You are on page 1of 24

klima komore

sadrzaj:
1. OSNOVNE KARAKTERISTIKE KLIMA KOMORA …………………….......……..…………………………….. 2

2. KONSTRUKCIJA I SASTAVNI ELEMENTI …………………….......…………....................................……… 3

3. DIMENZIJE SA TABELOM VELI¸INA ¸EONOG PRESEKA …………………........….......………………… 10

4. KRITERIJUMI ZA IZBOR VELI¸INE KLIMA KOMORE I IZBORNI DIJAGRAMI ……………………....... 12

5. OZNA¸AVANJE I IZVEDBE KLIMA KOMORA …………………….......….......................................………………15

6. DU¤INE I TE¤INE KLIMA KOMORA ………….........................................................................…………… 18

7. POSEBNE IZVEDBE KLIMA KOMORA ……………………................................................………………… 20

8. AUTOMATSKO UPRAVLJANJE RADOM KLIMA KOMORA ……...................................................…...... 22

SOKO IN¤INJERING, Bulevar Arsenija ¸arnojevi¯a 125, 11070 Beograd, Srbija


tel/faks: +381 11 313 05 61, 313 06 51, 313 05 90 www.sokoing.co.yu e-mail: office@sokoing. co.yu
OSNOVNE KARAKTERISTIKE
KLIMA KOMORA

Široko podru÷je primene od 1.000 m³/h do 85.000 m³/h. Mogu¯nost izbora sistema za iskoriš¯enje toplote otpadnog
vazduha, bilo sa plo÷astim rekuperatorom ili sa dva glikolna
Izbor izme¨u 18 standardnih preseka u svim izvedbenim
izmenjiva÷a me¨usobno povezana cevnim krugom sa
varijantama, s obzirom na namenu, mesto ugradnje i na÷in
pumpom.
monta¦e.

Jednostavna monta¦a; lako me¨usobno povezivanje Visok stepen kvaliteta svih ugra¨enih elemenata sa
elemenata u celinu, prilagodljivost raspolo¦ivom prostoru, tehni÷kom podrškom i rezervnim delovima.
mogu¯nost unošenja sekcija u elementima, te monta¦a istih
na licu mesta (u slu÷aju uskih transportnih puteva). Mogu¯nost odabira optimalnog sistema, specijalne
konstrukcije i izvedbe prema zahtevima kupca.
Kvalitetno odra¨ena ku¯išta imaju ravne i glatke površine
i izbegnuti su svi oštri rubovi i uglovi. Rad klima komore sa varijabilnom koli÷inom vazduha, na
zahtev kupca, mogu¯ je upotrebom dvobrzinskih motora ili
Mala mogu¯nost pojave kondenzata na ku¯ištu zbog dobre
frekventnih inventera koji obezbe¨uju kontinualnu regulaciju
toplotne izolacije i zaptivanja ku¯išta.
koli÷ine vazduha.
Dugi vek trajanja zbog upotrebe ner¨aju¯ih materijala pri
izradi ku¯išta. Svi zaptivni materijali su otporni na starenje. Klima komoru je mogu¯e opremiti sa kompletnom
pripadaju¯om regulacijskom opremom potrebnom za
Jednostavno i lagano odr¦avanje i lagan pristup svim
automatski rad komore.
ugra¨enim elementima prilikom servisiranja i ÷iš¯enja komore.

2
Konstrukcija i sastavni elementi

POSTOLJE
Postolje klima komore je odgovaraju¯e nosivosti, ra¨eno
od profila od pocinkovanog lima dovoljne debljine.
Prilago¨eno je za postavljanje na gumene rebraste amortizere
debljine 40 mm, koji spre÷avaju prenos vibracija sa klima
komore na gra¨evinsku konstrukciju. Konstruktivno je
obezbe¨ena ugradnja sifona dovoljne visine.

okvir kucišta
Okvir ku¯išta klima komore je rastavljiva konstrukcija od
vu÷enih (oja÷anih) aluminijumskih profila i rogljeva od
aluminijumskog liva velike krutosti i specijalnog oblika, koji
imaju dopunsku antikorozivnu zaštitu.
Aluminijumski profili i rogljevi mogu biti u ÷etiri razli÷ite
veli÷ine, zavisno od veli÷ine i namene klima komore.
Posebnu varijantu ÷ine profili i rogljevi za klima komore u
higijenik izvedbi.

oplate
Oplate su u sendvi÷ izvedbi od spoljašnjeg i unutrašnjeg
pocinkovanog lima izme¨u kojih se nalazi toplotno i zvu÷no
izolacioni materijal. Na poseban zahtev oplate mogu biti
obojene u ¦eljenu boju.

