Project: DuPont india Knowledge Centre, Hyderabad,
(Owner: E.1. DuPont india Private Ltd, Hyderabad
;nnexure fo scope of works to be consider
all vendor.
revised of
Engine Make & Alternator model no. to be funished.
Rating of the DG set shall be sullable for 1200 KW of power for continuous and variable
loads to operate on 24/7 operation.
Minimum expected running hour will be 1500 hours / year.
Ventilation i required for radiator cooling and enclosure cooling if required shall be
provided by the Vendor including necessary MCC's, starters and cablings et including
provision for future DG sets,
Make of Pane! will be one of approved / finalized panel vendor.
\Vendor shall provide one day tank each of 990 Itrs capacity and one indermediate tank of
960 ltrs and one spl tank of 600 Irs to be provided. Necessary valves, starters and MCC
shall be provided by the Vendor.
individual Nied Batteries for DG Staring considered inside the enclosure. Battery charger
shall be supplied by the Vendor and shall be mounted inside the enclosure,
Percentage block foading with TVD and recovery time shall be canfirmed by the Vendor.
Self supporting laitce type structural steel support for exhaust pipes shall be considered
‘with the individual pipes from each of the DG sets shall be considered.
MS Thickness of Fuel tank shall be minimum 3mm.
‘Vendor shall guarantee 75 dBA max during day time and 70 dBA during night time of
noise level at 1.0 mtr from the acoustic enclosure
Vendor to assess tho sizes and quantities for Control cables and shall submit a detalled
break up along with the offer including costing based on the layout drawings already
issued.
‘The Veniior shall carefully refer to the attached testing schedule for both Factory
‘Acceptance Test and Site testing, The testing requirement shell be fully complied and all
the necessary equipments, infrastructure and testing devices etc as required shall be
included in the commercial offer.
‘Alload bank of 2000 kW shall be used for carrying out tests at site and factory. If the
‘Vendor is unable to use 1 1kV load bank: itis suggested to use LV load bank by using a
4433/1 1kY step up Transformer.
All Vendors to include 2 years spare parts & consumable includes tools spare parts shall
bbe considered for 2000 hours / year.
Manual primary fuel pump is accepted by Consultant,
Last Modified: 14” May 07 1of2 Venkataramanan Associates
Servelec ConsultantsProject: DuPont India Knowledge Centro, Hyderabad.
Ownar: €1, DuPont India Pvt Ltd, Hyderbad
SI. No. Description Unit Particulars: Remarks,
40 | Engine/Ref Standards POTS FORA SILT Spa; pag
14 Name of manufacturer MH
12 Number of diesel engines ‘| Nos 4
13 Power rating of the engine at ste | KW
conditions 1660
[1.4 | Prime duty rating ofthe engine at | Kw
Sto conditions 1660
15 Model of te engine SIR Pree ~S
164 Gross engine BHP BHP
15.2 | Gross engine kW. kw 1674 (Mech)
1.5.3 | No. of eylinders nos 16
1.6.4 __ | Cylinder arrangement Vv
155 | Aspiration A
1.8.6 | Direction of rotation Anil clockwise Foor] daive.
15.7 | Operation speed RPM {S00
16.8 Maximum over speed allowed RPM 16sD
1.6.9 Maximum engine rating at site with | kW.
10% overload \+60
1.5.40 Mechanical efficiency of the % ‘
engine 4B i),
| 15.11 | Thermal efficiency of the engine [% Su 4,
16 Engine mounting Base. fanene.
1.6.4 Maximum bending moment kgf-m eee
7 Exhaust eysiem ae
ATA Exhaust system back KPa 6
pressure(max)
WZ ‘No. of exhaust outlets required No. 4
1.73 No. of silencers supplied with each | No. 4
engine
174 Noise reduction provided by the | dB(A)
silencers +S
175 Exhaust gas flow rate CFM 136 6y
176 Exhaust gas flow rate M3/Min_ 3 8 F