CATALOGUE
> 2015-2016
Reliable power
for a sustainable world
Reliable power for a sustainable world
Contents
Key 4 Sentinel Pro 48
Master HP 88
Areas / Scope
Modular UPS 104
SoHo Area 18
Multi Power 106
Data Centre Area 19
Multi Guard 112
E-Medical Area 20
Multi Guard Industrial 116
Industry Area 21
Transport Area 22
CPSS 120
Emergency Area 23
Central Supply Systems CSS 122
UPS Standard 24
Transfer Systems 126
iPlug 26
Multi Switch 128
iDialog 30
Multi Switch ATS 130
iDialog Rack 32
Master Switch STS Single-phase 132
Net Power 34
Master Switch STS Three-phase 134
Vision 36
Master Static Bypass 138
Vision Rack 40
Vision Dual 44
Power solutions 142 Connectivity 160
MBB100A 159
Services and contacts 178
4
1
UPS with UL certificate UPS classification Eco Level = 1
Airport/Shipyards
www.riello-ups.com 5
Riello Elettronica
and Riello UPS.
We transform energy, continuously.
6
BUSINESS UNITS
POWER
Riello UPS A global leader in power
continuity thanks to a comprehensive
range of UPS (Uninterruptible Power
Supplies).
AUTOMATION
Cardin A wide range of automation
systems for access control.
POWER
23
RPS S.p.A.
RIELLO RIELLO UPS Ltd
ENERDATA
CONSTANT
POWER SERVICES
CONTROLLED COMPANIES RIELLO TDL
RIELLO UPS
AUSTRALIA
800
RIELLO UPS
GmbH
RIELLO PCI
RIELLO POWER INDIA
SYSTEMS
EMPLOYEES RIELLO UPS
RIELLO
RIELLO ELETTRONICA ASIA
80
ONDULEURS S.p.A.
RIELLO UPS
SINGAPORE
BANATTIKA
(Riello UPS Romania)
BUSINESS COUNTRIES
ALARM
ENERBLU
9
INTERNATIONAL
COGENERATION
SYSTEM
AVS
CARDIN ELECTRONICS
ELETTRONICA
PRODUCTION SITES BELGIUM
GAMMA
CARDIN
ELETTRONICA SYSTEM SAFETY
Figures 2014 DEUTSCHLAND
CARDIN CEIMU CARDIN
AND SECURITY
ELETTRONICA ELETTRONICA
FRANCE
AUTOMATION
www.riello-ups.com 7
Riello UPS: Ducati sponsor since 2007
Perfect synergy
High performance
Unlimited energy
Italian technology
This is what we have in
common with Ducati
8
Riello UPS is the official sponsor of the Ducati Corse
MotoGP Team. Our partnership with Ducati provides
Riello UPS with high levels of visibility and worldwide
prestige. The two companies share values and
principles that unite them in perfect synergy.
www.riello-ups.com 9
Riello UPS
Brand Values
10
Energy and
sustainability
Reliable power for a sustainable world
Riello UPS manufactures efficient Riello UPS has always been a strong
solutions that ensure power quality supporter of the Code of Conduct
and business continuity, guaranteeing on Energy Efficiency and Quality of
power supply and the correct operation AC Uninterruptible Power Systems, a
of systems even in the event of critical document signed by the major European
situations. manufacturers of UPS addressed to the
European Commission.
Riello UPS is constantly implementing It sets out the energy efficiency targets
new solutions into its products that are for power ranges from 300 VA to >200
aimed at reducing power consumption kVA, from 25% to 100% loads. Riello UPS
by increasing efficiency, and actively was also the first European Manufacturer
participating in the promotion of to identify its products in terms of ECO
sustainable development. To this end energy efficiency ratings.
the company also sets up environmental
projects and makes large investments in
the development of new technologies for
harvesting clean and renewable energy
sources. Riello UPS ‘s social commitment
aims to help the present as well as shape
a bright future, combining the inevitable
need for energy with environmental
protection.
The environmental management system
employed by Riello UPS is ISO14001
certified.
www.riello-ups.com 11
ECO ENERGY LEVELS availability of the services provided. The ECO Energy Level is a tool
Equipment must operate at the highest implemented by Riello UPS to help
Riello UPS uninterruptible power possible levels of efficiency to reduce customers to identify the products
supplies power some of the most the strain on critical power supplies and with the highest levels of efficiency in
critical data centres and servers in use minimise the effect on the installation terms of energy protection; the 6 levels
today. Within these area. have recently been updated to comply
environments, Riello UPS models have always been with the stringent new efficiency levels
energy management compliant with the highest levels of required by the CoC.
is critical. efficiency in terms of energy protection In addition to this, the availability of
Running costs must and are classified according to a scale Smart Mode provides a further method
be minimized without with 6 levels, corresponding with the for improving efficiency by furthering
compromising efficiency value of the UPS with respect Eco Energy Levels assessment.
resilience, i.e. the to the European Code of Conduct; this is
ability to adapt to adverse external known as the Eco Energy Level. Riello UPS ‘s Eco Energy Level is more
conditions whilst ensuring complete than just a concept; it is a system that
demonstrates how the UPS that get the
highest marks (levels 4, 5 and 6) are more
efficient, and therefore more beneficial
economically and environmentally.
ECO Mode
The Eco Energy Level system
ECO
Mode demonstrates both how the most
efficient UPS provide energy savings
that allow the cost of their purchase to
CoC level
ECO
Mode
> standard CoC be recovered quickly with respect to
standard efficiency UPS, as well as how
their use leads to significant reductions
ECO = standard CoC in carbon emissions into the atmosphere.
Mode
An Energy Saving Calculator is available
at www.riello-ups.com to help calculate
the energy and cost savings as well as
< standard CoC the reduction in CO2 emissions that can
be achieved by using Riello UPS Eco
1 6
Energy Level products.
2 5
3 4
12
UPS SMART GRID READY a high level of safety, continuity and systems, variable power generators and
quality of supply. above all they can be combined with
Smart grids not only introduce new renewable energy sources.
concepts to power grids but also new In order to be “smart grid ready”, UPS
 business opportunities with regards must allow for the implementation of
to installations with UPS: batteries power accumulation solutions, and at
The evolution of electrical power grids of uninterruptible power supplies the same time ensure extremely high
is a key element for achieving greater represent significant investments, but levels of efficiency. They must also be
sustainability; particularly fundamental they are only partially used. Using able to independently select the most
are the power management systems for these distributed power accumulators efficient operating method based on
balancing supply and demand, for using and generating business in power the status of the grid. They must be
energy in the most sustainable and accumulation scenarios will become able to electronically interface with the
efficient way: smart grids. fundamentally important. energy manager using the smart grid
Smart grids are nothing more than Smart grids also mean the integration communication network. Always open
power grids that efficiently integrate and of different energy sources, two-way to technological innovation, Riello UPS
manage the behaviour and actions of all flow, information exchange grids and has invested in research and technology
the connected consumers (generators, centralised management. In this new to develop smart grid ready products,
output points, etc.), with the aim of scenario installations with UPS can take creating the Master HE, Master HP,
ensuring the economically efficient on new roles, becoming virtual power Master MPS and Multi Sentry ranges, the
operation of the electrical system, with plants, decentralised power accumulation first smart grid ready UPS on the market.
SMART
Meter
ENERGY MANAGER Photovoltaic Central
System
Battery set
SMART
Meter
SMART
Meter
UPS Riello
Server room
SMART
Meter
www.riello-ups.com 13
Guide to choosing a UPS
Choose the main parameters required for your installation and discover which UPS in the Riello
range can meet your needs. Further details are provided in the dedicated pages for each product.
Internal batteries
Transformerless
Manual bypass
Transforbased
Parallelable
Dry contact
DataCentre
Emergency
Tower / Rack
Transport
e-Medical
Industry
UPS VFD
/ Modular
UPS VFI
1/3 - 1
1/3 - 3
RS232
UPS VI
# Slot
Soho
1-1
3-3
EPO
USB
iPLUG T -
iDIALOG T -
iDIALOG RACK R
NET POWER T Q -
VISION T opt 1
MASTER HP T std 2
MASTER HE T std 2
MASTER HP UL T std 2
MULTI SWITCH - - - R - - - - - - 1
14
Key A 3.3 - 4 - 5 - 6 - 8 - 10 kVA E 5 - 6 kVA J 1÷8 x 15 kVA opt optional
B 6.5 - 8 - 10 kVA F 6.5 - 8 - 10 kVA K 1÷8 x 20 kVA std standard
C 6 kVA G 3ph input only Q 1000 ÷ 2000 VA
D 8 - 10 - 15 - 20 kVA H Except 30 kVA R 1 ÷ 28 x 42 kW
+ redundancy
Power info
UPS page
1200 kVA
1000 VA
1100 VA
1200 VA
1500 VA
1600 VA
2000 VA
2200 VA
3000 VA
3300 VA
4000 VA
5000 VA
6000 VA
6500 VA
8000 VA
100 kVA
120 kVA
125 kVA
160 kVA
200 kVA
250 kVA
300 kVA
400 kVA
500 kVA
600 kVA
800 kVA
400 VA
600 VA
700 VA
800 VA
10 kVA
12 kVA
15 kVA
20 kVA
30 kVA
40 kVA
60 kVA
65 kVA
80 kVA
26
30
32
34
36
40
44
48
52
56
62
66
70
80
88
92
96
100
122
122
102
R 106
J 112
K 116
138
128
130
132
134
www.riello-ups.com 15
Options and accessories compatibility table
Identify the UPS that supports the software and accessories your installation requires.
MULTICOM 352
MULTICOM 372
MULTICOM 382
MULTICOM 401
NETMAN 204
MODEM GSM
MULTIPANEL
MODEM 56k
Modem GPRS
RTG 100
iPLUG
iDIALOG
iDIALOG RACK P P P
NET POWER L P L P L P L P L L
VISION
VISION RACK
VISION DUAL
SENTINEL PRO
SENTINEL POWER
MULTI SENTRY
MASTER MPS
MASTER HP
MASTER HE
MASTER HP UL
MASTER INDUSTRIAL
MASTER FC400
MULTI POWER
MULTI GUARD
MULTI SWITCH
16
Key L 1000 - 1500 - 2000 VA P
In combination with
communication card adapter
M 3300 - 4000 VA
N 20 kVA 1:1, 40 kVA 3:3
O Included only in version N
Accessories info
MAN. BYPASS 16A RACK
Other specific
options can be
found on the
ACRONYMS
dedicated product
UPS page
MBB 100A
MBBR 16A
MBBR 16A
pages
MBB 16A
MBB 16A
iPLUG IPG 26
iDIALOG IDG 30
VISION VST 36
MASTER HP MHT 88
MASTER HE MHE 92
MASTER HP UL MHT UL 96
www.riello-ups.com 17
RECOMMENDED PRODUCTS
iPlug Net Power
Sentinel Pro
Sentinel Dual
Low Power
SoHo Area
REFERENCES
Italy Portugal
• Consip • Intermarché
• Carrefour
France
• Dico / Coop
FEATURES APPLICATIONS • Carrefour
Sweden Australia
• Ikea
• Low energy consumption • Entertainment systems • Toys “R” us
• Small footprint • Personal computers Germany • Lonely Planet
• Hilton Hotel
• Silent operation • xDSL connections United
• Mc Donald’s
Kingdom
• Advanced communication • POS systems UAE • ASDA
• Royal Intern.
The SoHo market is becoming more and efficiency and lowest environmental them off when not required.
more important, covering the market impact, whilst still providing the best The entire Off-line range offers maximum
sector that includes professionals, small possible performance. silent operation thanks to the employment
businesses and freelance professionals of high frequency components and the
working from home. No less important SMALL FOOTPRINT absence of moving parts, the noise level is
are domestic consumers, with the rise of The small footprint of Riello's UPS allow equal to 0 dbA.
entertainment devices and media centres them to be easily installed anywhere in
requiring ever higher quality power supply the office work space, without creating any ADVANCED COMMUNICATION
and protection from interference and interference with customer areas. There Riello UPS's UPS are equipped with USB
black-outs. are also rack versions. and RS232 communication ports, allowing
for full management and communication
LOW ENERGY CONSUMPTION SILENT OPERATION with the UPS to preserve data and make
Reducing energy consumption has become In the workplace and above all in the your IT systems secure.
an economical necessity as well as an home, the silent operation of equipment UPS with LI and OL technology are also
environmental obligation. It is therefore is very important. This is why our UPS equipped with expansion slots to house
essential to choose UPS that employ green are equipped with a sophisticated the various different communication
technology such as those made by Riello microprocessor control system able to options offered by Riello UPS.
UPS, designed to achieve the best energy reduce the speed of the fans and switch
18
RECOMMENDED PRODUCTS
Multi Sentry Multi Power
M
O
DU
LA
R
Master HP/HE Master MPS
Datacentre Area
REFERENCES
China Italy
• China Mobile • Poste Italiane
• Telecom Italia
Korea
FEATURES APPLICATIONS • ENI
• Telecom
• Enel
Germany
• Extremely high availability • Data centres • Sun
Malaysia
• CSF
• Low energy consumption • Server farms Microsystems
• German Spain
• Small footprint • Large databases Government • Globalswitch
• Flexible configurations • Telecommunications and IT • Deutsche Bank • Telefonica
• Allianz
• Banks and insurance United
India Kingdom
companies • Samsung India • ServerChoice
Electronics • UniLever
• Sify
Data centres represent one of a company's this level of availability can be achieved. provide the best energy efficiency and
most fundamental assets: a structure on The UPS must be versatile, compact and lowest environmental impact possible, with
which the entire organisation depends. parallelable in order to provide the required maximum performance. The Eco Energy
This is why it is important to ensure these flexibility; they should be able to adapt to all Levels help identify the most highly efficient
systems are both functional and reliable, types of load, both inductive and capacitive, Riello UPS products.
starting from the correct electrical layout and should also be able to integrate with
of the system and following precise quality the other components in the system (e.g. PHYSICAL SPACE
criteria. electrical generators). It is critical to optimise the space available
in data centres. Virtualising servers helps,
AVAILABILITY ENERGY CONSUMPTION but it is also useful to choose UPS with
According to the TIER standard, system Reducing energy consumption has become small footprints in order to avoid wasting
availability should fall between 99.9 and a necessity for all businesses as well as space. The Multi Sentry and Master HP UPS
99.999%: downtime is not an option. Using an environmental concern. It is therefore ranges have some of the smallest footprints
high quality Riello UPS uninterruptible fundamental to choose a UPS supplier available on the market.
power supplies in a well-designed system, that offers green products designed to
www.riello-ups.com 19
RECOMMENDED PRODUCTS
REFERENCES
Austria Italy
E-Medical Area • Country
Hospital Graz
• Ospedale le
Molinette - Turin
• Krankenhaus • Ospedale
(LKH) Salzburg Cardarelli -
Naples
France
• Clinique De La Korea
Sauvegarde - • E-HWA
FEATURES APPLICATIONS Lyon University
• Tropical Hospital - Seoul
• Extreme protection for • Back up of auxiliary Medicine Centre
Spain
- Marseille
critical applications power supply systems • Civil Hospital -
• Biomedical
Research Park -
• High resilience • Operating theatres Lyon
Barcelona
• Compliant with specific • Hospital services Germany Sri Lanka
• Klinikum Süd
standards Nürnberg
• Apollo Hospital
- Colombo
• Universität-
klinikum Aachen
More and more sectors of the economy providing compatibility with: IP protection of architecture aimed at increasing the
now rely on technology. Even medical and levels, input/output electrical isolation, availability and resilience of the system
healthcare services now generally rely on the possibility of housing internal isolation (parallelability and redundancy of power
digital technologies. Due to the critical transformers and auxiliary monitoring supply in accordance with the TIER standard).
nature of these applications, which are systems for electrical values. Electrical continuity cannot be guaranteed
closely linked with personal well being, Riello UPS responds to all needs with unless it is supported by suitable
the services and infrastructure must be products suited for all power and safety monitoring and control systems, which
designed to ensure maximum levels of requirements connected with different should be flexible and adaptable to the
reliability and operating safety. applications. various systems and protocols installed
in healthcare infrastructures. Riello UPS
SAFETY RELIABILITY develops, tests and perfects its products as
According to the standards that apply to In a medical context reliable services are well as the different monitoring and control
the sector, all medical equipment must critical and therefore the choice of UPS systems in-house, guaranteeing complete
adhere to stringent safety standards. based should favour the best technological flexibility with different protocols and a
on the type of application, the UPS must solutions (on line dual conversion). These rapid response to any interface problems.
ensure immunity from external influences, guarantee compatibility with all levels
20
RECOMMENDED PRODUCTS
M
O
DU
LA
R
Master SuperCaps UPS
Industrial
Industry Area
REFERENCES
Germany Spain
FEATURES APPLICATIONS • Mannesmann • Repsol
• Audi
Sweden
• Adidas
• Ericsson
• Extremely high reliability • Oil & Gas India • Saab
and strength • Power Generation, T&D • Metlon Industry
Russia
• Customisable • Water treatment Italy • Ece
• Compatible with long • Instruments and process • Benetton
UK
Treviso
autonomy times monitoring • Pirelli Milano
• Glaxo Smith
Kline
• ModBus and Profibus • Emergency systems • Ilva
• Corus
• La Doria
support • Fincantieri
Complex industrial installations are particularly control information cannot be tolerated. This special wiring (halogen free, etc) is often
critical and therefore require an exceptional is why high quality Riello UPS uninterruptible required, as well as fastening components
level of resilience and reliability under all power supplies are used: versatile, and systems that are highly resistant to
operating and environmental conditions. technologically advanced and suitable for mechanical stresses.
The UPS is a fundamental asset for guaranteeing operation in varied environmental conditions
service continuity and system safety. Riello (temperature, humidity, vibrations, FLEXIBILITY AND CUSTOMISATION
UPS's industrial solutions have been protecting fluctuating power supplies, etc.). UPS Riello are flexible, i.e. they can be adapted
oil and gas infrastructures, power stations to different power sources (single phase,
and other industrial installations for decades, STRENGTH three-phase, with or without neutral), they
making Riello UPS the industrial partner for In the industrial sector UPS are often required can be configured with isolation transformers
every business in the sector. to provide a high level of compatibility with not only at the output but also at the rectifier
stringent mechanical standards (IP protection and bypass. They are compatible with various
RELIABILITY level > 21, protection against vibration, remote control communication protocols
Operating continuity is fundamental in the structural rigidity). In addition to this, in and can be customised to the specific
industrial sector; a power shutdown or a order to fulfil general requirements, the use requirements of any system.
breakdown in the supply of monitoring/ of filters, isolated electrical connectors and
www.riello-ups.com 21
RECOMMENDED PRODUCTS
M
O
DU
LA
R
Master MPS Master FC400
REFERENCES
The infrastructure used in the transport and compatible with various remote control RELIABILITY
sector is increasingly technologically communication protocols, which should be Operational continuity is strategic to the
advanced and complex. At the same time complete, rapid and effective. transport sector. Downtime with regards
however, it must also provide an exceptional to power supply or monitoring/control
level of resilience and reliability under all GLOBAL STRENGTH information cannot be tolerated.
operating and environmental conditions. The need to ensure service continuity Continuity can be guaranteed by using high
UPS and power continuity play a major role requires high levels of compatibility with quality UPS that are versatile, technologically
in guaranteeing continuity and excellence in stringent mechanical standards (IP protection, advanced and parallelable, which are able
the services provided. vibrations, structural rigidity). The use of air to operate under critical environmental
filters, isolated electrical connectors and conditions (temperature, fluctuating power
FLEXIBILITY OF INSTALLATION special wiring is often required in order supplies, different types of load, etc.). Riello
Every application in the transport infrastructure to fulfil general requirements, as well as UPS with its range of transformer-less and
sector has its own particular specifications and fastening components and systems that are transformer-based products is able to satisfy
associated reference standards. highly resistant to mechanical stresses. Riello the most diverse and complex requirements
It IS therefore fundamental that the UPS are UPS is able to offer tailor-made solutions that to ensure operating continuity and reliability
adaptable to different power sources (single satisfy the requirements of special standards for users.
phase, three-phase, with or without neutral), or particular operating conditions.
22
RECOMMENDED PRODUCTS
Sentinel Pro
Sentinel Dual
High Power
CSS 1h e 3h
Emergency Area
Riello UPS centralised power supplies are • smoke extraction equipment, • Advanced diagnostics (information on
designed for buildings subject to fire pre- • carbon monoxide detection systems, display panel)
vention safety standards. • specific safety systems in sensitive • Interface device to provide information
Designed and built in compliance with areas. remotely
standard EN 50171 CPSS (Central Power • High short circuit current.
Supply Systems) and other guidelines. The main features of Riello UPS solutions
These systems are designed mainly to pro- are summarised here: This is joined by Riello UPS's long term
vide emergency lighting in the event of a • Regulatory compliance experience in emergency applications,
power blackout, however, they can also be • Autonomy of up to 3 h (and beyond on with thousands of installations all over the
used for other emergency systems, such as request) world.
for example: • Battery recharge time under 12 hours
• automatic fire prevention systems, • Battery monitoring system
• alarm units and emergency detection • Galvanic isolation of input/output
systems, (optional)
www.riello-ups.com 23
24
UPS Standard
www.riello-ups.com 25
SOHO
iPlug
VFD 5
TYPE
1:1 600-800 VA
The iPlug series is the ideal solution for Versatile, robust and
HIGHLIGHTS protecting household and small office contemporary design
systems. Its compact size and versatility The iPlug's compact and ergonomic design
• Compact (push-button operation, LED status panel allow it to be easily installed in professional
and user replaceable batteries), make and domestic environments.
• Versatile iPlug easy to install within a domestic iPlug is extremely versatile and its
environment to protect systems from surges innovative cable management feature
• Robust and blackouts. ensures a tidy, easy to manage installation.
When the mains fails, the load is powered
• Contemporary design from a pseudo-sine wave inverter, to provide Advanced communications
sufficient runtime for computer system PowerShield3 software allows for the safe
• Auto restart shutdown using PowerShield3 software, shutdown of connected IT systems on mains
which can be downloaded free from power supply failure.
• Battery swap www.riello-ups.com PowerShield3 provides efficient and intuitive
26
UPS management using bar chart displays versions, Mac OS X, Linux. CONFIGURATOR FOR
for important operating information. • Plug and play function. MODEL SELECTION
Auto restart 2-YEAR WARRANTY
The UPS automatically restarts upon the VA power
Load type rating *
restoration of mains power after having
shut down once the batteries have run out Personal computers 250
following a black out (Auto restart). LCD Monitors 70
Scanners, printers 200
Environmental protection Modems, TVs, DVD players,
ECO Line PlayStations, Hi-Fi systems, 50
With energy savings in mind, the iPlug range telephones, Faxes
features a shut-off button to reduce energy Laser printers ** 200
consumption during periods of prolonged * Estimated average value.
inactivity. ** iPlug filtered output power supply is recommended.
Applications
LCD monitors, personal computers, video
terminals, printers, scanners and fax
machines. AVAILABLE SOCKETS AVAILABLE OPTIONS
Features SOFTWARE
• Compact and ergonomic PowerShield3
• 5 sockets protected against black-outs
SCHUKO FRENCH ITALIAN BRITISH
• 3 sockets protected against overvoltage SOCKET SOCKET SOCKET SOCKET
for the supply of loads with larger CEE 7/7P CEE 7/5 CEI 23/16 BS1363A
www.riello-ups.com 27
MODELS IPG 600 IPG 800
POWER 600 VA/360 W 800 VA/480 W
INPUT
Nominal voltage 220-240 Vac
Input voltage tolerance
230 Vac (+20/-25%)
frequency
Frequency 50/60 Hz with automatic selection
OUTPUT
Voltage during
230 Vac (+20/-25%)
mains operation
Voltage during
230 Vac (+/- 10%)
battery operation
Frequency during
50 or 60 Hz (+/- 1%)
battery operation
Waveform Pseudo Sinusoidal
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 6-8 hours
OTHER FEATURES
Net weight (kg) 3,7 4,1
Gross weight (kg) 4 4,4
Dimensions (WxDxH) (mm) 185 x 313 x 99
Packaging dimensions
260 x 380 x 140
(WxDxH) (mm)
Protections Excessive low battery - overvoltage - short circuit
Communications USB
Output sockets 6 sockets (Schuko or Italian or French or British) + 2 IEC 320 C13
EN 62040-1-1 and Directive 2006/95/EC; EN 62040-3
Standards
EN 62040-2 and Directive 2004/108 EC
Certificates CE; GS/NEMKO on Schuko version
Operating temperature 0 °C / +40 °C
Colour Black
Altitude and relative humidity 6000 m max altitude, < 95% non-condensing
Equipment provided power cable, user guide
28
www.riello-ups.com 29
SOHO
iDialog
VFD 5
TYPE
1:1 400-1600 VA
HIGHLIGHTS The iDialog range is the ideal solution for Advanced communications
protecting PCs and peripherals in the home PowerShield3 software allows for the safe
and office. shutdown of connected IT systems on mains
• Compact iDialog is easy to install and economic to run power supply failure. PowerShield3 provides
for protecting: efficient and intuitive UPS management
• Silent operation • IT equipment such as PCs, Media Centres using bar chart displays for important
and peripherals, TVs, Home Cinema operating information.
