You are on page 1of 8

©IstockPhoto.

Com/fergregory

A History of Grounding
and Earthing Practices
in the United States
Part 1: A DISCUSSION OF HOW THE EARTH HAS BEEN USED FOR
ELECTRICAL CONDUCTION Through the 1920s

By Donald W. Zipse The 270-year history of using the earth as an


electrical conductor for man-made electricity is detailed
in this article. For the first 140 years of man-made elec-
The second part of this article will be published in tricity, scientists and engineers used earth, the surface of
the March/April 2019 issue of the magazine. the terrestrial ball we live on, as a conductor to return the
continuous flowing electric current back to the source. Edi-
son realized that using the earth as an electrical conductor
Digital Object Identifier 10.1109/MIAS.2018.2868363
presented a health hazard to humans and animals. For a
Date of publication: 5 November 2018 brief quarter of a century, it was not used as a conductor

1077-2618/19©2019IEEE j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 37


for continuously flowing man-made Grounding or earthing of electrical
electricity. In hindsight, one could systems predates Edison’s 1882 Pearl
reach the conclusion that the lack The fascinating Street man-made dc generating sta-
of knowledge of man-made electric-
ity allowed what seemed to be the
history of using the tion by 137 years. The article “Earth
Wires; or, the Earth as an Electric Cir-
correct action at the time, but what earth for conducting cuit Completer” was read before the
would later prove to be harmful to American Institute of Electrical Engi-
the human race and other animals. man-made electricity neers in Philadelphia, Pennsylvania,
The fascinating history of using the
earth for conducting man-made elec-
illuminates a in October 1884 and published in
Transactions of the American Insti-
tricity illuminates a bright future. bright future. tute of Electrical Engineers. Thomas
D. Lockwood, an electrician with the
In the Beginning American Bell Telephone Company
The discussion of the grounding/earth- stated that “there is no element or
ing practices in the United States begins with electrical adjunct of electrical science more important in many
experiments in Europe. However, this article has the follow- respects then the terrestrial ball itself, when we consider
ing parameters: the scope is limited to man-made electrical it in its relationship to the electrical circuit.” In England
currents produced from chemical reactions, batteries, or in July and August 1747, additional experiments were
generators. Excluded from this article are static, lightning, performed using the Thames and the New River. These
solar, fuel cells, wind generation, ac and/or dc high-voltage results were verified by Franklin in 1748. Thus, it was
transmission, computer grounding (see IEEE Standards 142 proven that dryer earth and/or water could be used for
and 1100), and traction companies, and so on. Grounding as part of an electrical circuit [4].
required by the National Electrical Code (NEC), Article 250, One of the earliest examples of the electrochemical
from the National Fire Protection Association (NFPA) is not telegraph was first suggested in 1753 and developed in
included in the discussion. The article is a narration of the 1804 by Francisco Salva Campillo, consisting of up to 35
significant historical events of earthing/grounding. multiple wires. Samuel Thomas von Sömmering in 1809
Telluric, or earth, currents are naturally occurring cur- improved upon the multiwire telegraph system.
rents that circulate in the earth’s crust, the outermost solid In the United States in 1836, Dr. David Alter of Elder-
shell, and the mantle, which is the area above the core. ton, Pennsylvania, which is 60 mi northwest of Pitts-
These telluric currents are low frequency in the range of burgh, conceived and demonstrated but did not develop
3–30 Hz and do not harm humans and animals as has a single-wire telegraph system that used the earth for
been proposed [1], [2]. the return man-made current. Samuel Morse developed
Grounding or earthing of electrical charge has been an alphabet consisting of dots and dashes, which was
understood through discharge of electrostatically charged patented in 1837. Steinheil proposed using only a single
components since the sixth century BC [3]. According conductor for telegraph systems in 1838 [6].
to Lockwood [4], [5], experiments on man-made current The earth, “when used in the arts of electrical com-
flow in the earth and or water were performed using sci- munication, it enables to reduce one-half of the number
entific methods in July 1746. Winkler, of Leipzig, charged of line wires, which would otherwise have to be used;
and discharged a battery consisting of three Leyden jars and when we consider the immense number of wires
using the river Pleisse as a return path for the man-made that even now fill our streets and line our highways, we
current. Additional verification of the ability of the earth cannot fail to reflect upon what might have been, had we
to conduct electricity was attributed to Le Monnier, Wat- been compelled to provide a separate return wire for each
son, Franklin, and De Luc, all making use of electrostatic telegraphic and telephonic circuit from 1837 until 1884” [4].
potential from frictional charging.
The use of water and damp ground as part of bat- Earthing/Grounding of
tery circuits was also studied in 1803 independently by Electrical Generating Systems
Basse, Erman, and Aldini and in 1808 by Coemmering
and Schilling. In 1833, Faraday’s note 292 stated “A good Edison’s Pearl Street Central Generating Station
discharging train was arranged by connecting metallically Thomas Alva Edison’s successful invention of an incan-
a sufficiently thick wire with the metallic gas pipes of the descent lamp was granted a patent on 27 January 1880,
house, with the metallic gas pipes belonging to the public and he formed the Edison Illuminating Company to use
gas works of London; and also with the metallic water his newly patented incandescent lamp. Edison proceeded
pipes of London. It was so effectual in its office as to to build and install a lighting system on a new passenger
carry of instantaneously electricity of the feeblest tension, and cargo steamship, the SS Columbia, being built in
even that of a single voltaic trough, and was essential to Chester, Pennsylvania, in 1880 [7]. It sailed between San
many of the experiments” [4]. Francisco, California, and Portland, Oregon.

