BUILDING CONSTRUCTION
INTRODUCTION
Buildings may collapse for a variety of reasons including stress, poor construction,
or deterioration. Firefighters should be aware of the potential and imminent
indicators of building collapse. They should be able to inspect a building and
identify those indicators which may lead to building collapse, both under normal
conditions and during fire suppression operations. These indicators, in some cases,
may be avoided or alleviated. Firefighters must know what to do under these
circumstances and when it is no longer safe to remain in, on, or near the building.
An example might include the steady build-up of the water level when fighting an
internal structure fire. It may be possible to reduce the amount of water on the floor
by either knocking out the lower windows at floor level or by drilling holes in the
floor.
9-1
Section 9 - Building Construction
OBJECTIVES
• Identify the five major types of building construction and the collapse
hazards of each.
• Identify the structural features which may influence fire spread and
safety, which would include:
9-2
Section 9 - Building Construction
TERMINOLOGY
9-3
Section 9 - Building Construction
Bearing Wall: A bearing wall is capable of supporting a vertical load, such as a floor
or a roof, in addition to its own weight.
Exterior Wall: An exterior wall separates the interior from the exterior of a building.
Such a wall is usually exposed to the outside, though not always. It forms the extent
or boundary of the building.
Interior Wall: This wall will be wholly within a building and will not be exposed
to weather.
Party Wall: A party wall usually separates two buildings of distinct ownership and
lies on the lot dividing line between the two properties. This wall can be either
bearing or non-bearing.
Fire Wall: This type of wall is erected to prevent the spread of fire. It must have
sufficient fire resistance to withstand the effects of the most severe fire that could
occur in the building. As well, it must provide a complete barrier to the spread of
fire. Any openings in this type of wall must be properly protected.
One-Hour Wall: This is a term often used in the fire service. There are 83 different
ways to construct a typical one-hour wall as described in Chapter 43, Table 43-A, of
the Uniform Building Code. A typical one-hour wall will be non-bearing and will
consist of either:
• 2"x4" wood studs, 16 inches centered, with both sides covered by one
layer of 5/8" type “X” gypsum wallboard.
• 3 1/4" “Tin Can” metal studs, 24 inches centered, with both sides
covered by one layer of 5/8" type “X” gypsum.
Partition: This is an interior wall, one story or less in height, which separates two
areas. A partition can be either bearing or non-bearing.
Fire Partition: This is a partition that will inhibit the spread of fire but does not
qualify as a fire wall.
Curtain Wall: A curtain wall is an exterior, non-bearing wall more than one story
in height. It is usually supported by the structural frame.
Panel Wall: This is an exterior wall one story in height. In a multistory building,
panel walls must be supported at each floor level.
9-4
Section 9 - Building Construction
Parapet Wall: This is defined as the portion of wall that extends above the roof of
a building.
Shear Wall: This type of wall is erected to assist in resisting the force of wind. It is
built within the building and usually is part of some required enclosure, such as an
elevator or stair shaft. This is a bearing wall.
9-5
Section 9 - Building Construction
Strengths: Ridge board, rafters (if 2x6 inches or larger) and the area where rafters
cross the outside walls.
Hazards: Older gables may use 2x4 inch rafters. Newer roofs use 3/8 or 1/2 inch
plywood as a decking instead of 1x4 inch or 1x6 inch stripping. Plywood will burn
and fail at a faster rate, offers little resistance to fire, and is difficult to remove for
ventilation purposes.
9-6
Section 9 - Building Construction
Description: Similar to gable roof, but no “A” frame configuration. Ends of roof
terminate in “hip” configuration. Conventional or ordinary construction consists of
ridge pole (board), hip rafters from the ridge pole down to and across the corners
at the outside walls. Valley rafters are utilized where two roof lines are joined
together. Ridge and rafters are usually 2x6 inches or larger. Rafters are usually 16
to 24 inches “on center”. Various degrees of pitch are utilized.
HIP ROOF
Strengths: Ridge pole, valley rafters, hip rafters, and the area where rafters cross the
outside walls.
Hazards: Similar to gable roofs, utilization of 2x4 inch rafters and 3/8 or 1/2 inch
plywood as a decking. Roofs with a steep pitch will require roof ladders to conduct
ventilation operations. If the roof is finished with tile, it becomes slippery when wet
and offers little footing when dry.