Izolacioni materijal mo¦e biti:


- Poliuretanska dvokomponentna smeša gustine 40 kg/m³
u tri debljine;
- Mineralna vuna gustine 75 kg/m³ u dve debljine.
Oplate poda koje se rade sa mineralnom vunom prema
potrebi imaju dodatna oja÷anja radi bolje krutosti.

3
ZAPTIVANJE I VEZIVANJE OPLATA
Zaptivanje oplata se obezbe¨uje samolepljivom zaptivnom
trakom debljine 4 mm, a kod higijenik izvedbe sa gumenim
zaptivkama.

Vezivanje oplata

- Fiksne - neskidive oplate su u÷vrš¯ene zavrtnjima u


plasti÷noj ÷auri, u dovoljnom broju komada, da bi veze
izdržale nadpritisak koji vlada u delovima klima komore;
- Skidive oplate pri÷vrš¯ene su aluminijumskim bravicama
koje se montiraju na okvir ku¯išta;
- Oplate u varijanti vrata sa šarkama, kontrolnim staklom i
bravama koje omogu¯avaju dobro dihtovanje, rade se na
filterskim i ventilatorskim sekcijama.

MONTAZA
Laka ugradnja, montaža, odnosno demontaža pojedinih
funkcionalnih elemenata klima komore, postiže se
postavljanjem kliza÷a, nosa÷a i pregradnih elemenata u
ku¯ište, koji su od pocinkovanog lima, a koji ujedno služe
i kao usmeriva÷i vazduha kroz klima komoru.
Izolacioni
materijal

UNUTRAŠNJI SPOLJAŠNJI
Debljina

UNUTRAŠNJI K STANDARDNA
(mm)

POCINKOVANI POCINKOVANI
POCINKOVANI LIM (mm) (W/m2 OC) BOJA
LIM (mm) LIM (mm)

za unutrašnju ugradnju plastificirani RAL 9006


25 # 0.6 0.75
do 40.000 m³/h # 0.6 mm RAL 5012
POLIURETAN

za spoljašnju ugradnju plastificirani RAL 9006


40 # 0.6 0.5
do 40.000 m³/h # 0.6 RAL 5012
plastificirani RAL 9006
50 preko 40.000 m³/h # 0.6 0.4
# 0.6 RAL 5012
MINERALNA

plastificirani RAL 9006


40 do 40.000 m³/h # 0.8 0.81
#1 RAL 5012
VUNA

plastificirani RAL 9006


50 preko 40.000 m³/h # 0.8 0.66
#1 RAL 5012

4
IZMENJIVACI TOPLOTE

proracun i izbor
Prora÷un i izbor izmenjiva÷a toplote vrši se pomo¯u softverskog paketa GÜNTNER sa mogu¯noš¯u izbora termodinami÷kih
parametara medija, kao i same geometrije izmenjiva÷a, tako da budu maksimalno prilago¨eni zahtevima.

IZVEDBA
Standardna izvedba svih izmenjiva÷a koji se ugra¨uju u
klima komoru, bilo da su hladnjaci, ispariva÷i, toplovodni
greja÷i, parni greja÷i ili kondenzatori, je:

- bakarne cevi (10, 12 ili 16 mm) orebrene sa aluminijumskom


lamelom sa naj÷eš¯im korakom od 2 do 4 mm;

- ekspandiranjem bakarnih cevi omogu¯en je tesan kontakt


sa kragnom lamele, a time je postignuta i odli÷na
provodljivost;

- okviri izmenjiva÷a ra¨eni su od pocinkovanog lima;

- sabirne cevi izmenjiva÷a (greja÷a i hladnjaka) mogu da


budu od bakra ili od ÷elika. Priklju÷ci na izmenjiva÷ima do
pre÷nika od 2 cola su navojni (po JUS-u), a preko 2 cola su
prirubni÷ki;

- sabirne cevi ispariva÷a i kondenzatora su bakarne i uvek


na lemljenje;

- prodori cevnih priklju÷aka izmenjiva÷a toplote kroz ku¯ište


zaptiveni su rozetnama. Na odgovaraju¯im mestima na
izmenjiva÷ima nalaze se priklju÷ci za odzra÷ivanje i
pra¦njenje.

5
REKUPERATORI

U cilju uštede energije (zna÷ajno smanjenje potrebnog


kapaciteta za grejanje) koriste se rekuperatori toplote, ÷iji
je zadatak da toplotu otpadnog vazduha predaju sve¦em
vazduhu.

Mogu¯e su dve varijante rekuperatora:

1. Plo÷asti rekuperatori, koji se ra÷unaju i biraju po


softverskom paketu firme “HEATEX”, uzimaju¯i pri tome u
obzir stepen rekuperacije (do 75%) i raspolo¦ivi napor.
Ugra¨ena je i obilazna by-pass regulaciona ¦aluzina za
obezbe¨enje rekuperatora toplote od smrzavanja;

2. Varijanta sa sistemom cirkulacije mešavine vode i glikola


u zatvorenom krugu dva izmenjiva÷a toplote sa pumpom.

