You are on page 1of 1

Enter the Values in the Boxes Only

Data
IEC Curve Selected Units
Entry
Ip Setting 0.74 Amps
Tp Setting 0.21 sec
Injected Current 10 4 times
Choose the Curve Normal Inverse
1
Current to be Injected 7.4 Amps
Calculated Tripping Time for 10 times
0.624 Secs
Current

Data
IEC Curve Selected Units
Entry
IEp Setting 0.10 Amps
TEp Setting 0.05 sec
Injected Current 10 4 times
Choose the Curve Normal Inverse
1
Current to be Injected 1 Amps
Calculated Tripping Time for 10 times
0.149 Secs
Current

You might also like