38 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019


The world’s next Edison lighting system was installed of the conductors among themselves or with the con-
in the printing firm of Hinds, Ketcham & Company in ductors of other circuits to such an extent that a sys-
New York, followed by the Edison installation at the Hol- tem so constructed would be impractical.
born Viaduct in London, England, which began operating Edison, because of his electrical-shocking problems,
in January 1882 [7]. The first central generating station in realized that he could save a conductor by using two
the United States was a central power plant at 255–257 dynamos in series with the center point between the two
Pearl Street in Manhattan, New York (Figure 1). The Pearl dynamos being the common conductor (see Figure 2).
Street central generating station began with one man- Edison recognized the hazards involved in using the earth
made dc reciprocating steam-driven 110-V dynamo on as a current return path. The Edison three-wire system
4 September 1882. is described in the Instruction Book No. 8148, published
It is assumed that Edison was well aware of the testing by the General Electric Company on 19 December 1900,
that was done in Europe proving that the earth and riv- and consists of a three-wire grounded midpoint at one
ers were excellent conductors of electricity and the work location only, which supplies phase-to-phase voltage
on the telegraph system, which used a single conductor of 220 and 110 V for lightning. This is the basis of the
with an earth return. Edison’s electrical generation was electrical distribution in homes today, except the single-
dc dynamos consisting of two wires, one of which was point grounding has not been followed in the present-day
a positive conductor and the other the negative conduc- electrical distribution system. The electrical industry has
tor. Edison’s electrical distribution system consisted of an forgotten what Edison learned more than 100 years ago.
insulated positive conductor that ran to junction boxes in
the street and then into the customers home or business. Grounding of ac Systems
Edison used the existing illuminating gas piping to run Initially, the Westinghouse/Tulsa system of ac genera-
his insulated positive conductor to the existing gas man- tion was considered unsafe by Elihu Thomson (1853–
tle, which he replaced with his electric incandescent lamp. 1937). During an interview by Dr. Edward W Rice, Jr.,
Edison then connected the neutral return current
to the existing gas pipe, which entered the earth. At
this point, this electrical connection of the gas pipe
to the earth could be considered the first grounding
electrode. Edison used the earth to return the negative
current back to the steam-driven dynamo at the Pearl
Street central generating station. Edison’s use of the
earth for the return current conductor caused havoc
in the area of his Pearl Street station as related by Tom
Shaughnessy [9]:
 Early on, Edison implemented a floating approach
for his dc systems after several events demonstrat-
ed the adverse effects of stray dc currents flowing
throughout buildings and neighborhoods. Once a
horse was shocked when it walked on “electrified
soil” near Edison’s Pearl Street generating station
and laborers working on his underground distribu-
tion system believe there was a “devil in the wire.”
Edison recognized the problem of using the earth to
return the current. Five years later, on 30 August 1887, Edi-
son was granted patent No. 369,280 “System of Electrical
Distribution,” which corrected the problem Edison created
by using the earth for a return current conductor. On page 2
of the patent beginning with line 31, it reads as follows:
All of such conductors from the generators at the sta-
tion to the lamps are made in pairs—one for the out-
going current and the other for the returning current
of electricity, the circuits throughout the system being
complete or around metal circuits, the conductors of
which are well insulated from each other and from
FIGURE 1. A photograph of 257 Pearl Street, Manhattan, in 1882.
the earth. The use of the earth for one-half of the cir- (Photo courtesy of Con Edison. Taken from http://theinstitute.ieee.
cuit would largely increase the difficulties arising org/tech-history/technology-history/edisons-pearl-street-station-
from the grounding of the conductors or the crossing recognized-with-milestone810.)

