Contents
Document purpose ...................................................................................................................................... 3
Starting PMM in vector control mode with Triol AK06 ...................................................................... 4
Preparation processes ................................................................................................................................. 7
Download PMM library to the controller: .......................................................................................... 8
Step by step instructions to start PMM in vector control mode .................................................... 11
Entering the main parameters .......................................................................................................... 11
Setting the control mode.................................................................................................................... 15
Appendix A – «Rs» motor parameter .................................................................................................... 16
Appendix B – auto-detection «Lsd», «Lsq» installation parameters .............................................. 17
Appendix C – auto-detect «Torque» parameter ................................................................................ 21
Appendix D – Troubleshooting .............................................................................................................. 25
Document purpose
This instruction allows you to successfully start PMM using Variable Speed
Drive Triol AK06 in vector control mode.
Triol vector control mode allows you to maximize the energy efficiency by
keeping the motor power factor close to 1, thereby minimizing heat dissipation
in the equipment caused by the exchange of reactive energy between the plant
elements.
As the vector control algorithm is a mathematical model of the entire
installation (VSD + step-up transformer + cable line + motor + pump), and
entering of accurate characteristics / parameters of the equipment allows to
ensure the correct operation of the installation.
Special algorithms integrated into Triol AK06 VSD allow you to automatically
determine motor parameters. In combination with the optional Triol Drive tool,
maximum efficiency and stable motor and pump performance are achieved by
precision setting of the vector control algorithm in the VSD.
Starting PMM in vector control mode with Triol AK06
Triol AK06 VSD allows you to start PMM in vector control mode knowing the
basic parameters of the equipment, which are given on the nameplates.
Unknown motor parameters such as: «Rs» is the stator winding resistance of
PMM, «Lsd» is the stator inductance of the motor along the d axis, «Lsq» is the
stator inductance of the motor along the q axis, Psi rotor is the stator winding
flux linkage with the rotor flow; are determined automatically.
A tool to reduce equipment startup time is PMM lib. This library is present in
Triol AK06 VSD with the UMKA03 controller starting from software version
33.58. A feature of this functionality is the ability to select PMM model from a
list of preloaded into the controller. When choosing a motor model, the VSD
controller automatically records the nominal motor parameters necessary for
the operation of the vector control algorithm. The list of recordable parameters
is given below:
«ESM rated power» parameter — motor rated power.
«ESM rated voltage» parameter — motor rated voltage.
«ESM rated current» parameter — motor rated current.
Count poles — the number of PMM poles pairs.
«Motor rated freq.» parameter — motor rated frequency.
«Motor rated PF» parameter — value of motor rated power factor.
Rs — motor stator winding resistance.
Lsd — motor stator inductance of the d axis.
Lsq — motor stator inductance of the q axis.
Psi rotor — flux linkage of the stator winding with the flow of the rotor.
It is recommended to configure the algorithm to work with a specific motor
model in the following sequence:
1. Determine the parameters of the motor «Rs», «Lsd», «Lsq» in the
workshop, if necessary, start on with no load test (having previously
determined inertia moment);
2. Determine the installation moment of inertia and start operating.
The PMM setting algorithm in the vector control mode is given in table 1.
Table 1 - startup algorithm.
Following General How to
№ What to do First start* Runtime
starts time perform
quickstart
1 Connect the VSD to the supply voltage. In workshop not required User data
manual
Enter installation parameters:
- motor (passport values of current, voltage,
frequency, cosfi, number of pairs of poles,
power, «Rs», «Lsd», «Lsq»);
2 - VSDs (inductance, capacitance, sinus filter in workshop not required 7 min
resistance of the VSD according to the data
in the instruction);
page 11 – 14
- mains supply (mains voltage and
frequency).
Set the frequency range of regulation: Up to
- set the maximum and minimum motor 34 min
3 control frequencies; in workshop not required 2 min
- establish a smooth start-up mode and
acceleration and deceleration rates.
Measure the resistance of the stator
4 windings of the motor and transfer the value in workshop not required 10 min page 16
to the controller using a multimeter.
Determine the value of motor inductances
5 using a special algorithm in Triol AK06 VSD in workshop not required 15 min page 17 – 20
without a step-up transformer.
Install the VSD at the facility, connect
quickstart
6 equipment in accordance with the required in workshop onsite User data
manual
scheme.
