R S INFRA PURCHASER STR DGN OF TT "DA (0 DEG.

)" WITH HTLS 132 KV D/C Kusaha –


PROJECTS NEA CONDUCTOR (WZ 4) Biratnagar TL
WIND PRESSURE CALCULATION (As per IS 802 (Part 1/Sec.1) 2015
Basic data :
Wind Zone = 4
Relibility level = 1
Terrain categeory = 2
Span = 330

Vb = Basic wind speed


Vb = 47 m/sec
K1 = Risk coefficient
K1 = 1.00
K2 = Terrain roughness coefficient
K2 = 1.08

VR = Metrological reference wind speed, as per cl no. 8.2


VR = Vb / K0, Where K0 = 1.375
VR = 47/1.375
VR = 34.18 m/sec

Vd = Design Wind speed, as per cl no. 8.3


Vd = VR x K1 x K2
Vd = 34.18x1x1.08
Vd = 36.92 m/sec

Pd = Design Wind Pressure, as per cl no. 8.4


Pd = 0.6 x Vd2
Pd = 0.6x36.92x36.92
2
Pd = 817.7 N/m
2
Pd = 83.4 kg/m (FOR FULL WIND)

RS/NEA/132KV/STR-DGN/DA/01 Page 4