DT-10-015 REV. 3
HYDRO ONE NETWORKS INC. MARCH 2013
Utility feeder
52
3 - Wire
DGEO/LSBS TT
A second station service
PCC may be considered if
another feeder with
genuine supply diversity is
available
Isolation
Device
M
DGEO/LSBS TT
Unbalance
Interconnection Protection3
Protection
Extended
Anti-Islanding
Basic Anti-Islanding Protection Protection Ferroresonance
Protection
1
BF HVI
50 51 672 212 46 32R 67N2 21N2 50N 51N
Anti-Islanding
Unbalance
or Ground
Protection
Phase fault Protection Ground fault Protection
Protection
Extended
VT 25
Transformer
Protection2
T1
Fuse
Station Service
DG LV
Protection 120V 120V
BF LVI
LVI
Critical Loads
Generator
Protection
LVI LVI
VT
Auxiliary
Load G
Xgn
3-Wire Connection
Delta:wye DGIT
1
DG Facility shall have an HVI or fuses to provide protection for DGIT and HV faults within the DG facility.
2
DG protection must be capable of selectively detecting faults on the DG side of the HVI to disable auto-reclosure
3
Refer to Table 10. Protection elements not sensitive to DGIT winding configuration may be connected to LV instrument transformer.
92