Mounting and Commissioning
33 commssonng
[RL-PARALLE Setting parameter at address 5371 (secondary setting
value)
Rye Re Measured parallel resistance (secondary measured
value)
Prpur Popa Associated active power in p.u. for the measured
parallel resistance
Use DIGSI to set the parallel load resistance with parameter 5311 R1-PARALLEL and the calculated correction
value with parameter 5313 CORR. R1-PAR... Activate the protection function with parameter 5301 1008
SEF-PROT. = ON,
NOTE
oie
You can set parameter 5311 R1-PARALLEL to the resistance R, measured in the idle state,
The following example provides orientation for the size of the correction value. The secondary values depend
‘on the system conditions. Therefore, they can deviate from the values in the example,
The load resistance converted to the secondary side was 61 @ (parameter 5311 RI-PARALLEL). The
following table shows the measured values:
[Measured value R SEF
[Measured value active power
a)
ae state R610
Maxiraum active power (or R= 59.10
lexample, 0.85 FIS,)
OFS,
BBS,
4 Rip-Riy 5910-619
AUPARALLEL 7, -P,,, "818 086-0 ~ 000664417
CORR. R-PAR.
In the example, you would set parameter $313 CORR. RL~PAR. to the value -0.037
3.3.22 Creating Oscillographic Recordings for Test
General
[At the end of commissioning, closing tests may be carried out to assure the stability ofthe protection during
the dynamic processes. A maximum of information on protection behaviour is supplied by fault recordings.
Prerequisite
‘Along with the possibility of storing fault recordings via pickup of the protection function, the 7UME2 also has
‘the capability of capturing the same data when commands are given to the device via the service program
DIGSI, the serial interface, or a binary input. For the later event, >7r'ig. wave. Cap. must be allocated to a
binary input. Triggering of the recording then occurs, for example, via the binary input when the protected
object is energised.
‘Such externally started test fault recordings (.., without a protection pickup) are handled by the device as
rrormal fault recordings, i. for each measurement record a fault log is opened with its own number, for
unequivocal allocation, However, these recordings are not displayed in the fault indication buffer, as they are
not fault events.
Triggering Oscillographic Recording
To tigger test measurement recording with DIGSI, click on Test in the left part of the window. Double click
the entry Test Wave Form in thelist of the window.
488 SIPROTEC 4, 7UM62, Manual
(€53000-61176-C149- Edition 08.2078Mounting and Commissioning
33 Commissioning
a co es aa oy]
Figure 3-40 Triggering oscillographic recording with DIGSI—Example
A test measurement record is immediately started. During recording, an indication is given in the left part of
the status bar. Bar segments additionally indicate the progress of the procedure.
For display and evaluation of the recording, you require one of the programs SIGRA or ComtradeViewer.
SIPROTEC 4, 7UM62, Manual 465