j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 39


should have an insulation resistance between con-
Electric ductors and between all conductors and the ground
Current (not including attachments, sockets, receptacles, and
Positive so on) and not less than the following.
+ Crosby then presents a table based on current from
100 V 2 Generator A Loads A 10 A at 4 MX up to 1,600 A and 11, 000 X.
– Note that, even in 2017, neutral-to-ground insulation
200 V
Neutral strength is still checked when installing tingle voltage
+ filters and mitigation. Often, additional wiring on subpan-
1 Lights
100 V Generator B B els has inadvertently introduced a ground on the neutral
– Negative that remains unacceptable in modern wiring codes after
119 years.

FIGURE 2. A three-wire dc electrical system with a conductor used as The NEC


current return path. The NEC has been sponsored by the NFPA since 1911. As
the result of efforts of various insurance, electrical, archi-
in 1932, Thomson said, “We took up the alternating tectural, and allied interests, the code dates to the work
current transformer system, which I had outlined as far performed by the National Electric Association in 1897.
back as 1879 at the Franklin Institute (Philadelphia). The NEC, which is revised every three years, applies to
And we built the system but didn’t consider it safe residences, commercial buildings, and industrial facilities.
until the development of the earthing of the secondary, It applies to the utilities’ office buildings and maintenance
which was an invention of mine for securing the safety buildings and others but not to the generation, distribu-
of the secondary lines of the transformer systems” [10]. tion, and transmission lines.
It was stated [11]: The purpose of the NEC is stated in Section 90-1: “The
One of the reasons why Thomson delayed his appli- purpose of this code is the practical safeguarding of per-
cation for this celebrated patent on alternating cur- sons and of buildings and their contents from hazards
rent distribution was his fear that the system would arising from the use of electricity for light, heat, power,
be dangerous when reduced to practice; the insula- radio, signaling and for other purposes.” Section 90-2 cov-
tion of the transformer might break down and the ers the scope: “It covers the electric conductors and equip-
high voltage of the primary would appear in the sec- ment installed within or on public and private buildings
ondary circuit. It was not until he discovered in 1885 and other premises, including yards, Carnival and park-
a way to avoid the danger, chiefly by grounding the ing lots, and industrial substations; also, the conductors
secondary in the transformer, that he was willing to that connect the installation to a supply of electricity, and
see the distribution system put into use. other outside conductors adjacent to the premises; also,
mobile homes and travel trailers” [12].
Codes and Standards Grounding is covered in Article 250, “Grounded Con-
ductors,” and in the 1951 edition, it was 21 pages long
The Underwriters’ Bureau of New England and the book was 4 in # 6.25 in, sized to fit in your
The NFPA can be traced back to a conference of insur- back pocket, which was the author’s first introduction to
ance organizations held in New York on 18–19 March the NEC. The latest edition from 2017 has 31 pages in a
1896. The first handbook was written by Everett U. book that is 8.5 in # 11 in. To detail the changes in just
Crosby. The preface states: “This compilation with added the grounding article of the NEC would probably end up
new material on the subject of protection against fire is as a book, and thus, the changes to the grounding sec-
intended as a book of reference for Inspectors and others tion of the NEC will not be covered in this article. The
in the employee of our members.” The 4.5 in # 7 in book NFPA publishes a handbook in each three-year cycle that
has 183 pages. explains the changes and the interpretation of the NEC.
Page 163 begins the section “Rules and Requirements
of the National Board of Fire Underwriters for the Instal- The National Electrical Safety Code
lation of Wiring and Apparatus for Electric Light, Heat and In the beginning of electrical distribution, each estate,
Power as Recommended by the Underwriters’ National town, or city had its own material and method of install-
Electric Association, edition of January 1, 1896.” As far as ing the conductors and generating equipment, each in
grounding is concerned, according to rule 46a, their own little area. This resulted in problems due to
The wiring in any building must test free from the lack of uniformity. The National Bureau of Standards
grounds: i.e., each main supply line and every (NBS) in 1913 had started to develop the National Electri-
branch circuit should have an insulation resistance cal Safety Code (NESC). In 1919, the NBS and the National
of at least 100,000 ohms and the whole installation Electric Light Association joined forces and made a survey