7 Chose motor from PMM lib. not required onsite 2 min page 11
Enter installation parameters:
- cable line (length (or descent depth), cable
cross-section, formation temperature;
7 in workshop onsite 4 min
- step-up transformer (power, frequency,
impedance, voltage of the primary winding page 22 – 25
and secondary winding). Up to
Determine the moment of inertia of the 23 min
8 installation using a special algorithm of the in workshop onsite 7 min
VSD.
Set up the necessary technological
quickstart &
equipment protection (overload, underload
9 In workshop onsite 10 min programming
etc..), connect downhole sensors,
manuals
peripherals and SCADA to the VSD.
10 The VSD is ready for operation in workshop onsite User data -
* equipment can be started immediately onsite
The total time for the first start of the VSD in vector mode is up to 57 minutes.
Also, there may be time for connecting additional equipment performed by
Customer’s staff. The next runtime is reduced by more than half. This is
achieved by loading the values of the parameters «Rs», «Lsd», «Lsq» of each
motor into the PMM lib. The library file is generated on a PC and can be
downloaded to any VSD.
To start a new motor model, complete all steps 1-10 in the workshop again and
add the new motor model to the library.
It is allowed to start the equipment immediately onsite. In this case, all the same
actions are performed as in the workshop. Parameters «Rs», «Lsd», «Lsq» can
be saved to the library only if they were determined without a cable line
connected to the motor.
Otherwise, the resistance of the cable line is taken into account in the
parameters «Rs», and the inductance of the cable line in the parameters «Lsd»,
«Lsq».
There may be the need for the user to update the VSD software, followed by
restoring the settings and calibrations of the VSD. This operation takes up to 25
minutes. This action applies to the VSD made prior to this manual.
ATTENTION! All personnel must use the product properly and safely
to prevent any injury or any kind of damage.
Preparation processes
In order to start using this functionality, it is necessary that the software version
33.58 or higher is installed in the controller of the VSD, and the IND lower level
controller must be flashed with software version 37.134 or higher.
The ability to select PMM from the list is available for both the «LF PMM VC»
operating mode and the «HF PMM VC» operating mode.
To check and update the current controller software version:
1. Follow the next steps:
«Status display» → « LEFT» → «System» → « RIGHT» → «VSDC parameters»
→ « RIGHT».
1. Check the software
version of the controller and
the VSD:
• The parameter «VSDC
software version»
informs about the
controller version
UMKA03. Version must
be 33.58 or higher;
• The parameter «Drive
software version»
informs about the drive
version IND. Version
must be 37.134 or
higher.
2. If you need to update
the software, follow the steps
below, otherwise go to the
section «Download the PMM
library to the controller».
3. The software update
must be performed according
to the algorithm described in
the document
«Troubleshooting Manual
AK06 UMKA03» in the
section «Instruction for
updating software UMKA and
IND». First you need to get
the latest software versions
from the Triol Customer
Service, as well as the motor
library file.
The controller displays a message about the need to reload the controller. You
must press «Enter» and wait until the controller automatically reboots.
3. Go to:
«Status display» → « LEFT» → «Modes of start» → « RIGHT».
Set parameters:
• «Startup mode» = Soft;
• «Acceleration rate»,
«Deceleration rate» = 2
Hz/s.
4. If motor hasn’t been chosen from list go to menu:
«Status display» → « LEFT» → «Drive settings» → « RIGHT» → «PMM Vector
mode» → « RIGHT » → «Set vector control» → « RIGHT», otherwise skip this
point.
Set «Count poles» according
to the motor poles pairs
number or it can be
calculated by formula below:
𝑓𝑚𝑜𝑡𝑜𝑟_𝑛𝑜𝑚𝑖𝑛𝑎𝑙 ∗ 60
𝐶𝑜𝑢𝑛𝑡 𝑝𝑜𝑙𝑒𝑠 =
𝑟𝑝𝑚
5. Go to:
«Status display» → « LEFT» → «Drive settings» → « RIGHT» → «PMM Vector
mode» → « RIGHT » → «Line and PMSM» → « RIGHT».
Set parameters according to
the VSD type:
• «L sin Filter»;
• «C sin Filter»;
• «R sin Filter».
b7. Go to:
«Status display» → « LEFT» → «Alarms» → « RIGHT».