9-7
Section 9 - Building Construction
CORRUGATED ROOF
Strengths: Ridge and area where roof crosses the outside bearing walls.
9-8
Section 9 - Building Construction
Hazards: Difficult to penetrate with chain-saw or rotary saw with a masonry blade.
Use a rotary saw with carbide-tipped wood blade to cut ventilation holes.
9-9
Section 9 - Building Construction
SAWTOOTH ROOF
Strengths: Substructure constructed from adequate (2x8 inch, 2x10 inch, etc.)
lumber. Easy to ventilate-open the hinged panes of glass. Consider the area where
rafters cross or are tied into the vertical walls as strong areas.
Hazards: Newer sawtooth roofs are covered with 1/2 inch plywood. Plywood
decking provides little resistance to fire.
9 - 10
Section 9 - Building Construction
Description: Wooden truss members constructed from 2x12 inch lumber with
sloping ends. Usually a heavy grade of construction. Metal tie rods may be used
vertically for additional support. Joists are 2x6 inch and 2x8 inch and covered with
1x6 inch sheathing and composition roofing material.
Hazards: Dependent on the size of lumber utilized and span of trusses. Trusses are
in “tension” and “compression” and will fail under severe fire conditions. If metal
tie rods are used, early failure of rods will affect the stability of the trusses.
9 - 11
Section 9 - Building Construction
walls. Tie rods may pass through the exterior wall to an outside plate facilitating
identification. Tension is maintained by turnbuckles. Top chords or arch members
may utilize laminated 2x12’s or larger. 2x10 inch rafters are covered by 1x6 inch
sheathing and composition roofing material.
Strengths: This roof utilizes a good size of lumber and 1x6 inch sheathing as the roof
decking. Consider the perimeter of the building and the bowstring arch members
as strong areas.
Hazards: The main hazard is early failure of metal tie rods and turnbuckles. Tie
rods (tension) provide lateral support to the walls and keep the arches (compres-
sion) from pushing the exterior walls outward, and prevent collapse of the building.
9 - 12
Section 9 - Building Construction
Description: Usually large size (2x12, 2x14 inch) of wooden members utilized to
construct truss arch. Some arches have multiple laminated beams to form one arch.
Rafters (2x10 inch or larger) are covered with 1x6 inch sheathing and composition
roofing material.
Strengths: Most roofs of this type are well-constructed. Consider the perimeter of
the building and the trussed arch members as strong areas.
Hazards: Determined by size of lumber and span of arches. Most roofs of this type
are well-constructed.
9 - 13
Section 9 - Building Construction
Hazards: Possible total roof collapse if fire removes more than 20% of roof structure.
Collapse may occur from the “domino effect.”
9 - 14
Section 9 - Building Construction
Description: Wood joists (or rafters) of various sizes laid across the outside walls
or outside walls to interior walls or structural supports. Joists may also be
suspended by metal hangers. Joists are covered with 1x6 inch sheathing or plywood
and composition roofing material. Very common roof.
Strengths: Dependent on the size of the joists and type of decking utilized.
Consider the perimeter of the building as a strong area.
Hazards: Degree of hazard presented by joist is based on span, size of joist, “on-
center spacing,” and if the joist is suspended by metal hangers. Roofs covered with
plywood instead of sheathing present a problem. Plywood may be found in 3/8 to
5
/8 inch thickness. Plywood offers little structural integrity under fire conditions
and is difficult to remove for ventilation purposes. Also, plywood may be burned
out from the underside and not show signs of weakness from the top of the roof.
9 - 15
Section 9 - Building Construction
Shake shingles: (Wood and Composite) Wood shingles or shakes are split pieces
of red cedar wood used for roofing or siding. They are usually attached to 1x6 inch
skip sheeting. Newer wooden shakes are now treated with fire retardent. Compos-
ite or shake substitutes are made to simulate wood shake shingles, but in fact are
made of a variety of non-combustible materials.
Hazards: Wood shakes are combustible. Skip sheeting offers little support when
weighted.
Strengths: Walking on the rafters, valley rafters or ridgepole offers the best support.