• Contemporary design systems, Satellite and Digital Terrestrial
Receivers and DVD recorders and players; Auto restart
• Auto restart • xDSL modems and routers; The UPS automatically restarts when the
• Small home appliances. mains power supply is restored, after auto
• Low power power.
consumption Silent operation
The UPS is silent in operation (0dBA) thanks ECO Line environmental protection
to its use of a fan-less design and high With energy savings in mind, the iDialog
frequency components. range features a shut-off button to reduce
30
MODELS IDG 400 IDG 600 IDG 800 IDG 1200 IDG 1600
POWER 400 VA/240 W 600 VA/360 W 800 VA/480 W 1200 VA/720 W 1600 VA/960 W
INPUT
Nominal voltage 220-240 Vac
Input voltage tolerance
230 Vac (+20/-25%)
frequency
Frequency 50/60 Hz with automatic selection
OUTPUT
Voltage during
230 Vac (+20/-25%)
mains operation
Voltage during
230 Vac (+/- 10%)
battery operation
Frequency during
50 or 60 Hz (+/- 1%)
battery operation
Waveform Pseudo Sinusoidal
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 6-8 h
OTHER FEATURES
Net weight (kg) 3,2 3,4 6,6 6,9
Gross weight (kg) 3,7 4,1 8,1 8,6
Dimensions (WxDxH) (mm) 90 x 232 x 192 93 x 310 x 270
Packaging dimensions
138 x 300 x 278 170 x 400 x 370
(WxDxH) (mm)
Protections Excessive low battery - overvoltage - short circuit
Communications USB USB + RS232
Output sockets 4 IEC 320 C13 6 IEC 320 C13
EN 62040-1-1 and Directive 2006/95/EC; EN 62040-3
Standards
EN 62040-2 and Directive 2004/108 EC
Certificates CE
Operating temperature 0 °C / +40 °C
Colour Black
Altitude and relative humidity 6000 m max altitude, <95% non-condensing
Standard equipment 2 output power supply cables, user manual
www.riello-ups.com 31
SOHO
iDialog
Rack
VFD 5
TYPE
1:1 600-1200 VA
32
MODELS IDR 600 IDR 1200
POWER 600 VA/360 W 1200 VA/720 W
INPUT
Nominal voltage 220-240 Vac
Input voltage tolerance
230 Vac (+20/-25%)
frequency
Frequency 50/60 Hz with automatic selection
OUTPUT
Voltage during
230 Vac (+20/-25%)
mains operation
Voltage during
230 Vac (+/- 10%)
battery operation
Frequency during
50 or 60 Hz (+/- 1%)
battery operation
Waveform Pseudo Sinusoidal
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 6-8 h
OTHER FEATURES
Net weight (kg) 5,5 9
Gross weight (kg) 7 10,5
Dimensions (WxDxH) (mm) 438 x 230 x 87 438 x 300 x 87
Packaging dimensions
503 x 330 x 211 503 x 400 x 211
(WxDxH) (mm)
Protections Excessive low battery - overvoltage - short circuit
Communications USB + RS232
Output sockets 2 IEC 320 C13 + 3 Shuko
EN 62040-1-1 and Directive 2006/95/EC; EN 62040-3
Standards
EN 62040-2 and Directive 2004/108 EC
Certificates CE
Operating temperature 0 °C / +40 °C
Colour Black
Altitude and relative humidity 6000 m max altitude, <95% non-condensing
Standard equipment Rack handles, user manual
Features
• Reduced energy consumption and 99% IDR 600
efficiency
DETAILS IDR 1200
PowerShield3
professional digital equipment such as
home cinema systems, satellite and digital
ACCESSORIES
terrestrial receivers and DVD players/ NETMAN 204 + box
recorders. NETMAN 302 + box
www.riello-ups.com 33
SOHO
Net
Power
VI 5
TYPE
LINE Tower
INTERACTIVE
1:1 600-2000 VA
The Net Power series is available in 600- of mains power (Cold Start)
HIGHLIGHTS 2000 VA models with digital technology: • High reliability with built-in battery test
when available the load is supplied from the • Auto restart (when mains power is
• Automatic Voltage mains power supply, which is amplitude- restored, after discharge of the batteries)
Regulation (AVR) stabilised by the automatic voltage regulator • Supplied with two IEC cables for powering
(AVR) and filtered against overvoltages by the loads.
• Advanced EMI filters.
communications When the mains fails, the load is powered Advanced communications
from a pseudo-sine wave inverter, to provide • Advanced multi-platform communications
• Automatic battery test sufficient runtime for computer system for all operating systems and network
shutdown using PowerShield3 software, environments: PowerShield3 supervision
which can be downloaded free from and shutdown software for Windows
www.riello-ups.com operating systems 8, 7, Hyper-V, 2012,
2008, and previous versions, Mac OS X,
Features Linux, VMWare ESXi, Citrix XenServer and
• Stabilisation and filtering of the mains other Unix operating systems
power supply using AVR and EMI filters • Standard USB interface, RS232 on models
for the suppression of atmospheric 1000 - 1500 - 2000.
disturbances
• Ability to switch on the UPS in the absence 2-YEAR WARRANTY
34
MODELS NPW 600 NPW 800 NPW 1000 NPW 1500 NPW 2000
POWER 600 VA/360 W 800 VA/480 W 1000 VA/600 W 1500 VA/900 W 2000 VA/1200 W
INPUT
Nominal voltage 220-230-240 Vac
Input voltage tolerance 230 Vac (±25%)
Frequency 50/60 Hz with automatic selection
OUTPUT
Voltage during mains operation 230 Vac (-8%, +10%)
Voltage during
230 Vac (+/- 5%)
battery operation
Frequency during battery
50 or 60 Hz (+/- 0.5%)
operation
Battery waveform Pseudo sinusoidal
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 6-8 h 2-4 h
OTHER FEATURES
Net weight (kg) 4,3 4,9 8 11,1 11,5
Gross weight (kg) 5,6 6,3 10 13,5 14
Dimensions (WxDxH) (mm) 100 x 287 x 142 146 x 350 x 160 146 x 397 x 205
Packaged dimensions
140 x 332 x 220 195 x 440 x 250 230 x 480 x 280
(WxDxH) (mm)
Protections Excessive low battery - overvoltage - short circuit
Communications USB USB + RS232
Output sockets 4 IEC 320 C13 sockets 6 IEC 320 C13 sockets
EN 62040-1-1 and Directive 2006/95/EC;
Standards
EN 62040-2 category C2 and Directive 2004/108 EC
Certificates CE
Operating temperature 0 °C / +40 °C
Colour Black
Altitude and relative humidity 6000 m max altitude, <95% non-condensing
Standard equipment 2 cables for powering loads; user manual
SOFTWARE
PowerShield3 NPW 600 NPW 1000 NPW 1500
NPW 800 NPW 2000
ACCESSORIES SERIAL PORT
RS232
NETMAN 204 + box
(only NPW 1000-2000) USB
COMMUNICATION
MULTICOM 302 + box PORT
(only NPW 1000-2000)
OUTPUT SOCKETS
www.riello-ups.com 35
SOHO
Vision
6
VI
TYPE
LINE Tower
INTERACTIVE
1:1 800-2000 VA
The Vision range is available in models from provides protection from surges,
HIGHLIGHTS 800 VA to 2000 VA with sinusoidal digital overvoltages and undervoltages, without
technology. battery intervention. Reduced battery
• Superior protection The Vision range, with its advanced usage ensures that the battery set is 100%
communications and connectivity options, is available for mains power supply failures
• Compact and the ideal solution for installations requiring and is able to provide greater autonomy. EMI
contemporary design superior protection and versatility in the filters then provide further protection from
power supply system. Vision is the ideal voltage surges and transients.
• High availability solution for the protection of peripheral When the mains power supply fails, the load
network devices, servers, and network back- is powered by the inverter and receives a
• Versatility up systems. perfectly sinusoidal supply for maximum
power continuity and reliability. With
• LCD display Superior protection energy savings in mind, the Vision range
The Vision range uses Line Interactive features a shut-off button to reduce energy
• Automatic Voltage technology and provides a sinusoidal consumption to zero during periods of
Regulation (AVR) output. This technology provides efficiency prolonged inactivity.
levels of 98% and therefore reduced energy
consumption. It also ensures a high level of High availability
protection against mains power disturbances. An EnergyShare socket allows load-
The automatic voltage regulator (AVR) shedding and the shutdown of less sensitive
36
peripheral devices to extend battery
runtime for critical loads. “Hot Swap”
batteries can be removed via the front panel
for easy and safe UPS maintenance.
Battery test facility to detect deteriorating
battery performance.
Deep discharge protection to reduce battery
ageing.
Versatility
Cold Start function to allow the UPS to
power up with no mains power supply
present.
LCD display
Vision models have a backlit LCD display
providing UPS status information, load and
battery performance.
Advanced communications
• Advanced multi-platform communications
for all operating systems and network
environments: PowerShield3 monitoring
and shutdown software for Windows
operating systems 8, 7, Hyper-V, 2012,
2008, and previous versions, Mac OS X,
Linux, VMWare ESXi, Citrix XenServer and
other Unix operating systems. AVAILABLE OPTIONS
• USB or RS232 serial port interface
(selectable) SOFTWARE MULTICOM 372
• Expansion slot for interface boards PowerShield3 MULTICOM 382
• Status, measurements, alarms and input, PowerNetGuard MULTICOM 401
output and battery parameters available MULTI I/O
on LCD display. ACCESSORIES Interface kit AS400
NETMAN 204 MULTIPANEL
Features MULTICOM 302 RTG 100
• EnergyShare socket MULTICOM 352
• Ability to switch on the UPS in the absence
of mains power (Cold Start)
• Batteries are user replaceable without
switching off equipment and without
interruption to the load (Hot Swap)
• Maximum reliability and protection of
PCs thanks to PowerShield3 monitoring
and shutdown software, which can be
DETAILS
downloaded free at
www.riello-ups.com
VST 800 VST 1500
• Fully configurable using UPS Tools VST 1100 VST 2000
configuration software
• Highly reliable batteries (automatic and USB
INPUT PLUG
ENERGYSHARE
www.riello-ups.com 37
MODELS VST 800 VST 1100 VST 1500 VST 2000
POWER 800 VA/640 W 1100 VA/880 W 1500 VA/1200 W 2000 VA/1600 W
INPUT
Nominal voltage 220 - 230 - 240 V selectable
Voltage tolerance 162 V - 290 V
Frequency 50/60 Hz with automatic selection
Frequency tolerance ±5%
OUTPUT
Nominal voltage 220 - 230 - 240 V selectable
Frequency 50 or 60 Hz with automatic selection
Waveform Sinusoidal
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 4-6 h
OTHER FEATURES
Net weight (kg) 10,5 11,3 16,5 18,5
Gross weight (kg) 12,2 13 18,4 20,4
Dimensions (WxDxH) (mm) 120 x 443 x 247 160 x 443 x 247
Packaging dimensions
208 x 530 x 342 250 x 540 x 354
(WxDxH) (mm)
Protections Overload - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / RS232 / slot for communications interface
Input plugs 1IEC 320 C14
Output sockets 4 IEC 320 C13 6 IEC 320 C13
EN 62040-1-1 and Directive 2006/95/EC
Standards
EN 62040-2 and Directive 2004/108 EC
Operating temperature 0 °C / +40 °C
Storage temperature -15 °C / 45 °C
Colour Black
Relative humidity <95% non-condensing
Noise < 40 dBA
38
www.riello-ups.com 39
SOHO DATACENTRE
Vision
Rack
VI 5
TYPE
LINE Rack
INTERACTIVE
1:1 800-1100 VA
The Vision Rack range is available in models voltage. This technology provides efficiency
HIGHLIGHTS
from 800 VA to 1100 VA with sinusoidal levels of 98% and therefore reduced
digital technology. energy consumption. It also ensures a high
• Superior protection The Vision Rack range, with its advanced level of protection against mains power
communications and connectivity options, disturbances.
• High availability is the ideal solution for installations The automatic voltage regulator (AVR)
requiring superior protection and versatility provides protection from surges,
• Versatility in the power supply system. Vision Rack overvoltages and undervoltages, without
is the ideal solution for the protection of battery intervention.
• LCD display peripheral network devices, servers, and Reduced battery usage ensures that the
network back-up systems. battery set is 100% available for mains
• Automatic voltage power supply failures and is able to provide
regulation (AVR) Superior protection greater autonomy.
The Vision Rack range uses Line Interactive EMI filters then provide further protection
technology and provides a sinusoidal output from voltage surges and transients.
40
When the mains power supply fails, the load Linux, VMWare ESXi, Citrix XenServer and • USB and RS232 interface
is powered by the inverter and receives a other Unix operating systems • Slot for communications boards
perfectly sinusoidal supply for maximum • USB or RS232 serial port interface • Maximum reliability and protection of
power continuity and reliability. (selectable) PCs thanks to PowerShield3 monitoring
• Expansion slot for interface boards and shutdown software, which can be
High availability • Status, measurements, alarms and input, downloaded free at www.riello-ups.com
An EnergyShare socket allows load- output and battery parameters available • Highly reliable batteries (automatic and
shedding and the shutdown of less sensitive on LCD display. manually-activated battery test)
peripheral devices to extend battery • Built-in short circuit protection
runtime for critical loads. Features • Auto restart (when mains power is
“Hot Swap” batteries can be removed • EnergyShare socket restored, after discharge of the batteries)
via the front panel for easy and safe UPS • Ability to switch on the UPS in the absence • Emergency power off contact (EPO).
maintenance. of mains power (Cold Start)
Battery test facility to detect deteriorating • User-replaceable battery set (Battery Swap) 2-YEAR WARRANTY
battery performance.
Deep discharge protection to reduce battery
ageing.
Versatility
Cold Start function to allow the UPS to
power up with no mains power supply
present.
Display
Vision models have a backlit LCD display
providing UPS status information, load and
battery performance.
Advanced communications
• Advanced multi-platform communications
for all operating systems and network
environments: PowerShield3 monitoring
and shutdown software for Windows
operating systems 8, 7, Hyper-V, 2012, DETAILS
2008, and previous versions, Mac OS X, VSR 800/1100
EPO
OPTIONS
www.riello-ups.com 41
MODELS VSR 800 VSR 1100
POWER 800 VA/640 W 1100 VA/880 W
INPUT
Nominal voltage 230 Vac (220, 240 V selectable)
Voltage tolerance 162 V - 290 V
Frequency 50/60 Hz with automatic selection
Frequency tolerance ±5% (3% to 10% configurable)
OUTPUT
Nominal voltage 230 Vac (220, 240 V selectable)
Frequency 50 or 60 Hz with automatic selection
Waveform Sinusoidal
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 4-6 h
OTHER FEATURES
Net weight (kg) 12 13
Gross weight (kg) 14,5 15,5
Dimensions (WxDxH) (mm) 19” x 420 x 1U
Packaged dimensions
595 x 540 x 140
(WxDxH) (mm)
Protections Overload - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / RS232 / slot for communications interface
Input plugs 1 IEC 320 C14
Output sockets 4 IEC 320 C13
Standards EN 62040-1-1 and Directive 2006/95/EC; EN 62040-2 and Directive 2004/108 EC
Operating temperature 0 °C / +40 °C
Storage temperature -15 °C / 45 °C
Colour Black
Relative humidity <95% non-condensing
Noise < 50 dBA
42
www.riello-ups.com 43
SOHO DATACENTRE
Vision
Dual
6
VI
TYPE
LINE ToweRack
INTERACTIVE
1:1 1100-3000 VA
The Vision Dual range (tower and rack), The UPS provides efficiency levels of 98%
HIGHLIGHTS
includes models from 1100 VA to 3000 VA and therefore reduced energy consumption.
with sinusoidal digital technology. It has an output power factor of 0,9.
• Automatic Voltage The Vision Dual range, with its advanced
Regulation (AVR) communications and connectivity options, is Superior protection
the ideal solution for installations requiring The automatic voltage regulator (AVR) provides
• Superior protection superior protection and versatility in the protection from surges, overvoltages and
power supply system. undervoltages, without battery intervention.
• High efficiency Vision Dual is the ideal solution for the Reduced battery usage ensures that the
protection of peripheral network devices, battery set is 100% available for mains power
• High availability conventional or rack servers, and network supply failures and is able to provide greater
back-up systems. autonomy. EMI filters then provide further
• Versatility Vision Dual has a practical, modern protection from voltage surges and transients.
design and includes several performance When the mains power supply fails, the load
• Advanced advantages over traditional on-line UPS. All is powered by the inverter and receives a
communications developed by the Riello UPS research and perfectly sinusoidal supply for maximum
development team. power continuity and reliability.
44
High availability Versatility for all operating systems and network
An EnergyShare socket allows load- Vision Dual can be installed as a tower or in environments: PowerShield3 monitoring
shedding and the shutdown of less sensitive 19” rack cabinets. The display panel can be and shutdown software included, with
peripheral devices to extend battery easily removed and rotated to suit the type SNMP agent, for Windows operating
runtime for critical loads. of installation required. systems 8, 7, Hyper-V, 2012, 2008, and
“Hot Swap” batteries can be removed Vision Dual is equipped with an emergency previous versions, Mac OS X, Linux,
via the front panel for easy and safe UPS power off (EPO) contact that allows for VMWare ESXi, Citrix XenServer and other
maintenance. remote shutdown in emergency situations. Unix operating systems
For business continuity applications requiring Cold Start function to allow the UPS to • USB or RS232 serial port interface
long battery runtimes, battery autonomy can power up with no mains power supply (selectable)
be extended up to several hours using ER present. • Expansion slot for SNMP agent interface
models (versions 2200 and 3000) fitted with Vision Dual models have a backlit LCD boards
more powerful battery chargers. display providing UPS status information, • Status, measurements, alarms and input,
Battery test facility to detect deteriorating load and battery performance. output and battery parameters available
battery performance. on LCD display.
Deep discharge protection to reduce battery Advanced communications
ageing. • Advanced multi-platform communications 2-YEAR WARRANTY
1. REMOVE THE DISPLAY PANEL 2. ROTATE THE DISPLAY PANEL AND INSERT IT 3. ROTATE THE UPS BY 90º 4. ATTACH THE RACK SUPPORTS
INTO POSITION
90°
90°
DETAILS
INPUT SOCKET VSD 1100/1500 BBX
INPUT THERMAL
PROTECTION
EMERGENCY SWITCH
DEVICE (ESD)
OUTPUT SOCKETS
ENERGY SHARE
VSD 2200/2200ER
BATTERY EXPANSION 3000/3000 ER INPUT PLUG
SOCKET
USB PORT
RS232 SERIAL
MULTICOM 401
MULTI I/O
Interface kit AS400
MULTIPANEL
www.riello-ups.com 45
MODELS VSD 1100 VSD 1500 VSD 2200 VSD 2200 ER VSD 3000 VSD 3000 ER
POWER 1100 VA/990 W 1500 VA/1350 W 2200 VA/1980 W 2200 VA/1760 W 3000 VA/2700 W 3000 VA/2400 W
INPUT
Nominal voltage 220-230-240 Vac
Voltage range without battery
162 Vac < Vin < 290 Vac
intervention
Maximum permitted voltage 300 V
Nominal frequency 50 or 60 Hz ±5Hz
Frequency range 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0,98
Current distortion ≤7%
OUTPUT
Voltage distortion with linear
< 3% / < 8%
load / with non-linear load
Frequency Selectable: 50 Hz or 60 Hz or self-learning
Waveform Sinusoidal
Current crest factor 2,5 : 1
Efficiency
98,5%
ECO and Smart Active Modes
Overload Times 125% for 10 seconds, 150% for 1 second
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 2-4 hours
OTHER FEATURES
Net weight (kg) 16,5 17,5 28 15,5 31,5 16,5
Gross weight (kg) 20 21 33 20,5 36,5 21,5
Dimensions (WxDxH) (mm) 87 x 450 x 425 (2U x 19” x 425) 87 x 450 x 625 (2U x 19” x 625)
Packaged dimensions (WxDxH)
240 x 500 x 600 240 x 600 x 760
(mm)
Protection against overvoltages 300 joules
Protections Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / DB9 with RS232 and contacts / Slot for communications interface
Input plugs 1 IEC 320 C14 1 IEC 320 C20
Output sockets 8 IEC 320 C13 8 IEC 320 C13 + 1 IEC 320 C19
Standards Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 62040-2 category C2 and Directives 2004/108/EL
Operating temperature 0 °C / +40 °C
Relative humidity <95% non-condensing
Colour Black
Noise level at 1 m (ECO Mode) < 40 dBA
Standard equipment provided Power cable, serial cable, USB cable, safety manual, quick start guide, user manual on CD-ROM
46
www.riello-ups.com 47
SOHO E-MEDICAL INDUSTRY EMERGENCY
Sentinel
Pro
6
VFI
TYPE
ONLINE Tower
1:1 700-3000 VA
USB GS Nemko
plug certified
Sentinel Pro has a unique and modern shows the input and output voltages,
HIGHLIGHTS
design and improved performance battery readings and UPS operating
developed by the Riello UPS research status information. The inverter and the
• Operating flexibility and development team. Sentinel Pro uses microprocessor control stage has been
on-line double conversion technology, completely redesigned to provide increased
• Emergency function resulting in the highest levels of reliability efficiency and greater configuration options.
and maximum protection for critical loads Maximum expandability: the Sentinel Pro
• Battery optimisation such as servers, and IT and voice/data is supplied as standard with a USB port and
applications. an expansion slot for protocol conversion or
• Runtime expandability For business continuity applications relay contacts boards.
requiring long battery runtimes, battery With energy savings in mind, Sentinel
• Low noise level autonomy can be extended up to several Pro is also fitted with a shut-off button to
hours using ER models fitted with more reduce energy consumption to zero during
powerful battery chargers. prolonged periods of inactivity (ECO LINE).
The front display panel has been entirely Sentinel Pro is available in 700 VA, 1000
redesigned, adding an LCD display that VA, 1500 VA, 2200 VA and 3000 VA models.
48
Operating flexibility
Different operating modes that can
be programmed according to on user
requirements and the load to be powered
have been introduced in order to reduce
energy consumption.
• On line: maximum load protection and
output voltage waveform quality
• Economy Mode: the UPS uses line
interactive technology, with the load
powered by the mains, reducing
consumption and thus improving
efficiency (up to 98%).
• Smart Active Mode: the UPS automatically
selects on-line or line interactive
operation, depending on the quality of
the mains supply, checking the number,
frequency and type of disturbances
present.
• Stand by Off (emergency): The UPS
supplies the load only when the mains
fails. The inverter begins working with a
progressive start-up sequence to prevent
inrush currents.
• Frequency converter operation (50 or 60
Hz).
Battery optimisation Low noise level
Emergency function The Sentinel Pro range has a deep discharge Thanks to the use of high frequency
This configuration ensures the operation of protection device to optimise battery life. components and load-based fan speed
emergency systems that must be supplied Periodically the UPS carries out a battery control, the noise produced by the UPS is
in the event of a mains power failure, such efficiency test (which can also be manually less than 40 dBA.
as emergency lighting, fire detection/ activated); its wide input voltage tolerance
extinguishing systems and alarms. When the range helps to reduce battery usage and Features
mains power supply fails, the inverter begins maintain performance over time. • Filtered, stabilised and reliable voltage:
powering the loads with a progressive start- double conversion on-line technology
up (Soft Start) in order to prevent overload. Runtime expandability (VFI compliant with IEC 62040-3) with
Sentinel Pro is compliant for installation Optional battery extension packs can be filters for the suppression of atmospheric
in medium-voltage transformer rooms in connected to increase UPS runtime. In disturbances.
accordance with applicable legislation, for addition the Sentinel Pro range includes • High overload capability (up to 150%)
the power supply with reserve charge of ER versions with no internal batteries and • Programmable Auto-restart when mains is
medium-voltage coils. more powerful battery chargers for longer restored
runtimes. • Battery start-up (cold start)
DETAILS
SEP 2200 SEP 3000
SEP 2200 ER SEP 3000 ER
COMMUNICATION SLOT
USB PORT
OUTPUT SOCKETS
INPUT SOCKET
www.riello-ups.com 49
• Power factor correction (UPS input power
factor, close to 1)
OPTIONS
• Wide input voltage tolerance range
(from 140 V to 276 V) without battery SOFTWARE MULTIPANEL382
MULTICOM
intervention. PowerShield3 MULTICOM
RTG 100 401
• Runtime extendable up to several hours PowerNetGuard MULTI I/O
Manual Bypass 16 A
• Fully configurable using UPS Tools Automatic Bypass 16 A
configuration software ACCESSORIES MULTIPANEL
• Highly reliable batteries (automatic and NETMAN 204101 PLUS RTG 100
manually-activated battery test) NETMAN 102
MULTICOM 302
PLUS Manual Bypass 16 A
• High level of UPS reliability (total NETMAN 202
MULTICOM 352
PLUS Automatic Bypass 16 A
MULTICOM 372 301
microprocessor control)
MULTICOM 382 302
• Low impact on the mains (sinusoidal take
MULTICOM 401 351
up).
MULTICOM
MULTI I/O 352
MULTICOM
Interface kit372
AS400
Advanced communications
• Multi-platform communication for
all operating systems and network
environments: PowerShield3 supervision
and shutdown software for Windows
BATTERY BOX
operating systems 8, 7, Hyper-V, 2012,
2008, and previous versions, Mac OS X,
Linux, VMWare ESXi, Citrix XenServer and MODELS BB SEP 36-A3 / BB SEP 36-M1 BB SEP 72-A3 / BB SEP 72-M1
other Unix operating systems
• UPS Tools configuration and customisation
software supplied as standard
• RS232 serial port and opto-isolated
333
contacts Dimensions
235
(mm)
• USB port BB
• Slot for communications boards. BB
2 6
42 44
15 19
0
2-YEAR WARRANTY 8
50
MODELS SEP 700 SEP 1000 SEP 1000 ER SEP 1500 SEP 2200 SEP 2200 ER SEP 3000 SEP 3000 ER
POWER 700 VA/560 W 1000 VA/800 W 1500 VA/1200 W 2200 VA/1760 W 3000 VA/2400 W
INPUT
Nominal voltage 220-230-240 Vac
Voltage range without battery
140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
intervention
Maximum permitted voltage 300 Vac
Nominal frequency 50/60 Hz
Frequency range 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0,99
Current distortion ≤7%
BYPASS
Voltage tolerance 180 - 264 Vac
Frequency tolerance Frequency selected (from ±1,5Hz to ±5Hz configurable)
Overload Times 125% for 5 seconds, 150% for 1 second
OUTPUT
Voltage distortion with linear
< 2% / < 4%
load / with non-linear load
Frequency Selectable: 50 Hz or 60 Hz or self-learning
Static variation ± 1%
Dynamic variation ≤ 5% in 20 msec.
Waveform Sinusoidal
Current crest factor 3:1
Efficiency
98%
ECO and Smart Active Modes
BATTERIES
Type VRLA AGM maintenance-free lead based; Supercaps
Recharge time 2-4 hours N.A. 2-4 hours N.A. 2-4 hours N.A.
