DISTRIBUTED GENERATION TECHNICAL INTERCONNECTION REQUIREMENTS

INTERCONNECTIONS AT VOLTAGES 50KV AND BELOW

DT-10-015 REV. 3
HYDRO ONE NETWORKS INC. MARCH 2013

Utility feeder
52
3 - Wire
DGEO/LSBS TT
A second station service
PCC may be considered if
another feeder with
genuine supply diversity is
available

Isolation
Device
M
DGEO/LSBS TT

Unbalance
Interconnection Protection3

Protection
Extended
Anti-Islanding
Basic Anti-Islanding Protection Protection Ferroresonance
Protection

3 VTs 27 59 81o 81u 47 81R 78 59I 59G

1
BF HVI
50 51 672 212 46 32R 67N2 21N2 50N 51N

Anti-Islanding
Unbalance
or Ground
Protection
Phase fault Protection Ground fault Protection

Protection
Extended
VT 25

Transformer
Protection2

T1
Fuse
Station Service
DG LV
Protection 120V 120V

BF LVI
LVI

Critical Loads
Generator
Protection
LVI LVI
VT

Auxiliary
Load G

Xgn
3-Wire Connection
Delta:wye DGIT

1
DG Facility shall have an HVI or fuses to provide protection for DGIT and HV faults within the DG facility.
2
DG protection must be capable of selectively detecting faults on the DG side of the HVI to disable auto-reclosure
3
Refer to Table 10. Protection elements not sensitive to DGIT winding configuration may be connected to LV instrument transformer.

Figure 19: 3-Wire DGIT Typical Protections