You are on page 1of 10

204

Above Ground Storage Tank - Direct Fill


Typical Non-EVR Direct Fill AST Application

A B C D
20 1

To Pressure Vacuum Vent


Suction
Pump
21

2
A
B C D PRODUCT KEY

3 9 OPW PART / DESCRIPTION PAGE


200TG-ENG Series Tank Gauge
16 1 224
(optional / see Note below)
2 61T Series Drop Tube 224
TOP OF AST 10
17 301 Series Emergency Vent - NPT Mount
(not supplied) 3 226
(See Vent Size Configuration Guide on page 216)
11 301 Series Emergency Vent - Flanged Mount
18 4 226
(See Vent Size Configuration Guide on page 216)
12 5 1711T-7085-EVR Cap 97
4 6 1611AV Series Vapor Recovery Adaptor 96
1DK-2100EVR 14
Drain Valve 7 1711LPC-0300 Low Profile Cap 97
4" Nipple 2" Nipple 8 61VSA Series Vapor Recovery Adaptor 95
(not supplied) (not supplied)
9 190 or 210 High-Flow Bulk Nozzle 188, 192
2" Nipple (supplied) 10 633BD Kamlok™ Coupler 222
19
TOP OF AST A) 634B-0150 Dust Cap or 634BK-0090
(not supplied) Lockable Dust Cap fits 633AST-2061 Spout
13 Adaptor
11 222
with 1DK-2100EVR B) 634B-0170 Dust Cap or 634BK-0100
Drain Valve 2" Pipe Lockable Dust Cap fits 633AST-3061 Spout
(not supplied) Adaptor
B 12
633AST-2061 (2" x 2") or 633AST-3061
(3" x 3") - Tank Inlet Spout Adaptor
222
TOP OF AST TOP OF AST
(not supplied) 13 332 Series Spill Container 218
5 7 (not supplied)
61fSTOP-XXXX Series Overfill Prevention
14 220
Valve
15 61FT Series Drop Tube 221
14
16 634B-0150 or 634BK-0090 Cap 222-223
6 OR 8 17 204247 Fill Prevention Cage 222
18 633AST Series Adaptor 222
19 53-00XX Series Double Tapped Bushing 128
20 62M Series Monitoring Probe Cap & Adaptor 98
15 21 FSA-400 Face Seal Adaptor 57

NOTE: The OPW 200TG and 144TA/444TA are not required for
Direct fill drop tubes shall be EVR compliance, but if a tank gauge or tank alarm is used on
TOP OF AST cut at 45º angle, with top of your tank that these two OPW products are the only CARB AST
(not supplied) cut no greater than 6" from EVR certified tank gauge and alarm.
the bottom of the tank (Or if
outside the State of California,
6" per local requirements)

205
206
Above Ground Storage Tank - Remote Fill - Remote Dispensing
Typical Non-EVR Remote Fill / Remote Dispensing AST Application

To Pressure Vacuum Vent


B
Vapor Return
A D
Fill Pipe
2 33 4 27

18
28
5

2424

11
A B C 25 or 26
PRODUCT KEY

14
KEY OPW PART / DESCRIPTION PAGE
7
23 1 178S Series Emergency Valve 235
19 2 821 Series Solenoid Valve 233
8 2" Nipple 3 21BV Series Ball Valve 234
(not supplied) Conduit
To 4 199ASV Series Anti-Siphon Valve 232
9 Remote 5 82RV Series Pressure Relief Valve 233
Alarm 6 53-00XX Series Double Tapped Bushing 127
Fill Pipe
7 634B-0150 or 634BK-0090 Cap 222-223
8 204247 Fill Prevention Cage 222
16
9 633AST-2190 Adaptor 222
2" Nipple 24
301 Series Emergency Vent - Threaded Mount
(not supplied) TOP OF AST 10 226
(See Vent Size Configuration Guide on page 216)
(not supplied)
6 301 Series Emergency Vent - Flanged Mount
11 226
(See Vent Size Configuration Guide on page 216)
12 61fSTOP-XXXX Series Overfill Prevention Valve 220-221
2" Pipe 22 13 61FT Series Drop Tube 221
(not supplied)
200TG-ENG Series Tank Gauge
20 21 14 224
17 (optional / see Note below)
TOP OF AST 12
15 15 61T Series Drop Tube 224
(not supplied)
16 TGTA-0400 4" Gauge/Alarm Combo Fitting (optional) 225
D 17 44TA-LLFS Liquid Level Float Switch 225