OTHER FEATURES
Net weight (kg) 10,9 13,3 7 14,8 25,6 14 28 15
Gross weight (kg) 12,5 14,9 8,6 15,5 28,8 17 31,2 18
Dimensions (WxDxH) (mm) 158 x 422 x 235 190 x 446 x 333
Packaging dimensions
245 x 500 x 340 325 x 585 x 470
(WxDxH) (mm)
Protection against overvoltage 300 joules
Protections Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / DB9 with RS232 and contacts / Slot for communications interface
Input plugs 1 IEC 320 C14 1 IEC 320 C20
8 IEC 320 C13
Output sockets 4 IEC 320 C13 8 IEC 320 C13
+ 1 IEC 320 C19
Standards Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 620040-2 category C2 and Directives 2004/108/EL
Operating temperature 0 °C / +40 °C
Relative humidity < 95% non-condensing
Colour Black
Noise level at 1 m (ECO Mode) < 40 dBA
Standard equipment provided Power cable, IEC-IEC cable, USB cable, safety manual, quick start guide
www.riello-ups.com 51
SOHO DATACENTRE E-MEDICAL
Sentinel
Dual
INDUSTRY TRANSPORT EMERGENCY
Low Power
6
VFI
TYPE
ONLINE ToweRack
52
1. REMOVE THE DISPLAY PANEL 2. ROTATE THE DISPLAY PANEL AND INSERT IT 3. ROTATE THE UPS BY 90º 4. ATTACH THE RACK SUPPORTS
INTO POSITION
90°
90°
www.riello-ups.com 53
DETAILS
INPUT SOCKET
ENERGY SHARE
OUTPUT SOCKETS
USB PORT
RS232 SERIAL
INPUT PLUG
ENERGY SHARE
EMERGENCY SWITCH
DEVICE (ESD)
OPTIONS
BATTERY BOX
BB BB
450
Dimensions
450
(mm)
5
5 62
42
87 87
54
MODELS SDH 1000 SDH 1500 SDH 2200 SDH 2200 ER SDH 3000 SDH 3000 ER
POWER 1000 VA/900 W 1500 VA/1350 W 2200VA/1980 W 2200VA/1760 W 3000 VA/2700 W 3000 VA/2400 W
INPUT
Nominal voltage 220-230-240 Vac
Voltage range without battery
140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
intervention
Maximum permitted voltage 300 V
Nominal frequency 50/60 Hz ±5Hz
Frequency range 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0,98
Current distortion ≤7%
BYPASS
Voltage tolerance 200 - 253 Vac
Frequency tolerance Frequency selected (from ±0.5Hz to ±5Hz configurable)
Overload Times 125% for 4 seconds, 150% for 0,5 seconds
OUTPUT
Voltage distortion with linear
< 2%
load / with non-linear load
Frequency Selectable: 50 Hz or 60 Hz or self-learning
Static variation ± 1%
Dynamic variation ≤ 5% in 20 msec.
Waveform Sinusoidal
Current crest factor 3:1
Efficiency
98%
ECO and Smart Active Modes
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 2-4 hours
OTHER FEATURES
Net weight (kg) 17,5 18 30,5 15 31 15
Gross weight (kg) 21 21,5 35 19,5 35,5 19,5
Dimensions (WxDxH) (mm) (T- 87 x 425 x 450) (R- 19” x 425 x 2U) (T- 87 x 625 x 450) (R- 19” x 625 x 2U)
Packaged dimensions (WxDxH)
550 x 600 x 245 600 x 760 x 245
(mm)
Protection against
300 joules
overvoltages
Protections Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / DB9 with RS232 and contacts / Slot for communications interface
Input plugs 1 IEC 320 C14 1 IEC 320 C20
Output sockets 8 IEC 320 C13 8 IEC 320 C13 + 1 IEC 320 C19
Standards Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 620040-2 category C2 and Directives 2004/108/EL
Operating temperature 0 °C / +40 °C
Relative humidity < 95% non-condensing
Colour Black
Noise level at 1 m (ECO Mode) < 40 dBA
Standard equipment provided Power cable, serial cable, USB cable, safety manual, quick start guide
www.riello-ups.com 55
SOHO DATACENTRE E-MEDICAL
Sentinel
Dual
INDUSTRY TRANSPORT EMERGENCY
High Power
6
VFI
TYPE
ONLINE ToweRack
Sentinel Dual is the best solution for load is powered continuously by the inverter
HIGHLIGHTS powering mission critical applications and which supplies a sinusoidal voltage, filtered
electro-medical devices requiring maximum and stabilised in terms of voltage, form
• High Power Factor 0,9 power reliability. and frequency. In addition, the input and
Flexibility of installation and use (digital output filters significantly increase the
• Simplified installation display, user-replaceable battery set), as load’s immunity to mains disturbances and
well as the many communication options lightning strikes.
• Operating mode available, makes Sentinel Dual suitable Technology and performance: selectable
selection for many different applications from IT to Economy Mode and Smart Active Mode
security. functions. Diagnostics: Standard digital
• High quality output Sentinel Dual can be installed on the floor or display, RS232 and USB interfaces
voltage in rack cabinets for networking applications. with PowerShield3 software included,
The Sentinel Dual range is available in communications slot for connectivity
• High battery reliability 3,3-4-5-6-8-10 kVA models with on-line accessories.
double conversion technology (VFI): the
56
1. RELEASE THE DISPLAY PANEL BY 2. ROTATE THE DISPLAY PANEL COUNTER 3. ROTATE THE UPS BY 90º 4. ATTACH THE RACK SUPPORTS
APPLYING PRESSURE TO THE CATCHES CLOCKWISE AND THEN SECURE IT BACK IN PLACE
90°
90°
www.riello-ups.com 57
BATTERY BOX
MODELS BB SDL 108-A4 / BB SDL 108-M1 BB SDL 192-A3/ BB SDL 192-A6 BC SDL 108-B1
Dimensions
4U
4U
BB
630
(mm) BB
455
BB
455
BB BB
19 19
” ”
0 0
52 66
0 21 5
17 0 17 66 5 65
5 52 5
DETAILS
SDL 8000
SDL 10000
SDL 6500 TM
SDL 3300 SDL 5000 SDL 8000 TM
SDL 4000 SDL 6000 SDL 10000 TM
USB PORT
SERIAL PORT
COMMUNICATIONS SLOT
INPUT SOCKET
OUTPUT SOCKETS
BATTERY EXPANSION
CONNECTOR
INPUT CABLE
ACCESS
OUTPUT CABLE
ACCESS
OPTIONS
58
MODELS SDL 3300 SDL 4000 SDL 5000 SDL 6000 SDL 8000 SDL 10000
POWER 3300 VA/2300 W 4000 VA/2400 W 5000 VA/4500 W 6000 VA/5400 W 8000 VA/7200 W 10000 VA/9000 W
INPUT
Nominal voltage 220-230-240 Vac
Minimum voltage 184 Vac
Nominal frequency 50/60 Hz ±5Hz
Power factor > 0,98
Current distortion ≤7%
BYPASS
Voltage tolerance 180 - 264 Vac (selectable in Economy Mode or Smart Active Mode)
Frequency tolerance Selected frequency ±5% (selectable by user)
Overload Times 125% for 4 seconds, 150% for 0,5 seconds
OUTPUT
Nominal voltage 220-230-240 Vac selectable
Voltage distortion < 3% with linear load / < 6% with non-linear load
Frequency 50/60 Hz selectable
Static variation 1,5%
Dynamic variation ≤ 5% in 20 ms
Waveform Sinusoidal
Crest factor 3:1
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 4-6 hours
OTHER FEATURES
Net weight (kg) 38 40 62 64 94 95
Gross weight (kg) 42,5 44,5 70 72 102 103
175 x 520 x 455 tower 175 x 660 x 455 tower 2 x (175 x 660 x 455) tower
Dimensions (WxDxH) (mm)
19” x 520 x 4U rack 19” x 660 x 4U rack 2 x (19” x 660 x 4U) rack
Packaged dimensions
540 x 620 x 280 720 x 530 x (270+15) 780 x 555 x (270+15)
(WxDxH) (mm)
Efficiency
98%
Line-interactive/Smart Active
Protections Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / RS232 + slot for communications interface
Input plugs 1 IEC 320 C20 Terminal block
Output sockets 2 IEC 320 C13 + 1 IEC 320 C20 Terminal board + 2 IEC 320 C13
Standards EN 62040-1 EMC EN 62040-2 Directives 73/23 - 93/68 - 2004/108 EC EN 62040-3
Operating temperature 0 °C / +40 °C
Relative humidity < 95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) < 40 dBA < 45 dBA
www.riello-ups.com 59
MODELS SDL 6500 TM SDL 8000 TM SDL 10000 TM
POWER 6500 VA/5850 W 8000 VA/7200 W 10000 VA/9000 W
INPUT
Nominal voltage 400 Vac three-phase + N
Minimum voltage (F + N) 164 Vac @ 100% load / 84 Vac @ 50% load
Nominal frequency 50/60 Hz ±5 Hz
Power factor > 0,95
BYPASS
Voltage tolerance 180 - 264 Vac (selectable in Economy Mode or Smart Active Mode)
Frequency tolerance Selected frequency ±5% (selectable by user)
Overload Times 125% for 4 seconds, 150% for 0,5 seconds
OUTPUT
Nominal voltage 220-230-240 Vac selectable
Voltage distortion < 3% with linear load / < 6% with non-linear load
Frequency 50/60 Hz selectable
Static variation 1,5%
Dynamic variation ≤ 5% in 20 ms
Waveform Sinusoidal
Crest factor 3:1
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 4-6 hours
OTHER FEATURES
Net weight (kg) 91 94 95
Gross weight (kg) 99 102 103
Dimensions (WxDxH) (mm) 2 x (175 x 660 x 455) tower / 2 x (19” x 660 x 4U) rack
Packaged dimensions
780 x 555 x (270+15)
(WxDxH) (mm)
Smart Active efficiency up to 98%
Protections Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / RS232 + slot for communications interface
Input plugs Terminal block
Output sockets Terminal board + 2 IEC 320 C13
Standards EN 62040-1 EMC EN 62040-2 Directives 73/23 - 93/68 - 2004/108 EC EN 62040-3
Operating temperature 0 °C / +40 °C
Relative humidity < 95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) < 45 dBA
Standard equipment provided 2 cable guides; cable tips; software; serial cable; keys for releasing display panel; handles kit
60
www.riello-ups.com 61
SOHO DATACENTRE E-MEDICAL
Sentinel
Power INDUSTRY TRANSPORT EMERGENCY
Green
6
VFI
TYPE
ONLINE Tower
1:1 6 kVA
1:1 3:1 8-20 kVA
Sentinel Power Green is the ideal the load is powered continuously by the
HIGHLIGHTS
solution for protecting IT systems, inverter which supplies a sinusoidal voltage,
telecommunications equipment and mission filtered and stabilised in terms of form and
• Small footprint critical systems such as safety devices, frequency.
ensuring maximum power reliability. Input and output filters provide significant
• Power factor 0,9 Sentinel Power Green is designed and further immunity from mains disturbances
built using state-of-the-art technology and and lightning strikes.
• High efficiency 97% components to provide maximum protection In terms of technology and performance,
to the powered loads with no impact on Sentinel Power Green is one of the best UPS
• Parallelable 2+1 downstream systems and optimised energy available on the market today: selectable
savings. Economy Mode and Smart Active Mode
• Simplified installation The series includes 6 kVA single/single- functions; custom diagnostics LCD display,
phase and 8-20 kVA single/single-phase RS232 and USB interfaces with Powershield3
• High quality output and three/single-phase models with on- software, ESD input, interface slot with
voltage line double conversion technology (VFI): optional boards.
62
High UPS reliability
• Total microprocessor control.
• Interruption-free static and manual
bypass.
• Specifications guaranteed up to 40°C (the
components are designed to work at high
temperatures and thus are subject to less
stress at normal temperatures).
Parallelable
Parallel configuration of 3 units for (2+1)
redundant or power parallel system. The
UPS continue to operate in parallel even if
the connection cable is interrupted (Closed correct UPS operation in emergency • Auto restart (automatic when mains supply
Loop). conditions. The Riello UPS battery care is restored, programmable via software or
system consists of a series of features display panel).
Operating mode selection and capabilities to optimise battery • Emergency function: the UPS can be
The operating mode can be programmed via management and obtain the best selected to function only when the mains
software or manually via the front display performance and operating life possible. power supply fails (emergency lights).
panel. • Unlimited extendible runtime using • Back-feed protection standard: to prevent
• On line: double conversion Mode: for matching Battery Boxes. energy from being fed back to the
critical applications. • The batteries do not cut in during mains network.
• Economy Mode: to increase efficiency (up failures of <40 ms (high hold up time) or • UPS digital updating (flash upgradeable).
to to 98%), allows for the selection of Line when the input supply is between 84 V to
Interactive technology (VI) to power low 276 V. Advanced communications
priority loads from the mains supply. • Compatible with Riello UPS TeleNetGuard
• Smart Active: the UPS automatically Low impact on the mains remote monitoring.
decides upon the operating mode (VI or Sinusoidal uptake of input current on single- • Advanced multi-platform communications
VFI) based on the quality of the mains phase/single-phase series. for all operating systems and network
power supply. environments: PowerShield3 monitoring
• Emergency: the UPS can be selected Other features and shutdown software for Windows
to function only when the mains power • Advanced diagnostics: status, operating systems 8, 7, Hyper-V, 2012,
supply fails (emergency only mode). measurements and alarms available on 2008, and previous versions, Mac OS X,
• Frequency converter operation (50 or 60 custom LCD display. Linux, VMWare ESXi, Citrix XenServer and
Hz). • Low noise (<40 dBA): can be installed other Unix operating systems.
in any environment thanks to its high • RS232 serial and USB ports.
High quality output voltage frequency switching inverter and PWM • Plug and play function.
• Even with non-linear loads (IT loads with a load-dependent digitally controlled fan • Slot for installation of communications
crest factor of up to 3:1). (>20 kHz, value above audible range). boards.
• High short circuit current on bypass.
• High overload capacity: 150% by inverter
(even with mains failure).
• Filtered, stabilised and reliable voltage
(double conversion on-line technology
- VFI compliant with EN62040-3), with
filters for the suppression of atmospheric
disturbances.
• Power factor correction: UPS input power
factor close to 1 and sinusoidal current
uptake.
Simplified installation
• UPS can be installed on a single-phase or
three-phase distribution network.
• Output terminal board + 2 IEC sockets for
powering local consumers (computers,
modems, etc.).
• Simplified positioning (built-in castors).
www.riello-ups.com 63
OPTIONS DETAILS
SPM 6 - SPH 8 - SPH 10 SPH 15 - SPH 20 - SPH 20 ER
SOFTWARE SPH 10 ER
PowerShield3
PowerNetGuard
USB PORT
ACCESSORIES
NETMAN 204 RS232 SERIAL PORT
BATTERY BOX
Dimensions
1320
(mm) BB
708
BB
4 5
26 65 40
0 81
2
64
MODELS SPM 6 SPH 8 SPH 10 SPH 10 ER SPH 15 SPH 20 SPH 20 ER
6000 VA/ 8000 VA/ 10000 VA/ 10000 VA/ 15000 VA/ 20000 VA/ 20000 VA/
POWER
5400 W 6400 W 9000 W 9000 W 13500 W 18000 W 18000 W
INPUT
220-230-240
Nominal voltage 220-230-240 Vac 1 ph / 380-400-415 Vac 3 ph + N
Vac 1 ph
Minimum voltage without
176 Vac @ 100% load / 110 Vac @ 50% load
battery intervention
Maximum operating
276 Vac
voltage
Nominal frequency 50/60 Hz ±10 Hz
BYPASS
Voltage tolerance 160 - 276 Vac (selectable in Economy Mode or Smart Active Mode)
Frequency tolerance Selected frequency ±10%
Overload Times 125% for 1 min, 150% for 10 seconds
OUTPUT
Nominal voltage 220-230-240 Vac selectable
Voltage distortion < 2% with linear load / < 5% with non-linear load
Current distortion 3%
Frequency 50/60 Hz selectable or with automatic selection
Static variation ± 1,5 %
Dynamic variation ≤ 5% in 20 ms
Waveform Sinusoidal
Crest factor ≥3:1
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 6-8 hours
Recharge current
n.a. 8A n.a. 8A
(only for ER versions)
OTHER FEATURES
Net weight (kg) 63 78 84 28 146 157 48
Gross weight (kg) 77 92 98 42 164 175 66
Dimensions (WxDxH) (mm) 262 x 654 x 708 350 x 731 x 818
Packaged dimensions
720 x 428 x 970 870 x 475 x 1075
(WxDxH) (mm)
Smart Active efficiency up to 98%
Protections Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / RS232 + slot for communications interface
Parallel max. 2 units in parallel with optional kit
Input plugs Terminal block
Output sockets Terminal block + 2 IEC 320 C13
Standards EN 62040-1 EMC EN 62040-2 Directives 2006/95/EC - 2004/108 EC EN 62040-3
Operating temperature 0 °C / +40 °C
Relative humidity < 95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) < 40 dBA
Moving the UPS castors
www.riello-ups.com 65
SOHO DATACENTRE E-MEDICAL
Power
6
VFI
TYPE
ONLINE Tower
USB Supercaps
plug UPS
Energy Service
share 1st start
Sentinel Power is the ideal solution for frequency. Input and output filters provide
HIGHLIGHTS powering sensitive, mission critical systems significant further immunity from mains
such as safety devices (electro-medical disturbances and lightning strikes.
• High UPS reliability devices), ensuring maximum power reliability. In terms of technology, performance
The series includes 5-6 kVA single/single- (selectable Economy and Smart Active
• Operating mode phase and 6,5-8-10 kVA single/single-phase Modes) and diagnostics (LCD custom display,
selection and three/single-phase models with on-line RS232 and USB interfaces with Powershield3
double conversion technology (VFI): the software included, ESD input, interface slot
• High quality output load is powered continuously by the inverter for optional boards), Sentinel Power is one
voltage which supplies a sinusoidal voltage, filtered of the best UPS available on the market.
and stabilised in terms of voltage, form and
• Simplified installation
• High battery reliability
• Low impact on the
mains
66
High UPS reliability Energy-share
• Total microprocessor control. Two 10 A configurable IEC output
• Interruption-free static and manual sockets allow for runtime optimisation
bypass. by programming the switching off of low
• Specifications guaranteed up to 40 °C (the priority loads on mains failure; alternatively,
components are designed to work at high emergency loads that are normally not
temperatures and thus are subject to less powered when mains is present can be
stress at normal temperatures). activated.
Simplified installation
• UPS can be installed on a single-phase or
three-phase distribution network
• Output terminal board + 2 IEC sockets for
powering local consumers (computers,
modems, etc.)
• Simplified positioning (built-in castors).
www.riello-ups.com 67
BATTERY BOX OPTIONS
615
Dimensions (only for 5000-6000 VA models)
(mm) MULTICOM 352
BB
MULTICOM 372
MULTICOM 382
5
78
MULTICOM 401
28
2
MULTI I/O
Interface kit AS400
DETAILS
SPW 5000 - SPW 6000
SPW 6500 - SPT 8000 - SPW 10000
EMERGENCY SWITCH
DEVICE (ESD)
IEC SOCKETS
USB PORT
MAINTENANCE BYPASS
INPUT SWITCH (SWMB)
(SWIN)
OUTPUT SWITCH
BATTERY FUSE PORT (SWOUT)
(SWBT)
68
MODELS SPW 5000 SPW 6000 SPT 6500 SPT 8000 SPT 10000
POWER 5000 VA/4000 W 6000 VA/4800 W 6500 VA/5200 W 8000 VA/6400 W 10000 VA/8000 W
INPUT
Nominal voltage 220-230-240 Vac single-phase 220-230-240 Vac single-phase or 380-400-415 Vac three-phase + N
Minimum voltage without
170 Vac @ 100% load / 140 Vac @ 50% load
battery intervention
Nominal frequency 50/60 Hz ±5 Hz
BYPASS
Voltage tolerance 180 - 264 Vac (selectable in Economy Mode or Smart Active Mode)
Frequency tolerance Selected frequency ±5%
Overload Times 125% for 4 seconds, 150% for 0,5 seconds
OUTPUT
Nominal voltage 220 - 230 - 240 Vac selectable
Voltage distortion < 3% with linear load / < 6% with non-linear load
Frequency 50/60 Hz selectable or with automatic selection
Static variation ± 1,5 %
Dynamic variation ≤ 5% in 20 ms
Waveform Sinusoidal
Crest factor ≥3:1
BATTERIES
Type VRLA AGM maintenance-free lead based
Recharge time 6-8 hours
OTHER FEATURES
Net weight (kg) 91 92 105 106
Gross weight (kg) 99 100 110 111
Dimensions (WxDxH) (mm) 282 x 785 x 615
Packaged dimensions
863 x 388 x (650+15)
(WxDxH) (mm)
Smart Active efficiency up to 98%
Protections Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
Communications USB / RS232 + slot for communications interface
Input plugs Terminal board
Output sockets Terminal board + 2 IEC 320 C13
Standards EN 62040-1 EMC EN 62040-2 Directives 2006/95/EC - 2004/108 EC EN 62040-3
Operating temperature 0 °C / +40 °C
Relative humidity < 95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) < 45 dBA
Moving the UPS castors
www.riello-ups.com 69
DATACENTRE E-MEDICAL INDUSTRY
Multi
Sentry
TRANSPORT EMERGENCY
10-20 kVA
6
VFI
TYPE
ONLINE Tower
USB SmartGrid
plug ready
The Multi Sentry series is ideal for by a DSP (Digital Signal Processor)
HIGHLIGHTS
protecting data centres and microprocessor, to provide maximum
telecommunications systems, IT networks protection to the powered loads with no
• Large power size and critical systems in general, where the impact on downstream systems, and
selection 10, 12, 15, risks connected with poor energy supply can optimised energy savings.
20 kVA compromise the continuity of activities and
services. The Multi Sentry series is available Zero impact source
• Small footprint in 10-12-15-20 kVA models with three- Multi Sentry solves installation problems in
phase/single-phase input and single-phase systems where the power supply has limited
• Zero impact source output, and 10-12-15-20 kVA models with power available, where the UPS is supported
three-phase input and output and on-line by a generator or where there are
• Flexibility of use double conversion technology in accordance compatibility problems with loads that
with VFI-SS-111 classification (as set out in generate harmonic currents; Multi Sentry
• Advanced standard IEC EN 62040-3). Multi Sentry is has a zero impact on its power source,
communications designed and built using state-of-the-art whether this is the mains power supply or a
technology and components. It is controlled generator:
70
• input current distortion < 3% the main causes of reduced reliability and (% PA UPS) P
Q
• input power factor 0,99 battery life. Using a high frequency battery
• power walk-in function that ensures charger, Multi Sentry reduces this value to
progressive rectifier start up negligible levels, prolonging battery life and 100 CAPACITIVE
• start-up delay function, to restart the maintaining high performance over a long
rectifiers when mains power is restored if period of time. Wide voltage range: the 80
there are several UPS in the system. rectifier is designed to operate within a wide
In addition, Multi Sentry plays a filtering and input voltage range (up to - 40% at half 60 cosfi 0.9
e.g.: 10 kVA UPS
power factor correction role in the power load), reducing the need for battery supplies
40 9 kW load
network upstream of the UPS, as it discharge and thus helping to extend
eliminates harmonic components and battery life. cosfi 1
20 e.g.: 10 kVA UPS
reactive power generated by the power supplies
utilities. Maximum reliability and % PA 0
9 kW load
www.riello-ups.com 71
BATTERY BOX
Dimensions
(mm) BB
1900
1600
1320
BB
BB
40 5 86
0 81 65 0 0
0 75 80
0
DETAILS
CONNECTORS
SLOTS FOR REPO - AS400
ACCESSORY USB - RS232
COMMUNICATION
CARDS PARALLEL
ENERGYSHARE SLOTS
SOCKETS (10A
MAX. TOTAL PARALLEL PCB
ON THE TWO (OPTIONAL)
SOCKETS) COMMUNICATION
AND RELATIVE PORTS (AS400,
PROTECTION USB, RS232)
BATTERY START
BUTTON SWBATT
(COLD START)
VENTILATION
MANUAL BY- FANS SWBYP
PASS SWITCH
BATTERY FUSE
HOLDER
ISOLATOR
OUTPUT SWITCH SWMB
TERMINAL
COVER PANEL
ENERGYSHARE
SOCKETS
BRAKE ROD
OPTIONS
72
MCM/MSM MCM/MSM MCM/MSM MCM/MSM MCT/MST MCT/MST MCT/MST MCT/MST
MODELS 10 BAT 12 BAT 15 BAT 20 BAT 10 BAT 12 BAT 15 BAT 20 BAT
INPUT
380-400-415 Vac three-phase + N / 220-230-240 Vac
Nominal voltage 380-400-415 Vac three-phase + N
single-phase + N
Nominal frequency 50/60 Hz
Frequency tolerance 40 - 72 Hz
Power factor at full load 0,99
Current distortion THDI ≤ 3%
BYPASS
Nominal voltage 220-230-240 Vac single-phase + N 380-400-415 Vac three phase + N
Number of phases 1 3+N
Voltage tolerance (Ph-N) 180 - 264 V (selectable)
Nominal frequency 50 or 60 Hz (selectable)
Frequency tolerance ±5 (selectable)
Bypass overload 125% for 60 minutes, 150% for 10 minute
OUTPUT
Nominal power (kVA) 10 12 15 20 10 12 15 20
Active power (kW) 9 10,8 13,5 18 9 10,8 13,5 18
Power factor 0,9
Number of phases 1 3+N
Nominal voltage (V) 220-230-240 Vac single-phase + N (selectable) 380-400-415 Vac three-phase + N (selectable)
Static variation ± 1%
Dynamic variation ± 3%
Crest factor 3 : 1 Ipeak/Irms
Voltage distortion ≤ 1% with linear load / ≤ 3% with non-linear load
Frequency 50/60 Hz
Frequency stability during
0,01%
battery operation
BATTERIES
Type VRLA AGM/GEL/NiCd/Li-ion/Supercaps
Recharge time 6 hours
INFO FOR INSTALLATION
Weight without batteries (kg)
80/105 82/110 90/115 95/120 80/105 82/110 90/115 95/120
(MCM/MSM)
Dimensions (WxDxH) (mm) 320 x 840 x 930 (MCM/MCT version) / 440 x 850 x 1320 (MSM/MST version)
Communications 3 slots for communications interface / USB / RS232
Operating temperature 0 °C / +40 °C
Relative humidity 90% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m [dBA ±2]
< 40 dBA
Smart Active
IP rating IP20
Smart Active efficiency up to 98% up to 99%
European Directives: L V 2006/95/CE low voltage Directive
EMC 2004/108/CE electromagnetic compatibility Directive
Standards
Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2
Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111
Moving the UPS castors / transpallet (10 - 20 kVA)
BAT
Also available with internal batteries
www.riello-ups.com 73
DATACENTRE E-MEDICAL INDUSTRY
Multi
Sentry
TRANSPORT EMERGENCY
30-200 kVA
6
VFI
TYPE
ONLINE Tower
USB SmartGrid
plug ready
The Multi Sentry series is ideal for minimize the impact on the grid. It is
HIGHLIGHTS protecting data centres and controlled by a DSP (Digital Signal Processor)
telecommunications systems, IT networks microprocessor, to provide maximum
• Complete range and critical systems in general, where the protection to the powered loads with no
30-200 kVA risks connected with poor energy supply can impact on downstream systems, and
compromise the continuity of activities and optimised energy savings.