Heavy felt: This is asphalt-impregnated felt which comes in rolls. A hot mop
procedure of tar is placed over plywood and the felt rolled over it. This material is
used predominately on flat roofs.
Hazards: This material will melt and burn. Since this is typically used on flat roofs,
firefighters will encounter lightweight construction methods on more recent homes.
Under heavy fire conditions, this type of roof can fail quickly.
Tile: These can be made from a variety of materials. They consist of:
• Slate
• Clay
• Concrete
• Lightweight concrete
The last three can be either Spanish style or flat style. Tile roofs are heavy and
usually supported by metal gusset plate trusses. The tiles are nailed to plywood
and are easily removed by hand.
9 - 16
Section 9 - Building Construction
Strengths: The overlap area offers most support. The tiles are non-combustible.
Hazards: Stability of roof is masked. Tiles can be extremely slippery when wet.
When ventilating, tiles must be removed and can slide off the roof and cause injury.
Ridge caps must be removed before a roof ladder can safely be hooked over the
ridge board. If trusses are exposed to fire the roof will collapse rapidly.
Steel roofing can be installed directly over an existing wood shake roof. This makes
it easy and less expensive to install. The panels are placed on a 2' x 2' batten and 1' x 4'
counterbatten grid system. To strengthen the roof, the panels are staggered like
brick work and nailed horizontally. One indication of this type of roofing is the
oversized metal trim, of 4' to 6', found on the fascia boards and the end caps. Another
indication is the steel roofing panels will not break when struck by a sledge or axe.
Sounding and/or walking on the roof should be done at the bottom of the panels
where the battens are located. Avoid areas that feel hot and sticky underfoot.
For more information review training video entitled "Stone-Coated Steel Roofs",
available at video library at headquarters.
Strengths: Strongest part of roof is at the bottom of the panels where the battens are
located. Panels are non-combustible.
Hazards: Two problems have surfaced in four Southern California cities when
fighting fires in structures with steel roofs. The first problem is rapid and undetec-
ted fire spread under the new roof. The method of applying steel roofs over existing
combustible roofs creates a space (approximately 4") between the old and the new
roof. This 4 inches of hidden space provides an avenue for the fire to spread rapidly
and to move undetected through the entire length of the roof. Once the original,
combustible roof is burning, the entire new roof must be removed to ensure
complete extinguishment.
9 - 17
Section 9 - Building Construction
Lightweight building and roof construction is currently very popular with archi-
tects and building contractors across the country. Considering the present cost of
labor, equipment, and building materials, it is not economically feasible to con-
struct buildings the same as 50 years ago. Ease of installation and utilization of
lightweight building materials have become the standard during the last 25 years.
Heavy timber, laminated beams, and 1x6 inch sheeting have been replaced by 2x4’s
and 1/2 inch plywood regardless of building size. New style buildings with their
characteristic concrete tilt-up walls, false fascias, and flat roofs are other indications
that lightweight construction may be present. As a result of architects' reducing the
size of what there is to burn, today’s fire departments are losing one of their most
valuable fireground factors-TIME.
This section will focus on the five major types of lightweight roof construction:
1. Panelized
2. Metal gusset plate trusses
3. Open web construction
4. Wooden “I” beams
5. Steel roofing
NOTE: This type of construction may also be utilized in floors , walls, etc.
9 - 18
Section 9 - Building Construction
1. Laminated beams
2. Purlins
3. 2x4 inch joists
1
4. /2 or 5/8 inch plywood decking
Panelized roofs do not have a space between the ceiling and underside of the roof
occupied by the familiar trussed joist construction. The roof is usually constructed
by laminating beams of various sizes (6x36 inches are common). The beams are
supported at their ends by pilaster or posts and additional posts may be supporting
the beam along the span. The beams will be spaced from 12 to 40 feet apart and may
be bolted together to create lengths well in excess of 100 feet.
Wooden purlins are installed with metal hangers on 8 foot centers. The common
size of a purlin is 4x12 inches with the length depending on the spacing between
beams. Joists measuring 2x4 inches x 8 feet are installed with metal hangers on 2 foot
centers between the purlins and run parallel to the beams.Sheets of plywood (4 x 8 feet
1
x /2 inch) are nailed over this framework. The plywood is then covered with
composition roofing material. A three-layer insulation paper is stapled to the
underside of the roof between the beams and purlins. This paper offers little
protection to the 2x4 inch joists and 1/2 inch sheets of plywood. Insulation paper
consists of tar- impregnated kraft paper covered on either side by thin aluminum
foil.