10 18 175 Series Swing Check Valve 236


19 6211R Series Remote Spill Container 219
1611AN-0200 or 1612AN-0200 - 2" Remote Fill or
13 20 1611AN-0300 or 1612AN-0300 - 3" Remote Fill 223
Kamvalok Adaptor
TOP OF AST
(not supplied) A) 634B-0140 Dust Cap fits 633AST-0150 Adaptor
B) 634B-0150 Dust Cap fits 633AST-2061 or
633AST-0200 Adaptor
21 C) 634B-0160 Dust Cap fits 1611AN-0200 or 633ST- 222
12" 0250 or 1611AN-2040 or 1612AN-2040 Adaptors
D) 634B-0170 Dust Cap fits 1611AN-3060 or
11 1612AN-3060 Adaptors
22 1711D / 1712D Series Kamvalok Coupler 223
Direct fill drop tubes shall be cut at 45º
angle, with top of cut no greater than 12" 23 1711T-7085-EVR Cap or 1711LPC-0300 Low Profile Cap 97
TOP OF AST
from the bottom of the tank (Or if outside the (not supplied) 144TA/444TA Series Tank Alarm
24 (optional / see Note below) 225
State of California, per local requirements)
25 1611AV Vapor Recovery Adaptor 96
NOTE: The OPW 200TG and 144TA/444TA are not required for EVR compliance, but if a tank 26 61VSA Series Vapor Recovery Adaptor 95
gauge or tank alarm is used on your tank that these two OPW products are the only CARB AST
27 62M Series Monitoring Probe Cap & Adaptor 98
EVR certified tank gauge and alarm.
28 FSA-400 Face Seal Adaptor 57

207
210
Above Ground Storage Tank - Remote Fill
Typical Diesel/Fuel Oil/Generator Application

To Pressure Vacuum Vent


C D
1 3 4 B 12
Vapor Return
19

A Fill Pipe 30

13
2

31

3
29

28

31
PRODUCT KEY
A B C
OPW PART / DESCRIPTION PAGE
10 16
1 821 Series Solenoid Valve 233
5 2 82RV Series Pressure Relief Valve 233
3 21BV Series Ball Valve 234
6 2" Nipple
TOP OF AST (not supplied) 4 199ASV Series Anti-Siphon Valve 232
(not supplied) Conduit
To Remote 5 634B-0150 or 634BK-0090 Cap 222-223
7
Alarm 6 204247 Fill Prevention Cage 222
Fill Pipe 7 633AST-2190 Adaptor 222
8 53-00XX Series Double Tapped Bushing 128
17 9 61T Series Drop Tube 224
2" Nipple 11
TOP OF AST
(not supplied) 301 Series Emergency Vent - NPT Mount
(not supplied) 10 226
(See Vent Size Configuration Guide on page 216)
8 301 Series Emergency Vent - Flanged Mount
11 226
(See Vent Size Configuration Guide on page 216)
TOP OF AST
(not supplied) 12 62M Series Monitoring Probe Cap & Adaptor 98
13 FSA-400 Face Seal Adaptor 57
2" Pipe
(not supplied) 14 14 61fSTOP-XXXX Series Overfill Prevention Valve 220-221
18
D 26 or 27 9 15 61FT Series Drop Tube 221

16 200TG-ENG Series Tank Gauge 224


TOP OF AST (optional / see Note below)
(not supplied) 17 TGTA-0400 4" Gauge/Alarm Combo Fitting 225
25
20 18 44TA-LLFS Liquid Level Float Switch 225
19 175 Series Swing Check Valve 236
15
20 6211R Series Remote Spill Container 219