• Small footprint services.
The Multi Sentry series is available in Zero impact source
• High efficiency up to 30-40-60-80-100-125-160-200 kVA models
with three-phase input and output and
Multi Sentry solves installation problems in
systems where the power supply has limited
96,5% on-line double conversion technology in power available, where the UPS is supported
accordance with VFI-SS-111 classification (as by a generator or where there are
• Zero impact source set out in standard IEC EN 62040-3). compatibility problems with loads that
Multi Sentry is designed and built using generate harmonic currents; Multi Sentry
• Flexibility of use state-of-the-art technology and components. has a zero impact on its power source,
It has a fully controlled IGBT rectifier to whether this is the mains power supply or a
• Advanced
communications
74
generator:
• input current distortion < 2,5%
• input power factor 0,99 MST 30÷200
• power walk-in function that ensures Legacy UPS
progressive rectifier start up
Efficiency %
• start-up delay function, to restart the 100
rectifiers when mains power is restored if
98
there are several UPS in the system.
In addition, Multi Sentry plays a filtering and 96
power factor correction role in the power 94
network upstream of the UPS, as it
92
eliminates harmonic components and
reactive power generated by the power 90
utilities. 88
86
High efficiency
State-of-the-art three-level NPC inverters 84
are used across the power range (30÷200) to 82
achieve an operating efficiency of 96,5%.
80
This technology halves (50%) the energy
dissipated in a year by traditional UPS, with 78
an efficiency level of 92%. Its exceptional 76
performance makes it possible to recover 0 20 30 40 60 80 100 120
the capital investment cost in less than three
Load %
years of operation.
Battery care system Multi Sentry reduces this value to negligible Low running costs
Proper battery care is critical to ensuring levels, prolonging battery life and maintain- Advanced technology and use of high
correct UPS operation in emergency ing high performance over a long period of performance components, allows Multi
conditions. The Riello UPS battery care time. Sentry to provide exceptional performance
system consists of a series of features and Wide voltage range: the rectifier is designed and efficiency, with a compact size:
capabilities to optimise battery management to operate within a wide input voltage range • the smallest overall footprint is only 0,37
and obtain the best performance and (up to - 40% at half load), reducing the need sqm for Multi Sentry 40 kVA with batteries
operating life possible. for battery discharge and thus helping to • the type of input stage (IGBT rectifier)
Battery recharging: Multi Sentry is suitable extend battery life. ensures an input power factor close to 1
for use with hermetically sealed lead-acid with low current distortion, avoiding the
(VRLA), AGM and GEL batteries and Open Maximum reliability and need for bulky and expensive filters
Vent and Nickel Cadmium batteries. availability • unity output power factor for MST 160
Depending on the battery type, different Distributed parallel configuration of up to 6 – 200 make it suitable to any data centre
charging methods are available: units per redundant (N+1) or power parallel application ensuring full power availability
• One-level voltage recharge, typically used system. The UPS continue to operate in no matter what the utilities power factor
for widely available VRLA AGM batteries parallel even if the connection cable is range (typically from 0,9 lagging to 0,9
• Two-level voltage recharge according to IU interrupted (Closed Loop). leading)
specification
• Charge blocking system to reduce
electrolyte consumption and lengthen the
life of VRLA batteries.
Recharge voltage compensation based on
temperature in order to prevent excessive
battery charges or overheating.
Battery tests to diagnose in advance any
reduction in performance or problems with
the batteries.
Deep discharge protection: during extended
low-load discharges, the end-of-discharge
voltage is increased - as recommended by
battery manufacturers - to prevent damage
or reduced battery performance.
Ripple current: recharge ripple current
(residual AC component) is one of the main
causes of reduced reliability and battery life.
Using a high frequency battery charger,
www.riello-ups.com 75
• more active power than a traditional UPS, Advanced communications
guaranteeing a greater margin when sizing Multi Sentry is equipped with a back-lit
UPS for potential future load increases. graphic display (240x128 pixels) providing
• smart ventilation principle on MST UPS information, measurements, operating
160-200 manages the number of states and alarms in different languages. It
operating fans and their speed according can also display wave forms and voltage/
to room temperature and load level. This current forms.
preserves the life span of the fans and at The default screen displays UPS status,
the same time we reduce noise level and graphically indicating the status of the
overall power consumption for various assemblies (rectifier, batteries,
unnecessary UPS ventilation. inverter, bypass).
• Advanced multi-platform communications
Flexibility for all operating systems and network
With its flexible configuration, performance, environments: PowerShield3 monitoring
accessories and options, Multi Sentry is and shutdown software included for
suitable for use in a wide range of Windows operating systems 8, 7, Hyper-V,
applications: 2012, 2008, and previous versions, Mac
• suitable for powering capacitive loads, OS X, Linux, VMWare ESXi, Citrix XenServer
such as blade servers, without any Multi Sentry MST 160-200 and other Unix operating systems
(% PA UPS) P
Q • optional temperature sensor for external
battery cabinets, to assist recharge voltage
CAPACITIVE compensation
100
• high power battery chargers to optimise
charge time in the event of long runtimes
80
• optional dual input mains power supply
60 cosfi 0,9 • isolation transformers for modifying the
e.g.: 200 kVA UPS neutral earthing (separate power sources),
supplies
40 200 kVA load or for galvanic isolation between the input
and output
cosfi 1
20 e.g.: 200 kVA UPS • 220 V three-phase IN/OUT version and
supplies 50/60 Hz frequency for 10-40 kVA power
200 kW load
% PA 0
ratings
25 50 75 100 (% P UPS) P
• different sized battery cabinets and
20
capacities, for extended runtimes
cosfi 0,9 • with the MST 60-100 the UPS can be
40
e.g.: 200 kVA UPS
supplies
raised up to 25 cm from the ground to
60
200 kVA load allow the cables to pass more freely to/
from the UPS terminal board
80 • MST 160-200 could be equipped with a
INDUCTIVE side mounted top entry cabinet to arrange
100 UPS cabling from the top. MST 60-100 with Socle box (h: 1850 mm)
76
BATTERY BOX
DETAILS
MST 160 - 200
(front)
MST 125 MST 60 - 80 - 100
PARALLEL
(front) (front)
SLOT MST 30 - 40
PARALLEL
CONNECTORS SLOT COMMU-
(front)
REPO - AS400 NICATIONS
USB - RS232 INTERFACE
COMMUNICATIONS SLOT
COMMUNICATIONS INTERFACE SLOT
INTERFACE CONNECTORS
SLOT REPO - AS400
CONNECTORS USB - RS232
REPO - AS400
SCHUKO USB - RS232 PARALLEL
SOCKET SLOTS
CONNECTORS
REPO - AS400
USB - RS232
SWBATT
SWIN
SWBYP
SWMB S S
W
SWOUT
W O
M U
B T
SWBYP SWMB
SWMB
SWBYP SWOUT
S S
W W
B
SWOUT Y
P
I
N
SWIN
SWMB
SERVICE
PERSONNEL ONLY
RISERVATO AL SERVICE
NUR SERVICE TECHNIKER
RESERVÉ AU PERSONNEL
SOLO PERSONAL TECNICO
SWBYP
SWIN
SLOT FOR
SLOT FOR MULTICOM MULTICOM
382/392 BOARD 382/392
BOARD
ENERGYSHARE ENERGYSHARE
SOCKETS SOCKETS SLOT FOR MULTICOM
382/392 BOARD
OPTIONS
www.riello-ups.com 77
MODELS MST 30 BAT MST 40 BAT MST 60 MST 80 MST 100 MST 125 MST 160 MST 200
INPUT
Nominal voltage 380-400-415 Vac three-phase + N
Nominal frequency 50/60 Hz
Frequency tolerance 40 - 72 Hz
Power factor at full load 0,99
Current distortion THDI ≤ 3% THDI ≤ 2,5%
BYPASS
Nominal voltage 380-400-415 Vac three-phase + N
Number of phases 3+N
Voltage tolerance (Ph-N) 180 - 264 V (selectable)
Nominal frequency 50 or 60 Hz (selectable)
Frequency tolerance ±5 (selectable)
Bypass overload 125% for 60 minutes, 150% for 10 minute
OUTPUT
Nominal power (kVA) 30 40 60 80 100 125 160 200
Active power (kW) 27 36 54 72 90 112,5 160 200
Power factor 0,9 1
Number of phases 3+N
Nominal voltage 380-400-415 Vac three-phase + N (selectable)
Static variation ± 1%
Dynamic variation ± 3%
Crest factor 3 : 1 Ipeak/Irms
Voltage distortion ≤ 1% with linear load / ≤ 3% with non-linear load
Frequency 50/60 Hz
Frequency stability during bat-
0,01%
tery operation
BATTERIES
Type VRLA AGM/GEL/NiCd/Li-ion/Supercaps
Recharge time 6 hours
INFO FOR INSTALLATION
Weight without batteries (kg)
135 145 190 200 220 250 450 460
(MCT/MST)
650 x 840 x
Dimensions (WxDxH) (mm) 440 x 850 x 1320 500 x 850 x 1600 850 x 1050 x 1900
1600
Communications 3 slots for communications interface / USB / RS232
Operating temperature 0 °C / +40 °C
Relative humidity 90% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m [dBA±2]
< 40 dBA < 63 dBA < 50 dBA
(Smart Active)
IP rating IP20
Smart Active efficiency up to 99%
European Directives: L V 2006/95/CE low voltage Directive
EMC 2004/108/CE electromagnetic compatibility Directive
Standards
Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2
Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111
Moving the UPS castors (30 - 200 kVA)
BAT
Also available with internal batteries
78
www.riello-ups.com 79
DATACENTRE E-MEDICAL INDUSTRY
MPS
VFI
TYPE
ONLINE Tower 4
SmartGrid Flywheel
ready compatible
Supercaps Service
UPS 1st start
Flexibility
Master MPS is suitable for a wide range of
applications including IT and the most
demanding industrial environments. The UPS
is suitable for power capacitive loads such as
blade servers, from 0,9 leading to 0,8 lagging. Detail of connection area
With a broad range of accessories and
options, complex configurations and system
architectures can be achieved to guarantee • 3 slots for the installation of optional Options
maximum power availability and the option to communications accessories such as • UPS Group Synchroniser (UGS)
add new UPS without interruption to existing network adapters, potential free contacts, Allows two or more non-parallel UPS
installation. etc. devices to remain synchronised even
• REPO Remote Emergency Power Off for during mains power failure.
Battery care system: maximum switching off the UPS via a remote The UGS also enables a Riello UPS to be
battery care emergency button synchronised with another power source
Normally the batteries are kept charged by • Input for the connection of the auxiliary that is independent and of a different
the rectifier; when mains power fails, the contact of an external manual bypass power rating.
UPS uses this energy source to power the • Input for synchronisation from an external
consumers. Proper battery care is therefore source • Parallel Systems Joiner (PSJ)
critical to ensuring correct UPS operation • Graphic display panel for remote Allows two groups of UPS to be connected
under emergency conditions. The Riello UPS connection. in parallel whilst operating, in the event of
battery care system consists of a series of maintenance (with no interruption to the
functions designed to optimise battery Maximum reliability and output), using a power coupling switch.
management and achieve the best availability Should one of the UPS in one of the
performance and operating life possible. • Distributed or centralised parallel parallel groups fail, it is automatically
Master MPS is also compatible with different configuration of up to 8 units per excluded.
battery technologies: vented open lead acid, redundant (N+1) or power parallel system. The PSJ connects the remaining UPS, to
VRLA AGM, Gel, NiCd, Flywheels, Supercaps Parallel configurations using models with the other parallel group via an external
and Lithium. different power ratings are also possible. bypass, in order to continue to guarantee
• Hot System Expansion (HSE): allows the load redundancy.
Specific solutions addition of a further UPS into an existing
The UPS can be adapted to meet the most system, without the need to switch off the
specific requirements. Contact our TEC team existing UPS or transfer them to bypass
to discuss specific solutions and options not mode. This guarantees maximum load
listed in this catalogue. protection, even during maintenance and
system expansion.
Advanced communications • Maximum levels of availability, even in the
• Compatible with TeleNetGuard for remote event of an interruption to the parallel bus
monitoring. cable: the system is “FAULT TOLERANT”. It
• Advanced multi-platform communications is not affected by connection cable faults
for all operating systems and network and continues powering the load without
environments: PowerShield3 monitoring disruption, signalling an alarm condition.
and shutdown software included for • Efficiency Control System (ECS): a system
Windows operating systems 8, 7, Hyper-V, to optimise the operating efficiency of
2012, 2008, and previous versions, Mac parallel systems, according to the power
OS X, Linux, VMWare ESXi, Citrix XenServer required by the load. N +1 redundancy is
and other Unix operating systems. guaranteed, with every UPS working in
• Compatible with TeleNetGuard remote parallel at the best load level possible to
monitoring service achieve higher overall efficiency.
• RS232 serial and USB ports
www.riello-ups.com 81
DIMENSIONS
1400
1900
1900
1900
1400
1400
1400
0 0 0 0 0 0
555 74 800 74 825 74 800 80 1070 74 1070 80
Solution to ensure redundancy up to the distribution of the Solution to ensure redundancy of the power supply even during
power supply to the loads and improved STS operation. maintenance. + High availability and redundancy
+ Downstream fault discrimination
Battery
Battery
Battery
Battery
Battery
Battery
Battery
UGS
Sinchroniser PSJ
Static Transfer
SWITCH SWITCH
Load 3
Load 1 Load 2 Load 1 Load 2
Static Transfer
SWITCH
Load 4
DETAILS
RS232-REPO SWBYP
CONNECTORS FAN FUSES
DRY CONTACTS
SWMB
COMMUNICATIONS
INTERFACE SLOT
SWOUT
PARALLEL
INTERFACE
UGS
INTERFACE
MULTI I/O
MODEM
INTERFACE
DIGITAL I/O
AND GENERATOR
INTERFACE
82
OPTIONS
BATTERY BOX
Dimensions
1900
1400
1400
(mm) BB BB
BB
86 86
55 0 0 0 0 0
5 74 74 80
Dimensions Dimensions
1900
1900
1900
1400
1400
1900
1900
(mm) (mm)
TC TC TC
E E E
64 64 0 0 0 0
0 0 0 0 74 74 00 64 64 80 80
27 80 40 85 40 10 0 0
0 0 0
MODELS TBX 10 T - TBX 80 T TBX 100 T - TBX 160 T TBX 200 T - TBX 250 T
UPS MODELS MPT 10-80 MPT 100-160 MPT 200
Dimensions
1900
1900
1400
(mm)
64 0 0 80
0 74 64
0 80 0 80
0
www.riello-ups.com 83
MODELS MPM 10 BAT MPM 15 BAT MPM 20 BAT MPM 30 MPM 40 MPM 60 MPM 80 MPM 100
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 - 65 Hz
Soft start 0 - 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BYPASS
Nominal voltage 220 - 230 - 240 Vac single-phase + N
Nominal frequency 50 or 60 Hz (selectable)
OUTPUT
Nominal power (kVA) 10 15 20 30 40 60 80 100
Active power (kW) 9 13,5 18 27 36 54 72 90
Number of phases 1
Nominal voltage 220 - 230 - 240 Vac single-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Residual ripple voltage < 1%
Temperature compensation -0,5 Vx°C
Typical charge current 0,2 x C10
INFO FOR INSTALLATION
Weight without batteries (kg) 200 220 230 270 302 440 500 580
800 x 800 x
Dimensions (WxDxH) (mm) 555 x 740 x 1400 800 x 740 x 1400
1900
Remote signals dry contacts
Remote controls ESD and bypass
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C/ +40 °C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 60 dBA 62 dBA
IP rating IP20
Smart Active efficiency up to 98%
Directives LV 2006/95/EC - 2004/108/EC; Safety IEC EN 62040-1;
Standards
EMC IEC EN 62040-2; Performance IEC EN 62040-3
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS transpallet
BAT
Also available with internal batteries
84
MODELS MPT 10 BAT MPT 15 BAT MPT 20 BAT MPT 30 MPT 40 MPT 60 MPT 80
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 - 65 Hz
Soft start 0 - 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BYPASS
Nominal voltage 360-400-420 Vac three-phase + N
Nominal frequency 50 or 60 Hz (selectable)
OUTPUT
Nominal power (kVA) 10 15 20 30 40 60 80
Active power (kW) 9 13,5 18 27 36 54 72
Number of phases 3+N
Nominal voltage 380 - 400 - 415 Vac three-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Residual ripple voltage < 1%
Temperature compensation -0,5 V/°C
Typical charge current 0,2 x C10
INFO FOR INSTALLATION
Weight without batteries (kg) 228 241 256 315 335 460 540
Dimensions (WxDxH) (mm) 555 x 740 x 1400 800 x 740 x 1400
Remote signals dry contacts
Remote controls ESD and bypass
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C / +40 °C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 60 dBA 62 dBA
IP rating IP20
Smart Active efficiency up to 98%
Directives LV 2006/95/EC - 2004/108/EC; Safety IEC EN 62040-1;
Standards
EMC IEC EN 62040-2; Performance IEC EN 62040-3
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS transpallet
BAT
Also available with internal batteries
www.riello-ups.com 85
MODELS MPT 100 MPT 120 MPT 160 MPT 200
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 - 65 Hz
Soft start 0 - 100% in 120’’ (selectable)
Permitted frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BYPASS
Nominal voltage 360-400-420 Vac three-phase + N
Nominal frequency 50 or 60 Hz (selectable)
OUTPUT
Nominal power (kVA) 100 120 160 200
Active power (kW) 90 108 144 180
Number of phases 3+N
Nominal voltage 380 - 400 - 415 Vac three-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Residual ripple voltage < 1%
Temperature compensation -0,5 V/°C
Typical charge current 0,2 x C10
INFO FOR INSTALLATION
Weight (kg) 600 610 690 790
Dimensions (WxDxH) (mm) 800 x 800 x 1900
Remote signals dry contacts
Remote controls ESD and bypass
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C / +40 °C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 65 dBA 68 dBA
IP rating IP20
Smart Active efficiency up to 98%
Directives LV 2006/95/EC - 2004/108/EC; Safety IEC EN 62040-1;
Standards
EMC IEC EN 62040-2; Performance IEC EN 62040-3
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS transpallet
86
www.riello-ups.com 87
DATACENTRE E-MEDICAL INDUSTRY
Master
TRANSPORT EMERGENCY
HP
6
VFI
TYPE
ONLINE Tower
SmartGrid Flywheel
ready compatible
Supercaps Service
UPS 1st start
HIGHLIGHTS The Master HP series from 100 to 600 kVA Maximised cost savings
is the Riello UPS solution for installations The Master HP has the ability to monitor the
requiring high energy efficiency and mains input quality and to select the best
• IGBT-based rectifier maximum power availability. operating mode based on the interference
technology Master HP Series provides maximum present (Smart Active mode) or circular
protection and power quality for data redundancy (Parallel Energy Saving mode,
• Compact and reliable centres and industrial loads. The UPS has which allows the UPS to regulate available
an IGBT-based rectifier, DSP (Digital Signal capacity based on the immediate demands
• Galvanic isolation Processors) technology and provides true of the load, automatically switching to
On-line, double conversion power standby in the event of excess capacity), the
• High overload capacity protection, (VFI SS 11 - Voltage and Master HP also offers high levels of
Frequency Independent in accordance with efficiency for partial loads, resulting in
• LCD graphic display IEC EN 62040-3). reduced operating costs.
88
Power continuity
For years, Riello UPS has developed and
supplied solutions for dealing with the
different requirements and problems that
inevitably arise in critical applications.
Riello UPS offers flexible, high-availability
solutions that are able to adapt to different
system structures and critical levels. Riello
UPS creates UPS systems that can tolerate a
number of component or subsystem failures,
while continuing to operate normally,
providing power without interruption. This
is achieved by careful design, installing
redundant elements, eliminating common
failure points, scheduling maintenance
activities and controlling and supervising
the system operating parameters and
environment. The TEC service team is ready
to provide guidance and advice on projects.
Main features
• High efficiency (up to 98,5%)
• Compact size: e.g.: only 0,85 m2 for the • High Short circuit current
Master HP 250 kVA • Higher immunity to harmonics or energy
• Reduced weight backfeed generated by the load.
• Double load protection, both electronic
and galvanic, towards the battery.
Advanced supervision
Master HP series UPS have a front panel
The entire Master HP range is suitable for
mounted graphic display providing UPS
use in a wide range of applications. Thanks
information, measurements, status updates
to the flexibility of configuration, available and alarms in different languages, with wave
options and accessories, it is suitable for form displays including voltage/current and
supplying any type of load, e.g. capacitive providing a kWh reading that can be used to
loads such as blade servers etc. measure IT loads and calculate a datacentre
Power supply reliability and availability PUE (power usage effectiveness) ratio.
are ensured for critical applications
by distributed or centralised parallel Smart Grid Ready
configurations of up to 8 units, for redundant Being smart grid ready, Master HP allows for
(N+1) or power parallel configurations and the implementation of power accumulation
all the different configurations offered by solutions, and at the same time ensures
the Master MPS range. extremely high levels of efficiency. It is
also able to independently select the
Zero impact source most efficient operating method based on
Master HP has a zero impact on connected the status of the grid. Master HP UPS are
power sources - grid networks or generators: also able to electronically interface with
• ≤ 3% input current distortion the energy manager using the smart grid
• Input power factor 0,99
communication network.
• power walk-in function - to ensure a
progressive rectifier start-up
• start-up delay function - to restart the
rectifier when the mains power supply is
restored.
1900
1900
problems
• The UPS can be supplied from 2
independent lines 0 00
800 85 1000 85
0 1500 00 2100 10
• Fault on DC bus will not affect the by-pass 10
availability
www.riello-ups.com 89
OPTIONS DETAILS
RS232-REPO SWBYP
CONNECTORS FAN FUSES
ACCESSORIES DRY CONTACTS
RTG 100
56K Modem MULTI I/O
MODEM INTERFACE
GSM Modem
PRODUCT ACCESSORIES
Isolation transformer
Synchronisation device (UGS):
see Master MPS on page 82 DIGITAL I/O
AND GENERATOR
INTERFACE
Hot connection device (PSJ): see Master
MPS on page 82
Digital I/O and Generator interface
Parallel configuration kit (Closed Loop)
Battery cabinets empty or for
extended runtimes NOTE : The layout of controls and connectors may vary based on the size of the UPS
Top Cable Entry cabinets
IP rating IP31/IP42
Dimen-
Dimensions
1900
sions
1900
1900
1900
BB TC (mm) TC TC
(mm) E E
E
86 0 0 0 00
0 80 27 80 40 85 40 10
0 0 0
Dimensions
1900
1900
1900
(mm)
120
64 0 80 0 0 00
0 80 0 80 10
90
MODELS MHT 100 MHT 120 MHT 160 MHT 200 MHT 250 MHT 300 MHT 400 MHT 500 MHT 600
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Frequency 45 - 65 Hz
Power factor > 0,99
Harmonic current distortion <3% THDi
Soft start 0 - 100% in 120’’ (selectable)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BYPASS
Nominal voltage 360-400-420 Vac three-phase + N
Nominal frequency 50 or 60 Hz (selectable)
OUTPUT
Nominal power (kVA) 100 120 160 200 250 300 400 500 600
Active power (kW) 90 108 144 180 225 270 360 450 540
Number of phases 3+N
Nominal voltage 380 - 400 - 415 Vac three-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Ripple current Zero
Recharge voltage
-0,5 Vx°C
compensation
INFO FOR INSTALLATION
Weight (kg) 656 700 800 910 1000 1400 1700 2100 2400
Dimensions (WxDxH) (mm) 800 x 850 x 1900 1000 x 850 x 1900 1500 x 1000 x 1900 2100 x 1000 x 1900
Remote signals dry contacts (configurable)
Remote controls ESD and bypass (configurable)
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C / +40 °C
Relative humidity <90% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m 63 - 68 dBA 70 - 72 dBA
IP rating IP20 (others on request)
Smart Active efficiency up to 98,5%
Standards Safety: EN 62040-1-1 (Directive 2006/95/EC); EMC: EN 62040-2 (Directive 2004/108/EC)
Classification in accordance
(Voltage Frequency Independent) VFI - SS - 111
with IEC 62040-3
Moving the UPS transpallet
www.riello-ups.com 91
DATACENTRE E-MEDICAL INDUSTRY
Master
TRANSPORT EMERGENCY
HE
6
VFI
TYPE
ONLINE Tower
SmartGrid Flywheel
ready compatible
Supercaps Service
UPS 1st start
• LCD Display
92
Complete galvanic separation This provides savings in installation costs in the battery is extremely reduced; this
Master HE UPS feature an output isolation via: arrangement enhance the battery reliability
transformer (delta zig/zag type) on the • a smaller electrical infrastructure. since it is no longer connected to UPS DC
inverter as part of the inverter circuit • smaller circuit protection devices bus.
inside the UPS cabinet, providing galvanic • less wiring.
isolation between the load and the battery Master HE also performs the role of a filter Main features
with improved versatility in system and power factor corrector, protecting the • High efficiency up to 99,4% (stand by on
configuration, allowing: upstream power supply from any harmonics mode)
• Complete UPS output galvanic isolation for and reactive power generated by the critical • Compact size: e.g.: only 0,85 m2 for the
critical infrastructures from the battery DC load. Master HE 250 kVA
power source; • Reduced weight for tranformer based UPS
• two truly separated supply inputs (main Flexibility • Double load protection, both electronic
and bypass), which can be taken from two Master HE is suitable for a wide range of and galvanic, towards the battery.
different power sources (with different applications including IT and the most The entire Master HE range is suitable for
neutrals); this is particularly well suited demanding industrial environments use in a wide range of applications. Thanks
to parallel systems in order to ensure and processes. With several operational to the flexibility of configuration, available
selectivity between the two sources, thus configurations including On-Line, Eco, options and accessories, it is suitable for
improving the reliability of the entire Smart Active, Stand By, Frequency supplying any type of load, e.g. capacitive
installation; Converter and Voltage Stabiliser. A broad loads such as blade servers, rather then
• No neutral input connection is required at range of accessories and options, complex motor drivers or any other critical vertical
the UPS rectifier input stage; this method is configurations and system architectures can application.