40 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019


of the existing electrical distribution systems, and they transmitted across the metal electrode-earth soil interface
found that some areas had unsafe electrical systems. The in a way that is best described as follows [15]:
requirements of the original code were based on good Around a grounding electrode, the resistance of the
engineering theory and generally accepted good practice. soil is the sum of the series resistance of virtual
The publication consisted of separate editions of shells of earth, located progressively outward from
“Grounding Rules” and “General Rules, Parts 1, 2, and 3.” the rod. The shell nears the rod has the smallest cir-
In 1972, the NBS resigned from being the Secretariat and cumferential area or cross-section, so it has the high-
the IEEE became the Secretariat. All parts of the NESC are est resistance. Successive shells outside this one has
published together in one document. Like the NFPA, the progressively larger areas, and thus progressively
IEEE also publishes a handbook on the NESC [13]. lower resistances. As the radius from the rod in­­
creases, the incremental resistance per unit of radius
IEEE Guide for Safety in ac Substation decreases effectively to nearly zero.
Grounding, Standard 80 For additional information, consult Chapter 4, “Con-
The first edition of Standard 80 was published in 1961 [14]. nection to Earth” [15].
To protect workmen within a fenced substation enclosure, A typical 16-mm (5/8-in) diameter rod that was
a grid of buried copper wires is installed, which offers 3-m (10-ft) long, buried vertically in the earth from the
protection against step and touch potentials. Guide 80 ­surface, would have a sphere of influence extending
provides considerable detail on increasing the underfoot out 7.6 m (25 ft). A sphere of 3 m (10 ft) captures 94%
resistance to reduce the flow of current through models of of the total resistance.
the worker’s foot or feet. This grid system is installed over
the total area of the substation switchyard and may extend General Practice Regarding Operating
beyond the substation fence. Electrical Systems Grounded or Isolated
A typical grid design is based on the maximum Neutral
amount of fault current expected to flow through the Figure 3 shows the wiring diagram for an ungrounded
earth when a transmission conductor falls to the ground. delta-connected generator or transformer, while Figure 4
Since this standard is a guide, the key word is may. A shows the wiring diagram for an ungrounded wye-con-
typical grid may use 4/0 copper conductor buried 0.3–0.5 m nected generator or transformer. In Figure 5(a), a wye-con-
(12–18 in) below grade and spaced 3–7 m (10–20 ft) apart. figured generator or transformer is grounded at the source.
Under high soil resistivity conditions in areas where The neutral is not carried with the phase conductors.
people would walk, a typical mesh would consist of num- H.H. Dewey [16] stated that, from the beginning of
ber-6 AWG copper conductors in a square grid pattern of power transmission in 1888 or 1890 to 1910 or 1912, there
0.6 m # 0.6 m ^24 in # 24 in h installed 0.05–0.15 m (2–6 in)
below the earth’s surface.
The key points in substation grounding are to protect
Phase A
workers from harmful and dangerous step touch poten-
tial, while conducting a short circuit current of thousands Phase B 2,000 V
of amperes lasting for a short duration (seconds) until the
protective device clears the fault. Usually, primary pro- 2,000 V
2,000 V
tection within 3–10 ac cycles and backup protection will
Phase C
operate in a modern substation within half a second.