OTPADNI
VAZDUH

SVE¤
VAZDUH

REKUPERACIJA TOPLOTE SA
GLIKOLNIM IZMENJIVA¸IMA

ELIMINATORI KAPLJICA

Smešteni su na svim mestima gde treba spre÷iti prelaz


kapljica u susednu sekciju, a to mo¦e biti iza hladnjaka,
ovla¦iva÷a i plo÷astog rekuperatora.

Lamele su ra¨ene od pocinkovanog lima, koje se montiraju


u sklopu sa plasti÷nim odstojnicima.

Lako mogu da se izvuku iz ku¯išta.

6
VENTILATORI

Ventilatori u klima komorama su centrifugalni, radijalni, sa dvostranim usisom, firme “NICOTRA”, izabrani pomo¯u njihovog
softverskog paketa.

Za ukupne padove pritiska cca 800 Pa koriste se ventilatori sa unapred zakrivljenim lopaticama.

Za ukupne padove pritiska preko gore navedenih vrednosti koriste se ventilatori sa unazad zakrivljenim lopaticama.

KRITERIJUM ZA IZBOR
Osnovni kriterijum za izbor veli÷ine ventilatora je maksimalni stepen korisnosti u radnoj ta÷ki ventilatora, što zna÷i i najmanju
snagu elektromotora potrebnu za pogon ventilatora i najni¦i nivo buke.

Ventilator je zajedno sa elektromotorom, remenicama i


remen kaiševima, postavljen na zajedni÷ki nosa÷, koji je
preko antivibracionih amortizera oslonjen na ku¯ište komore.

Sa druge srane, potisna strana venilatora sa ku¯ištem je


povezana elasti÷nom vezom (plastificirano ceradno platno
sa prirubnicama od Al profila).

POGON VENTILATORA
Pogon ventilatora – osim ventilatora sa remenskim pogonom
koriste se i ventilatori sa direktno kuplovanim motorom i
slobodno rotiraju¯i ventilatori (ventilatori bez spiralnog
ku¯išta).

ELEKTROMOTORI
Elektromotori u klima komorama su trofazni asinhroni, oblika
B-3 sa zaštitom IP54. U skladu sa standardom JUS ISO 5291 za prenos snage
sa osovine motora na osovinu ventilatora koriste se:
Naj÷eš¯e koriš¯eni su ÷etvoropolni motori, a nešto re¨e
- klinaste dvodelne remenice (venac + elesti÷na ÷aura) sa
šestopolni i dvopolni, dok se u izuzetnim slu÷ajevima koriste
jednim, dva, tri ili ÷etiri ¦leba tipa SPZ, SPA, SPB, SPC;
osmopolni motori.
- klinasto remenje 10, 13, 17, 22 za profile remenice
Z, A, B, C.

7
FILTERI

Mogu¯nost jednog ili više stepeni filtracije, u zavisnosti od


objekta za koji se koriste klima komore.

Za svaku klima komoru preporu÷uje se ugradnja filtera


najmanje G3 klase.

Grubi filteri G3 i G4 mogu biti u varijantama cik-cak ili


vre¯asti.

Fini filteri klase F5 do F9 su vre¯asti filteri.

Od ostalih tipova mogu na zahtev da se ugrade:


- apsolutni filteri klase H10 do H13; Filter vre¯asti
- filteri sa patronama od aktivnog uglja za izdvajanje
štetnih plinova i mirisa;
- metalni filteri za izdvajanje masno¯a.

Usisna sekcija

DEMPERI

Okvir sa prirubnicama i lamele od aluminijuma.

Zakretanje lamela je veoma lagano, zahvaljuju¯i sistemu


zup÷anika izra¨enih brizganjem od ABS plastike, a ostvaruje
Demper se preko mesingane ÷etvrtke 12 x 12 mm.

Mogu¯nost izuzetno dobrog dihtovanja preko gumenih


profila.

Pogon dempera je ru÷ni (sa ru÷icama od Al liva) ili motorni.

Mogu¯nost lakog uspostavljanja spregnutog pogona kod


meša÷kih sekcija.

Meša÷ka sekcija

Elektri÷ni greja÷i

8
PRIGU Š IVACI ZVUKA

Kulise prigušiva÷a imaju okvir od pocinkovanog lima, unutar koga se nalaze plo÷e od mineralne vune koje su efikasni apsorpcioni
materijal. Spoljne površine plo÷a su zašti¯ene protiv otpadanja deli¯a.

Prigušiva÷ke kulise se kao kompaktna celina montiraju u klima komoru.

Naj÷eš¯i tip prigušiva÷a je sa debljinom kulise d = 100 mm i razmakom izme¨u kulisa s = 50 mm (33% slobodnog popre÷nog
preseka).

Standardne du¦ine kulisa, zavisno od ¦eljenog stepena prigušenja, su: 600 mm, 900 mm, 1200 mm i 1500 mm.

Spratna sekcija

Prigušiva÷ke kulise

9
K-80

2600
DIMENZIJE I OBLIK K-70

2400
K-60
CEONOG PRESEKA

2400
K-50

2000
Dimenzije ÷eonog preseka odre¨ene su koli÷inom vazduha K-40

1955
koju treba da obradi klima komora.
K-35

1955
Pri odre¨ivanju dimenzija uzete su u obzir maksimalne brzine
strujanja vazduha preko svetlog preseka klima komore, a K-30 3675

1955
3675
sve to u skladu sa uklapanjem sandardnih veli÷ina filtera.
K-25

1755
3080

K-20 3080

1555

10
2440
K-15

1355
2130
K-12

1335
1850
K-9 1850

1130
A1
1850
A
K-7

930
1640

K-5 1335

720
1250
K-4

720
1250
H2

1250
H1

720
K-3
H

K-2 1040

720
840
K-1

520
650
650
TABELA ZA VELICINE PO CEONOM PRESEKU KLIMA KOMORE
SVETLI PRESEK VELI¸INA I
DIMENZIJE ¸EONOG PRESEKA
IZMENJIVA¸A BROJ FILTERA
TIP
KOMORE
A A1 H H1 H2 L B

592 x 592
490 x 592
287 x 592

K-1 592 650 437 520 580 400 350 1


K-2 592 650 637 720 780 400 550 1
K-3 782 840 637 720 780 600 550 1 1
K-4 982 1040 637 720 780 800 550 2
K-5 1192 1250 637 720 800 1000 550 2

11
K-7 1192 1250 842 930 1010 1000 750 2 2
K-9 1192 1250 1042 1130 1210 1000 950 4
K - 12 1277 1335 1247 1335 1415 1050 1150 4 2
K - 15 1582 1640 1257 1355 1435 1370 1150 2 4
K - 20 1792 1850 1457 1555 1635 1550 1350 3 3 3
K - 25 1792 1850 1657 1755 1835 1550 1550 3 6
K - 30 1792 1850 1857 1955 2035 1550 1750 9
K - 35 2072 2130 1857 1955 2035 1800 1750 9 3
K - 40 2392 2440 1857 1955 2035 2100 1750 12
K - 50 2970 3080 1850 2000 2100 2700 1750 15
K - 60 2970 3080 2250 2400 2500 2700 2150 10 10
K - 70 3565 3675 2250 2400 2500 3300 2150 12 12
K - 80 3565 3675 2450 2600 2700 3300 2350 24
KRITERIJUMI ZA IZBOR
VELICINE I TIPA KLIMA KOMORE

Veli÷inu i tip klima komore odre¨uju dva nezavisna kriterijuma ili zadana podatka:

1. Koli÷ina vazduha, koju treba da obradi klima komora, odre¨uje dimenziju ÷eonog preseka klima komore;
2. Potrebne funkcijske jedinice klima komore tj. vrste obrade vazduha odre¨uju tip klima komore.

Pri izradi izbornih dijagrama, na osnovu koli÷ina vazduha koje treba da obradi klima komora, usvojene su slede¯e maksimalne
dozvoljene brzine strujanja vazduha preko svetlog preseka izmenjiva÷a i svetlog preseka klima komore (tj. na filterima):

brzina vazduha preko Brzina vazduha preko


svetlog preseka hladnjaka preseka grejaCa
To je najstro¦i kriterijum i maksimalna brzina iznosi do 3 m/s. Manje strog kriterijum brzine vazduha je usvojen za greja÷e i
Pri tome postoje dva slu÷aja: maksimalna brzina iznosi do 3,6 m/s. Ovaj kriterijum va¦i kada
klima komora u svom sastavu nama sekciju hladnjaka vazduha.
1. Za brzine vazduha do 2,4 m/s preko hladnjaka, u komoru
se ne ugra¨uju eliminatori kapljica;

2. Za brzine vazduha izme¨u 2,4 m/s i 3 m/s preko Brzina vazduha preko
hladnjaka, u komoru se ugra¨uje eliminator kapljica. svetlog preseka klima
komore
Brzina vazduha preko svetlog preseka klima komore tj. preko
filtera kre¯e se do 2,4 m/s. Ako klima komora u svom sastavu
uopšte nema izmenjiva÷e, tada na svetlom preseku klima
komore mo¦e da se ide brzinom maksimalno do 4 m/s.

Dijagrami za izbor veli÷ine klima komore dati su u dve varijante:

i varijanta
Dijagram izbora u zavisnosi od dozvoljene brzine na svetlim presecima izmenjiva÷a.

ii varijanta
Dijagram izbora u zavisnosi od dozvoljene brzine na svetlom preseku komore tj. na filterima.

12
I VARIJANTA

2 x log V

4.00

12
15
2
3
35
40
50
60
7
80

1
2
3
4
5
7
9
-

K-
K-
K-
K-
K-
K-
K-
K-
K-
K-
K 0
K-25
K- 0
K-
K-
K-
K-
K- 0

3.50
3.25

3.00

2.75

2.50

13
2.25

IZMENJIVA¸I
2.00

BRZINA VAZDUHA ( m/s )


1.75

1.50
0.5 0.75 1.0 1.5 2. 3. 4. 5. 6. 7. 8. 9. 10 15 20 30 40 50 60 70 80 90 100 110 log V
PROTOK VAZDUHA (m³/h) x 1000

0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 1.5 2 2.5 3 3.5 4 4.5 5 6 7 8 9 10 15 20 25 30
PROTOK VAZDUHA (m³/s)
II VARIJANTA

2 x log V

4.00

12
15
2
3
3
40
50
60
7
80

1
2
3
4
5
7
9

K-
K-
K-
K-
K-
K-
K-
K-
K-
K-
K- 0
K-25
K- 0
K- 5
K-
K-
K-
K- 0

3.50
3.25

3.00

2.75

2.50

14
FILTERI
2.25

2.00

BRZINA VAZDUHA ( m/s )


1.75

1.50
0.5 0.75 1.0 1.5 2. 3. 4. 5. 6. 7. 8. 9. 10 15 20 30 40 50 60 70 80 90100 110
log V
PROTOK VAZDUHA (m³/h) x 1000

0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.25 1.5 2 2.5 3 3.5 4 4.5 5 6 7 8 9 10 15 20 25 30
PROTOK VAZDUHA (m³/s)
Vrste obrade vazduha
Suština klimatizacionog sistema je u tome, da sa odgovaraju¯im protokom i kvalitetom vazduha (temperatura, vla¦nost, ÷isto¯a ... )
postigne u klimatizovanom prostoru ¦eljene parametre komfora. To se posti¦e kombinacijom osnovnih procesa obrade vazduha,
razli÷itih mogu¯nosti za vo¨enje vazduha i primenom razli÷itih sistema automatike.

Ventilacija Hla¨enje
odsisavanje vazduha Hladnjak sa hladnom vodom
ubacivanje vazduha Ispariva÷ - direktna ekspanzija
varijanta sa dva ventilatora za ubacivanje i Rekuperacija toplote
izvla÷enje vazduha sa meša÷kom sekcijom Plo÷asti rekuperator
Filtriranje Dva glikolna izmenjiva÷a u zatvorenom
sa jednim stepenom filtriranja krugu sa pumpom
sa dva stepena filtriranja Vla¦enje
Grejanje Parom - izotermsko vla¦enje
topla voda grejanje Adijabatsko vla¦enje
grejanje parom niskog pritiska
elektri÷ni greja÷i Odvla¦ivanje
gasni greja÷ Prigušivanje

Oznacavanje klima komora


K - - - X X * * * X - -

KLIMA KOMORA

Veli÷ina "K" po izbornom


1, ... ,80 dijagramu str.13
Strana L-leva
U - unutrašnja
poslu¦ivanja D-desna
V - vanjska ugradnja
Hg - higijenik Izvedba obzirom
B na mesto monta¦e Varijanta Pl - poliuretan
- bazenska
oplate Mv - mineralna vuna
K - krovna
H - horizontalna
S - spratna Izvedba obzirom
Vr - vertikalna na na÷in monta¦e
P - paralelna
1..... 14 za H Broj podgrupe koji najpribli¦nije
1..... 10 za S definiše tra¦enu "K" - str.16 i 17

Funkcijske jedinice koje sa÷injavaju klima komoru


po redosledu u smeru strujanja vazduha

VR - Ventilatorska sekcija remeni pogon PG - Predgreja÷ FK - Filter kasetni


VD - Ventilatorska sekcija direktan pogon GW - Greja÷ toplovodni FV - Filter vre¯asti
VS - Ventilatorska sekcija GP - Greja÷ parni FA - Filter apsolutni
- slobodno rotiraju¯i ventilator GE FAU
- Greja÷ elektri÷ni - Filter sa aktivnim ugljem
FVz - Fleksibilna veza
GPL - Greja÷ gasni RG - Rekuperator lamelni - greja÷
U - Usisna sekcija sa jednim demperom
GK - Greja÷ kondenzator RH - Rekuperator lamelni - hladnjak
M - Meša÷ka sekcija sa dva dempera
HLW - Hladnjak - voda RPD - Rekuperator plo÷asti - dijagonalni
MD - Meša÷ka sekcija sa tri dempera
HLI - Hladnjak - ispariva÷ RPDB - Rekuperator plo÷asti - dijagonalni sa
UM - Sekcija za umirenje vazduha - "by-pass" – om
KO - Sekcija sa kompresorom
I - Izlazna sekcija
EK - Eliminator kapljica
PZ - Prigušiva÷ zvuka
OP - Ovla¦iva÷ parni
OA - Ovla¦iva÷ adijabatski
OK - Ovla¦iva÷ kontaktni
P rim e r o z na k e :
K15 – U – H 12 – F V z ; V R ; MD; F V; G W; H L I ; E K ; OP ; VR ; F Vz – P l-L

15
Klima komore u horizontalnoj izvedbi su predstavljene sa 14 podgrupa, podeljenih na osnovu sastava
funkcionalnih celina koje sadr¦i.