21 144TA/444TA Series Tank Alarm 225


(optional / see Note below)
1611AN-0200 or 1612AN-0200 - 2" Remote Fill or
22 1611AN-0300 or 1612AN-0300 - 3" Remote Fill 223
12" Kamvalok Adaptor
21 A) 634B-0140 Dust Cap fits 633AST-0150 Adaptor
B) 634B-0150 Dust Cap fits 633AST-2061 or
633AST-0200 Adaptor
23 C) 634B-0160 Dust Cap fits 1611AN-0200 or 222
633ST-0250 or 1611AN-2040 or
Direct fill drop tubes shall be cut at 45º angle, with 1612AN-2040 Adaptors
24 top of cut no greater than 12" from the bottom of D) 634B-0170 Dust Cap fits 1611AN-3060 or
the tank (Or if outside the State of California, per 1612AN-3060 Adaptors
22 23 local requirements) 24 1711D / 1712D Series Kamvalok Coupler 223
25 1711T-7085-EVR Cap or 1711LPC-0300 Low Profile Cap 97
NOTE: The OPW 200TG and 144TA/444TA are not 26 1611AV Vapor Recovery Adaptor 96
required for EVR compliance, but if a tank gauge or
tank alarm is used on your tank that these two OPW 27 61VSA Series Vapor Recovery Adaptor 95
products are the only CARB AST EVR certified tank Automatic Tank Monitoring & Leak Flexible Piping Systems for Fuel Oil &
30 242-249 28 39
gauge and alarm. Detection Equipment Generator Applications
211 31 Probes & Sensors for Liquid & Vapors 250-261 29 Underground Containment Systems 40
212
Above Ground Storage Tank - Direct Fill
Typical OPW Phase I System for AST
The first Above Ground
Storage Tank (AST)
products in the industry A B C D*
to be certified by CARB
3
CARB REQUIRED PRODUCTS

To Pressure Vacuum Vent


Suction
1 Pump

4
A C D* The first Above Ground
5 Storage Tank (AST) products
11
in the industry to be
17 certified by CARB
12
TOP OF AST CARB REQUIRED PRODUCTS
18
(not supplied)
OPW PART / DESCRIPTION PAGE
13 1 62M Series Monitoring Probe Cap & Adaptor 98
19
2 FSA-400 Face Seal Adaptor 57
4" Nipple 200TG-ENG Series Tank Gauge
3 (optional / see Note below) 224
6 (not supplied)
1DK-2100EVR 4 61T Series Drop Tube 224
Drain Valve 2" Nipple (supplied) 2" Nipple 301 Series Emergency Vent - NPT Mount
5 226
(not supplied) (See Vent Size Configuration Guide on page 216)
301 Series Emergency Vent - Flanged Mount
14 20 6
(See Vent Size Configuration Guide on page 216)
226
TOP OF AST with 1DK-2100EVR
(not supplied) Drain Valve 7 1711T-7085-EVR Cap 97
8 1611AV Vapor Recovery Adaptor 96
TOP OF AST 2" Pipe 9 1711LPC-0300 Low Profile Cap 97
(not supplied) (not supplied)
10 61VSA Series Vapor Recovery Adaptor 95
B Any Combination 11 1711D / 1712D Series Kamvalok Coupler 223
TOP OF AST
A) 634B-0140 Dust Cap fits 633AST-0150 Adaptor
7 9 (not supplied)
15 B) 634B-0150 Dust Cap fits 633AST-2061 or
633AST-0200 Adaptor
12 C) 634B-0160 Dust Cap fits 1611AN-0200 or 222
633ST-0250 or 1611AN-2040 or
* When used with 1612AN-2040 Adaptors
8 OR 10 an Automatic or D) 634B-0170 Dust Cap fits 1611AN-3060 or
Mechanical Tank 1612AN-3060 Adaptors
Gauge, a Sticking
1611AN-2040 or 1612AN-2040 - 2" Direct Fill
Port is optional on
13 or 1611AN-3060 or 1612AN-3060 - 3" Direct 223
16 an (AST) Above
Fill Kamvalok Adaptor
Ground Storage
Tank. 14 332 Series Spill Container 218
Direct fill drop tubes shall be
cut at 45º angle, with top of 15 61fSTOP-XXXXT Series Overfill Prevention Valve 220-221
TOP OF AST cut no greater than 6" from
16 61FT Drop Tube 221
(not supplied) the bottom of the tank (Or if
outside the State of California, 17 634B-0150 or 634BK-0090 Cap 222-223
6" per local requirements)
18 204247 Fill Prevention Cage 222

19 633AST Series Adaptor 222


NOTE: The OPW 200TG and 144TA/444TA are not required for EVR compliance, but if a tank gauge
or tank alarm is used on your tank that these two OPW products are the only CARB AST EVR certified 20 53-00XX Series Double Tapped Bushing 128
tank gauge and alarm.