Strengths: The strengths of this roof are beams, purlins, perimeter of building
(where roof ties into the exterior walls).
Hazards: Span supports for beams of 4 inch hollow steel pipe may be found. Expect
weakening and/or collapse of these supports with failure of large portions of the
roof under heavy fire conditions. When the insulation paper is subjected to fire, the
foil will peel away from the middle layer of tar-impregnated paper. This paper will
then begin to give off flammable gases which build up between the insulation paper
and plywood decking.
When ignition temperature is reached, the gases will flash resulting in heavy char
to the wood and burning insulation dropping to the floor below. Fire is then able
to expose the 2x4 inch joists and 1/2 inch plywood decking which offer little
resistance to fire.
When walking across a panelized roof, utilize the beams or purlins. Any other
section of this roof is comprised of 2x4’s and 1/2 inch plywood which will rapidly
fail when exposed to fire.
9 - 19
Section 9 - Building Construction
Utilizing 2x4’s, spans of up to 55 feet will be found. A point of interest with this
type of construction (also open web construction and wooden “I” beams) is the
9 - 20
Section 9 - Building Construction
fact that trusses are supported at their outside edges only (unless used as a
cantilever truss). Interior partition walls do not support the truss at any point along
the bottom chord. Eighteen gauge “roof truss clips” may be found at various
chords. These clips are nailed to the bottom chord and to the top plate of the interior
wall. Roof truss clips provide some lateral stability for partition walls. In this
configuration, interior partition walls could be classified as “free standing.”
Common on-center spacing for this construction is 2 feet and may be covered with
1
/2 inch plywood. Used in floor and roof systems.
Strengths: Consider the area where the trusses cross or are tied into the outside
bearing walls as strong areas.
Hazards: Extensive use of 2x4 inch trusses with metal gusset plate connectors
equals short burning time and early failure and collapse. These trusses are under
tension and compression and, when the bottom chord or webbing fails, either from
connector plates that have pulled out or from deep char, the truss will fail. When
the metal connector plates and surrounding wood are exposed to fire, the plates will
fail in a short period of time by pulling out of the wood. The bottom chord of the
truss has replaced the 2x6 inch or larger ceiling joist of conventional construction.
Coupled with the fact that these bottom chords do not rest on the interior walls
which offer additional support, expect total collapse of portions or the entire roof
in a short period of time. As in other truss-type construction, depth of cuts for
ventilation purposes are critical.
An additional hazard is identification of the construction of the roof you are about
to ventilate. A simple flat roof may be constructed from different types of joists or
trusses, yet there is a wide range of strength factors inherent in different types of
construction.
9 - 21
Section 9 - Building Construction
Description: Open web construction consists of bottom and top parallel wooden
supporting beams called chords which are cross-connected by steel tube web
members. The top chord (supported) and under-load offer a bridging effect causing
the top chord member to be in compression and the bottom chord member
(unsupported) to be in tension. Open web construction is prefabricated at the
factory before installation with either parallel chords laid on edge or with flat-laid
chords. The steel tube web members are prefabricated from 1 to 2 inch cold rolled
steel tubing with the ends pressed flat into a semicircular shape and a hole punched
through each end. These flattened ends are then inserted into slots in the chords.
Steel pins (up to 1 inch) are then driven through the flat ends of the web members
completing the assembly. When the prefabricated joists are installed, top chord
members are secured to the top of bearing walls with bottom chord members
remaining unsupported away from the wall. Spans to 70 feet are possible using a
single 2x4 or two 2x3’s as top and bottom chord members. 2x4’s exceeding lengths
of 20 feet are made possible by joining different lengths of 2x4’s in a glued mitered
“finger joint”. Normal on-center spacing is 2 feet. Used in floor and roof systems.
Strengths: Consider the perimeter of the building where the roof ties into the
exterior wall as a strong area.
Hazards: The hazards of this roof are many. Basically, this roof is constructed of
2x4’s or 2x3’s under tension and compression and 1/2 inch plywood decking. These
components offer minimum resistance to fire. Some construction leaves the chords
exposed to the interior of the structure which increases the exposure hazard and
allows larger areas of the roof to be exposed to fire. Expect to find a lack of fire stops
in this construction. Due to the size of the lumber and chord members in tension and
compression, expect rapid failure of this construction. When 2x4’s are laid flat as
chords (1 1/2 inch thick) with 1/2 inch plywood decking, firefighters only have to cut
2 inches deep (when cutting for ventilation purposes) to cut through the chord
members. This may cause partial roof failure of the area supported by the severed
chords.
9 - 22
Section 9 - Building Construction
Shown are typical bearing conditions one might encounter with truss construction.
Note how some extend well past the bearing wall. If a fire were to burn through the
truss on the inside, the remainder of the truss could topple over. Beware of this
situation!
Truss joists are lighter in weight than most other systems. This feature cuts erection
costs, speeds construction and makes possible the use of less costly footings,
foundations and bearing walls. For these reasons truss construction is very popular
in commercial areas. A truss may span up to 25 feet in most floor systems and up
to 40 feet in many roofs. Multiple spans are possible up to 70 feet total length.
1. Top chord
2. Bottom chord
3
3. /8 inch plywood stem
The stem is joined to the top and bottom chords by a continuous glued edge joint.
Two by fours are used as chords, but 2x3 inch chords are very common. Some chords
may resemble plywood because of laminations. However, the laminations (trade
name of Micro Lam) or veneers run horizontally in the chords. Micro Lam differs
from plywood where every other veneer is 90O to the preceding veneer. The Micro
Lam veneers are stronger than solid sawn lumber. In the 2x3 inch configuration,
spans of up to 40 feet will be found. Until adequately braced and the plywood
9 - 23
Section 9 - Building Construction
Strengths: Consider the perimeter of the building where the roof ties into the
exterior walls as a strong area.
Hazards: What there is to burn consists of a 3/8 inch plywood stem and 2x3 or 2x4
inch chords. It will take little time for the 3/8 inch plywood to burn, weaken and
cause collapse of the chords and the roof. Buildings will be found with open and
unprotected chords. Common practice is to run heating and air conditioning
ducting of various sizes through the stems which removes a good percentage of the
stem and gives fire horizontal access to adjacent “I” beams. As with other
lightweight roofs, depth of cuts for ventilation purposes is critical.
block, non-bearing exterior walls; the concrete block bearing walls supporting a
metal roof structure. On all three types, the steel roof support system may be either
one of the following: a system of solid steel girders and beams, lightweight open-
web bar joist, or a combination of both. The collapse danger to a firefighter from a
non-combustible building is roof cave-in from the unprotected steel open-web bar
joist. The main disadvantage of the open-web bar joists is its susceptibility to
damage by a fire in the combustible contents inside the building. Tests have shown
that unprotected lightweight open-web bar joist can fail when exposed to fire for
five to ten minutes. This possibility makes it extremely dangerous for a firefighter
to operate on a roof supported by steel open-web bar joists which are being heated
by flames. The open-web bar joist is the main structural hazard of non-combustible
construction.
There are several design features relating to ordinary construction which warrant
close observation. These include efflorescence, parging, and spreaders. Efflores-
cence results when large amounts of soluble salts are used in mortar and excessive
water penetrates the masonry. Efflorescence appears as a white powdery substance
on the wall and indicates weakened mortar. Parging is the plastering over of a
masonry wall with concrete. It is frequently a cosmetic fix for an unattractive,
deteriorated wall. A wall out of alignment is always a sign of danger. Spreaders are
intended to spread the load among one or more structural members and are
frequently used to support a wall in trouble. They are often indicated on the outside
of a wall by a circle, star, channel, or other device; arranged in a pattern they usually
serve a decorative purpose. When placed at random, these spreaders provide
additional strength to the wall.
9 - 25
Section 9 - Building Construction
9 - 26
Section 9 - Building Construction
STRUCTURAL COLLAPSE
There are many causes of structural collapse in buildings. Failure can result from
architectural faults in the original construction, the age of the building, slip-shod
repairs, and heavily-laden floors. Firefighters must be able to identify the indica-
tions of potential and imminent collapse for the safety of both themselves and others
at an incident.
