Enhanced Safety
Internal Arc compliant Switchgear Assemblies
intemal arc fault is a type of short
circuit with a huge energy level up to
20 MW qycle, very high temperature
up to 3000°C, and pressure rise up
to 3 atm. resulting in extensive
damage, monetary loss and even
personnel injury. Despite the
continuous improvement in design
of electrical switchgear and
controlgear assemblies, failures may
occasionally occur during its
operation. The probability of the
occurrence of an internal arc in
Voltage (LV) switchgear
assemblies during its entire service
fetime is rather low but it
cannot be completely disregarded
Low
PROSPECT / RETROSPECT
Ithas always been common practice
to include arc fault containment in
Medium Voltage (MV) and High
Voltage (HV) switchgear. However
the same is not included for LV
assemblies. Therefore IEC 61641
Report marks the first attempt to
measure the ability of LY switchgear
to contain the effects of an arcing
fault
The Internal Arc Fault Test is neither
‘a type test nor a mandatory tes
LV Switchgear Assemblies. tt is a
special test subject to an agreement
between manufacturer and user.
Great effort has been involved in the
creation of an enclosure system
-Mr. AP Rao; Mr. P Patel;
Mr. TN Shah
‘Switchgear Design & Development Center
which minimizes the possibilty of an
arc fault occurring and also limits
the effect of accidental arcs. This is
accomplished by containment
within the enclosure and allowing
the safe release of the resulting
over-pressure and gases
L8iT takes pride in the fact that all
the products and designs are proven
to be reliable and fit for this
purpose. (See table below)
This issue of L&T Current Trends
elaborates various aspects of
intemal arc compliant switchgear
assemilies
TESTS CONDUCTED BY L&T
Sr.No. Product eppcebte IES Certified for
Guide
i Power Control Center 1EC SOKA 0.5 sec
2. Motor Control Center sical TOKAV 0.5 secIntroduction
An arc fault normally begins as a
short circuit between two or more
contact points, and can quickly
develop to pose a serious threat to
personnel safety. With an internal
core temperature of 3000°C, an arc
lasting just 500 ms can cause
‘tremendous damage
Causes of Internal Arc Faults
> Ageing of insulating materials
under electrical stress
> Corrosion
v
Thermal overstressing
Over-voltage
> Defective installation
> No maintenance or incorrect
maintenance
> Mal-operation/ abuse
> Pollution - humidity, small
rodents penetrating in the
switchgear
Development of Internal Arc
fault resistant Switchgear
Assembly
It is a well known fact that the arc
resistance is quite high. Itis possible
that under internal arc fault
condition, short circuit protective
device may not operate as current
can be below pickup current of
magnetic release.
When an internal arcing fault
occurs, a lighting plasma arc forms
short circuit and eneray of many
mega joules is released within a
fraction of second. Most of that
energy is transferred to the
Arc fault occurs due to
reduction of dielectric
clearances normally caused
by human intervention.
‘Once the path is
established, short circuit
current flows through air
until the upstream
protection device clears the
fault.
surrounding air which is heated to
several thousand Kelvin within
milliseconds. This causes the gas to
expand. explosively emitting a
pressure wave. At such high
temperature, part of the energy is
consumed by dissociation and
ionization of the gas molecules;
another part of it is emitted as
thermal radiation, heating the
surrounding material. Progressing
intime, an increasing part of the
energy is consumed by heating
and melting and evaporation of
material, known as the thermal
phase. Finally, hot gases at high
pressure, carrying gleaming
particles, are emitted to the
surrounding medium.
Under internal arc fault condition
mechanical parts are subjected to
considerable amount of stress due
to development of high pressure in
the enclosure. To avoid the
destruction of switchgear assembly
it is necessary to integrate
overpressure relief systems in
form of ventilation
vent outlets
persons close te
openings,
etc. Besides this,
the switchgear are
also at risk during the internal arc
‘The safety of operators against
hot gases, radiation and
fragmentation of the enclosure
must be secured.
The spatial and temporal
distributions of pressure and
‘temperature and gas velocities, that
result from an intemal arc fault,
plays @ key role in determining
mechanical design of flaps & vents.
{As shown in the figure flaps can be
incorporated at the top of enclosure
to release ionized gases within
enclosure. Hot gases formed inside
enclosure flows through cable
compartment & ionized gases will
get released to environment
without any damage to assembly or
surroundings.
Consequences of internal arc
fault
During an internal arc fault,
enormous amount of energy is
released within milliseconds. The arcTable 1
‘Arc Duration (ms)
Effect on personnel & Equipment
<10 Little or no injuryidamage
10-100 Risk of injuny/damage
100-500 High risk of injuny/damage
energy is directly proportional to the
square of the arc current and the
time duration, during which the arc
sustains, ie, energy is proportional
tort
Table 1 shows the effect of arc on
personnel & equipment
Internal Arc Fault Test
The arcing phenomenon is complex
therefore itis difficult to predict the
behavior of arc and its secondary
effects. Consequently, it has not
been possible to arrive at
internationally acceptable safety
criteria that would take into
account all the possible
ramifications of internal arcing
faults. The absence of such a
standard means the ability of a
manufacturer's assembly to
withstand the effects of an internal
arc fault may never be known until
one actually occurs.