Turn ON the «Overtorque
protection» and «Phasing
failures». In «Overtorque
protection» set «Overtorque»
parameters to «On».
In «Phasing failures» set
«Phasing Iu Iv Iw» and
«Phasing Ia Ib Ic» parameters
to «On».
Turn OFF next alarms:
«Overload», «Underload»,
«Current unbalance», «Low
frequency».
Go to each protection’s menu
and change «Protection»
parameter to «Off» in every
protection menu.
b8. Go to:
«Status display» → « LEFT» → «Calc. of step-up transf.tap voltage» →
« RIGHT».
Set parameters:
• «Setting depth» equal to
the cable line length of
submersible units. If
there are no cable line
set 0;
• «Prim winding voltage»
equal to the supply
power network (380 V or
480 V);
• «Step-up tr. Tap U» equal
to the supply power
network (380 V or 480 V).
b9. Go to:
«Status display» → « LEFT» → «Drive settings» → « RIGHT» → «PMM Vector
mode» → « RIGHT» → «Line and PMSM» → « RIGHT».
Set parameters:
• «Psi rotor» according to
motor nameplate.
If the value of «Psi rotor» is
unknown, it can be calculated
using the formula below:
𝑈𝑚𝑜𝑡𝑜𝑟_𝑖𝑑𝑙𝑒 ∗ 1,41
𝑃𝑠𝑖 𝑟𝑜𝑡𝑜𝑟 =
1,73 ∗ 2 ∗ 3,14 ∗ 𝑓𝑚𝑜𝑡𝑜𝑟_𝑛𝑜𝑚𝑖𝑛𝑎𝑙
Where:
- 𝑈𝑚𝑜𝑡𝑜𝑟_𝑖𝑑𝑙𝑒 - linear Back-emf of the motor idling at the motor rated frequency. If
this parameter is unknown, then it can be calculated as:
𝑟𝑝𝑚𝑚𝑜𝑡𝑜𝑟_𝑛𝑜𝑚𝑖𝑛𝑎𝑙
𝑈𝑚𝑜𝑡𝑜𝑟_𝑖𝑑𝑙𝑒 = OR 𝑈𝑚𝑜𝑡𝑜𝑟_𝑖𝑑𝑙𝑒 = 𝑟𝑝𝑚𝑚𝑜𝑡𝑜𝑟_𝑛𝑜𝑚𝑖𝑛𝑎𝑙 ∗ 𝑘𝑒
𝑘𝑉 𝑜𝑟 𝑏𝐸𝑀𝐹
Set parameters:
• «Step-up tr. power»
according to the step-up
nameplate;
• «ESP rated efficiency»
according to the pump
characteristic;
• «ESP head» according to
the pump characteristic.
c8. Go to:
«Status display» → « LEFT» → «Calc. of step-up transf.tap voltage» →
« RIGHT».
Set parameters which are
given in the table below:
yes Have the «Lsd and Lsq» no yes Have the «Lsd and Lsq» no
parameters been defined with parameters been defined with
the cable line? the cable line?
c10. Go to:
«Status display» → « LEFT» → «Drive settings» → « RIGHT» → «PMM Vector
mode» → « RIGHT» → «Set. vector control» → « RIGHT».
Set parameters:
• «Setting start frequency»,
«Setting switching»,
«Step-up transformer
satur. control» to «On»
state.
• «Switch I/F – U/F» =
«I/F».
Now the VSD is ready to auto-detect «Torque» value.
Follow the steps to begin auto set process:
• press « Start» button;
• no need to change «frequency setting» parameter;
• wait until auto set process finish;
• if «Auto-set» procedure is completed successfully, message «Autoset»
appears at UMKA03 display;
• if «Auto-set» procedure isn’t completed successfully, message «Failcacl»
appears at UMKA03 display;
• if «Torque» parameter has value 32.767 it means that auto-detection is
not completed successfully;
• if the VSD stops the auto-detection process by any alarm, find the reason:
- check if the entered parameters data are correct. If data incorrect fix it
otherwise contact Triol Service Support;
- to restart the definition algorithm «Torque» – set «Autoset» parameter
to «Inductance» state and press « Start» button.
Appendix D – Troubleshooting
Accident / non-
Reasons Remedy
compliance
1. Verify that the following settings are configured
correctly: