You are on page 1of 4

AERIAL

ACSR / 1350

APPLICATION STANDARD BS 215 Part 2:1970

Bare overhead reticulation for medium spans, normally at low


and medium voltages CONDUCTOR Aluminium Alloy 1350 +
Galvanised Steel wire
ACSR = Aluminium Conductor Steel Reinforced.
STRAND CONSTRUCTION As Below

Code Name Item Conductor Nominal Approximate Standard


Number Overall Mass Pack
Aluminium Steel Diameter Size

Actual
Area No./mm No./mm Mm kg/km metres
Mm²

Jaguar 66605000 210.6 18/3.86 1/3.86 19.3 670 2000

Panther 66370000 212.1 30/3.00 7/3.00 21.0 970 2000


Lion 66380000 238.3 30/3.18 7/3.18 22.3 1100 2000
Bear 66390000 264.4 30/3.35 7/3.35 23.5 1210 2000
Goat 66400000 324.3 30/3.71 7/3.71 26.0 1490 2000
Antelope 66420000 374.1 54/2.97 7/2.97 27.21 1410 2000
Sheep 66410000 375.1 30/3.99 7/3.99 27.9 1720 2000
Bison 66430000 381.7 54/3.00 7/3.00 27.0 1440 2000
Zebra 66450000 428.9 54/3.18 7/3.18 28.6 1620 2000
Deer 66440000 429.6 30/4.27 7/4.27 29.9 1970 2000

1.2.3.3.7
CONDUCTOR ELECTRICAL CHARACTERISTICS
CODE NAME Equivalent Electrical Maximum Maximum Current Ratings @ 75°C Inductive Single
Areas DC AC (a) Reactance Phase
Aluminium Copper Resistance Resistance Winter Summer to 0.4m Voltage Drop
@20°C @75°C Night Noon @ 0.4m
spacing
mm² mm² Ω/km Ω/km A A Ω/km mV/A.m

Jaguar 210.6 128.4 0.137 0.167 776 640 0.251 0.60


Panther 212.1 129.3 0.136 0.166 798 657 0.248 0.60
Lion 238.3 145.3 0.121 0.148 860 707 0.244 0.57
Bear 264.4 161.2 0.110 0.134 918 753 0.240 0.55
Goat 324.3 197.7 0.089 0.109 1048 857 0.234 0.52
Antelope 374.1 228.1 0.077 0.095 1114 911 0.232 0.50
Sheep 375.1 228.7 0.077 0.095 1146 936 0.230 0.50
Bison 381.7 232.7 0.076 0.094 1129 923 0.231 0.50
Zebra 428.9 261.5 0.067 0.083 1214 990 0.227 0.49
Deer 429.6 262.0 0.067 0.083 1252 1019 0.225 0.48
(a) Wind Speed 1m/sec, emissivity 0.5, absorptance 0.5. Air temperature 10°C for winter night, 25°C for summer noon. Intensity of
solar radiation 1000 W/m² for summer noon. Angle of wind to conductor axis is 60o. For current ratings at different conductor
operating temperatures, refer to the graph on next two pages.
Calculation based on IEEE Std 738 – 1993.

CONDUCTOR PHYSICAL PROPERTIES


CODE NAME Nominal Total Cross Calculated Approx. Final Coefficient of
Overall Sectional Area Minimum Mass Modulus of Linear
Diameter Breaking Elasticity Expansion
Load
Mm mm² kN kg/km GPa /° x 10-6

Jaguar 19.3 222.3 47 670 66 21.2


Panther 21.0 261.5 92 970 80 17.8
Lion 22.3 293.9 101 1100 80 17.8
Bear 23.5 326.1 111 1210 80 17.8
Goat 26.0 400.0 136 1490 80 17.8
Antelope 26.2 422.6 118 1410 69 19.3
Sheep 27.9 462.6 156 1720 80 17.8
Bison 27.0 431.2 121 1440 69 19.3
Zebra 28.6 484.5 132 1620 69 19.3
Deer 29.9 529.8 179 1970 80 17.8

1.2.3.3.7

General Cable New Zealand Ltd South Island Customer Services Auckland Service Centre Wellington Service Centre
HEAD OFFICE 75-89 Main South Rd 14-18 Vestey Drive 109 Port St
75-89 Main South Rd PO Box 8044 PO Box 22-160 PO Box 38-271
PO Box 8044 Riccarton Otahuhu Petone
Riccarton Christchurch Auckland Wellington
Christchurch Free Phone: 0800 222-537 Ph: 0800 222-537 Ph: 0800 222-537
Ph: (03) 348 5199 Fax: (03) 341 0844 Ph: 0800 CABLES Ph: 0800 CABLES
Fax: (03) 348 2009 Free Fax (Orders): 0800 242 267 Free Fax (Orders): 0800 242 267 Free Fax (Orders): 0800 242 267
Website: www.generalcable.co.nz

Diagrams of cables are illustrative only and are not necessarily to scale.

This brochure is distributed with the understanding that the authors and editors are not responsible for the results of any actions taken on the basis of information in this work , or any errors or omissions. Further,
General Cable New Zealand Ltd is not engaged in rendering professional services. General Cable New Zealand Ltd expressly disclaims all and any liability to any person in respect of anything and of the
consequences of anything done or omitted to be done by any such person in reliance whether whole or partial of the whole or any of the contents of this publication. All rights reserved. No part of this work covered
by copyright may be reproduced or copied in any form or by any means without the written permission of General Cable New Zealand Ltd.
Current rating versus conductor temperature (Summer/noon)

1400

1300

1200

1100 Jaguar
Panther
1000 Lion
Current rating (A)

Bear
900 Goat
Antelope
800 Bison
Sheep
700 Zebra
Deer
600

500

400

300
45 50 55 60 65 70 75 80 85 90 95 100 105 110

Conductor operating temperature (oC)

1.2.3.3.7

.
Current rating versus conductor temperature (Winter/night)

1650

1550

1450

1350
Jaguar
Panther
Current rating (A)

1250
Lion
Bear
1150
Goat
Antelope
1050
Bison
Sheep
950
Zebra
Deer
850

750

650

550
45 50 55 60 65 70 75 80 85 90 95 100 105 110

Conductor operating temperature (oC)

1.2.3.3.7

You might also like