Although many LV switchgear
manufacturers were carrying out
‘their own safety testing as long ago
as 1984, there were no guides as to
‘the conditions under which this
testing had to be conducted.
Consequently, a customer had no
way of comparing the safety of one
manufacturer's switchgear with
another's
IEC 61641 was first technical report
for low voltage switchgear &
control-gear assemblies which
provide guidelines for testing under
conditions of arcing due to internal
fault. The second and latest edition
of IEC 61641 was published in
2008.
Procedure of Internal arc fault
test
The test should be carried out on a
test specimen not previously
subjected to an arcing test or on a
specimen cleaned & prepared
accordingly. The specimen & the
equipment in it may be repaired or
replaced before each test
The mounting conditions should be
as close as possible to those of
normal service. The arcing test is
carried out as a three phase test
according o the service conditions
Voltage: The applied voltage of the
test circuit is 105% of the rated
operational voltage.
Current: To test a permissible
current under arcing conditions, the
‘test supply is adjusted by making a
short circuit as close as possible to
the incoming terminals of the
assembly.
Frequency: Frequency of test
voltage for a rated frequency of 50
Hz or 60 Hz, at the beginning of the
test should be between 45 Hz & 67
Hz, At other frequencies it should
not deviate from the rated value by
more than + 10 %.
Duration of test: The power supply
duration of the assembly under test
is given by the manufacturer. It is
chosen according to the time
response of electrical protection
devices. If details regarding these
devices are not known, power
supply duration of at least 0.1 s is
applied. Normally this duration
shouldnot exceed 0.55
Arc Initiation: The arc is initiated
between the phases without
connection to earth by means of a
bare copper ignition wire
connecting the adjacent conductors
across the shortest distance, &
connected to three phases,
With regard to test current, the sizes,
of copper ignition wire given in
Table 2 should be used,
Table 2
Test crank M5 | Wire size mm
5 O75
325 10
>a0 15
A test is not necessary at any area
which fulfils the requirement of an
arc-free zone. The ignition wire is
connected only to accessible bare
conductors. Insulating material onconductors is not to be destroyed,
removed or punctured when the
ignition wireis connected.
Indicators: Black cretonne should
be used for the indicators so
arranged that their cut edges do not
point towards the test unit, Care
should be taken in mounting the
indicators to ensure that they do not
ignite each other.
The indicator dimensions should be
about 150 mm X 150 mm
Indicators should be fitted vertically
at all sides of assembly which are
readily accessible to operating
personnel. Indicator should be
placed up to maximum height of 2
m & distance of 300 mm 5 % from
assembly, facing all points where
gasis likely to be emitted
Assessment criteria for the test
> Correctly secured doors, covers,
etc. donot open.
Test sample
> Parts of assembly, which may
cause a hazard, donot fy off
v
Arcing does not cause holes to
develop in the freely accessible
external parts of the enclosure
as result of burning or other
effect
> Indicators do not ignite.
is still
¥
The protective circuit
effective
¥
The assembly is capable of
confining the arc to the defined
area where itis ignited, & there
is no propagation of the arc to
other areas within the assembly.
v
The switchgear assembly shall
withstand dielectric voltage at a
value of 1.5 times the rated
operational voltage for 1
minute,
Conclusion
While working on Switchboard
Indicator
General test setup for internal arc fault test
assemiblies, panel operators are
exposed to potential risks during
normal operation of low voltage
power distribution switchgear due
to the high levels of energy that are
involved when internal arc fault
occurs. An arc withstand panel
proves to be a great option for life
extension, improved productivity
and most importantly operating
personnel safety. This is @ voluntary
test made either at the discretion of
the manufacturer, or subject to an
agreement between manufacturer
and user, but arc fault resistant
assemblies should be considered for
any application where the safety of
personnel or the reliability of
equipmentis a majorconcern
ooo
Visit us at
ELECRAMA-2010
: Venue :-
Elecrama, Bombay Exhibition
Centre, Mumbai, India
-: Stall no.
H1N41P42, Hall no. 1
-: Dates
20-24 January 2010
~: Visiting hours :~
1000hrs to 1800hrs only for
business visitors
6 For farther dotals on this subject please contact )
( Electrical Systems & Equipment, Larsen & Toubro, SakiVihar oad, PO. Box 8901, Powal, Mumbai 400 072 )
"Tel +91-22:5705 174812857 & Fax: 022-6705 1024 * E-mail ese-cmt@)ntebg.com
q Print by Printania Offset Put. L1a,0 20/21, Shalimar Indusinal Estate, Matunga (East), Mumbai 400 019. Te: 2407 7996/
9866/8540 Fax
2402 4703 Email. pdsé@rediinal.com The views expressed inthis magazine are nat necessariy those
of the management of Larsen & Touro The contents of this magazine should not be reproducted without the
\antton permission of the Elton. Not for sale-onlyforeculation among the customers. Edlforial Coordinatrs "Mahendra Gehio,
eer )\ Swat Rangaaian Hama Shan
/