213
214
Above Ground Storage Tank - Remote Fill - Remote Dispensing
Typical OPW Phase I System for AST

The first Above Ground


Storage Tank (AST)
products in the industry
to be certified by CARB

To Pressure Vacuum Vent


CARB APPROVED PRODUCTS
B
OPW RECOMMENDED PRODUCTS Vapor Return
A*
Fill Pipe

2 3 4 D 27

18
5 28

26

* When used with an Automatic or Mechanical


Tank Gauge, a Sticking Port is optional on an
(AST) Above Ground Storage Tank.
The first Above Ground Storage
A* B C 23 or 24 Tank (AST) products in the
7
15 industry to be certified by CARB
8 25
19 APPROVED PRODUCTS RECOMMENDED PRODUCTS
2" Nipple
KEY OPW PART / DESCRIPTION PAGE
9 (not supplied) Conduit
1 178S Series Emergency Valve (optional) 235
To
Remote 2 821 Series Solenoid Valve (optional) 233
6 Alarm 3 21BV Series Ball Valve (optional) 234
Fill Pipe
4 199ASV Series Anti-Siphon Valve (optional) 232
2" Nipple 5 82RV Series Pressure Relief Valve (optional) 233
(not supplied) 16 6 53-00XX Series Double Tapped Bushing (optional) 128
26
6 7 634B-0150 or 634BK-0900 Cap 222-223
TOP OF AST
(not supplied) 8 204247 Fill Prevention Cage 222
9 633AST Series Adaptor 222
2" Pipe 301 Series Emergency Vent - Threaded Mount
(not supplied) 10 226
(See Vent Size Configuration Guide on page 216)
22 301 Series Emergency Vent - Flanged Mount
TOP OF AST 11 226
(See Vent Size Configuration Guide on page 216)
(not supplied) 12 17 20 21
12 61fSTOP-XXXXT Series Overfill Prevention Valve 220-221
13 61FT Series Drop Tube 221
14 61T Series Drop Tube 224
14
D 200TG-ENG Series Tank Gauge
10 15 224
(optional / see Note below)
16 TGTA-0400 4" Gauge/Alarm Combo Fitting (optional) 225
17 44TA-LLFS Liquid Level Float Switch (optional) 225
TOP OF AST 18 175 Series Swing Check Valve (optional) 236
(not supplied) 19 6211R Series Remote Spill Container 219
1611AN-0200 or 1612AN-0200 - 2" Remote Fill or
20 1611AN-0300 or 1612AN-0300 - 3" Remote Fill 223
Kamvalok Adaptor
13 A) 634B-0140 Dust Cap fits 633AST-0150 Adaptor
11 B) 634B-0150 Dust Cap fits 633AST-2061 or
633AST-0200 Adaptor
21 C) 634B-0160 Dust Cap fits 1611AN-0200 or 633ST- 222
0250 or 1611AN-2040 or 1612AN-2040 Adaptors
*When used with an Automatic or 12" Direct fill drop tubes shall be cut at D) 634B-0170 Dust Cap fits 1611AN-3060 or
Mechanical Tank Gauge, a Sticking Port 45º angle, with top of cut no greater TOP OF AST 1612AN-3060 Adaptors
is optional on an (AST) Above Ground than 12" from the bottom of the tank (not supplied)
1711D, 1711DL, 1712D, 1712DL Series
Storage Tank. (Or if outside the State of California, 22 223
Kamvalok Couplers
per local requirements)
23 1611AV Vapor Recovery Adaptor 96
24 61VSA Series Vapor Recovery Adaptor 95
NOTE: The OPW 200TG and 144TA/444TA are not required for EVR compliance, but if a tank gauge or
tank alarm is used on your tank that these two OPW products are the only CARB AST EVR certified tank 25 1711T-7085-EVR Cap or 1711LPC-0300 Low Profile Cap 97
gauge and alarm. 26 144TA/444TA Series Tank Alarm 225
(optional / see NOTE below)
27 62M Series Monitoring Probe Cap & Adaptor 98
215 28 FSA-400 Face Seal Adaptor 57

You might also like