IEEE Recommended Practice for Grounding of Industrial


FIGURE 3. An electrical system source connected in delta
and Commercial Power Systems, Standard 142 ungrounded—not connected to the earth.
The first edition of Standard 142, known as the Green
Book, was published in 1956 [15]. The key word in a rec-
ommended practice standard is should. Standard 142
covers system grounding, equipment grounding, static Phase A
and lightning protection grounding, connection to the
2,000 V
earth, and sensitive electronic equipment grounding. Phase B
In the 1991 edition, Chapter 4, “Connection to Earth,”
2,000 V
details the grounding resistance of a grounding electrode,
a ground rod, and its sphere of influence. 2,000 V
As the earth is (relatively) infinite in its size compared Phase C
to grounding systems as we know them, so too is its
capacity to absorb a virtually unlimited supply of current. FIGURE 4. An electrical system source connected in wye
Practically, however, this unlimited current to the earth is ungrounded—not connected to the earth.

j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 41


was no general practice about the question of operating or three times the normal voltage, culminating in insula-
electrical systems either with a grounded neutral or with tion failure. Dewey went on to write, “The evidence was
the neutral isolated [16]: not conclusive at that time and perhaps is not conclusive
There was no decided difference in the results of today (1923), but there are certain fundamental prin-
operating either with the neutral grounded or ciples that seem to be reasonable definite and most of
ungrounded. As they (the electrical systems) grew them tend to show important advantages in favor of the
in extent, voltage surges began to make them- grounded neutral system” [16].
selves felt over wide areas, resulting in breakdown Note that Figure 5 is not the multigrounded neutral sys-
of insulation at various points. Any line-to-ground tem. Figure 5 refers to the connection to ground of the neu-
fault on an ungrounded electrical system will tral at the source transformer only or at all transformers.
result in voltage rise on the ungrounded phases of
1.7 per unit, which can lead to insulation or arrest- Ungrounded Versus Grounded Wye Three:
er failure from temporary overvoltage. In the case Phase Distribution Systems
of neutral instability, during ferroresonance, line to Ungrounded electrical distribution systems, whether
ground voltage can exceed 2.5 times normal volt- a single- or three-phase system, presented a problem
age on delta systems. In seeking a remedy, many of locating where a phase-to-ground fault occurred.
engineers grounded the neutral of their generators The inability to locate a phase-to-ground fault on an
or transformers. ungrounded electric distribution system resulted in the
The ideal solution would have been to install insulat- grounded system being preferred prior to 1923. Unground-
ing material of a higher rating. However, such a material ed electrical distribution systems normally would have
was not available in 1923. The lack of sufficient insulation ground-detection lights. A lamp would be connected to
to withstand the voltage surges resulted in grounding the each phase and to the earth. The lamp or lamps, depend-
electrical system at the generator or at the transformers. If ing whether it was a single- or three-phase system, would
more than one transformer were connected to the system be extinguished on the faulted phase. One could distin-
for transmission purposes, sometimes each transformer guish which phase but not where on the distribution sys-
was grounded. tem the fault occurred.
Any arcing fault on an ungrounded electrical system A method of temporarily changing an ungrounded
will result in the electrical system voltage rising to two system into a grounded system, thus enabling the fault
to be detected, was described by Ackerman [17] in 1923.
In the 1950s, a pulsing device was developed that, when
attached to an ungrounded electrical distribution system,
Phase A
would put electrical current pulses on the energized elec-
2,000 V trical system, which would allow someone with a sensi-
Phase B
tive ammeter to clamp around the conductors or, if the
2,000 V conductors were in a conduit, around the conduit. The
2,000 V
electrical pulse would hopefully have a stronger deflec-
tion of the ammeter on the conduit containing the faulted
Phase C conductor allowing one to find the fault location. The
present state of the art (2017) in detecting and locating
faults on delta systems, ungrounded delta systems, and
FIGURE 5. An electrical system source connected in wye grounded—
connected to the earth at one location only—unigrounded. high-resistance grounded systems are well advanced.