Large, unprotected floor areas are also responsible for building collapse under fire
conditions. Floors without physical barriers can become completely engulfed by
fire. Because there is nothing to stop the progress of fire, a draft effect is created
moving the fire across the floor. When a floor becomes enveloped in flame,
firefighters find it difficult to fight the fire due to intense heat. Firefighting under
these circumstances is accomplished through halls, doors, and windows and in the
case of very large floors, the fire will be extremely difficult to contain because the
fire hose stream cannot reach the center of the floor.
Building collapse can result from the high temperatures which unprotected metal
structures may endure during a fire. Steel is used frequently in building construc-
tion for reasons of strength, elasticity, and cost. The problem arises when the metal
is subjected to temperatures of over 1,000 degrees. The steel will expand and
possibly disrupt other structural components. Under even higher temperatures,
the metal can give way completely. Firefighters should be aware that when
comparing steel and wood, where the structural members are of equal strength, a
wooden support will resist fire much better than steel. Large wooden members will
burn slowly and resist fire for longer periods of time than unprotected steel, which
has a poor record of withstanding fire.
The following list of events should serve as warnings of imminent building collapse
and firefighters observing any of these during fire operations must leave the
building and report conditions to the company officer.
BUILDING INTERIORS
There are three principal elements which determine the fire resistance of a building:
the fire resistance of the building itself, contents or processes within the building,
and the characteristics of the interior finish of the building. The interior finishes
include but are not limited to: wood, plywood, plywood paneling, plaster, gypsum
wallboard, fibrous ceiling tiles, plastics, and a variety of wall coverings. Surface
coatings may also exist such as paint, varnish, and acoustic spray which will add to
fire characteristics. Interior finishes can affect a fire in four ways:
1. They may influence the rate at which the fire build-up reaches “flash
over”.
4. They can add toxic gas and smoke which will contribute to life and
property hazards.
Once a fire has gained some headway, the upper portion (ceiling) will become
extremely hot as the gases fill it. If this area becomes hot enough, the gases may
ignite. This is commonly referred to as “flashover”. Thermal radiation emanates
from the combustion, heating the materials in the area rapidly. When the combus-
tible materials have become heated to their ignition temperatures, simultaneous
ignition will occur. An interior finish which absorbs and holds heat would be more
preferable because it would inhibit flashover for a longer period of time.
Many burning interiors are dangerous not only because of the heat factor but also
due to the smoke and toxic gases they release. In fact, fire tests have shown a greater
threat to life because of toxicity and smoke inhalation. Firefighters must always
wear SCBAs when fighting interior fires so they are not overwhelmed by toxic gas
or smoke.
9 - 29
Section 9 - Building Construction
TILT-UP CONSTRUCTION
HIGH-RISE CONSTRUCTION
The construction industry today uses two different types of framework for high-rise
structures: structural steel, and reinforced concrete. Buildings with a reinforced
concrete framework are made either by connecting large sections of concrete called
9 - 30
Section 9 - Building Construction
Construction engineers state that within 24 hours of pouring, the entire concrete
floor can collapse on firefighters if the wood formwork below has been destroyed
by fire. At this time it is most dangerous for a fire to occur in the formwork; however,
even the concrete floors in place for 48 hours or more, without the formwork below,
can collapse in small sections if they are heated by a scrap lumber fire. Conse-
quently, the fire department faces problems with concrete construction in three
distinct areas: collapse during construction with no fire, fire during construction,
and fire in a completed, occupied building.
Individual fireproofing provides protection for each piece of steel. In one method,
steel is encased in a structure. Concrete, terra cotta, metal lath and plaster, brick and
gypsum board are materials commonly used. This method is called encasement. In
another method, fireproofing is directly applied to the steel, usually by spraying.
Materials are asbestos fiber (no longer used), an intumescent coating containing
9 - 31
Section 9 - Building Construction
non-combustible fibers which smell and char when exposed to flame, and
cementatious coatings.