H1 H2

592
592
H3 H4
592

592
592

592
H5 H6
592

592
592

592
H7 H8
592

592
592

592
H9 H10
592

592
592

592
592

H11
592

592

H12
592
592

H13
592

592

H14
592

16
Klima komore u spratnoj izvedbi su predstavljene sa 10 podgrupa, podeljenih na osnovu sastava
funkcionalnih celina koje sadr¦i.

592
592
S1 S3

592

592
592

592
S2 S4

592
592
592

592
592

592

S5 S6
592

592
592

592
592

592
592

592

S7 S8
592
592

592
592

S9
287
490

P
592

287
490
592

S10

17
FUNKCIJSKE JEDINICE I NJIHOVE DUZINE

Za definisanje dužina jedinica odre¨en je modul M = 325 mm, ÷ijim umnožavanjem i dodatkom za konstrukciju može da se odredi
kona÷na dužina. Prema tome dužina jedinice iznosi: L = n x 325 + K.
Dužine pojedinih jedinica su fiksne, dok dužine drugih jedinica zavise od veli÷ine klima komore, što se vidi iz grafi÷kog prikaza
koji sledi:

GW/GP/GE/PG RG HLW/ HLI/ RH FK FV(G4) / FA FV(F7) / FAU


+EK

M 2M 2M M 1,5M 2M

VR PZ

K-1 do K-4 n=2.5


K-5 n=3
K-7 n=3.5 Prigušenje 15 dB n=2
K-9, K-12 n=4 Prigušenje 18 dB n=3
K-15 n=4.5 Prigušenje 22 dB n=4
K-20, K-25 n=5 Prigušenje 26 dB n=5
K-30, K-35 n=6
K-40, K-50 n=6.5
K-60 do K-80 n=7.5

nxM nxM

M MD
U

K-1 n=1 K-1 n=2


K-2 do K-5 n=1.5 K-2, K-3 n=2.5
K-7 do K-9 n=2 K-4, K-5 n=3
K-12, K-15 n=2.5 K-7, K-9 n=3.5
K-20, K-25 n=3 K-12 n=4
K-30 do K-40 n=3.5 K-15 n=4.5
K-50 n=3.5 K-20, K-25 n=5
K-60, K-70 n=4 K-30 do K-40 n=6
K-80 n=4.5 K-50 n=6.5
K-60, K-70 n=7.5
nxM K-80 n=8.5
M nxM

UM OP/OA
DEMPER PRIRUBNICA

K-1 do K-4 n=1


K-5 do K-9 n=1.5
K-12 do K-40 n=2
K-50, K-60 n=2.5
K-70, K-80 n=3

125 32
nxM 3.5 M

RDP RDPB

K-1 n=2
K-2, K-3 n=2.5
K-4, K-5 n=3
K-7, K-9 n=3.5
K-12 n=4
K-15 n=4.5
K-20 do K-50 n=5
K-60, K-70 n=6.5
K-80 n=8.5

nxM
nxM

18
duzine i tezine klima komora
DUŽINE I TEŽINE FUNKCIJSKIH JEDINICA

GW / GP/
HLW / HLI / RG FK FV(G4) / FA FV(F7) / FAU U M MD UM VR OP / OA RDP
GE / PG

L G L G L G L G L G L G L G L G L G L G L G L G

TIP KOMORE
(mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg) (mm) (kg)

K-1 325 22 650 47 325 18 490 19 650 25 325 16 400 22 700 41 325 13 840 46 1250 54 700 35
K-2 325 25 650 55 325 24 490 25 650 32 325 17 500 30 840 57 325 14 840 62 1250 61 840 52
K-3 325 28 650 62 325 29 490 31 650 40 325 20 500 35 840 66 325 16 840 75 1250 70 840 73
K-4 325 31 650 69 325 32 490 34 650 44 325 22 500 39 1040 74 325 17 840 83 1250 76 1040 90
K-5 325 36 650 81 325 37 490 39 650 51 325 24 500 42 1040 77 490 27 1040 123 1250 84 1040 100
K-7 325 46 650 104 325 42 490 44 650 57 325 31 700 66 1250 125 490 33 1250 153 1250 105 1250 140
K-9 325 52 650 121 325 49 490 52 650 68 325 35 700 73 1250 138 490 36 1400 210 1250 113 1250 161
K-12 325 62 650 144 325 56 490 58 650 75 325 39 900 102 1400 194 650 52 1400 272 1250 130 1400 192