Utilizing the Neutral


In a wye transformer connection, the midpoint, the neutral
Phase A
point, can be connected to the earth as is shown in Figure 5
Phase B 25,000 V without using the neutral for any electrical loads. Figure 6
indicates the neutral is also connected to the earth, but the
25,000 V
Transformer 14,400 V neutral conductor is extended along with the phase con-
25,000 V
14,400 V ductors. The configuration shown in Figure 6 allows electri-
Phase C
cal loads and service transformers to be placed between
any of the three-phase conductors and the neutral.
14,400 V
This connection, phase to neutral, will force electric
current to flow over the neutral back to the transformer.
FIGURE 6. An electrical system source connected in wye with
neutral conductor grounded and a grounded conductor carried with So far, this electrical connection is acceptable if the neu-
phase conductors—connected to the earth at one location only— tral is insulated or treated as being potentially energized.
unigrounded. However, modifications will be made in the near future

42 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019


in the name of safety that will negate Georg Simon Ohm published the
the safety for the human and ani- results of his studies of resistance in
mals, especially cows, in the last half The requirements 1827 defining Ohm’s law where volts
of the 1900s. (V) equals the resistance (R) of the
In 1914, Jollyman et al. wrote about
of the original code conductor times the current (I) flow-
the Pacific Gas and Electric Compa- were based on ing in the conductor, V = R # I, which
ny’s practices, which included the uti- applies only to dc. If we simplify the
lization of the neutral in distribution good engineering complex calculations for ac to obtain
systems. Transformers are wound for an ease of understanding the prob-
only 57.7% of the insulation voltage
theory and generally lem by assuming that the impedance
requirements for a full voltage, phase- accepted good and capacitance of the distribution
to-phase transformer. This amounts to lines are negligible, we can apply
a substantial savings. In addition, there practice. Ohm’s law to obtain an estimate.
is only a one-phase bushing on the An example of the problem is if we
transformers. This is additional sav- assume that the lineman is working
ings over the costs of fully rated two- 5 mi from the substation and the resis-
bushing transformer and full transformer insulation ­rating. tance of the neutral conductor between the substation and
The savings equate to additional profits for the utilities [18]. the lineman was 1 X/mi and the neutral conductor was car-
The authors continued to cite additional savings in the rying 50 A, then the rise in voltage would be 250 V. Based
construction of the distribution line. The pin-type insula- on the average conditions of a distribution circuit at that
tor, the insulator screwed onto a wooden pin mounted in time, it was determined that if the neutral was grounded
a cross arm, was the only type that was available in 1904. every quarter of a mile, the maximum voltage between the
Savings were generated by applying only 57.7% of the volt- two grounds would be 35  V. Also, at that time, everyone
age rating to the insulator. Instead of having an unground- assumed that the voltage was the parameter that would
ed electrical system with 25,000 V between phases and the harm humans.
earth, they now had, with a grounded neutral, only 14,400 V The NESC requires a neutral to have at least four
to the earth from any phase. There was still between phas- ground connections in each mile. This multigrounding
es of 25,000 V, but the pin insulator was only stressed to of the neutral conductor resulted in what is known as the
14,400 V. This resulted in additional cost savings. multigrounded neutral distribution system. The outcome
This appears to be a sensible
move, but this electrical configura-
tion later led to other problems. In Clamp
3.25-in × 4.25-in × 5–7-in
hindsight, increasing the insulation 5,000-V Arrester 6,600-V Pin Cross Arm
rating would have been the correct Porcelain Insulator
method to resolve the problem and
protect the public and animals from
the dangers and hazards of stray
uncontrolled return neutral current
This dimension is increased

flow over the earth. Throttle Fuse


2–6 in

extended to the next pole.