Membrane fireproofing does not protect individual members. In one method, wire
lath and cement plaster are used. In another method, the fireproofing of the floor is
accomplished by a rated floor-ceiling assembly. The efficiency of fireproofing
depends first on the competence of the subcontractor and the willingness of the
builder to demand quality work. It further depends on the building department
staff who inspect the original installation to determine that fireproofing and fire
protection are not compromised. This is particularly important in the case of spray-
on fireproofing and membrane-floor and ceiling assemblies. Finally, it is a serious
error to consider all high-rise buildings as a single problem. There are fire-
significant construction differences among high-rises. The particular buildings
within San Diego must be studied in detail to determine the particular potential
modes of building failure.
In a study carried out by the NFPA, it was found that inferior construction,
unprotected openings, large open areas, and inoperative fire doors were major
determinants in the amount of damage done to a structure and its interior in fire
conditions. These features were found to contribute to the spread of fire. Further-
more, it was determined that the speed of flame spread over a substance is directly
influenced by the amount of flammable vapors released by combustible materials
when they are heated, their texture, and thickness. The following structural features
will help limit the spread of fire if they are constructed properly (i.e., they do not
violate the building code). For more information on these features and other less-
common ones, refer to the current Uniform Building Code.
Fire Walls
Fire walls are typically constructed of concrete, structural clay tiles, or some other
structurally sound and non-combustible material and must have a fire-resistive
rating of at least one hour.
Fire walls must be able to remain intact if and when there is collapse on either side.
A fire wall will be continuous from the foundation to a parapet above the roof line
of the building. The height of the parapet portion is dictated to be at least 30 inches
above the roof line. In addition, these walls must have a minimum thickness
dictated by the type of construction (refer to Chapter 43, Table 43-A of the Uniform
Building Code). All fire walls must have parapets, wing walls, be attached to the
foundation, and have fire- resistive ratings as required by location, type of construc-
tion, and occupancy. Openings in fire walls must conform to the requirements of
the building.
9 - 32
Section 9 - Building Construction
Some of the code violations firefighters may encounter when dealing with fire walls
include: inferior construction materials, lack of thickness in the wall, no parapets,
and openings that are not correctly constructed, inoperative, or blocked open.
Firefighters should always inspect fire walls during pre-fire planning and inspec-
tions to determine aspects of construction and imperfections which may create
hazards during a fire.
Fire Partitions
Fire partitions are installed as a impedence to fire spread, but are not considered a
fire wall. They are constructed of non-combustible or protected combustible
materials and are attached or supported by structural components having a fire-
resistant rating equal to or better than the fire partition (usually one to two hours).
As with fire walls, openings must conform to the requirements set forth to provide
adequate fire protection. The fire resistance of a fire partition will be governed by
the type of construction used in the building.
Three-Hour Protection:
These openings are often given a class rating of “A” and must provide three
hours of fire protection equally on both sides. These enclosures cannot
contain any glass and are located in walls that separate buildings or separate
buildings into fire areas.
These enclosures protect openings into vertical shafts (e.g., stairwells and
elevator shafts) and are often classified with a rating of “C”. As well, one to
1 1/2 hour protection must be provided in exterior wall openings. Exterior
wall openings are often referred to as Class “D” openings.
45-Minute Protection:
These enclosures must provide 3/4 of an hour protection against fires. The
openings they protect are usually located in corridors and room partitions,
generally considered Class “C” and in exterior walls that are subject to light
or moderate exposure to fire (Class “E” and “F”).
9 - 33
Section 9 - Building Construction
Fire Doors
Typically, fire doors are used for the protection of both vertical and horizontal
openings. Fire doors can be horizontal or vertical sliding, single or double
swinging, or overhead rolling. Any of these door types may or may not be
If fire doors contain glass, it must be at least 1/4 inch thick and must be safety
protected with wire. Fire doors can be considered safe if they contain a current label
from the “Underwriters Laboratories” or “Factory Mutual Laboratories” as evi-
dence of testing. For more information refer to NFPA Standard # 80.
9 - 34
Section 9 - Building Construction
There are locations where fire windows are covered by shutters (i.e., at three-
quarter, one-, and 1 1/2 hour openings). The shutters must carry a rating equal to
or greater than the wall opening they are protecting. These fire shutters must either
remain closed or must close automatically under fire conditions. Once closed, fire
shutters must remain secure to be considered effective in reducing fire spread. Of
the different types of fire shutters, the automatic rolling shutters installed over
windows on the interior side of the building are considered the most useful and
practical.