particularly favourable in order to prevent be achieved to guarantee maximum power Power supply reliability and availability
the transmission of common neutral availability and the option to add new UPS are ensured for critical applications
disturbances via the neutral conductor; without interruption to existing users. by distributed or centralised parallel
• No effects to the UPS output performance Using the Riello UPS Group Synchroniser configurations of up to 8 units, for redundant
or reduced impact of the inverter power (UGS) and Parallel Systems Joiner (PSJ), (N+1) or power parallel configurations and
components whilst supplying specific sophisticated inter group parallel and all the different configurations offered by
loads; in addition the inverter transformer redundant systems can be achieved to the Master MPS range.
minimizes the impact of third harmonic provide the highest possible levels of
disturbances, prevents the effects of resilience and availability. Smart Grid Ready
energy back-feed into the inverter when Being smart grid ready, Master HP allows for
supplying industrial load applications and Specific solutions the implementation of power accumulation
can supply unbalanced loads. The UPS can be adapted to meet your solutions, and at the same time ensures
• High inverter short circuit current to clear requirements. Contact our TEC team to extremely high levels of efficiency. It is
faults which occur between phase and discuss specific solutions and options not also able to independently select the
neutral on load side (up to three times listed in this catalogue. most efficient operating method based on
nominal current). the status of the grid. Master HE UPS are
Output transformer housed within the Battery care system: maximum also able to electronically interface with
cabinet which allows for a significant battery care the energy manager using the smart grid
reduction in the footprint and provides Master HE series UPS include a range of communication network.
space savings. features designed to prolong battery life
and reduce their usage such as different Advanced supervision
Zero impact source recharging methods, deep discharge Master HE series UPS have a front panel
The Master HE series features the added protection, current limitation and voltage graphic display providing UPS information,
measurements, status updates and alarms in
advantages of the Zero Impact Source compensation according with battery room
different languages, with wave form displays
formula offered by an IGBT-based rectifier temperature.
including voltage/current and provide a kWh
assembly. This eliminates problems Thanks to the STEP-UP/STEP-DOWN
reading that can be used to measure IT loads
connected with installation in networks converter, that provides to recharge and and calculate a datacentre PUE (power usage
with limited power capacity, where the UPS discharge the battery, the current ripple effectiveness) ratio.
is supplied by a generator set or anywhere
there are compatibility problems with loads
that generate current harmonics. Master HE DIMENSIONS
series UPS have zero impact on the power
supply source, whether it is a mains grid or MHE 100 MHE 160 - MHE 200 MHE 300 MHE 500
MHE 800
MHE 120 MHE 250 MHE 400 MHE 600
generator set:
• input current distortion < 3%
• input power factor 0,99
• power walk-in function that ensures
1900
1900
1900
1900
1900
www.riello-ups.com 93
OPTIONS DETAILS
RS232-REPO SWBYP
CONNECTORS FAN FUSES
ACCESSORIES DRY CONTACTS
RTG 100
56K Modem MULTI I/O
MODEM INTERFACE
GSM Modem
PRODUCT ACCESSORIES
Isolation transformer
Synchronisation device (UGS):
see Master MPS on page 82 DIGITAL I/O
AND GENERATOR
INTERFACE
Hot connection device (PSJ): see Master
MPS on page 82
Digital I/O and Generator interface
Parallel configuration kit (Closed Loop)
Battery cabinets empty or for
extended runtimes NOTE : The layout of controls and connectors may vary based on the size of the UPS
Top Cable Entry cabinets
IP rating IP31/IP42
Dimen-
Dimensions
1900
sions
1900
1900
1900
BB TC (mm) TC TC
(mm) E E
E
86 0 0 0 00
0 80 27 80 40 85 40 10
0 0 0
Dimensions
1900
1900
1900
(mm)
120
64 0 80 0 0 00
0 80 0 80 10
94
MHE MHE MHE MHE MHE MHE MHE MHE MHE MHE
MODELS
100 120 160 200 250 300 400 500 600 800
INPUT
Nominal voltage 380 - 400 - 415 Vac 3-phase
Frequency 45 ÷ 65 Hz
Power factor > 0,99
Harmonic current distortion <3% THDi
Soft start 0 ÷ 100% in 120’’ (selectable)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment Back Feed protection; separable bypass line
BYPASS
Nominal voltage 360-400-420 Vac 3-phase + N
Frequency 50 or 60 Hz selectable
OUTPUT
Nominal power (kVA) 100 120 160 200 250 300 400 500 600 800
Active power (kW) 100 120 160 200 250 300 400 500 600 800
Number of phases 3+N
Nominal voltage 380 - 400 - 415 Vac 3-phase + N (selectable)
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor (lpeak/lrms) 3:1
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERIES
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Ripple current Zero
Charge voltage compensation -0,5 Vx°C
INFO FOR INSTALLATION
Weight (kg) 730 785 865 990 1090 1520 1670 2500 2830 3950
3200 x
Dimensions (WxDxH) (mm) 800 x 850 x 1900 1000 x 850 x 1900 1500 x 1000 x 1900 2100 x 1000 x 1900 1000 x
1900
Remote signals volt-free contacts (configurable)
Remote controls ESD and bypass (configurable)
Communication Double RS232 + remote contacts + 2 slots for communications interface
Ambient temperature 0 °C / +40 °C
Relative humidity < 90% non-condensing
Colour Dark grey RAL 7016
Noise level (@ 1 m) 63 ÷ 68 dBA 70 ÷ 72 dBA
Protection level IP20 (others upon request)
Smart Active Efficiency > 99%
Double Conversion Efficiency up to 95,5%
Regulations Safety: EN 62040-1 (directive 2006/95/EC); EMC: EN 62040-2 (directive 2004/108/EC)
Classification according to
(Voltage Frequency Independent) VFI - SS - 111
IEC 62040-3
www.riello-ups.com 95
DATACENTRE E-MEDICAL INDUSTRY
HP UL
6
VFI
TYPE
ONLINE Tower
Flywheel Supercaps
compatible UPS
The incredible levels of quality, reliability More than just an innovative and
HIGHLIGHTS and energy savings offered by the Master HP technologically-advanced UPS, it is a leap
range of UPS have been extended to include into the future of three-phase technology.
• High efficiency a 480 Vac - 60 Hz version, certified as UL,
with power ratings from 65 to 250 kVA. Thanks to its double conversion on-line
• IGBT-based rectifier IT department managers, facility managers technology based entirely on IGBT and
technology and CTOs are under increasing pressure digital signal processors (DSP), the Master
to achieve zero downtime and to size data HP UL range ensures maximum power
• Compact and reliable centre or industrial installations to be supply protection and quality for any type
flexible in the face of continuous changes of load, IT or industrial, in particular for
• Galvanic isolation and expansion. As the search for the most mission critical applications, with VFI SS
reliable and efficient power supply system 111 classification (Voltage and Frequency
• High overload capacity becomes ever-increasingly critical, Riello Independent) in accordance with IEC EN
UPS has been continuously investing in 62040-3. This range was designed using
• North American power solutions to meet the demands of a new configuration that includes an IGBT
voltage (480 Vac) a range of our clients; a commitment that sinusoidal input rectifier instead of the
resulted in the Master HP UL range. conventional thyristor system.
96
Differently from other UPS technologies
available on the market, double conversion
technology with galvanic isolated output
guarantees a quality power supply that is
completely protected from all electrical
anomalies at the input. Even in the event of
serious power supply problems, the output
power remains stable.
1900
1900
0 0 0
800 85 100
0 85 1400 85
www.riello-ups.com 97
MODELS MHT UL 65 MHT UL 80 MHT UL 100 MHT UL 125 MHT UL 160 MHT UL 200 MHT UL 250
INPUT
Nominal voltage 480 Vac three-phase + N
Frequency 45 - 65 Hz
Power factor > 0,99
Harmonic current distortion <3% THDi
Soft start 0 - 100% in 30’’ (selectable)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BATTERIES
Type VRLA AGM / GEL; NiCd; Li-ion; Supercaps and Flywheel
Ripple current Zero
Recharge voltage compensation -0,5 Vx°C
OUTPUT
Nominal power (kVA) 65 80 100 125 160 200 250
Active power (kW) 58,5 72 90 112,5 144 180 225
Number of phases 3+N
Nominal voltage 480 Vac three-phase + N
Static stability ± 1%
Dynamic stability from ± 5% to ± 1% in 20 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 60 Hz
Overload 110% for 60’; 125% for 10’; 150% for 1’
INFO FOR INSTALLATION
Weight (lbs [kg]) 1500 [680] 1610 [730] 1742 [720] 1851 [840] * 2138 [970] * 2247 [1110] *
Weight without manual bypass - - - 1984 [900] 2534 [1145] 2799 [1270]
(lbs [kg])
Dimensions (WxDxH) (inches [mm]) 31,5 x 33,5 x 75 [800 x 850 x 1900] 55 x 33,5 x 75 [1400 x 850 x 1900] *
Dimensions without manual bypass
- 39 x 33,5 x 75 [1000 x 850 x 1900]
‑(WxDxH) (inches [mm])
Remote signals dry contacts (configurable)
Remote controls ESD and bypass (configurable)
Communications Double RS232 + dry contacts + 2 slots for communications interface
Operating temperature 0 °C / +40 °C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m (ECO Mode) 65 dBA 68 dBA
IP rating IP20
Smart Active efficiency up to 98,5%
UL Standard 1778: 2nd edition from 65 to 125 kVA, 4th edition from 160 to 250 kVA;
National Electrical Code (NFPA-70); NEMA PE-1; CUL - CSA C22.2; ASME;
Standards
ASA-C-39.1-1984; FCC section 15 subsection J class A; NEC; OSHA; IEEE 587; ANSI C 62.41-1980; ISO 9000
Lighting and Power Equipment, Auxiliary (OUST)
Classification in accordance with
(Voltage Frequency Independent) VFI - SS - 111
IEC 62040-3
Moving the UPS transpallet
* with Top Cable Entry
98
www.riello-ups.com 99
INDUSTRY TRANSPORT
Master
Industrial
VFI
TYPE
ONLINE Tower 4
Service
1st start
100
Redundant ventilation OPTIONS DIMENSIONS
Redundant ventilation at 100% load is MIM 30 - MIM 40 MIM 60 - MIM 80
SOFTWARE & ACCESSORIES
standard, ensuring operation with a normal
See Master MPS
load with half of the fans operating; in
PRODUCT ACCESSORIES
addition, each fan is monitored and an alarm
Isolation transformer
signal is provided in the event of failure.
1900
Synchronisation device (UGS)
1900
The Easy Source input features, the Battery
Hot connection device (PSJ)
Care System, and the flexibility and Digital I/O and Generator interface
communications capabilities are the same as Parallel configuration kit (Closed Loop)
0
those of the conventional Master MPS range 80
0 1200 80
Battery cabinets empty or for 800
www.riello-ups.com 101
TRANSPORT
Master
FC400
VFI
TYPE
ONLINE Tower 4
Service Airport/
1st start Shipyards
102
Easy installation and maintenance DIMENSIONS
The Master FC400 requires a small space
for installation (only 0,86m2 for a 125 kVA MFC 30 MFC 60 - MFC 80 MFC 60 D - MFC 80 D MFC 125 D
model). The main assemblies of the UPS can MFC 100 - MFC 120 MFC 100 D
be easily accessed for maintenance, via the
removable front panel. Fans located in the
top of the UPS cabinet, eliminate the need
1900
1900
for side or rear access, and allow the UPS
1900
to be placed against a wall.
1400
Applications 0 0
74
0
80
0 1070 80 1200 80
555 800
Master FC400 provides additional
protection for a wide range of applications,
including:
• Powering airplanes in airports OPTIONS
• Radar and flight-control systems
• Naval applications
• Military applications SOFTWARE & ACCESSORIES IP rating IP31/IP42
• Power for test benches. See Master MPS Parallel configuration kit (Closed Loop)
12 pulse version (D)
Battery Back-up PRODUCT ACCESSORIES Filtering of 5th and 11th harmonics (HC)
MFC is also available as UPS with battery Top Cable Entry cabinets
Input isolation transformer
back-up. Digital I/O and Generator interface
www.riello-ups.com 103
104
Modular UPS
www.riello-ups.com 105
DATACENTRE TRANSPORT
Multi
Power
6
VFI
TYPE
ONLINE Modular
3:3 1-28 x 42 kW
up to 1 MW
+ redundancy
USB SmartGrid
plug ready
The Riello MULTI POWER (MPW) is the as healthcare, power generation, social
HIGHLIGHTS ultimate modular UPS for DATA networking, telecommunications, commerce
CENTERS and other CRITICAL LOADs. and education.
• Utmost Availability The MULTI POWER is designed to protect Subsequently, any activities and equipment
any critical high-density computer and IT related to data storage, processing and
PRODUCTS
edge power components and innovative
control technologies have been used in the Outstanding Performances
development of the MPW power modules and • The advanced technologies deployed
other major aspects of the system. The major within the MPW guarantees full rated
power components and assemblies within the power even with unity power factor loads Power Module 42 kW
MPW have been specifically designed and (kVA=kW) without any power downgrading
tailor made in conjunction with the respective even when operating at temperatures up to
component manufacturers. This design work 40°C.
ensures that the MPW achieves the highest • High system efficiency whilst operating
levels of power and performance. in on-line double-conversion mode
In order to optimize the overall performance greater than 96,5%. Even when loaded
of the finished product, Riello’s R&D team at only 20%, the MPW still achieves an
made the decision to specifically design outstanding performance greater than
certain power components, including the IGBT 95%. This superior performance ensures
modules and associated packages. Rather extremely low losses at any load level
than using standard components that are whilst maintaining a true modular solution Battery Shelf - 4 x Battery Units
readily available in the marketplace, the Multi for any changing UPS environment in terms
Power hosts one single optimised and reliable power demands.
power assembly which guarantees the best • Low input harmonic pollution, with near
availability and overall efficiency. unity input power factor and an extremely
The Power Module itself utilizes a “wireless wide input voltage operating range (+20/-
power principle” meaning that the power 40%), requiring only a minimum upstream unique microprocessor, but by three - each
interconnection distances between the power source rating and subsequent having different and specific duties. Likewise,
cards, power components and connectors reduced investment costs. the Power cabinet features two separate
are shorter. In this way we reduce any risk microprocessors; one to regulate the overall
related to connection problems between the Multiple Controls UPS operations and a separate one to manage
assemblies and also minimize the overall The entire Multi Power solution was communication with the user.
power losses. developed with particular care to ensure In addition, three dedicated communications
operational reliability and prevent any bus manage and transmit the data.
Scalability possible failures due to miscommunication In terms of the monitoring and control of the
Multi Power provides a comprehensive, easy- between the component parts of the system. overall system, all major components are
to-integrate power protection solution for The Power Modules are not controlled by one continually temperature monitored within
data centers and any critical IT application
matching the evolving demands of a
networked environment.
The end user can easily increase power,
redundancy level and battery autonomy by
simply adding additional UPS Power Modules
and Battery Units.
Two different cabinet frames are available to
build the system: The Power Cabinet and the
Battery Cabinet.
The available UPS power and redundancy
level can expand vertically from 42 to 294kW
in one single Power cabinet (1 to 7 Power
Modules including redundancy). Similarly
up to four Power Cabinets can be connected
in parallel, increasing the capacity from
294kW up to 1176kW. The Battery cabinet
accommodates multiples of 4 battery units,
with up to 36 units within a single frame with
a maximum of 10 Battery cabinets connected
in parallel.
In addition, the MPW is available as an
optimized solution providing a Multi Power/
Battery combination with three UPS Power
Module slots and five battery shelves. This
solution can be utilized within extremely
compact areas requiring a small footprint with Power Cabinet (1÷7 x Power Modules) x 4
www.riello-ups.com 107
each of the Power Modules. In addition, up speed controlled fans to ensure tthere is no
to four-temperature sensors are embedded energy wasted as the load level applied to
within the Power cabinet to ensure constant the system increases or decreases. At the
and efficient operation. same time each fan features a so-called
The UPS module is equipped with three third wire (the controller) which immediately
warns the microprocessor in the event of
a fault; in which case the microprocessor
will increase the speed of the remaining
operational fans in order to compensate for
the cooling deficiency. The Battery unit also
contains dedicated internal protection and a
sophisticated control system to monitor the
status of each module. This makes it possible
to check the voltage/current supplied by each
single battery module and therefore identify
and warn the user if one of them is defective
or beginning to fail. This significantly reduces
the risk of a battery pack failure causing
a problem to the system by immediately
warning the user of the impending issue in
order for the appropriate preventive actions
to be taken before it is too late.
108
(% PA UPS) P
unit as standard. The system is equipped Advanced Communications Q
with a Manual bypass change over switch Users can benefit from the different
and Backfeed control with a mechanical communication systems developed
100 CAPACITIVE
interlock contactor inbuilt, eliminating any specifically for IT personnel, facilities
maintenance-related downtime. managers and service engineers.
80
Combination systems (Power cabinet with The 7”LCD touch screen, communication
Battery cabinet) are supplied with a battery slots, relay cards along with the dedicated 60 cosfi 0,9
switch and shunt trip to enable remote service ports, all ensure that the UPS setup, 100% kVA
battery switch operation. control and monitoring is easy, along with the 40
All these features ensure easy UPS expansion, intergration into any building management
cosfi 1
operation and maintenance; minimizing system and data center infrastructure 20 100% kVA=kW
downtime, decreasing the Mean Time to management (DCIM). Multi Power is
Repair (MTTR) and removing any possible compatible with the very latest operating % PA 0
25 50 75 100 (% P UPS) P
risk to power continuity, when carried out by systems including
20
authorized service personnel. • Windows 7, 8
Flexibility is measured by the ease of both • Hyper-V cosfi 0,9
40 100% kVA
on site installation and the operations • Windows Server 2012, 2008, and previous
undertaken by the user. Input/Output/ versions 60
battery terminal bars are deployed enabling • Mac OS X
authorized installers to easily terminate the • Linux 80
cables either from the top or the bottom of • VMWare ESXi INDUCTIVE
the system. Mechanical supports and cable • Citrix XenServer 100
glands as well as the terminal bar positioning and many other Unix operating systems.
(in the centre of the cabinet) are purposely
(% PA UPS) P
positioned to reduce the installation time and Q
costs.
OPTIONS
CABINETS
Mo
Dimensions du
lar
(mm) BC BB
1900
1600
BB
1320
BB
60 50
40 5 0 10 86
0 81 65 0 0
0 75 80
0
www.riello-ups.com 109
DETAILS
MPW Power Cabinet MPW Power Cabinet
42-294 kW 42-294 kW
(front) (back)
AUXILIARY SIGNAL BOARD
A
U
SWIN X
SWMB E
X
T
SWBYP
C
SWBATT O
N
SWOUT T
A
CONNECTIVITY TEMP C
T
S
PANEL (CP)
AUXILIARY
OPENING
RELEASE
SWBATT
SIGNAL
BOARD R.E.P.O.
MANUAL BY-
PASS SWITCH
(SWMB)
10/100 NETWORK
POWER SUPPLY
UNIT (PSU)
POWER MODULE
(PM)
MAIN
COMMUNICATION
UNIT (MCU)
COMMUNICATION MONITORING
SLOTS UNIT (MU)
MONITORING
POWER MODULE UNIT (MU)
(PM)
POWER SUPPLY
UNIT (PSU)
BATTERY UNIT (BU)
CONNECTIVITY
PANEL (CP)
AUXILIARY
SIGNAL
MANUAL BY- BOARD
PASS SWITCH
(SWMB)
BYPASS MODULE
(BM)
RELAY
SLOT
BATTERY SWITCH
(SWBATT)
BATTERY SWITCH
(SWBATT)
BATTERY UNIT (BU)
110
MODEL MPW - from 42 to 294 kW1
INPUT
Voltage [V] 380-400-415 Vac Three-Phase plus neutral
Voltage tolerance [V] 240 to 480 2
Frequency tolerance [Hz] 40 to 72
Power factor 1
THDI [%] < 3,5
BYPASS
Nominal power [kW] 252 (Power Cabinet) / 126 (Combo cabinet)
Nominal voltage [V] 380-400-415 Vac Three-Phase plus neutral
Voltage tolerance [V] from 180 (adjustable 180-200) to 264 (adjustable 250-264) referring to Neutral
Nominal frequency [Hz] 50 or 60
Overload 125% for 10 minutes; 150% for 1 minute
BATTERIES
Layout Modular type made up by Battery Unit (named BU) or Free Standing Battery Box / Shelf
VRLA batteries lined up Constant voltage and current measuring
Battery Unit features
Battery status monitoring via MPW LCD display
OUTPUT
Nominal voltage [V] 380/400/415 Vac Three-Phase plus neutral
Nominal frequency [Hz] 50 or 60
Voltage stability [%] ± 0,5
Dynamic stability EN62040-3 class performance 1 distorting load
OVERALL SPECIFICATION
Power Module nominal power
42
[kW] (Named PM)
Output power factor [pf] 1
Eco Mode Efficiency Up to 99%
Cabinet type Power Cabinet Combo Cabinet Battery Cabinet
Nominal Power [kW] 294 126 N.A.
Parallelable (up to) 4 4 N.A.
3 x PM 3
Cabinet lay out description 7 x PM3 9 x Battery shelves
5 x Battery shelves
Weight [kg]
320 360 280
(without PM3 /BU4)
System Noise Level at 1 m
< 68 <65 N.A.
[dBA±2] (Smart Active)
Cabinet IP rating IP20 finger proof (either with cabinet doors open or close)
NOTE: All performances quoted in a single row refer to any UPS system configuration from one to seven modules running in parallel unless specified differently.
www.riello-ups.com 111
DATACENTRE E-MEDICAL
Multi
Guard
VFI 5
TYPE
ONLINE Modular
Service
1st start
The Multi Guard modular UPS is a scalable Each module has an individual power
HIGHLIGHTS three-phase / three-phase uninterruptible capacity of 15 kVA, and a standard cabinet
power supply system with double can be fitted with up to 8 modules to reach
• Power flexibility conversion technology. Its power capacity 120 kVA. If the load is within permitted
15-120 kVA ranges from 15kVA to 120kVA, delivering the limits, modules can be hot-swapped to
best combination of reliability, functionality enable true power continuity without any
• UPS module with and flexibility. interruptions.
hot-swap function The Multi Guard N+X parallel architecture
adopts a highly intelligent modular design System features
• Modular power and to achieve maximum power availability and • Maximum 120kVA capacity in a 19“ rack.
runtime redundancy. • Input power factor >0,99
It is specially designed to meet the THDi <2% and output voltage distortion
• Intelligent battery protection demands of mission critical equal to 1,5%.
charging system loads in data centres or other important • 15 kVA per module with hot-swap
applications. function.
• High MTBF and low
MTTR
112
• The LCD display on the front panel Intelligent recharging system
displays unit status and important The Multi Guard UPS system applies a two-
information such as input and output step intelligent charging system. The first
nominal values, capacity, temperature and stage is a constant charging current that
autonomy. can recharge the battery capacity to 90%
• Communication port for standard Ethernet very quickly. The system then transfers to
and relay contact board. a constant voltage mode to guarantee the
• DSP technology, IGBT input. battery can stay fully charged all the time.
• 36 Ampere battery charge current on a This intelligent charging system not only
120 kVA system. reduces the battery recharging time but
also extends battery life, saving on battery
Further advantages replacement costs.
• The Multi Guard UPS power modules use
the latest DSP microchip technology. This Modular Autonomy
reduces hardware components, increases The Multi Guard 30 and 60 versions are
UPS reliability and also makes it easier to designed to build up internal run time using
update and maintain the software. a single battery module for all power and
• The UPS operates with load sharing autonomy requirements.
technology. Should any of the UPS The same battery module is also used
modules fail, the load will be taken to build up the required autonomy in an
over by the rest of the modules without external cabinet.
interruption. This increases the real
time operation and power availability Low total Cost of Ownership (TCO):
compared to other standby UPS. − Lower system set-up costs
• The Multi Guard UPS is designed to − Lower energy costs
connect to external battery banks in order − Lower cooling costs
to ensure the required battery run time. − Lower expansion costs
− Lower maintenance costs.
GMT 60 kVA
Advanced Modular Design
The Multi Guard system contains UPS UPS power selection
modules, a LCD Display module, the PDU The Multi Guard can be configured from 1
and other accessories. Each UPS module up to 8 modules in its cabinet to form the
is a fully independent 15kVA UPS. Thanks most suitable N + X configuration for the
to the advanced wireless parallel control application.
technology and smart communication, the Multi Guard grows as your needs grow by
UPS modules and LCD display modules simply adding further UPS modules and
can be easily replaced at any time without battery modules to the existing frame. The
affecting UPS operation. The user friendly initial investment is recuperated in cost
“plug & play” design simplifies UPS savings. New power supply requirements
servicing and maintenance. can be satisfied without complex and costly
The Multi Guard de-centralises the control replacement operations.
units in each UPS Module. The LCD Display
module is for display and communication
purposes only. If the LCD Display module
fails, the UPS system still functions and
supports the load without any interruption.
Redundancy
High capacity MTBF Easy
maintenance
System MTBF for two modules in parallel
is more than 1.000.000 hours and power
availability is above 99,999%.
Each 15-120 kVA redundant configuration
guarantees correct operation even in
the event of the failure of one of the
UPS modules. The module replacement
procedure only takes 5 minutes for full
system recovery.
This solution allows you to:
• Minimise downtime;
• Reduce the number of stored spare parts;
• Avoid the need for specialised technicians
Scalability
www.riello-ups.com 113
OPTIONS
PRODUCT ACCESSORIES
Modular battery cabinet
(9 shelves, 36 battery modules)
Relay alarm board
Battery cabinets for any autonomy
requirements
MULTI GUARD 30
MULTI GUARD 60
The Multi Guard 60 system allows you to No. OF POWER Typical autonomy
kVA
install from one to four UPS modules (15 MODULES (min)(*)
kVA to 60 kVA) in a 19” rack cabinet, which is 1 15 113
able to house up to 5 battery shelves. 2 30 54
If redundancy is required (N+1 modules) the 3 45 30
max. output power will be 45 kVA. 4 60 21
(*) The autonomy refers to the max. number of installed
batteries inside the UPS
OPTIONAL
The Multi Guard 120 system allows you to No. OF POWER Typical autonomy
kVA
install from one to eight UPS modules (15 MODULES (min)(*)
kVA to 120 kVA) in a 19” rack cabinet, with 1 15 217
batteries housed in an external cabinet. This 2 30 103
cabinet houses the same battery modules as 3 45 65
those used for the GMT 30/60 versions, up
4 60 49
to a maximum of 9 battery shelves.