to 4 ft if the secondary is
3–6 in

Distribution Systems

Multigrounded Neutral
The next major development in the
history of grounding occurred in ap­­
proximately 1915, when it was real-
ized that linemen were being injured
and/or electrocuted from working Lightning Arrester
on the neutral barehanded. T he Ground
neutral was grounded at a single
point at the substation transformer, Install the secondary ground
pipe 4 ft from the pole and bury
and, therefore, the lineman errone- the ground wire 1 ft below
ously assumed that it was safe to the surface of the ground.
handle the neutral conductor bare-
handed anywhere on the distribu- FIGURE 7. A pole-mounted two-bushing transformer with lightning arrester separately
tion system. connected to the earth with no connection to secondary conductors 1926 era.

j anuary /F e bruary 2019 œ IEEE Industry Applications Magazine 43


is that the neutral conductor is in parallel with the earth have been the defendant, thus there may be a difference
and the amount of current entering the earth cannot be of opinion. The author considers any continuous flow of
controlled and where in the earth this stray current flows man-made current in and/or over the earth to be danger-
cannot be defined. The way the NESC was written, you ous, hazardous, and unacceptable.
could have four grounds on the first four poles of a mile
and meet the requirement. The 2007 edition corrected Author Information
this oversight; however, it is not retroactive. Donald W. Zipse (don.zip@ieee.org) is with Electrical
It has been reported that Prof. Charles F. Dalziel, Uni- Forensics, LLC, Wilmington, Delaware. He is a Life Fellow of
versity of California at Berkeley, required his students to the IEEE. This article first appeared as “History of Ground-
participate in experiments to measure the human animal’s ing/Earthing Practices in the United States” at the 2017 IEEE
response to voltage and current by placing their feet into Petroleum and Chemical Industry Technical Conference.
a bucket of salt water and having them hold onto a con- This article was reviewed by the IAS Petroleum and Chemi-
ductor. Dalziel then applied varying amounts of current cal Industry Committee.
and measured their response. Edward Owens, a Gen-
eral Electric Company employee, was a student of Dalziel, References
confirmed that Dalziel did have his freshman students [1] L. J. Lanzerotti and G. P. Gregori, “Telluric currents: The natural
environment and interactions with man-made systems,” in Studies in
participate in determining the level of current that would Geophysics: The Earth’s Electrical Environment. Washington, D.C.: Nat.
harm a human. Dalziel stated in 1946, “perhaps the most Academy Press, 1986, pp. 232–258.
serious misconception concerns the effects of voltage ver- [2] H. R. Nelson, L. R. Denham, and D. J. Siebert. (1986, May 12). Tel-
luric and earth currents, lighting strike locations and natural resource
sus the effects of current. Current and not voltage is the exploration. 2014 AAPG Annual Convention and Exhibition. Houston,
proper criterion of shock intensity” [19]. Texas. [Online]. Available: http://www.searchanddiscovery.com/pdfz/
documents/2014/41332nelson/ndx_nelson.pdf.html
[3] Internet Encyclopedia of Philosophy. (2018). Thales of Miletus (c.
Wiring Transformer and Secondary 620 B.C.E.—c. 546 B.C.E.). [Online]. Available: http://www.iep.utm.edu/
Electrical Systems in 1926 thales/
Post wrote about the eastern and southeastern 11  coun- [4] T. D. Lockwood, “Earth wires: Or the earth as an electric circuit com-
pleter,” Trans. Amer. Inst. Electrical Engineers, vol. 1, no. 8, pp. 1–8, 1884.
ties of Wisconsin served by Milwaukee Electric Railway & [5] Elect. Engineer, vol. 8, no. 82, Oct. 1888.
