9 100
Continuous (575 V) [KVA] 12.9 17.9 21.9 26.9 33.9 40.8 51.8 61.7 82.7 99.6
Continuous (690 V) [KVA] 15.5 21.5 26.3 32.3 40.6 49.0 62.1 74.1 99.2 119.5
Rated Input Current
Continuous (525 – 690 V) [A] 15 19.5 24 29 36 49 59 71 87 99
Intermittent (525 – 690 V) [A] 23.2 21.5 31.2 26.4 38.4 31.9 46.4 39.6 54 53.9 72 64.9 87 78.1 105 95.7 129 108.9
Estimated power loss at rated [W] 228 285 335 375 480 592 720 880 1200
maximum load
Efficiency 0.98
Max. cable cross-section
(input mains terminals, motor output [mm2] 35 (1/0)
terminals, brake resistor terminals, ([AWG2])
DC Link)
Max. external input (mains) fuses [A] 63 80 100 125 160
Weight [kg] 27 65
IP00 D3 D4
Enclosure IP21/IP54 D1 D2
P90K P110 P132 P160 P200
Intermittent HO NO HO NO HO NO HO NO HO NO
Typical Shaft Output (690 V) [kW] 90 110 132 160 200 250
Output Current
Continuous (575 – 690 V) [A] 108 131 155 192 242 290
Intermittent (575 – 690 V) [A] 162 144 197 171 233 211 288 266 363 319
Output Power
Continuous (550 V) [KVA] 108 131 154 191 241 289
Continuous (575 V) [KVA] 108 130 154 191 241 289
Continuous (690 V) [KVA] 129 157 185 229 289 347
Rated Input Current
Continuous (550 V) [A] 110 130 158 198 245 299
Continuous (575 V) [A] 106 124 151 189 234 286
Continuous (690 V) [A] 109 128 155 197 240 296
Estimated power loss at rated maximum load [W] 2264 2662 2664 3114 2953 3612 3451 4292 4275 5156
Efficiency 0.98
Max. cable cross-section IP20 [mm2]
(input mains terminals, motor output terminals, ([AWG2]) 2 x 70 (2 x 2/0) 2 x 185 (2 x 350 mcm)
brake resistor terminals, DC Link)
Max. external input (mains) fuses [A] 250 315 350 400
Weight
IP00 [kg] 82 91 112 123
IP21, IP54 [kg] 96 104 125 136
23
Dimensions VLT® AutomationDrive
In mm
Min. 100
Exhaust
205 (220)
75 60
Exhaust ∅5
A1 Enclosures
190
200
279
∅5
Min. 100
Inlet
Inlet
Rear View
205 (220) 90
∅ 5,5 70
Exhaust
A2 Enclosures
257
268
341
Min. 100
Inlet
∅ 5,5
Inlet
Rear View
205 (220)
130
∅ 5,5 110
Exhaust
A3 Enclosures
257
268
341
∅ 5,5
Min. 100
Inlet
Inlet
Rear View
24
650
420
480
In mm
242
242
242
Min. 200 Min. 200
Inlet Exhaust
Inlet
260
Inlet
Inlet
200
Exhaust
260
A3 Gehäuse A1 Gehäuse180
Exhaust
Exhaust
Dimensions VLT® AutomationDrive
∅9
∅9
∅ 6,5
∅ 6,5
∅9
∅9
210
Rear View
210
215
Rear View
Rear View
624
454
402
25
B2 Enclosures B1 Enclosures A5 Enclosures
Dimensions VLT® AutomationDrive
In mm
Min. 200
Exhaust
249 (262) 165
∅ 6,8 140
Exhaust
B3 Enclosures
399
380
419
Min. 200
∅ 6,8
Inlet
Rear View
Inlet
231
242
Min. 200
Exhaust
495
520
460
595
Min. 200
Inlet
∅ 8,5
Rear View
Inlet
648
680
Min. 200
Inlet
∅9 Rear View
Inlet
26
770
In mm
370
Min. 225 Min. 225 Min. 225 Min. 225
Inlet Exhaust
Min. 200 Min. 200
Inlet Exhaust
Inlet Exhaust
630
800
36 36
Inlet
Inlet
Inlet
335
334
334
A3 Gehäuse A1 Gehäuse180
Exhaust
Exhaust
Exhaust
598
Dimensions VLT® AutomationDrive
488
∅9
∅ 8,5
∅ 8,5
∅9
∅ 8,5
∅ 8,5
334
210
270
308
330
370
Rear View
Rear View
Rear View
739
631
521
660
550
27
C4 Enclosures C3 Enclosures C2 Enclosures
Dimensions VLT® AutomationDrive
In mm
74 420
D1 Enclosures (Floor- or cabinet Mount)
765 m3/hr
Min. 22
Exhaust
170 m3/hr
1166
1209
981
Min. 225
310
Inlet
163 380
417
Optional pedestal 176F1827 available
for stand-alone floor mount installations
(adds 200 mm to height)
420
72
765 m3/hr
Min. 225
Exhaust
170 m3/hr
D2 Enclosures (Floor- or cabinet Mount)
423
Min. 225
Inlet
157 380
28
Dimensions VLT® AutomationDrive
In mm
408
66 765 m3/hr 255 m3/hr
A1 Gehäuse180
1046
997
818
147
Min. 225
Inlet
157
375
417
408
66 765 m3/hr 255 m3/hr
Min. 225
Exhaust
1327
1280
1099
161
Min. 225
Inlet
151 375
417
Drives shown with optional
disconnect switch
29
VLT® AutomationDrive Options
Typecode Position
Typecode Position
B
• For the majority of applications this input enables the user to implement safety in a cost-effective way.
For applications that work with more advanced products like Safety PLC, Lightcurtains etc. the new Safe PLC interface 14
enables the connection of a two wire safety link
• The Safe PLC Interface allows the Safe PLC to interrupt on the plus or the minus link without interfering the sense signal
of the Safe PLC
Ordering number 130B1120 uncoated – 130B1220 coated (Class 3C3/IEC 60721-3-3)
Typecode Position
D
Typecode Position
LCP
Screw terminals
Screw terminals as an alternative to the standard springloaded terminals.
• Pluggable
• Terminal name is described
Ordering number 130B1116
Please refer to the product and design manuals for selection and dimensioning
34
VLT® AutomationDrive Accessories
Note: Missing numbers can be found in the design manual or can be delivered on request
35
What VLT® is all about
Danfoss Drives is the world leader among dedicated drives providers
– and still gaining market share.
Melbourne: Tel. (03) 9703 5100, Fax. (03) 9703 5159 • Sydney: Tel. (02) 8845 1800, Fax. (02) 9638 6088 • Brisbane: Tel. (07) 3690 1899, Fax. (07) 3630 2122 • Adelaide: Tel. (08) 8150 7400, Fax. (08) 8443 8033
Perth: Tel. (08) 9333 3800, Fax. (08) 9479 7200 • Auckland: Tel. (09) 270 2110, Fax. (09) 270 2112 • Christchurch: Tel. (03) 379 4365, Fax. (03) 379 4365
www.danfoss.com/pacific • Email Australia: motioncontrols@danfoss.com.au • Email New Zealand: drives@danfoss.co.nz
After Hours Service Support: Australia Tel. 1800 063 330 • New Zealand (Nth) Tel. 09 259 2519