5 75 36
6 90 30
7 105 22
8 120 10
114
MODEL GMT - from 15 kVA to 120 kVA
INPUT
Voltage 380-400-415 Vac, three-phase + N
Voltage tolerance from 294 Vac to 520 Vac
Frequency tolerance between 40 Hz and 70 Hz
Power factor >0,99
THDI < 2%
BYPASS
Voltage 380-400-415 Vac, three-phase + N
Voltage tolerance from 323 Vac to 437 Vac
OUTPUT
Voltage 380-400-415 Vac, three-phase + N (selectable)
Voltage stability ≤ 1,5%
Frequency 50 Hz / 60 Hz
UPS MODULE
Power 15 kVA / 13,5 kW
Output power 15 kVA x number of modules, up to a maximum of 8
SPECIFICATIONS
Noise level at 1 m (ECO Mode) from ≤ 60 dBA to ≤ 62 dBA
Operating temperature O °C / +40 °C
Humidity 20% - 90% non-condensing
Storage temperature -15 °C +55 °C
UPS module weight (kg) 35
UPS module dimensions
440 x 700 x 131
(WxDxH) (mm)
GMT 30 cabinet dimensions
600 x 1000 x 1500
(WxDxH) (mm)
GMT 60 cabinet dimensions
600 x 1000 x 2000
(WxDxH) (mm)
GMT 120 cabinet dimensions
600 x 1000 x 2000
(WxDxH) (mm)
Modular battery cabinet di- 9 battery shelves, 36 battery modules
mensions (WxDxH) (mm) 597x1003x2000
Eco Mode efficiency up to 99%
Standards Safety: IEC 62040-1 EMC: IEC 62040-2
Moving the UPS transpallet
www.riello-ups.com 115
DATACENTRE E-MEDICAL INDUSTRY TRANSPORT
Multi
Guard
Industrial
6
VFI
TYPE
ONLINE Modular
HIGHLIGHTS The Multi Guard Industrial range was High adaptability to input voltage
specially developed to ensure power Multi Guard Industrial is available in two
continuity in all sectors deemed critical due versions: single-phase and three-phase
• High adaptability to to the specific environmental conditions or output, whilst the input stage accepts both
input voltage industrial processes requiring protection. a triplet of three-phase supplies out-of-
Multi Guard Industrial is available in a 20 phase by 120° (three-phase 400 V+N) or a
• Zero impact source kVA stand alone version and in modular triplet of power supplies in phase (single-
versions from 20 to 160 kVA. The two phase 230 V+N). Thanks to its power supply
• Compatible versions are available in both single-phase recognition function the UPS is able to adapt
with industrial and three-phase output configurations. to the input power supply with no need for
environments This high level of flexibility allows Multi additional configuration, ensuring the same
Guard Industrial to accept both single-phase performance under both applied voltage
• Modular Plug & Play and three-phase inputs with no need for conditions.
solution special set ups or operator intervention,
ensuring full compatibility with any power Zero impact source
• Complete flexibility supply network. Thanks to the technology it employs,
116
Parallel configuration and programmable relay Harting connectors
contacts board
Multi Guard Industrial solves all problems out so that the communication signal The cabinet is also equipped with an area
connected with insertion into power supply connections are segregated and separated that can be used for the insertion of a whole
grids with limited power, where the UPS is from the power connections (input, output, range of accessories for monitoring power
supplied by a generator and where the same bypass line, battery), thus ensuring complete that the user can request (surge arresters,
network includes single-phase (e.g. railway immunity from interference generated by energy meters, earth discharge detectors,
voltage) and three-phase (e.g. emergency the power supply grid, which is typically output distribution, release coils, etc), making
power supply from a generator) supplies. disturbed in industrial environments. the solution compact and optimised for any
Multi Guard Industrial has zero impact on Both versions (single-phase and three- field of use.
the power supply source, whether it is a phase output) are provided with a bypass
mains grid or generator set, single-phase or line separated from the power supply line. Modular Plug & Play solution
three-phase: This ensures greater availability in that Multi Guard Industrial can be purchased as
• power supply voltage recognition (single/ the customer may have a preferential line a single 20 kVA UPS module and installed
three-phase), with no need for setting up for the bypass that is not restricted by the in any cabinet or mechanical support
or reconfiguring parameters potential interference or interruptions that provided by the user. The power terminals
• input current distortion < 3% the UPS power supply line may be subject to. (input, output, battery) are connected by
• input power factor 0,99 The UPS module has a front to back air Harting connectors, ensuring simplicity and
• power walk-in function that ensures flow, allowing the UPS to be installed in operating safety during insertion/removal,
progressive rectifier start up any environment and preventing the types protection against electrical contacts and
• start-up delay function, to restart the of ingress problems associated with top- immunity from environmental conditions
rectifiers when mains power is restored if vented circulations cabinets. typical of industrial environments (dust,
there are several UPS in the system. Every UPS module in the Multi Guard humidity, suspended chemical particles).
• ‘cold start’ function for starting the UPS Industrial range can be equipped with a The removal and replacement of a faulty
from the battery. parallel board, a relay board with eight module or the addition into the system of
In addition, Multi Guard Industrial plays a programmable outputs and three inputs a further UPS module to increase available
filtering and power factor correction role (one of which is programmable), and two power or redundancy can be carried out
in the power network upstream of the UPS slots for housing communications interface easily by the operator responsible for the
as it eliminates harmonic components boards from the MultiCOM range, making the system.
and reactive power generated by utility UPS compatible with the various types of
suppliers. protocols and supervision systems typical of Complete flexibility
the industrial environment. Multi Guard Industrial is the ideal solution
Compatible with industrial The cabinet is designed to house up to four for industrial environments in which the
environments UPS modules. I t has an area that contains all UPS must adapt to the various requirements
The mechanical structure of Multi Guard the protection devices and disconnectors typical of this application. Aside from the
Industrial makes it particularly versatile for for the individual modules (4 input distinction between single-phase and three-
use in many different sectors. disconnectors, 4 battery disconnectors, phase output voltages, the UPS module
The basic building blocks are 20 kVA UPS. 4 bypass line disconnectors and 4 output can be used as a stand-alone unit or in a
The cabinet is able to house up to four 20 disconnectors), as well as a manual parallel configuration; by simply adding the
kVA modules and up to two cabinets can be bypass for isolating the four modules and parallel configuration board in the slot on
connected in parallel for a total of eight UPS guaranteeing power continuity in the event the front of the module, the UPS can grow as
modules and 160 kVA of power. of the complete failure of all the UPS units or requirements demand (from 20 to 160 kVA).
The module connection clamps are laid in the event of scheduled system overhaul. Multiguard Industrial ensures horizontal
www.riello-ups.com 117
scalability that minimises the system
footprint, the user can thus have power
capabilities from 20 to 80 kVA without
increasing the footprint. This is particularly
advantageous when the system is installed
in environments with space limitations (e.g.
containers, historic buildings, sites spread
out over a territory).
Each UPS is equipped with a graphic display,
a programmable relay board slot and two
slots for communications interfaces, all
situated at the front for quick and organised
installation.
Every UPS module in the Multi Guard
Industrial range is completely independent Detail of protective devices and disconnectors
with regards to the control and management
of the operator interfaces; this facilitates same: this allows for rapid and intuitive boards that the installation technician must
all monitoring, control and fault-detection access to information as well as simplified position inside the destination cabinet or
operations, ensuring increased reliability management of the spare parts in storage. near the module.
in that any malfunctions in parts or
accessory will not propagate through the Stand-alone version:
entire system. Multi Guard Industrial is a Different from the cabinet version, the stand
UPS that uses many components also used alone system is supplied with input, bypass
in the Multi Sentry range; in particular line, output and battery connectors with
the display and navigation menus are the loose cables three metres in length and filter
OPTIONS DETAILS
R.E.P.O
MULTICOM 302 Internal batteries
BATTERY TEMPERATURE SENSOR
MULTICOM 352 MST range battery cabinets
MULTICOM 382 COMMUNICATIONS BOARD SLOT
OUT
BYPASS
BATTERIES
INPUT
118
GMI single-phase output (GMI M) GMI three-phase output (GMI T)
MODEL from 20 kVA to 160 kVA from 20 kVA to 160 kVA
INPUT
380-400-415 Vac, three-phase + N and 220-230-240 Vac single-phase + N
Voltage
(input voltage recognition function)
Voltage tolerance -40/+20% *
Frequency tolerance between 40 Hz and 72 Hz
Power factor >0,99
THDI < 3%
BYPASS
Voltage 220-230-240 Vac, single-phase + N 380-400-415 Vac, three-phase + N
Voltage tolerance 180 - 264 V (selectable) referring to neutral phase
Overload 125% for 60 minutes; 150% for 18 minutes
OUTPUT
Voltage 220-230-240 Vac, single-phase + N (selectable) 380-400-415 Vac, three-phase + N (selectable)
Voltage stability ≤ 1%
Frequency 50 Hz / 60 Hz
UPS MODULE
Power 20 kVA / 18 kW
Output power 20 kVA x number of modules, up to a maximum of 8 (max. 160 kVA)
BATTERIES
Layout independent batteries for each UPS module or shared by the UPS system
Type VRLA AGM/GEL
Recharge time 6 hours
SPECIFICATIONS
Noise level at 1 m (ECO Mode) from ≤ 52 dBA to ≤ 70 dBA
Operating temperature O °C / +40 °C
Humidity 20% - 90% non-condensing
Storage temperature -15° +55°
UPS module weight (kg) 64
UPS module dimensions
620 x 745 x 320
(WxDxH) (mm)
GMI cabinet weight (kg) 200 (UPS modules excluded)
GMI cabinet dimensions
850 x 850 x 2060
(WxDxH) (mm)
Modular battery cabinet 9 battery shelves, 36 battery modules
dimensions (WxDxH) (mm) 597 x 1003 x 2000
Eco Mode efficiency up to 99%
Standards Safety: IEC 62040-1 EMC: IEC 62040-2
Moving the UPS transpallet (UPS cabinet) - 2 operators (UPS module)
* conditions applied
NOTE : The GMI UPS is also compatible with the battery cabinets in the Multi Sentry range (MST)
www.riello-ups.com 119
120
CPSS
Central Power Supply Systems
www.riello-ups.com 121
Central
Supply
Systems
1:1 3:1 6-15 kVA
3:3 10-100 kVA
EN50171 PRODUCTS
VERIFIED BY
CERTIFIED
The CSS (Central Supply Systems) range autonomy to be carried out with extreme
HIGHLIGHTS by Riello UPS is certified and designed in ease and in complete safety by simply
compliance with standard EN 50171 and is operating an input switch. This switch
CERTIFIED COMPLIACE WITH therefore the ideal solution for installation interrupts the power supply to the machine
STANDARD EN 50171 in buildings subject to fire safety regulations without interrupting the bypass line, which
Ideal for emergency lighting and alarm and in particular for the power supply of is able to support the load in the event of
systems. emergency lighting systems. In addition test failure.
the CSS range by Riello UPS is also suitable
DUAL INPUT
for supplying power to other emergency HIGH RECHARGE CURRENT AND
Simplicity and safety for the periodical
systems such as automatic fire extinguishing BATTERY CARE SYSTEM
system operation check.
systems, alarm systems and emergency Proper battery care is critical to ensuring
PROTECTION AGAINST BATTERY detection systems, smoke extraction correct CSS operation in emergency
INVERSION equipment and carbon monoxide detection conditions.
Protection for emergency services and devices as well as dedicated security The Riello UPS battery care system consists
safety for operators. systems in sensitive areas. of a series of features and capabilities
The use of centralised supply systems (CSS) designed to obtain the best performance,
HIGH RECHARGE CURRENT
ensures a significant reduction in system extend operating life and satisfy the
Reduced recharge times.
set-up and maintenance costs as well as recharge times imposed by the standard.
CONTINUOUS OVERLOAD OF 120% making periodical checks simpler and faster The Riello UPS CSS range is designed in
Large power reserve. to perform. compliance with standard EN 50171 and
ensures high current levels are available
CASING COMPLIANT WITH
DUAL INPUT for the batteries, allowing recharge of up to
STANDARD EN 60598-1
The Riello UPS CSS range is equipped with 80% of full autonomy within 12 hours.
High mechanical protection.
DUAL INPUT as standard on all models. Riello UPS CSS are suitable for use with
BATTERIES WITH 10 YEAR LIFE This important feature allows the mandatory hermetically sealed lead-acid (VRLA), AGM
Long battery life. scheduled checks on system operation and and GEL batteries and Open Vent and Nickel
122
Cadmium batteries. Different charging GENERAL FEATURES in accordance with the parameters set out in
methods are available depending on the In addition to the features mentioned here, standard EN 50171.
battery type. the Riello UPS CSS range has all the features In particular the models in the 3h range
The recharge voltage compensation function of reliability and flexibility common to the feature transformer-based technology
based on temperature prevents excessive UPS range it derives from, as well as offering and provide maximum protection for the
battery charges and overheating. compatibility with the main options and connected load.
The deep discharge protection prevents accessories. The models in the 3h range are based on
reduced battery performance and battery transformer-less technology, therefore
damage. MODELS providing improved efficiency and reduced
The Riello UPS CSS range is based on both footprints.
HIGH OVERLOAD CAPACITY single-phase and three-phase models
As required by standard EN 50171, the Riello divided into two product families, 1h and 3h,
UPS CSS range is designed and sized to optimised to offer maximum runtimes of 1
support continuous overloads (with no time hour and 3 hours respectively at nominal load
limits) of up to 120% of the machine's nominal
power rating.
OPERATING MODE
Every Riello CSS model supports all the operating modes set out and described in standard EN50171, as below:
www.riello-ups.com 123
6 10 15 10 15 20 30 40 60 80 100
CSS 1h models 1 ph 1 ph 1 ph 3 ph 3 ph 3 ph 3 ph 3 ph 3 ph 3 ph 3 ph
INPUT
220 - 230 - 240 Vac 1 ph
Nominal voltage 380 - 400 - 415 Vac 3 ph + N
380 - 400 - 415 Vac 3 ph + N
Nominal frequency 50/60 Hz
Frequency tolerance 40 - 72 Hz
BYPASS
Nominal voltage 220 - 230 - 240 Vac 1 ph 380 - 400 - 415 Vac 3 ph + N
Number of phases 1 3+N
Voltage tolerance 180 - 264 V (selectable)
Nominal frequency 50 or 60 Hz (selectable)
Frequency tolerance ±5 (selectable)
OUTPUT
Nominal power (kVA) 6 10 15 10 15 20 30 40 60 80 100
Active power (kW) 5,4 9 13,5 9 13,5 18 27 36 54 72 90
Power factor 0,9
Number of phases 1 3+N
Nominal voltage 220 - 230 - 240 Vac 1 ph 380 - 400 - 415 Vac 3 ph + N
Static variation ± 1%
Dynamic variation ± 3%
Crest factor 3 : 1 Ipeak/Irms
Voltage distortion ≤ 1% with linear load / ≤ 3% with non-linear load
Frequency 50/60 Hz
Frequency stability during
0,01%
battery operation
Overload 120% continuous, 132% 10 min, 160% 1 min, 180% 5 s
BATTERIES
Type VRLA AGM/GEL 10 years (external)
Recharge time 80% of full autonomy in 12 hours
Typical recharge current 0,2 x C10
Temperature compensation -0,5 V/°C
INFO FOR INSTALLATION
Weight without batteries (kg) 107 112 122 112 122 138 148 194 204 224 250
650 x 840
Dimensions (WxDxH) (mm) 440 x 850 x 1320 500 x 850 x 1600
x 1600
Communications 3 slots for communications interface / USB / RS232
Operating temperature 0°C / +40°C
Relative humidity 90% non-condensing
Colour Dark grey RAL 7016
IP rating IP20
Smart Active efficiency up to 99%
EN 50171 - European Directives: L V 2006/95/CE low voltage Directive
EMC 2004/108/CE electromagnetic compatibility Directive
Standards
Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2
Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111
Moving the CSS castors (6 - 80 kVA) / transpallet (100 kVA)
124
6 10 15 10 15 20 30 40 60 80 100
CSS 3h models 1 ph 1 ph 1 ph 3 ph 3 ph 3 ph 3 ph 3 ph 3 ph 3 ph 3 ph
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Nominal frequency 50/60 Hz
Frequency tolerance 40 - 72 Hz
BYPASS
Nominal voltage 220 - 230 - 240 Vac 1 ph 380 - 400 - 415 Vac 3 ph + N
Number of phases 1 3
Voltage tolerance ± 5% ÷ ± 25%
Nominal frequency 50 or 60 Hz (selectable)
Frequency tolerance ± 1% ÷ ± 6%
OUTPUT
Nominal power (kVA) 6 10 15 10 15 20 30 40 60 80 100
Active power (kW) 5,4 9 13,5 9 13,5 18 27 36 54 72 90
Power factor 0,9
Number of phases 1 3+N
Nominal voltage 220 - 230 - 240 Vac 1 ph 380 - 400 - 415 Vac 3 ph + N
Static variation ± 1%
Dynamic variation ± 3%
Crest factor 3 : 1 Ipeak/Irms
Voltage distortion ≤ 1% with linear load / ≤ 3% with non-linear load
Frequency 50/60 Hz
Frequency stability during
0,05%
battery operation
Overload 120% continuous, 130% 60 min, 145% 10 min, 170% 1 s
BATTERIES
Type VRLA AGM/GEL; NiCd; Li-ion 10 years (external)
Recharge time 80% of full autonomy in 12 hours
Typical recharge current 0.2 x C10
Temperature compensation -0,5 V/°C
INFO FOR INSTALLATION
Weight without batteries (kg) 200 220 230 241 256 315 335 460 540 600 610
Dimensions (WxDxH) (mm) 555 x 740 x 1400 800 x 740 x 1400 800 x 800 x 1900
Communications 2 slots for communications interface / 2 RS232 / dry contacts
Operating temperature 0°C / +40°C
Relative humidity 90% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m 60 dBA 62 dBA 65 dBA 68 dBA
IP rating IP20
Smart Active efficiency up to 98%
EN 50171 - European Directives: L V 2006/95/CE low voltage Directive
EMC 2004/108/CE electromagnetic compatibility Directive
Standards
Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2
Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111
Moving the CSS transpallet
www.riello-ups.com 125
126
Transfer Systems
www.riello-ups.com 127
DATACENTRE
Multi
Switch
1:1 16 A
or SSH which makes the Riello UPS Multi after AC voltage drops to zero. The IEEE
HIGHLIGHTS
Switch an ideal device for the IT manager who 1100-1999 standard also references the ITI
needs flexibility and protection for their IT curve. The SSI (Server System Infrastructure)
• Redundant power equipment. standard recommends a hold-up time for
supply Multi Switch provides installations with power power supplies to be a minimum of 21ms for
supply continuity. Its operating principle a voltage range of 100-240V.
• Load protection ensures higher reliability than a single UPS, Multi Switch units switch sources under these
(with or without its own internal bypass).
• Versatile to use
Operating principle
The Riello UPS Multi Switch is a high Multi Switch provides direct distribution of
availability and versatile intelligent switch eight 10 A IEC outlets in a system with two Ouput 1
that provides redundant power to connected input power lines (two mains inputs, or two Max 4 A
equipment with two AC input sources. The UPS).
Riello UPS Multi Switch supplies power to Multi Switch is able to connect to either of the Ouput 2
the connected loads from a primary mains two input power lines, whilst simultaneously Max 4 A
source. The transfer time from one source If one of the loads fails (e.g. short circuit), Multi
according the ITI (CBEMA) chart does not Switch disconnects the group of sockets Ouput 4
impact the operation of the connected where the load is connected, thus preventing Max 4 A
Input 1
equipment as the switching occurs safely other loads from being switched off (i.e. in the
between the two input sources regardless of event of poor discrimination of the protection Ouput 5
Max 4 A
any phase differences. The Riello UPS Multi devices). Input 2
128
industry standard times.
The switching time includes the time for the
DETAILS
built-in intelligence to determine whether the
MSW (2 inputs - 8 outputs) OUTPUT SOCKETS
voltage and frequency are in range. Any point
COMMUNICATIONS
of failure in the electronics does not cause a FRONT INTERFACE SLOT
MODELS MSW
NOMINAL CURRENT (A) 16
INPUT
Nominal voltage - sources S1/S2 230 Vac single-phase + N
Input voltage tolerance 180-276 Vac (selectable)
Switched input phases ph+N (two poles)
Nominal frequency 50/60 Hz
Input sockets 2 IEC 320 (16 A)
OPERATING SPECIFICATIONS
Transfer type “Break Before Make” (no overlapping sources)
Transfer time following source failure < 8 msec (S1/S2 synchronised) 20 msec (S1/S2 non synchronised)
OUTPUT
Nominal voltage choice of one of the two input power sources
Max. load for each output 4A
Output sockets 8 IEC 320 10 A
ENVIRONMENTAL SPECIFICATIONS
Efficiency at full load > 99%
Noise at 1 m from front (from 0 to full load) < 35 dBA
Storage temperature -10 °C up to +50 °C
Operating temperature O °C - 40 °C
Relative humidity 90% non-condensing
Max. installation height 1000 m at nominal power (-1% power for every 100 m above 1000 m) - Max 4000 m
Reference standard EN 62310-1 (safety) EN 62310-2 (electro-magnetic compatibility)
INFO FOR INSTALLATION
Weight (kg) 10
Dimensions (WxDxH) (mm) 19” x 360 x 2U
Colour RAL 5004
IP rating IP 20
Communications RS232 / Slot for communication interface
www.riello-ups.com 129
DATACENTRE
Multi
Switch
ATS
1:1 16 A
HIGHLIGHTS interface, SNMP, or SSH which makes the after AC voltage drops to zero. The IEEE
Riello UPS Multi Switch ATS an ideal device 1100-1999 standard also references the ITI
for the IT manager who needs flexibility and curve. The SSI (Server System Infrastructure)
• Redundant power protection or their IT equipment. standard recommends a hold-up time for
supply Multi Switch ATS provides installations power supplies to be a minimum of 21ms for
with power supply continuity. Its operating a voltage range of 100-240V.
• Load protection principle ensures higher reliability than a Multi Switch ATS units switch sources under
single UPS, (with or without its own internal these industry standard times.
• Versatile to use bypass). The switching time includes the time for the
built-in intelligence to determine whether
The Riello UPS Multi Switch ATS is a high Operating principle the voltage and frequency are in range.
availability intelligent switch that provides Multi Switch ATS provides direct distribution Any point of failure in the electronics does
redundant power to connected equipment of eight 10 A IEC outlets or one 16 A IEC outlet not cause a drop out of the output voltage
with two AC input sources. The Riello UPS in a system with two input power lines (two because the unit incorporates redundancy
Multi Switch ATS supplies power to the mains inputs, or two UPS). of its electronic circuitry to avoid fault
connected loads from a primary mains Multi Switch ATS is able to connect to tolerance.
source. If that primary source becomes either of the two input power lines, whilst
unavailable, the Riello UPS Multi Switch simultaneously monitoring the power uptake.
automatically transfers loads to the
secondary source. The transfer time from Protection against load faults
one source according the ITI (CBEMA) If one of the loads fails (e.g. short circuit), Ouput 1
chart does not impact the operation of the the Multi Switch ATS disconnects the group Max 10 A
connected equipment as the switching of sockets where the load is connected, thus
occurs safely between the two input sources preventing other loads from being switched
regardless of any phase differences. The off (i.e. in the event of poor discrimination of
Input 1
Riello UPS Multi Switch ATS monitors the the protection devices).
current and provides warnings when power
consumption draws near the maximum Protection against power Input 2
Ouput 2
rating which helps prevent downtime to the supply faults Max 10 A
equipment. If one of the two power sources falls outside
Riello UPS Multi Switch ATS has 8 IEC 10 tolerance levels, Multi Switch ATS will
A and 1 IEC 16 A outlets allowing several transfer the load to the second power source
devices to be plugged directly into the ATS (switching is instantaneous if the two sources
Ouput 3
without the need for an additional PDU. The are in phase).
Max 10 A
units have a connectivity slot which allows Multi Switch ATS units switch power with no
for LAN connection and remote management impact to IT equipment. Per the ITI Curve,
through PowerShield3 software, Web typical power supplies will operate 20ms
130
Features
• Full protection for loads against mains and
DETAILS
load failures
• Redundant power supply MTA ON/OFF SWITCHES
MODELS MTA
NOMINAL CURRENT (A) 16
INPUT
Nominal voltage - sources S1/S2 230 Vac single-phase + N
Input voltage tolerance 180-276 Vac (selectable)
Switched input phases ph+N (two poles)
Nominal frequency 50/60 Hz
Input sockets 2 IEC 320 (16 A)
OPERATING SPECIFICATIONS
Transfer type “Break Before Make” (no overlapping sources)
Transfer time following source failure < 8 msec (S1/S2 synchronised) 20 msec (S1/S2 non synchronised)
OUTPUT
Nominal voltage choice of one of the two input power sources
Max. load for each output 10 A on IEC-320 C13 - 16 A on IEC-320 C19
Output sockets 4+4 IEC-320 C13 (10 A) + 1 IEC-320 C19 (16 A)
ENVIRONMENTAL SPECIFICATIONS
Efficiency at full load > 99%
Noise at 1 m from front (from 0 to full load) < 35 dBA
Storage temperature -10 °C up to +50 °C
Operating temperature O °C - 40 °C
Relative humidity 90% non-condensing
Max. installation height 1000 m at nominal power (-1% power for every 100 m above 1000 m) - Max 4000 m
Reference standard EN 62310-1 (safety) EN 62310-2 (electro-magnetic compatibility)
INFO FOR INSTALLATION
Weight (kg) 6
Dimensions (WxDxH) (mm) 19” x 330 x 1U
Colour RAL 5004
IP rating IP 20
Communications RS232 / USB / Slot for communication interface / Relay contacts port
www.riello-ups.com 131
DATACENTRE E-MEDICAL INDUSTRY TRANSPORT
Master
Switch
STS Single-phase
1:1 32-63-120 A
Master Switch Single-phase (MMS) is part of The constant monitoring of the output
HIGHLIGHTS the Master Switch range and offers solutions current allows for the rapid identification of
suitable for protecting single-phase loads any short circuit currents in the consumers,
• Operating flexibility with different power ratings. MMS is preventing short circuits from propagating
available in three sizes - 32, 63 and 120 A to other loads.
