Dec., 2000 Technical Bulletin No. 1001

Why Determine Tensile Strength


and Percent of Elongation?
Tensile strength and elongation are two test ELONGATION - Elongation is defined as
results which are commonly seen in all pub- the distance (in percent) the membrane will
lished modified bitumen manufacturer’s litera- stretch from its original size to the point at
ture. This information is very important in that which it breaks.
it tells what the membrane will do as far as WORK - (Also Load-Strain Product, Load
“work” performance. (Work performance Strain Modulus) - Work is defined, in the
being the amount of distortion the membrane case of modified bitumen products, as the
will undergo without destruction.) amount of energy the membrane can with-
All roofing membranes whether convention- stand before destruction occurs. Visually
al BUR, modified bitumen, PVC, EPDM, etc. given in Newtons (N), this quantity is easily
undergo stresses and strains which cause determined by multiplying the tensile at break
the membrane to distort or deform. Much of by the elongation as a percent.
this occurs at details such as: pipe penetra-
tions, parapet walls and area dividers. A
membrane, over its lifetime, will undergo For example: If a specimen of membrane
many cycles of stress; nor mally due to has a tensile strength of 150 lbf. and an elon-
changes in atmospheric temperature.The gation of 10% you do the following:
membrane must be able to cope with the Multiply 150 X 10 = 1500
forces it encounters in order to protect the 1500 is your Load-Strain Product in lbf.
system from intrusion by water.
To convert to Newtons;
Testing for tensile strength and elongation is
Multiply 1500 X 4.448222.
performed using a mechanical testing appa-
Hence - 6672 N.
ratus (Instron). Specimens of membrane are
stretched to the breaking point, using this There is much debate as to whether tensile
device, and in doing so, the tensile strength strength or elongation should be considered
and elongation is determined. the most important. Neither are singularly
important, but together they are extremely
The following are definitions of terms used
in this procedure: important.

TENSILE STRENGTH - Tensile strength is


defined as the force required to break the To show you how important “work” is, sever-
specimen or cause complete separation of al examples are provided on the back. È
constituents in a linear direction. Fig. 1 is a typical chart read-out from pulling

MANUFACTURERS OF ADVANCED TECHNOLOGY WATERPROOFING MEMBRANES


3
Technical Bulletin No. 1001, continued

a fiberglass reinforced modified bitumen It can be easily seen that the polyester rein-
membrane. The tensile obtained is 185 lbf forced membrane can perform more “work”
and elongation is 14%. than can the fiberglass reinforced membrane.
Fig. 2 is a typical chart read-out from pulling In order to get the same amount of “work” out
a polyester reinforced modified bitumen of the fiberglass membrane as compared to
membrane. The tensile obtained is 105 lbf the polyester membrane, the tensile of the
and elongation is 55%. fiberglass membrane would have to be 413
lbf with an elongation of 14% or a tensile
From the charts, let’s compute the load- strength of 185 lbf with an elongation of 31%.
strain product or “work” which the respective
membranes can perform. As you can see the “work” that the mem-
brane can perfor m is ver y impor tant in
Fig. 1: (Fiberglass Reinforced) regards to how well the membrane will per-
185 X 14 = 2,590 Load-Strain Product form in the field.
Fig. 2: (Polyester Reinforced) It is a “give and take” situation...
105 X 55 = 5,775 Load-Strain Product
 , 
, , ,
,, ,
Fig. 1 185 Fig. 2 105






Fiberglass Polyester
Reinforced Reinforced
Membrane Membrane
Tensile - 185 Tensile - 105
,






Elongation - 14% Elongation - 55%



,











14% 55%

116

BITEC vs. Derbigum SP



,








Temperature - 25°C (77°F)

,
Specimen - 2" wide
Cross HD. S. - 20" min.

BITEC APS-4T Owens Corning


Membrane Derbigum SSP
Tensile - 116 lbf/in. Tensile - 116 lbf/in.
Elongation - 40% Elongation - 3%
Load/Strain Product - 20,640 N Load/Strain Product - 1548 N
,







40% 3%
,

Note: Shaded area in the curve is the “work” performed.