19
K-15 325 74 650 171 325 62 490 64 650 84 325 43 900 115 1640 218 650 56 1640 353 1250 145 1640 240
K-20 325 97 650 230 325 72 490 75 650 98 325 52 1100 155 1850 294 650 64 1850 453 1250 171 1850 338
K-25 325 112 650 253 325 85 490 88 650 115 325 58 1100 177 1850 336 650 73 1850 615 1250 192 1850 490
K-30 325 127 650 290 325 95 490 98 650 129 325 65 1200 211 2130 390 650 84 2130 750 1250 215 1850 578
K-35 325 144 650 320 325 99 490 103 650 134 325 70 1200 227 2130 431 650 89.4 2130 1030 1250 229 1850 681
K-40 325 159 650 357 325 111 490 115 650 149 325 75 1200 245 2130 465 650 97 2350 1135 1250 247 1850 734
K-50 325 195 650 437 325 122 490 126 650 165 325 86 1300 319 2350 165 840 157 2350 1350 1250 299 1850 932
K-60 325 227 650 510 325 136 490 140 650 182 325 97 1500 398 2600 182 840 172 2600 1600 1250 331 2350 1215
K-70 325 265 650 600 325 154 490 158 650 206 325 128 1500 446 2600 206 1040 232 2600 1750 1250 388 2350 1450
K-80 325 290 650 660 325 172 490 176 650 230 325 140 1700 540 2950 230 1040 250 2600 1900 1250 436 2950 1930

Za sve veli÷ine klima komora postoje tri razli÷ite dužine sekcije prigušiva÷a zvuka zavisno od stepena prigušivanja pri 250 Hz:

D (dB) 15 18 22 26
L (mm) 700 1040 1400 1640
POSEBNE IZVEDBE KLIMA KOMORA

592

Potis - ubacivanje
Svež vazduh

592

592

Odsis - izvla÷enje
Otpadni vazduh

592
bazenske klima komore

1. KLIMA KOMORE ZA BAZENSKE PROSTORE

Ove klima komore se koriste za obradu vazduha u pokrivenim Kompletna klima komora i svi njeni sastavni elementi
pliva÷kim bazenima, gde je osim pripreme vode, najva¦nije (ventilatori, izmenjiva÷i, nosa÷i...) zašti¯eni su epoksidnim
odr¦avanje klimatskih uslova, koji ¯e kupa÷ima pru¦iti što bojama, što omogu¯uje dug vek trajanja ure¨aja.
je mogu¯i ve¯i ugo¨aj tokom cele godine, i ujedno zaštititi
konstrukciju bazenskog prostora od ubrzanog propadanja.
Klima komora se radi kao jedna celina, opremljena sa svom
pripadaju¯om regulacijskom opremom potrebnom za
automatski rad, kao i sa elektro ormanom u svom sastavu.
Zadatak je odr¦avanje slede¯ih parametara vazduha:
- temperatura vazduha 30OC, pri temperaturi vode u bazenu
od 28OC; Rad celokupnog sistema je potpuno automatski i upravljan
- maksimalna relativna vla¦nost 55% - 60%. je sa mikroprocesorom – PXC52 ''SIEMENS'' ÷iji su kriterijumi
vo¨enja klima komore maksimalni konfor uz maksimalnu
uštedu energije.

U klima komoru su ugra¨eni svi potrebni elementi za


ventilaciju, grejanje, hla¨enje i odvla¦ivanje, koriste¯i pri Mikroprocesor ima mogu¯nost povezivanja na centralni
tome rekuperaciju toplote. sistem nadzora i upravljanja.

20
2. Krovne klima komore

Varijante ovih klima komora se koriste kod objekata koji Konstruktivno su izvedene tako da su otporne na atmosferske
imaju male raspolo¦ive unutrašnje prostore, a imaju uticaje.
mogu¯nost iskoriš¯enja prostora na krovovima.
Montiraju se na pripremljene temelje, koji obezbe¨uju dobro
zaptivanje i slivanje vode sa komore.
Prednost ovih klima komora je u direktnoj vezi sa razvodom
vazduha u spuštenom plafonu, što zna÷i znatno kra¯i put Posebnu varijantu ÷ine paketne klima komore sa direktnom
kanala na objektu. ekspanzijom, ÷ija je prednost u tome što nema rada na
freonskim instalacijama na terenu.

ventilaciona - krovna - komora

Detalj postavljanja
na temelje

krovna komora
287
490

krovna klima komora - direktna ekspanzija - kompaktna celina


287
490

21
AUTOMATSKO UPRAVLJANJE
RADOM KLIMA KOMORA

Naše klima komore nudimo sa kompletnom automatikom za vo¨enje sistema prema odgovaraju¯oj aplikacionoj šemi
za dati sistem.