• Load protection - and is therefore able to satisfy various MMS is equipped with thermal-magnetic
requirements for the protection of single- protection for the two sources, ensuring
• Complete diagnostics phase loads. rapid intervention in the event of faults and
integrated back feed protection.
• Hot Swap function Flexibility of use MMS ensures switching times between the
All MMS versions are designed with criteria two power sources of less that a quarter of a
that facilitate on-site installation as well as cycle, both in the event of manual switching
diagnostics, control and maintenance and in the event automatic switching
operations. All models are equipped with a triggered by a fault in the power source.
manual bypass and the hot swap function
allows for rapid corrective interventions by Complete diagnostics
non-specialised personnel in the event of All MMS versions are equipped with
faults. 32-character LCD displays and control
panels with multi-function keys. This allows
Load protection for rapid and intuitive monitoring of supply
With MMS transfer switch loads are readings, switch status and environmental
protected against critical environmental conditions. MMS is equipped with three
situations and mains power interference. standard programmable dry contacts, an
Microprocessor control and the use of input for emergency shutdown, a 232 serial
thyristor static switches ensure continuous connection and a slot for housing the
monitoring of the power supply sources and expansion board, thus ensuring complete
reduced switching times between the two availability of interface solutions for remote
sources in the event of a fault. control and monitoring.
132
MODELS MMS 32 MMS 63 MMS 120
NOMINAL CURRENT (A) 32 63 120
INPUT
Nominal voltage - sources
220 - 230 - 240 Vac single-phase + N
S1/S2
Input voltage tolerance 180-264 Vac (selectable)
Switched input phases ph+N (two poles)
Nominal frequency 50/60 Hz
Input frequency tolerance
+/-10% (selectable)
range
Distribution compatibility IT, TT, TNS, TNC
OPERATING SPECIFICATIONS
Transfer type “Break Before Make” (no overlapping sources)
Intervention method in the
hot swap function
event of failure
Available transfer methods Automatic / Manual / Remote
Transfer time following source < 4 msec (S1/S2 synchronised)
failure 10 msec (S1/S2 non synchronised)
ENVIRONMENTAL
SPECIFICATIONS
Efficiency at full load > 99%
Noise at 1 m from front (from
< 40 dBA
0 to full load)
Storage temperature -10 °C up to +50 °C
Operating temperature O °C - 40 °C
Relative humidity 90% non-condensing
Max. installation height 1000 m at nominal power (-1% power for every 100 m above 1000 m) - Max 4000 m
Reference standard EN 62310-1 (safety) EN 62310-2 (electro-magnetic compatibility)
INFO FOR INSTALLATION
Weight (kg) 10 12 20
Dimensions (WxDxH) (mm) 19” x 520 x 2U 19” x 520 x 3U
Colour RAL 7016
IP rating IP 20
OPTIONS DIAGRAM
FRONT
SOFTWARE SERIAL RS232
LED MIMIC PANEL
PowerShield3 REPO MAINTENANCE
CONNECTORS
PowerNetGuard WITH DRY
BYPASS
CONTACTS
COMMUNICATIONS
INTERFACE SLOT
ACCESSORIES
BACK INPUT SWITCH
NETMAN 204 (SWIN) S1
MULTICOM 302 INPUT SWITCH
(SWIN) S2
MULTICOM 352 IN/OUT TERMINAL
BOARD
Carry out manual bypass operation Remove the screws placed Replace the faulty unit with Fix the parts, follows start up
on faulty unit selecting S1 or S2 on left/right side and a new one procedure and return back from
extract the unit manual bypass
All operations are carefully described on operating manual.
www.riello-ups.com 133
DATACENTRE E-MEDICAL TRANSPORT EMERGENCY
Master
Switch
STS Three-phase
3:3 100-600 A
Service
1st start
134
3P + N 3P + N
the power supply. In the extreme case of automatic intervention of the protection Source 1
Input
Source 2
Input
a downstream short circuit, Master Switch devices when a return of power to one of the Input Input
MCCB 1 MCCB 2
disconnects the load in order to avoid two Master Switch inputs is detected.
jeopardising the operation of the other
loads (i.e. in the event of poor selectivity of Accessibility S2 S1
the protection devices). The layout of the moving components and Maintenance
Switch 2
Maintenance
Switch 1
LEDs FUNCTION
L1 S1 Priority Source
L2 S2 Priority Source
L3 S1 Present
L4 S2 Present
L5 Static transfer switch SS1 closed
L6 Static transfer switch SS2 closed
L7 Alarm indicator
L8 Output selector ON/OFF
5 function keys and LCD operation
www.riello-ups.com 135
MASTER SWITCH IN REDUNDANT MODE
[AS] [PS]
[AS] = Secondary
USER 2 [PS] = Priority
USER 1
[PS] [AS]
[AS] = Secondary
USER 2 [PS] = Priority
Battery
Battery
Battery
Load 4
136
MODELS MTS 100 MTS 150 MTS 200 MTS 250 MTS 300 MTS 400 MTS 600
NOMINAL CURRENT 100 A 150 A 200 A 250 A 300 A 400 A 600 A
INPUT
Nominal voltage - sources
380 - 400 - 415 Vac three-phase + N
S1/S2
Input voltage tolerance 180-264 Vac (selectable)
Switched input phases 3+N (4-pole) - 3 (3-pole)
Nominal frequency 50/60 Hz
Input frequency tolerance
+/-10% (selectable)
range
Distribution compatibility IT, TT, TNS, TNC
OPERATING SPECIFICATIONS
Transfer type “Break Before Make” (no overlapping sources)
Available transfer methods Automatic / Manual / Remote
Transfer time following source < 4 msec (S1/S2 synchronised)
failure 10 msec (S1/S2 non synchronised)
ENVIRONMENTAL
SPECIFICATIONS
Efficiency at full load > 99%
Noise at 1 m from front (from
55 dBA 55 dBA 55 dBA 55 dBA 55 dBA 55 dBA 57 dBA
0 to full load)
Storage temperature -10 °C up to +50 °C
Operating temperature O °C - 40 °C
Relative humidity 95% non-condensing
Max. installation height 1000 m at nominal power (-1% power for every 100 m above 1000 m) - Max 4000 m
Reference standard EN 62310-1 (safety) EN 62310-2 (electro-magnetic compatibility)
INFO FOR INSTALLATION
Weight (kg) 155 160 205 210 235 240 375
950 x 730 x
Dimensions (WxDxH) (mm) 685 x 530 x 1500 685 x 580 x 1770
1900
Colour RAL 7016
IP rating IP 20
Moving the STS transpallet
www.riello-ups.com 137
DATACENTRE INDUSTRY TRANSPORT
Master
Static
Bypass
3:3 800-3000 kVA
Service
1st start
HIGHLIGHTS The centralised bypass is an alternative various requirements with flexible solutions
to the distributed bypass. Technically the that are able to adapt to the growing
two solutions fulfil the same purpose, i.e. demands of the market in terms of the levels
• Flexibility to guarantee power continuity, but have of power and performance required.
different architectures.
• The ideal solution for Whilst it is true that distributed bypass Flexibility
installations with UPS solutions are the most common due to their The Riello UPS centralised bypass (named
in parallel greater flexibility of use and low initial cost, it is MSB) is available in four standard power
than 1 MVA also true that in the medium/large data ratings: 800, 1200, 2000 and 3000 kVA.
centre market centralised bypass solutions Intermediate solutions within this range can
• High system reliability are preferable in terms of technical be made, as well as solutions greater than
performance, footprint and sometimes cost, 3000 kVA based on the requirements of the
• Centralised diagnostics above all in large installations where the customer or application.
number and type of protections as well as The MSB centralised bypass can be
system wiring have an impact. integrated with the Master HP range; in
The data centre and data-storage market fact it can be associated with up to 7 UPS
in general is destined for large growth. It modules in the range, obviously without
is therefore important to respond to the static bypass and associated bypass line
138
(named MHU). Based on requirements, MSB the common points. Even minimal variations preferable for power levels above one
can also be compatible with the Master MPS in the line impedances of the individual megawatt.
range, thus ensuring complete flexibility bypasses can cause current equipartition
aimed at satisfying all power and power problems between the UPS and associated High system reliability
supply requirements. overcurrent in the cables whenever they When compared to a solution with a
Riello UPS provides the same flexibility as supply from the bypass. This can lead to the distributed bypass and a considerable
the Master HP for the battery bus, so that the inappropriate cut-in of protection devices number of UPS modules arranged in parallel
MHU units can operate with both shared or and can generate heat, with the end result of (more than 4), the MSB solution significantly
separate batteries. minimising power continuity and increasing reduces the amount of components (SCR,
The 800 kVA MSB is supplied with a power consumption for cooling the system. switches, control elements for individual
comprehensive cabinet including bypass The Riello UPS centralised bypass (MSB) is static bypasses, coupling inductances),
line input switch (SWBY), system output the ideal solution for eliminating all critical consequently increasing system reliability.
switch (SWOUT) and manual bypass (SWMB). issues connected with power distribution
The 1200 kVA model is supplied as standard over bypass lines. When activated, all power Power supply from bypass line:
without any switches but can be equipped flows through a single static bypass module, “On Line” mode
with the same, suitably proportioned, ensuring: Recent design philosophies for data centres
switches provided for the 800 kVA model • High reliability are pushing towards making systems
(SWBY, SWOUT, SWMB). • Improved energy efficiency operate on bypass lines not only in the
The more powerful models are supplied • Exceptional ability to withstand short- event of an emergency, but as an alternative
with no switches; the bulky sizes of circuits downstream of the system to “ON-Line” mode, thus improving system
disconnection devices at these power • Centralised system control both with regards efficiency. For this reason power circulation
levels are such as to favour tailor-made to accessibility to system information and through a single line (centralised bypass),
engineering solutions as an additional part with regards to manoeuvrability since the eliminates all problems connected with
of the system attestation and distribution system is equipped with a single manual current distribution, which must be ensured
cabinets where the centralised bypass and system bypass. in the event of the operation of UPS modules
MHU modules are fitted. By opting for the solution with a centralised in parallel with distributed by‑passes. The
bypass, the individual MHU units are greater the power rating of the UPS, the
The ideal solution for installations provided without integrated static bypasses, exponentially greater the risk of minimal
with UPS in parallel greater than 1 MVA thus eliminating critical components (static impedance differences in the bypass lines
Medium-high power systems are often circuit and associated line protections generating large imbalances in current
comprised of N UPS of small-medium power such as disconnectors and/or fuses). This circulation, with a serious risk of protection
ratings arranged in parallel. It is clear that translates into a lower installation cost cut-in, compromising power supply
the larger the size of the individual UPS by eliminating the cables for the auxiliary continuity. With the centralised bypass
modules or the number of units configured power supply lines to the individual the static circuit is single and independent
in parallel, the more complex and extensive modules. and the current flows through a single
the system wiring shall be. Particular These advantages grow exponentially as the channel, ensuring immunity from interaction
attention should be paid to the length power levels at play and number of modules problems between individual UPS units.
of the power lines for the individual UPS increase. This is why the centralised bypass
bypasses, so that they are equidistant from solution is technically and economically
Battery
Battery
Battery
Battery
Battery
Load Load
www.riello-ups.com 139
Power supply from bypass line: even damage the bypass thyristors. Centralised diagnostics
in an emergency Riello UPS are equipped with sophisticated The use of the MSB centralised bypass
The static bypass is a support device aimed parallel control logics that ensure centralises the diagnostics and control of
at ensuring power continuity in the event synchronism between the various units the bypass line.
of inverter failure. In the event of N UPS arranged in parallel under all operating The display provides information concerning
configured in parallel the failure of a single conditions. The Riello MSB centralised the voltage and current supplied and the
inverter module should automatically bypass in any case ensures complete status of the individual UPS modules (MHU).
exclude it from the parallel system, ensuring immunity from any problem connected with Differently from a system with distributed
the correct operation of the other units and switching synchronism between modules bypass, the centralised bypass is equipped
the reliability of the system. even in the most extreme cases as long as with a single disconnection device for
For this reason automatic switching to the static module is single and independent. the bypass line and can be provided with
bypass lines takes place only when there In addition, differently from a distributed an integrated manual bypass. The single
is a serious fault with the inverter or due parallel configuration of the same power disconnection device guarantees that the
to external forces, such as a short circuit rating, the centralised bypass can be manoeuvres are carried out quickly and with
downstream of the system. oversized to guarantee increased overload a minimum margin of error, guaranteeing
These events are both rapid and capacity and the ability to withstand short once again improved system reliability. The
unpredictable and, based on the power circuits. MSB bypass provides dedicated housings
available on the line, can generate short The ventilation system for the MSB static for the various remote control systems such
circuit currents that can be extremely bypass is designed to guarantee operation as: three-contact relay board (standard), two
high. In the event of distributed parallel even in the event of the failure of several communications slots and full compatibility
configurations where N static by‑passes are fans. In order to constantly monitor the with the communications interfaces in the
arranged in parallel, minimal differences status of the fans, a control circuit can be Riello UPS range for UPS in the MHT / MPT
(even in the order of fractions of a provided to control the operation of each ranges.
millisecond), can generate uncontrolled individual ventilation fan.
transients and current flow between UPS
units such as to trigger protection devices or
OPTIONS DETAILS
ACCESSORIES
NETMAN 204
MULTICOM 302
MULTICOM 352 SWOUT
MULTI I/O
SWBYP
Interface kit AS400
MULTIPANEL SEE
MASTER HP
RTG 100
DIGITAL I/O
56K Modem AND
GENERATOR
GSM Modem INTERFACE
SWIN
PRODUCT ACCESSORIES
Top Cable Entry cabinets
IP rating IP31/IP42
Manoeuvring switches
Digital I/O and Generator interface
DIMENSIONS
1900
1900
1900
00 00
1000 85
0 1400 00 2600 10 4400 10
10
140
MODELS MSB 800 MSB 1200 MSB 2000 MSB 3000
OPERATING SPECIFICATIONS
Nominal power (kVA) 800 1200 2000 3000
Nominal voltage 380 - 400 - 415 Vac three-phase + N
Input voltage tolerance ± 15% (selectable from ± 10% to ± 25% from front panel)
Frequency 50/60 Hz
Frequency tolerance ± 2% (selectable from ± 1% to ± 6% from front panel)
Standard equipment provided Back Feed protection
Permitted overload* 110% for 60 min; 125% for 10 min; 150% for 1 min
ENVIRONMENTAL
SPECIFICATIONS
Noise at 1 m from front
< 65 dBA
(from 0 to full load)
Storage temperature -10 °C up to +50 °C
Operating temperature O °C - 40 °C
Relative humidity 90% non-condensing
Max. installation height 1000 m at nominal power (-1% power for every 100 m above 1000 m) - Max 4000 m
Reference standard EN 62040-1 general safety requirements; IEC 62040-2 electromagnetic compatibility
INFO FOR INSTALLATION
Weight (kg) 570 800 1200 2400
Dimensions (WxDxH) (mm) 1000 x 850 x 1900 ** 1400 x 1000 x 1900 2600 x 1000 x 1900 4400 x 1000 x 1900
Communications Double RS232 + dry contacts + 2 slots for communications interface
Colour Dark grey RAL 7016
IP rating IP20 (others on request)
Moving the UPS transpallet
www.riello-ups.com 141
142
Power Solutions
www.riello-ups.com 143
Power solutions
SuperCaps UPS
SOLUTIONS WITH SUPERCAPS
SuperCaps UPS are a type of uninterruptible Their back-up time is dependent on the load
HIGHLIGHTS power supply developed by Riello UPS, but is sufficient to supply it until the mains
which use super capacitors to accumulate power is restored or until reserve power
CLEAN ENERGY energy instead of conventional batteries. from a generator starts automatically.
An eco-friendly, battery-free uninterruptible Autonomy in the range of seconds (1 to Most UPS are installed as standard with
power system.
60 sec) . The innovative Riello SuperCaps batteries lasting 5-10 minutes to protect
HIGH EFFICIENCY INNOVATIVE UPS are designed to provide complete the load against generator start up failure.
TECHNOLOGY power supply protection for sensitive and For modern data centres, electro-medical
Modular expansion options for more power mission-critical loads, protecting them from and industrial applications, an efficient
and runtime. mains disturbances and providing sufficient generator set supported by a UPS with a
LONG OPERATING LIFE power to compensate for interruptions in relatively brief autonomy offers the most
5 to 10 times standard lead batteries mains supply. SuperCaps UPS are a type of efficient and effective power continuity
HIGH NUMBER OF CYCLES
uninterruptible power supply developed by solution, with conventional batteries
Million vs. ca 300 of lead batteries Riello UPS , which use super capacitors to providing sufficient runtime to cover most
LOW MAINTENANCE COSTS accumulate energy instead of conventional power interruptions.
Easy to install and maintain. batteries. However, SuperCaps UPS do not have
HIGH WORKING TEMPERATURE Traditionally UPS rely on batteries for batteries and therefore provide long term
No need of cooling or heating systems accumulating energy, but at least 87% of savings in terms of battery installation,
LOW FOOTPRINT & WEIGHT power supply interruptions last for less than monitoring, maintenance, replacement
a second(1). SuperCaps UPS provide greater and recycling costs. In addition, when
energy efficiency, lower costs and reduced compared to the 5-7 year lifecycle of
SuperCaps module footprints – ideal for installations where standard batteries, SuperCaps UPS have
floor space is at a premium. a theoretically infinite lifecycle. These
At the heart of the Riello SuperCaps UPS is a cost savings, along with the reduced
sophisticated control system that manages footprint make SuperCaps UPS the ideal
the charge-discharge cycle of the super- solution for critical installations that are
capacitors and optimises their lifecycle, particularly sensitive to short power supply
which may exceed a million cycles. interruptions.
(1)
Electric Power Research Institute study
144
SENTINELPROSC
MODELS SEP 700 SC SEP 1000 SC SEP 1500 SC SEP 3000 SC
SENTINELPOWERSC
MODELS SPW 6000 SC SPT 8000 SC SPT 10000 SC
MULTISENTRYSC
MODELS MST MST MST MST MST MST MST MST MST MST
10 SC 12 SC 15 SC 20 SC 30 SC 40 SC 60 SC 80 SC 100 SC 120 SC
INPUT Nominal voltage 220-230-240 Vac 1ph / 380-400-415 Vac 3ph
Nominal frequency 50/60 Hz
Power factor 0,99
Current distortion ≤ 3%
OUTPUT Nominal power (VA) 10 12 15 20 30 40 60 80 100 120
Power (W) 9 10.8 13.5 18 27 36 54 72 90 108
Nominal voltage 220-230-240 Vac 1ph / 380-400-415 Vac 3ph
BACKUP Autonomy 21 s 17 s 14 s 10 s 14 s 9s 7s 15 s 11 s 20 s
Recharge time 6-8 min
DATA Net weight (kg) 123 128 133 138 163 171 190* 200* 220* 380*
Dimensions (WxDxH) (mm) 850 x 1320 x 440 850 x 1600 x 500 855 x 1900
x 750
MASTERHPSC
contact our TEC service for configurations.
www.riello-ups.com 145
Power solutions
Master VDC
FLYWHEEL SOLUTIONS
TRANSPORT EMERGENCY
Master VDC is a scaleable system comprised sufficient to allow the UPS to ride through
of one or more UPS units and VDC-XE short breaks in mains power.
flywheels. Master VDC is ideal for modern
ECO targeted data centres looking to achieve Flywheel VDC-XE
the lowest possible PUE ratios and highest Thanks to their extremely high levels of
Flywheel Service
compatible 1st start levels of reliability. reliability, the VDC series of flywheel energy
Master VDC UPS provide a number of storage systems provide UPS with a secure
advantages over more traditional battery- and reliable source of power that forms the
HIGHLIGHTS equipped systems including: up to 99% first line of defence against interruptions
efficiency, a compact footprint (up to 50% to the mains power supply; a fundamental
CLEAN ENERGY reduction), lower Total Cost of Ownership (TCO) defence for all mission critical applications.
An eco-friendly, battery-free uninterruptible and almost instantaneous recharge times. The VDC flywheel systems are fully
power system.
A single flywheel module provides sufficient independent standalone devices. They
HIGH EFFICIENCY INNOVATIVE runtime for the start-up of a local standby are designed for applications such as data
TECHNOLOGY generator to power the UPS, which then centres, hospitals and industrial installations.
Modular expansion options for more power provides a continuous quality power supply. They provide a clean source of back up power
and runtime.
The entire system can be scaled for reliable by converting the kinetic energy stored
LONG OPERATING LIFE power (N+x) and increased runtime via the within a rotating mass into electrical power
20 year design life for the flywheel parallel operation of several UPS and/or using a built-in IGBT-based converter.
component compared with 7 years for a
flywheel modules (and a small battery pack VDC series flywheels store kinetic energy
typical battery.
if required, for additional reliability). in the form of a rotating mass (spinning
LOW MAINTENANCE COSTS In a standard configuration (1 x UPS and 1 x at 36,000 RPM) within a vacuum-sealed
Easy to install and maintain. flywheel), the runtime available is more than container. The VDC build technology includes
146
MASTER VDC CONFIGURATION EXAMPLES
MODULARITY
Autonomy:
example with load at
MHF 100
+ + 100% :
42s, 1xVDC-XE
82s, 2xVDC-XE
Autonomy:
example with load at
MHF 300 + + 50% :
27s, 1xVDC-XE
54s, 2xVDC-XE
Autonomy:
example with load at
+ + +
MHF 300P 50% :
54s, 2xVDC-XE
or 27s, 1xVDC-XE
N+1 Parallel
UPS Configuration
BATTERY HARDENING
DIMENSIONS
VDC-XE
1872
2
762 76
www.riello-ups.com 147
MASTER VDC: UPS MODULE SPECIFICATIONS
MODELS MHF 100 MHF 120 MHF 160 MHF 200 MHF 250 MHF 300 MHF 400 MHF 500 MHF 600
INPUT
Nominal voltage 380 - 400 - 415 Vac three-phase
Frequency 45 - 65 Hz
Power factor > 0,99
Harmonic current distortion <3% THDi
Soft start 0 - 100% in 120’’ (selectable)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Standard equipment provided Back Feed protection; separable bypass line
BATTERIES
Type Flywheels
Ripple current Zero
Recharge voltage compensation -0,5 Vx°C
OUTPUT
Nominal power (kVA) 100 120 160 200 250 300 400 500 600
Active power (kW) 90 108 144 180 225 270 360 450 540
Number of phases 3+N
Nominal voltage 380 - 400 - 415 Vac three-phase + N
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Voltage distortion < 1% with linear load / < 3% with non-linear load
Crest factor 3:1 lpeack/lrms
Frequency stability on battery 0,05%
Frequency 50 or 60 Hz (selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
INFO FOR INSTALLATION
Weight (kg) 656 700 800 910 1000 1400 1700 2100 2400
Dimensions (WxDxH) (mm) 800 x 850 x 1900 1000 x 850 x 1900 1500 x 1000 x 1900 2100 x 1000 x 1900
Remote signals dry contacts (configurable)
Remote controls ESD and bypass (configurable)
Communications Double RS232 + dry contacts + 2 slots for communications interface
Ambient temperature 0°C / +40°C
Relative humidity <95% non-condensing
Colour Dark grey RAL 7016
Noise level at 1 m 63 - 68 dBA 70 - 72 dBA 70 dBA 70 dBA
IP rating IP20 (others on request)
Smart Active efficiency up to 98,5%
Standards Safety: EN 62040-1-1 (Directive 2006/95/EC); EMC: EN 62040-2 (Directive 2004/108/EC)
Classification in accordance with
(Voltage Frequency Independent) VFI - SS - 111
IEC 62040-3
Moving the UPS transpallet
148
MASTER VDC: (FLYWHEEL ONLY) RUNTIME IN SECONDS
VDC-XE 300 kW MHF 100 MHF 120 MHF 160 MHF 200 MHF 250 MHF 300 MHF 400 MHF 500 MHF 600
Number of FLYWHEELS POWER 100 120 160 200 250 300 400 500 600
1 100% 40 33 22 15 9 5 - - -
2 79 65 49 39 30 24 14 8 -
3 118 98 73 58 46 38 28 20 14
4 156 129 97 77 61 51 38 30 23
5 195 162 121 97 77 60 48 38 31
Number of FLYWHEELS POWER 100 120 160 200 250 300 400 500 600
1 75% 54 45 33 25 17 11 5 - -
2 106 88 65 52 41 34 24 16 10
3 157 131 98 78 62 51 38 30 23
4 208 173 129 103 82 68 51 40 33
5 260 217 162 129 103 86 64 51 42
Number of FLYWHEELS POWER 100 120 160 200 250 300 400 500 600
1 50% 82 68 51 40 32 25 11 5 4
2 159 132 99 79 63 52 39 30 23
3 237 197 147 118 94 78 58 46 38
4 313 260 195 156 124 103 77 61 51
5 391 326 244 195 156 129 97 77 64
Number of FLYWHEELS POWER 100 120 160 200 250 300 400 500 600
1 25% 39 135 101 80 64 53 39 26 23
2 313 260 195 156 124 103 77 61 50
3 465 387 290 232 185 154 115 92 76
4 614 511 383 306 245 204 152 122 101
5 767 639 479 383 306 255 191 152 126
All runtimes refer to UPS with 0,9pf and 94% efficiency for 100%, 75% and 50% load, and 92% efficiency for 25% load. With no battery connected.
www.riello-ups.com 149
150
Software
and accessories
www.riello-ups.com 151
Software
PowerShield3
SHUTDOWN SOFTWARE
PCs, saving any active work on the most to ensure UPS system security. Using the
widely used applications. Users can define new discovery/ browsing function, all
HIGHLIGHTS the shutdown priorities for the various UPS connected to a protected computer
GRAPHIC MONITORING OF UPS AND computers in the network and can also and/or LAN can be displayed in a list
ENVIRONMENTAL SENSOR STATUS customise the procedure. format for monitoring. In the absence of a
PowerShield3 is a simple but powerful UPS management
tool. A graphic version is available for all operating • With multi-platform compatibility, LAN connection, support is provided for
systems.
PowerShield3 uses the TCP/IP modem-based communication.
