Connecting External
Data Acquisition Systems (DAS)
to Solectria
PVI 23TL, PVI 28TL
and PVI 36TL Inverters
WARNING: This indicates a fact or feature very important for the safety
of the user and/or which can cause serious hardware damage if not
applied appropriately. Use extreme caution when performing this task.
Care must be taken when daisy chaining the inverters as shown above
utilizing a Shielded Twisted Pair Modbus cable such as Belden 9841.
Star or T connections should be avoided.
The shield continuity should be maintained for the entire length of the
daisy chain and should only be connected to ground (GND) at the Data
Acquisition System (DAS).
DOCR-070585-A 2|P a g e
Quick Reference Guide (Rev A) DAS PVI 23-28-36TL
Fig. 2: The above image shows the Modbus (RS-485) cable connection where
the Modbus daisy chain ends. Notice how the cable shield is not landed inside
the inverter.
DOCR-070585-A 3|P a g e
Quick Reference Guide (Rev A) DAS PVI 23-28-36TL
4. If the inverter is the last device in the daisy chain, make sure the Modbus
termination switch S402 is in the ON position (Up towards the LCD) for
Modbus termination. Do not turn the switch to the ON position in any of
the other inverters.
5. Only connect the cable shield to ground (GND) at the DAS. Do not connect
the shield to any of the inverters.
Fig. 3: Notice how the cable shield is daisy chained together and not landed
inside the inverter. S402 is in the OFF position, or down towards the Phoenix
connector when the inverter is in the middle of the daisy chain.
Warning: Risk of Electric Shock.
Make sure all shield wires are properly secured and insulated to
prevent shorting to any other components inside the inverter.
DOCR-070585-A 4|P a g e