Light Company where there were 21,000 farms. On 1 Janu- [6] Wikipedia. (2018). Electrical telegraph. [Online]. Available: http://
ary 1926, there were only 2,740 farms receiving electric en.wikipedia.org/wiki/Electrical_telegraph
[7] C. Sulzberger, “First Edison light at sea, the SS Columbia story, 1880–
service, 13% of the total [20]. The object of the utility was 1907,” IEEE Power Energy Mag., vol. 13, no. 1, pp. 92–101, Jan–Feb. 2015.
to discourage the use of motors and encourage the use of [8] N. Cawthorne, Tesla vs. Edison. New York: Chartwell Books, 2016.
lights and electric ranges. Operation of motors was prohib- [9] T. Shaughnessy, “PowerCet corporation,” Santa Clara, CA, no. 3, Sum-
mer 1997.
ited from sundown to 11 p.m. [10] Edison Tech Center. (2010). The accomplishments and life of Edwin
Figure 7 shows two-phase conductors supplying the two- Wilbur Rice, Jr., 1862–1935. [Online]. Available: http://edisontechcenter
bushing transformer from 1926. The secondary neutral is .org/rice.html
[11] K. T. Compton, “Biographical memoir of Elihu Thomson (1853–
connected to the earth at a remote distance from the pole 1937),” in Biographical Memoirs, vol. XXI. Washington, DC: National
where the lightning arrester is connected to the earth [21]: Academy of Sciences of the United States of America.
Up to 1923, only about 120,000 of the 6,250,000 [12] National Fire Protection Association, National Electrical Code. Bos-
ton, MA: National Fire Protection Assoc., 1968.
farms in The United States had been wired to use [13] A. L. Clapp, National Electrical Safety Code Handbook. Piscataway,
electricity. By 1930 according to a radio speech made NJ: IEEE, 1984.
by the General Electric Company’s President over [14] IEEE Guide for Safety in AC Substation Grounding, IEEE Standard
80-1986, 21 Mar. 1985.
radio station WGY… shows that only about one-tenth [15] IEEE Recommended Practice for Grounding of Industrial and Com-
of the farms are connected to public service electric mercial Power Systems, IEEE Standard 142-2007, 7 June 2007.
lines and in the second place, that only a small part [16] H. H. Dewey, “General considerations in grounding the neutral of
power systems,” Trans. Amer. Inst. Electrical Engineers, vol. XLII, pp.
of the power used on any farm is electric power. 405–416, Jan. 1923.
This low usage of electricity continued until the late [17] P. Ackerman, “Ground selector for ungrounded three-phase distribu-
1930s when there was an increase in the number of farms tion systems,” Trans. Amer. Inst. Electrical Engineers, vol. 42, no. 4, pp.
311–319, April 1923.
connected to the electrical distribution system. There were [18] J. P. Jollyman, P. M. Downing, and F. G. Baum, “Experience of the
few electric motors used on the farms. The motors that Pacific Gas and Electric Co. with the grounded neutral,” Proc. Amer. Inst.
were used were for water supplies and cream separators Electrical Engineers, vol. 33, no. 5, pp. 747–752, Apr. 1914.
[19] C. F. Dalziel, “Dangerous electric currents,” Trans. Amer. Inst. Electri-
[21]. With the low electrical usage, the amount of hazardous cal Eng., vol. 65, no. 8, pp. 579–585, Apr. 1946.
stray uncontrolled continuous flow of man-made electric [20] G. G. Post, “Important features of a successful plan for rural elec-
current over the farm was much lower than it is today. trification,” Trans. Amer. Inst. Electrical Engineers, vol. 45, no. 5, pp.
515–521, Jan. 1926.
[21] Subject Committee on Grounding, “Present day practice in ground-
Acknowledgments ing of transmission systems second report,” Trans. Amer. Inst. Electrical
This article contains the opinions of the author who has Engineers, vol. 50, no. 3, pp. 892–900, Sept. 1931.

testified for the plaintiff in cases where utility companies 

44 IEEE Industry Applications Magazine œ j anuary/F ebruary 2019

You might also like