DETAILED DISPLAY OF ALL UPS AND communications protocol to achieve
ENVIRONMENTAL SENSOR PARAMETERS
PowerShield3 provides all the information required for standardised management and monitoring Developed for virtualized systems
first level diagnostics.
across the widest possible range of PowerShield3 permits to initiate live
EVENTS LOG AND GRAPHIC DISPLAY OF MAIN
PARAMETERS platforms. This makes it possible to migration of virtual machines (VM) to
All changes in UPS operating states are logged, as well monitor computers with different automatically and transparently migrate
as the main physical values and parameters. These
constantly recorded values are displayed in graphic operating systems from a single console, VMs during power disturbance to protected
format.
for example monitoring a UNIX server devices by UPS with migration systems
UPS CONTROL PROGRAMMING from a PC running Windows and also such as VMware vMotion™ and Microsoft
This allows you to automate all the actions normally
carried out by the user: turning the server on and off, connecting to UPS located in different Live Migration. PowerShield3 can monitor
UPS battery test, etc.
geographical areas using dedicated and manage UPS either inside or outside
BLOCK DIAGRAM OF OPERATION
A display of UPS operation in the form of a block networks (intranets) or the Internet. the data centre. Can also measure power
diagram makes the analysis of UPS operating states • With event scheduling, PowerShield3 consumption to help calculate power usage
more intuitive.
users can program their own shutdown effectiveness (PUE), a the standard metric
PowerShield3 provides efficient, user- procedures, detailing power-off and utilized for gauging data centre power efficiency.
friendly UPS management, displaying all power-up scenarios to increase system
major operational information such as security and save energy. Supported operating systems
input voltage, applied load and battery • With messages management, PowerShield3 • Windows 2000, 2003 Server, XP, Vista,
charge. The software also provides detailed keeps users constantly informed about the 2008 Server, 7, 8, on X86, X86_64 and IA
information on fault conditions and UPS status of UPS and environmental sensors, 64 processors
operating states. Developed with a client/ either locally or via network messages. • Microsoft Hyper-V
server architecture, it is the ideal tool for A list can also be defined of users who • Microsoft SCVMM™
managing multi-platform network systems. should receive e-mails, faxes, voice • Linux on X86, X86_64 and IA64 processors
messages and SMS messages when faults • Novell Netware 3.x, 4.x, 5.x, 6
Features or sudden mains power supply failures • Mac OS X
• PowerShield3 free version: supports a occur. • VMWare ESX, ESXi.
single UPS for the operating systems • Integrated SNMP agent: PowerShield3 • Citrix® XenServer,
highlighted in green. features an integrated SNMP agent for • Xen® open source platforms
• PowerShield3 full version: supports up UPS management which can send all • The most common UNIX operating systems such as:
to maximum of 32 UPS for all operating the information required and generate IBM AIX, HP, SUN Solaris INTEL and SPARC, SCO
systems. traps using the RFC1628 standard, and Unixware and Open Server, Silicon Graphics IRIX,
• With sequential and priority-based environmental sensors. Compaq Tru64 UNIX and DEC UNIX, Open BSD
shutdown, PowerShield3 provides • Secure, easy to use and connect; UNIX and FreeBSD UNIX, NCR UNIX
unattended shut-down of all networked communication is now password protected • HP OPEN VMS.
152
PowerNetGuard
INVENTORY MANAGER SOFTWARE
www.riello-ups.com 153
Accessories
NetMan 204
CARD - ETHERNET - SNMP
updates via email
Features • MODBUS/TCP
The NetMan 204 network agent allows UPS • 32bit RISC processor • BACNET/IP
directly connected over LAN 10/100 Mb • Compatible with 10/100 Mbps Ethernet • Maximum expandability
connections to be managed using the main and IPv4/6 networks • USB host for Pendrive USB connection
network communication protocols (TCP/ • wifi ready • Events log and data management
IP, HTTP and SNMP). It is the ideal solution • Compatible with PowerShield3 and • Wake-on-LAN management for starting
for the integration of UPS over Ethernet TeleNetGuard computers via TCP/IP network
networks with MODBUS/TCP or BACNET/ • SNMP v1 and v3 with RFC1628 for • Other standards: DHCP, DNS, RARP, FTP,
IP protocols. It was developed to integrate PowerNetGuard and NMS connection NTP, ICMP, IGMP
UPS into medium-sized and large networks, • SNMP v1, v2 and v3 with RFC3433 for the • Management of environmental sensors
to provide a high level of reliability in management of environmental sensors • Configurable via Telnet or SSH sessions, and web
communication between the UPS and • HTTP for UPS control via web browser • Firmware upgradeable via USB port, FTP
associated management systems. • SMTP for alarm notifications and UPS status and HTTP.
Environmental sensors
FOR NETMAN 204
UPS
Riello Netman
154
MultiCOM 302
CARD - MODBUS/JBUS INTERFACE
MultiCOM 352
CARD - INTERFACE DUPLEXER
MultiCOM 372
CARD - RS232 INTERFACE
www.riello-ups.com 155
MultiCOM 382
CARD - RELAY I/O INTERFACE
The MultiCOM 382 provides a set of and Battery Low warnings with potential
relay contacts for managing UPS alarm free changeover or normally open contacts.
notifications and operating states. The board
has two removable terminal boards. One of Features
these terminal boards includes the ESD (UPS • Max. current 3A at 250Vac
Emergency Shut Down) and RSD (Remote • Signal-contact customisation.
Shut Down) signals. For compatibility, refer to the Table on page 16
The board also provides the possibility of
associating Battery Working, Bypass, Alarm
MultiCOM 401
BOX - PROFIBUS DP INTERFACE
Multi I/O
BOX - RELAY I/O CARD & MODBUS/JBUS INTERFACE
156
I/O
EXPANSION BOARD
The I/O expansion board for the Master Each output or input can be configured with
range is equipped with: different meanings, using the associated
• 6 outputs with NC/NO potential-free menu.
contacts (250 V/5 A), electrically isolated
from each other and from other circuits For compatibility, refer to the Table on page 16
• 2 self-powered inputs.
Modem GSM
MODEM
RTG 100
GPRS MODEM
The GPRS RTG 100 terminal is able to or PowerShield3 software with a valid
manage UPS connected directly to the GSM alternative to connection systems
mobile telephone network. employing communication cables.
It was developed to integrate UPS into the
TeleNetGuard remote control system for Features
complete control of UPS and diagnostics in • Ability to send SMS messages detailing
the event of failure UPS operating states and alarms
without the need for landline connections. • Compatible with PowerShield3 and
The RTG 100 is able to communicate TeleNetGuard
constantly with UPS to provide the • Events log management
TeleNetguard remote control system • Firmware upgradeable via GSM.
www.riello-ups.com 157
Multi Panel
REMOTE DISPLAY INTERFACE
Features
• High visibility LCD with graphic functions
• Management of three independent serial
lines
• Port configuration for MODBUS/JBUS as
RS232 or RS485
• Suitable for integration with the main BMS
management programs
• Firmware upgradeable via serial port.
158
Multi Pass 10, 16, and 16-R
MAINTENANCE BYPASS
MBB32A
MAINTENANCE BYPASS
Available in a 32 A single-phase
configuration, enables UPS servicing up to
6kVA in a quick and safe manner ensuring
power continuity. Equipped with a metal
bracket for wall mounting.
MBB125A 4P
www.riello-ups.com 159
160
Connectivity
www.riello-ups.com 161
Connectivity
Index of configurations
Connecting a UPS to other devices, sensors, other hand provides the UPS with input This brief overview summarises some of the
computers and other specific devices, parameters from the working environment. basic connectivity configurations, grouped
means on the one hand allowing the user By processing these parameters the according to the end purpose and situation
to monitor UPS operating parameters and UPS is able to activate/deactivate itself, surrounding each case.
prevent critical situations, and on the communicate its status and much more.
1 2
162
DISTRIBUTED CONNECTION (MULTIPOINT)
Connection with more than 1 UPS.
2
The FULL version of PowerShield3 software
is required as well as a NetMan 204
UPS communication board on each UPS.
Riello
1
1 UPS connected to load
3
5 2 NetMan 204 board
3 Firewall
2 4 Switch
5 Remote computer connected via web
UPS
6 Local computer
Riello
7 Local computer that controls the UPS (8)
1 4 via USB or RS232, and UPS (1) via LAN
and Ethernet
8 UPS connected to load
USB or RS232
Ethernet
World Wide Web
6
UPS
Riello
2
1
UPS
Riello
8
7
3
5 Remote computer connected via web
1 6 Local computer
Ethernet
World Wide Web
2
Parallel setup bus
6
2
www.riello-ups.com 163
CONNECTION WITH SEVERAL SYSTEMS IN PARALLEL AND STS
The FULL version of PowerShield3 software
8
1
should be used for managing setups with
several UPS installed in parallel, and
each UPS must have a NetMan 204 board
2 installed.
5
1 UPS arranged in parallel connected to an
STS channel
2 NetMan 204 board
4 3 UPS arranged in parallel connected to an
STS channel
4 Switch
5 Firewall
6 STS connected to load
7 UGS
2
2 8 Local computer with PowerShield3
2
software version FULL
1
7 3 9 Remote computer connected via web,
running PowerShield3 software version
FULL
2 UGS management of parallel setup
Parallel setup bus
Ethernet
World Wide Web
6 6
Parallel setup bus
Power connection
9
2
3
4
164
MODBUS SERIAL FIELD BUS CONNECTION
For UPS management in industrial or civil
1
environments requiring Modbus protocol
communication over RS 485 line.
2 1 UPS connected to load
2 NetMan 302 board
3 SCADA management system
Ethernet
Modbus RS485
www.riello-ups.com 165
POWERSHIELD3 ON VIRTUALIZED SYSTEMS:
WMWARE ESX; MICROSOFT HYPER-V; CITRIX
1
PowerShield3 software should be used for
managing setup with UPS, a specific script
to shut down the virtualized system must
2 be used, UPS must have a NetMan 204
board installed.
1 UPS
2 NetMan 204
3 3 Virtualized system
Ethernet
Power connection
Storage
Network
Server
Hypervisor
Power infrastructure
166
www.riello-ups.com 167
168
Technical pages
www.riello-ups.com 169
POWER PROBLEMS
Overvoltage
+15%
Nominal
voltage
-15%
Undervoltage
Blackout
0V
170
TYPES OF UPS
Classification of UPS according to the CEI EN 62040-3 standard (method of specifying
performance and test requirements).
Off-line (VFD)
In normal operating mode, the load is VFD
TYPE
powered directly from the mains through
the UPS static switch. UPS VFD
When the mains voltage is not within
the UPS preset tolerances, the load is
transferred to the inverter in about 2-4 ms
using battery power. The voltage generated
by the inverter is typically step-wave or
square-wave.
www.riello-ups.com 171
EVALUATION PARAMETERS
Watt: VA x Pf
(the PF sometimes is identified with the
COSφ) Runtime
The batteries supplied with the UPS are
The PF or the COSφ is rarely indicated so valve-regulated batteries (VRLA) better
the correct sizing requires you to know the known as sealed batteries with immobilized
active power (W) of the loads. electrolyte and very low gas loss and which,
However the experience shows that the therefore, can be installed in public places
new IT system loads, such us the computer and offices without special precautions.
servers, typically have the power factor 0,9 Normally batteries are supplied together
or greater while the personal computers with the UPS and may be kept in the same
have the Pf 0,60 - 0,75. cabinet or in additional cabinets with an
isolation switch.
Crest factor
A linear load absorbs a sinusoidal current
that has an effective value (I EFF usually
measured and declared) and a peak value
(IPK).
The Crest Factor value is defined as:
CF = IIPK
EFF
The normal value for a linear load is CF
= 1.41. Most loads applied to UPS are
non-linear loads; they absorb distorted
currents that have a CF greater than 1.41
and therefore require higher peak currents
resulting in increased distortion of the
output compared to equivalent linear loads.
The EN62040-1 Standard defines a typical
non-linear load with CF = 3, used for testing
UPS that can be used in the absence of other
data.
172
MAINS DISTURBANCES
Nominal Voltage
induced by problems that occur on the high- - Faults with all electrical/electronic
voltage grid (≥ to 1min). equipment (100% <overvoltage<150%):
e.g. damage to circuit boards, power packs,
computers/servers, faults with lighting
systems etc.
Blackout
Nominal Voltage
Consequences:
- Computer Applications: system blackouts
with corruption or loss of data, overheating
Flicker effect
The flicker effect is a flickering of lights
and ageing of electronic components
induced by rapid variations in voltage.
resulting in operational paralysis.
These voltage variations are caused by loads
- Industrial applications: Instability
in which the power absorption varies very
of asynchronous motors and loss of
quickly: arc furnaces, welding machines,
synchronization of synchronous motors,
rolling machines, laser cutters.
opening of contactors (undervoltage>
30%), power-off of discharge lamps with
undervoltage >50% for 20-40ms, with
Consequences:
the flickering of lights is very unpleasant for
subsequent return of power that only occurs
those who witness it.
after several minutes, resulting in operational
paralysis.
Flicker effect
www.riello-ups.com 173
HARMONICS
Definition of harmonics Origin of harmonics - the magnetic fields generated by the high
Given a sinusoidal (fundamental) magnitude, Devices that generate harmonics are order harmonics are at high frequency
one can define as harmonic a sinusoidal present in the industrial sector, the service and easily generate unwanted inductive
multiple frequency magnitude. The order of sector and also in the home. Harmonics couplings that can produce malfunctions
the harmonic is the relationship between are generated by non-linear loads: a load in the most sensitive components such as
its frequency and that of the fundamental: is defined as non-linear when the current differentials.
for example, if the fundamental is 50 Hz, which it absorbs does not have the same
the third-order harmonic, or third harmonic form as the voltage that supplies it. Power In general, therefore, the economic effects
has a frequency of 150 Hz. The sum of the electronics such as rectifiers, inverters, of harmonics can be seen in terms of a
fundamental and the harmonics gives rise to electronic starters, variable frequency shorter useful life of an installation, of a
a function that is periodic but not sinusoidal motor drives, switching power supplies, lower yield and a high likelihood of reduced
(distorted waveform). A distorted waveform discharge lamps are classic examples of performance.
is therefore equivalent to a presence of non-linear loads. The powering of non-linear
harmonics, and vice versa. In general, any loads causes the appearance of THDIs (Total An Uninterruptible Power Supply (UPS)
periodic function can be broken down into a Harmonic Distortion Currents) circulating in in a double conversion configuration is
series of sinusoidal functions (Fourier series). the system. In turn, harmonic currents that a possible solution to the problem of
pass through the power supply circuit (lines harmonics generated by loads. Since the
and transformers), cause the deformation of UPS is interposed between the loads and the
the mains voltage: the harmonic distortion mains, it absorbs all the harmonics of the
in voltage THDU (Total Harmonic Distortion loads and only provides the mains with the
Voltage). harmonics originating from the operation
of the UPS itself. These values are certain
Consequences: the damage caused by and defined in the properties shown on the
harmonics can be summarized as follows: nameplate.
- the electronic power regulation systems
may be disturbed by the fact of having to Riello offers UPS with various technological
work with voltages that are not perfectly solutions for the input stage ranging from
sinusoidal. six-pulse or twelve-pulse rectifiers with
- the electronic signal systems, designed optional anti-harmonic filters to the ultra-
to work with very low currents, can modern IGBT rectifiers with PFC (Power
easily be “fooled” by the presence of Factor Control).
disturbances induced by high-frequency
electromagnetic fields.
- the harmonic components of order 3
(150 Hz) in three-phase systems become
homopolar, i.e. they converge on the
neutral conductor and overload it. In
the absence of the neutral, circulating
currents may occur inside the three-phase
appliances, connected in triangular form,
generating dangerous overloads in this
situation, too. In single-phase systems,
personal computers are classic examples
of heavily-distorted loads with a high
content of 3rd order harmonics which, as
described above, will have an effect on
the neutral. The conductor of the latter
must therefore be sized appropriately,
otherwise overheating will occur, thus
reducing its life and quality.
174
UPS CONNECTED IN PARALLEL
Introduction The UPS connected in parallel are of the various UPS, and the connection
UPS can be connected in parallel in order to coordinated by a board, which controls the from their output terminals to a single
increase reliability in the supply of power to exchanges of information. The information node for the power supply to the load,
the load and the power available on output. is exchanged between the UPS via a cable with the cables having the same section
Up to 8 units can be connected in parallel. that connects them in a ring circuit. The ring and total length. This recommendation is
Our recommendation is to connect units of connection provides a redundancy in the necessary to ensure the distribution of
the same power. connection cable (communication by cable power during operation on the by-pass line:
It is necessary, therefore, to install an between the single units). This is the most UPS in distributed parallel have a static
electronic card (on each UPS) which reliable way to connect the UPS with each switch for each UPS, while the centralized
guarantees the frequency synchronicity other. It also allows the connection and hot parallel system (increasingly less used) has
of the UPS connected in parallel together disconnection of a UPS. a single static switch (with by-pass function)
with the mains supply, in order to avoid Each UPS has its own controller that external to the UPS and is dimensioned for
exchanges of current among the UPS in continuously communicates with the entire the entire power of the parallel system.
parallel and between the UPS in parallel system so as to ensure correct operation. The distribution of the load in normal
and the mains supply (only in inverter/mains The cable transmits signals from a “Master” operation is automatic.
and/or mains/inverter switching). UPS to the other “Slaves” with an opto- Normally parallel systems are available for
The load that can be applied to a system isolated system so as to maintain the control UPS with power exceeding 10kVA; further
with multiple machines in parallel can be systems electrically isolated from each details about the types of configurations can
higher than the load that can be sustained other. be found in the description of the individual
by each unit thanks to automatic power- The operating logic provides for one unit, products.
sharing. Increased reliability is only the first one that is activated, to become
achieved on condition that the total system “Master” and to take control of the other
power, with one unit deactivated, remains “Slaves”. In the event of failure of the
higher than the demand. This condition is “Master” unit, there will be an immediate
always achieved by adding a redundant unit. transfer of control to a “Slave” who in turn
A redundant unit is obtained with a UPS will become “Master”.
that is additional to the minimum number The parallel systems may work with one
of elements required to power the load, so battery on each UPS module or one battery
that after the automatic exclusion of a faulty for the whole system. The exact connection
unit, the power supply can continue in a in parallel provides for the connection from
correct manner. a single mains node to the input terminals
Battery
Battery
Battery
Battery
Battery
Load Load
Battery
Battery
Battery
UGS
Battery
Battery
Battery
Battery
Sinchroniser
PSJ
Static Transfer
SWITCH
SWITCH
Load 3
Load 1 Static Transfer Load 2
SWITCH
Load 1 Load 2
Load 4
www.riello-ups.com 175
BATTERIES
The battery is a delicate part of the UPS Requirements on installing Batteries are an independent source of
system. For this reason it is necessary to batteries energy and so it is absolutely necessary to
pay attention to the selection and to the The internal gas recombination or VRLA install a protection device with adjustments
installation conditions. A low-quality battery batteries, can be installed in places normally appropriate to their capacity and the
or one not installed correctly can result in a frequented by people; in fact, the necessary discharge currents. It is advisable to have a
loss of load. air exchange is negligible but should not be protection device for each battery branch
overlooked, as prescribed in the European if the batteries were installed with multiple
standard EN 50272-2. Although VRLA branches in parallel.
batteries function within the specified
temperature limits for UPS, they do have Ventilation requirements for
an accelerated ageing if the temperature batteries according to the
is higher than the nominal working EN50272-2 standard
temperature (20°-25°C). For every 10°C over The batteries shown in this catalogue, are all
the nominal temperature the expected life of the internal gas recombination or VRLA
of the battery is halved. type, also known as sealed Pb batteries.
These batteries do not require any particular
Example: battery with a nominal T of 25°C = devices, except in the event of large
4-5 years of life; operating at 35°C the life capacity installations (more than 100 Ah).
duration becomes 2-2.5 years. With larger capacity facilities, it is necessary
to provide adequate ventilation.
One normally provides for the replacement The purpose of ventilating the room where
of batteries during the life of a UPS. the batteries are installed is to maintain
When positioning the batteries, check the the hydrogen concentration below the 4%
equipment manual to avoid making this threshold of the Lower Explosion Limit (LEL).
operation difficult! The rooms where the batteries are installed
The room where the batteries are located are considered safe from the point of view
should be maintained at temperatures of explosions when the concentration of
between 20-25°C to maximize the life hydrogen is kept below this safety limit, with
expectancy of the batteries; in addition, the natural or forced (artificial) air ventilation.
area must be at least 2 m high to facilitate The minimum air flow for ventilating the
installation. rooms where the batteries are installed
The floor must be able to withstand a load must be calculated in accordance with
equal to the weight of the batteries, which local specifications. In the absence of such
may reach a total of about 2,300-2,400 kg/ specifications, one can use the European EN
sq.m. The doors of these rooms must open 50272 as the reference standard.
outwards.
When the batteries are mounted inside
a cabinet, access must only be possible
after the battery has been isolated and a
door has been opened using the special
tool. The correct charging voltage for the
batteries varies according to the ambient
temperature.
Modern UPS are able to regulate the
charging voltage by means of temperature
sensors. In the event of batteries connected
externally to the unit and if the room
temperature is not stable, it is advisable
to mount a temperature sensor which will
transmit information to the battery-charger.
If the batteries are open vase, they must be
installed in a special room following the EN
50272 standard on premises, in particular
complying with the air exchange calculation
in accordance with the formula specified in
paragraph 1.2 of the standard. If forced air
ventilation is used, any failure of this must
be reported to the UPS so that the battery-
charger is stopped, thereby avoiding the
possible build-up of hydrogen inside the
room.
176
BATTERY CURRENT VALUES CHARGING
WITH VOLTAGE-CURRENT CONTROLLED CHARGER
NOTE: For input/output cable sections sizing please refer to UPS manuals where you can find maximun current indications.
www.riello-ups.com 177
178
Services
and contacts
www.riello-ups.com 179
Services
PRE-SALES
CONSULTANCY RENTING
tec@riello-ups.com
180
TELENETGUARD
TECHNICAL ASSISTANCE REMOTE MONITORING
24/7
service@riello-ups.com
www.riello-ups.com 181
Operating Offices
LEGNAGO (VR)
Head Office AFTER-SALES SUPPORT (UPService)
Viale Europa, 7 service@riello-ups.com
37045 LEGNAGO (Verona)
Tel +39 0442 635811
Fax +39 0442 629098
www.riello-ups.com
riello@riello-ups.com
CORMANO (MI)
Sales Office
Via Somalia, 20
20032 CORMANO (Milano)
Tel +39 02 663271
Fax +39 02 66327351
ROME
Sales Office
Via Fosso della Magliana, 34/G
00148 ROME
Tel +39 06 65192125
Fax +39 06 65192247
182
UNITED KINGDOM SPAIN CHINA
RIELLO UPS Ltd. RIELLO ENERDATA s.l.u. Riello UPS (Asia) Co., Ltd.
Unit 50 Clywedog Road North C/ Labradores, Bolg2, No.451 Duhui Road,
Wrexham Industrial Estate 13 Parque Empresarial Minhang District-201108 Shanghai
Wrexham LL13 9XN Prado del Espino Tel +86 21 50464748
Tel +44 800 269 394 28660 Boadilla del Monte - Madrid Fax +86 21 50464648
Fax +44 1978 729 290 Tel +34 916 333 000
Fax +34 916 321 793 Sales office Beijing
CONSTANT POWER SERVICES Ltd. Unit 3B,Building B,
Riello House, Works Road, Delegacion Andalucia Jinyuan Century Business Centre,
Letchworth C/ Aviación 18, P. I. Calonge, No.1, Yuanda Road, Haidian District
SG6 1AZ Hertfordshire Edificio Morera y Vallejo 1, 100097 Beijing
Tel +44 330 1230125 1ª Planta Tel +86 10 82038861 / 8862
Fax +44 1462 422754 41007 Sevilla Fax +86 10 82038863
Tel +34 955 040 044
GERMANY Fax +34 955 040 041 Sales office Guangzhou
Address Unit 1507 East Building,
RIELLO UPS GmbH RIELLO TDL s.l. Dongshan Square, No. 65,
Wilhelm-Bergner-Str. 9b C/Berguedà, 6 bis Xianlie Zhong Road, Yuexiu District
21509 Glinde Pol. Ind. Plà de la Bruguera 510095, Guangzhou
Tel +49 40 / 527 211-0 08211 Castellar del Vallès, Barcelona Tel +86 20 28848001
Fax + 49 40 / 527 211-200 Tel +34 93 74 71 210 Fax +86 20 28848002
Fax +34 93 71 46 562
RIELLO POWER SYSTEMS GmbH Sales office Jinan
Neufahrner Str. 12b ROMANIA Room 3508, Building2
85375 Neufahrn/Grüneck Inzone Center, No.22799
Tel +49 8165 / 9458-0 S.C. Banattika S.r.l. Jingshi Road, Jinan
Fax +49 8165 / 9458-26 (Riello UPS Romania) Tel +86 531 87969877
Str. Varsovia Nr. 4 Fax+86 531 87960977
FRANCE 307160 Dumbravita
Timis County - Romania Sales office Xi’an
RIELLO ONDULEURS S.a.r.l. Tel +40 256 214 681 A2604, Oak Constellation ,
2/4 Rue du Bois Chaland, Fax +40 256 214 682 No. 3, Ke Ji 5th Road,
ZAC du Bois Chaland High-Tech Zone, Xi’an
91090 Lisses AUSTRALIA Tel +86 29 89526941
Tel +33 1 60 875454 Fax+86 29 89526943
Fax +33 1 60 875450 RIELLO UPS AUSTRALIA Pty. Ltd.
Unit 22/80 Box Road Sales office Chengdu
Agence Rhone Alpes - Sud Taren Point NSW 2229 Room 1703, Level 17,
147 Avenue M. Mérieux, Tel +61 2 9531 1999 Raffles City Tower 2,
Parc de Sacuny, Park Avenir 1 Fax +61 2 9531 1988 No. 3 Section 4,
69530 Brignais South Renmin Road, Chengdu
Tel +33 4 72 177108 Unit 17/810-818 Princes Hwy Tel +86 28 6511 2870/71
Fax +33 4 78 351422 Springvale VIC 3171 Fax+86 28 6511 8199
Tel +61 3 9574 6922
Fax +61 3 9574 6933 INDIA
www.riello-ups.com 183
Reliable power for a sustainable world
Ra
adhuis
laan7
NL3271BSMi j
nsheer
enl
and
T+31(
0)186603921-F+31 (0)
1866041
24
www.ber
v e
.nl-i
n f
o@berve
.nl