Mogu¯nost prilago¨avanja zahtevima objekta pomo¯u velikog izbora aplikacionih šema od kojih je predstavljen manji broj.

T (±
M 5K)
T

T
M

T
T
p

M M 100 % sve¦ vazduh


Hla¨enje sa hladnom vodom
Toplovodno grejanje

T
M
M
Mešanje sve¦eg i opticajnog vazduha
M
T
Hla¨enje sa hladnom vodom
Elektri÷ni greja÷ - jedan ili više stepeni
T T
p

T
M

T
M
T

T T
p p

100 % sve¦ vazduh


M * *
Hla¨enje direktna ekspanzija - jedan ili više stepeni
Toplovodno grejanje

T
M
M
T
M

T T
p p

M M
* *
Mešanje sve¦eg i opticajnog vazduha
Hla¨enje direktna ekspanzija - jedan ili više stepeni
Toplovodno grejanje - predgreja÷ i greja÷

22
T
M
M
Mešanje sve¦eg i opticajnog vazduha
M
T Hla¨enje sa hladnom vodom
Toplovodno grejanje
T T Vla¦enje adijabatsko ili izotermsko
p
M

M M

M
T
T 100 % sve¦ vazduh
p
Hla¨enje sa hladnom vodom
Toplovodno grejanje
M
Rekuperator sa glikolnim
M T izmenjiva÷ima u zatvorenom krugu

T T
T
p p

M M

f p
1f
2
~

M T p T
p
f
T 1f T
M 2
~

T T p
p p

M M 100 % sve¦ vazduh


Hla¨enje sa hladnom vodom
Toplovodno grejanje
Plo÷asti rekuperator

Odabrana aplikacija omogucava:


Regulaciju temperature i vla¦nosti klimatizovanog prostora
sa ograni÷enjem maksimalne i minimalne temperature (senzori
temperature i vlage - prostorni, kanalski);
Kontrolu dempera (sve¦eg i recirkulacionog vazduha pomo¯u Zaštitne funkcije:
pokreta÷a dempera) sa opcijama "Free cooling" i "Free
heating"; Nadzor potisnog i odsisnog ventilatora sa diferencijalnim
Ventilator odsisa i potisa sa dvobrzinskim motorom, ili presostatom;
frekventnom regulacijom broja obrtaja;
Nadzor filtera sa diferencijalnim presostatom;
Vodeni greja÷ ili elektri÷ni greja÷ sa kontrolom predgrevanja;
Regulaciju ventila hladnjaka, greja÷a i rekuperatora; Zaštita od smrzavanja:
Regulaciju pumpe hladnjaka, greja÷a i rekuperatora; - toplovodnog greja÷a (sa mraz termostatom postavljenim
Hla¨enje sa direktnom ekspanzijom: višestepena regulacija u struji vazduha),
kompresora, regulacija ventilatora kondenzatora i elektronski - plo÷astog rekuperatora sa "by pass" ¦aluzinama;
termoekspanzioni ventili;
Preoptere¯enje elekri÷nog greja÷a.
Adijabatsko / izotermsko vla¦enje sa ON/OFF ili kontinualnom
regulacijom.

23
Krug automatike se sastoji od mikroprocesora, tj. slobodno
programabilnog kontrolera, sa svojim korisni÷kim
aplikacionim softverom i korisni÷kim interfejsom, uz
odgovaraju¯i broj ulazno-izlaznih signala preko kojih se
usaglašavaju sve funkcije klima komore, sa mogu¯noš¯u
komunikacije i povezivanja na centralni sistem nadzora i
upravljanja.

Izbor proizvo¨a÷a automatike zavisi od kupca naše opreme


i od uklapanja sa ostalom automatikom na objektu.

CAREL - programabilni kontroleri serije pCO prilago¨eni


za slo¦ene aplikacije klimatizacionih sistema u varijantama
pCO², pCOXS.

humiFog
gaSteam
humuSteam
heaterSteam
Sonda temperature
sve¦eg vazduha
Diferencijalni
presostat CAREL ovla¦iva÷i

Sonda temperature
ubacnog vazduha

Pokreta÷ dempera Pokreta÷ trokrakog


sve¦eg vazduha ventila greja÷a/hladnjaka
Programabilni pCOXS
kontroler

FENIKS - programabilni kontroleri serije MR 5000 u


varijantama MR 5100, MR 5200, MR 5300, MR 5500.

SIEMENS - programabilni kontroleri serije Synco u


varijantama SyncoTM 100, SyncoTM 200, SyncoTM 700.
SyncoTM700

SyncoTM100 SyncoTM200

24

You might also like