Ventilation Devices
These systems are designed to complement other fire safe-guards and are not
replacements for fire protection devices. Vents are very useful in smoke and heat
dissipation, especially in buildings where vapors and dusts are highly combus-
tible. For a venting system to be considered effective, it should be free of any human
element. Rather, it should be automatic using fusible links, hinged dampers, and
counterweights that are heat reactive. Types of vents include: monitor controlled,
continuous gravity, unit type, sawtooth roof skylights, and exterior wall openings.
Monitors usually make use of fusible links which are effective from as low as 165°F
to 212 ° F or higher, if so required. The fusible links operate vent doors that may be
glass, metal panels, or louvered when heat containment is not a factor.
Continuous gravity vents are narrow slot openings which are attached to weather
hoods on the roof. Many will have movable shutters which will open automatically
in the event of a fire. This style of vent is most common in buildings where high heat
production is of concern.
9 - 35
Section 9 - Building Construction
Unit-type vents are lightweight metal frames or housings with built-in shutters that
open in the event of high heat or fire (e.g., fusible links). This type of structure is
most commonly associated with curtain boards.
Sawtooth roof skylights are sashes of glass usually non-wired which can be opened
to form a vent. Often this style of venting device must be operated manually and
is influenced by wind direction and force.
Exterior wall openings are most effective in structures where heat and smoke do not
have to travel more than 60 feet. They are usually characterized by louvered, open
vents but can also remain closed and automatically open in the event of fire.
Fire dampers are generally automated and once closed, will remain closed until
manually opened. These devices are required in a number of circumstances which
include:
There are other circumstances where fire dampers will be required and a number
of exceptions pertaining to particular situations. For more information on fire
dampers, firefighters should refer to NFPA 90A, 90B & 91.
9 - 36
Section 9 - Building Construction
Smoke dampers are commonly required in air conditioning systems and are
intended to interrupt the flow of air or smoke through the system when the air
conditioner is shut down.
Fire Stops
Fire stops are utilized to prevent fire spread within the hollow walls, floors, and
other internally open areas within a building or structure. They are usually pieces
of wood (2x4 inch) placed between wall studs, partitions, ceiling planks, etc., to cut
off any draft within the hollow areas. When fire stops are not used it's probable that
a fire could rage through the structure, burning unexposed internal areas before it
is ever discovered. The minimum fire stopping would include isolation of all
hollow walls at the floors and ceilings, isolation of the ceilings at the walls and
curtain boards. For more information on fire stopping refer to NFPA 101 (6-13).
Fire Loads
A comprehensive understanding of building construction requires basic knowl-
edge of the concept of loads and how they are applied. There are several types of
loads: designed loads are those the building architect anticipated and planned for;
and conversely, undesigned loads are unanticipated. Undesigned loads can be
concentrated or applied to a relatively small area, or equally distributed over a
larger surface. These loads can be further subdivided into dead and live loads.A
dead load
is the weight of the building and any part of a structure which is permanently
attached to it ( dead loads may also be considered static, as they are relatively
unchanging). A live load is not built in and can be categorized as an impact load (if
it is in motion when applied). A suspended load is held in place by attachment to
a building component above it. Any load can change in nature when portions of the
building fail. For example, a large printing press permanently attached to the third
floor would be considered a dead load; should the floor fail, the falling press would
become an impact load upon those floors beneath it.
Loads are applied in three ways: an axial load passes through the center of mass of
the supporting element perpendicular to the cross section; an eccentric load is one
perpendicular to the cross section of the supporting element that does not pass
through the center of mass; a torsional load is one parallel to the cross section of the
supporting member which does not pass through the long axis. These loads are
applied through three forces: compression tends to push or squeeze a material
together; tension tends to pull materials apart; and shear tends to break material by
causing its molecules to slide past one another.
Building materials are also classified as brittle (weak in tension and shear and tend
to break without bending), or ductile ( tend to deform before breaking).
9 - 37
Section 9 - Building Construction
REFERENCES
Building Construction for the Fire Service, Francis L. Brannigan, NFPA, Quincy,
Massachusetts 1993.
9 - 38